Changes for page 01 Program execution

Last modified by Leo Wei on 2024/12/24 22:42

From version 13.12
edited by Stone Wu
on 2022/09/23 16:10
Change comment: (Autosaved)
To version 8.1
edited by Leo Wei
on 2022/07/20 09:54
Change comment: Renamed from xwiki:PLC Editor2.1 User manual.2\.1 LX5V user manual.01 Program execution.WebHome

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -PLC Editor2.WebHome
1 +PLC Editor2.1 User manual.2\.1 LX5V user manual.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Stone
1 +XWiki.admin
Content
... ... @@ -1,124 +122,3 @@
1 -= **Summary** =
2 -
3 -This manual has a comprehensive introduction to the basic functions of WECON PLC Editor and the actual use. This book is completely aimed at zero-based readers, is an essential reference book for entry-level readers to quickly and fully grasp WECON PLC and WECON PLC Editor.
4 -
5 -This book starts from the basic product of WECON PLC and the basic concept and operation of WECON PLC Editor. It combines with a large number of cases and graphic analysis to comprehensively and deeply explain the use of WECON PLC Editor Software, as well as PLC program.
6 -
7 -WECON technology Co., Ltd. All rights reserved.
8 -
9 -= Precautions =
10 -
11 -Before the installation, operation, maintenance and repair of the micro programmable control, please read this manual and other related manuals to ensure correct use. Please use it after you have mastered the operation method, safety information and all
12 -
13 -== Design ==
14 -
15 -In the event of an abnormality in the external power supply or failure of the programmable controller, to ensure the safe operation of the entire system, be sure to install a safety circuit outside the programmable controller.
16 -
17 -1. Be sure to install an emergency brake circuit, a protection circuit, an interlock circuit for reverse operation, such as an emergency brake circuit, a protection circuit, a forward and reverse circuit, and an interlock circuit for the upper and lower positioning limits to prevent machine damage, in the external circuit of the programmable controller.
18 -1. When the programmable controller CPU detects abnormal conditions such as WDT errors through self-diagnosis, all outputs are shut off. In addition, when the programmable controller CPU cannot detect abnormalities in the input/output control part, etc., it cannot control the output. At this time, in order to make the machine operate safely, please design the external circuit and mechanism.
19 -1. Due to the failure of the relay and transistor of the output unit, it is impossible to control the state of the output to ON or OFF. In order to ensure the safe operation of the machine, please design external circuits and mechanisms for output signals related to major accidents.
20 -
21 -== Installation ==
22 -
23 -* Please use it in the general specification environment described in the manual.
24 -** Do not use in the following places: places with dust, oily smoke, conductive dust, corrosive gas, flammable gas; places  exposed to high temperature, condensation, wind and rain; places with vibration or impact. Electric shock, fire, and misoperation can also cause product damage.
25 -* When processing screw holes and wiring, do not let iron filings or wire ends fall into the ventilation window of the programmable controller. It may cause fire, malfunction, or misoperation.
26 -* Please insert the connecting cable and display module accurately into the specified sockets. Poor contact may cause misoperation.
27 -
28 -(% class="box infomessage" %)
29 -(((
30 -**✎Note:**
31 -
32 -* To prevent the temperature from rising, do not install at the bottom, top or vertical direction.Be sure to install it horizontally on the wall as shown on the right.
33 -* Please leave a space of more than 50mm between the host and other equipment or structures.Try to avoid high-voltage lines, high-voltage equipment, and power equipment.
34 -)))
35 -
36 -== Wiring ==
37 -
38 -The signal input and output lines of the programmable controller cannot pass through the same cable.
39 -
40 -In addition, signal input lines and output lines cannot pass through the same pipeline with other power lines and output lines, and cannot be bundled together.
41 -
42 -If implemented according to the above precautions, even if the input and output wiring is as long as 50 to 100m, there is almost no noise problem. But generally for safety, the wiring length should be within 20m.
43 -
44 -(% style="text-align:center" %)
45 -[[image:PLC Editor2.01 Program execution.WebHome@1652145475206-244.png||height="179" width="200" class="img-thumbnail"]]
46 -
47 -(% class="box infomessage" %)
48 -(((
49 -**✎Note:**
50 -
51 -* The installation and wiring must be performed when the external power supply is cut off. Otherwise, it may cause electric shock or product damage.
52 -* After installation and wiring, etc., the terminal cover must be installed before power-on operation to avoid electric shock.
53 -)))
54 -
55 -(% class="table-bordered" %)
56 -|=(% scope="row" %)(((
57 -
58 -
59 -
60 -[[image:PLC Editor2.01 Program execution.WebHome@1652145267405-613.png||class="img-thumbnail"]]
61 -
62 -**Danger**
63 -)))|(((
64 -(% style="text-align:center" %)
65 -[[image:PLC Editor2.01 Program execution.WebHome@0-1.png||height="141" width="400" class="img-thumbnail"]]
66 -
67 -It is very dangerous to close the positive and negative contactors at the same time. For loads like this, in addition to the interlock set by the internal program of the programmable controller, the interlock shown above must also be set outside the programmable controller.
68 -)))
69 -|=(((
70 - [[image:PLC Editor2.01 Program execution.WebHome@1652145275238-798.png||height="45" width="50" class="img-thumbnail"]]
71 -
72 -**Attention**
73 -)))|Do not connect the empty terminal to the outside, otherwise the product will be damaged.
74 -
75 -* Please connect the AC power supply to the dedicated terminal according to the content in the manual.
76 -* If the AC power supply is connected to the DC input/output terminal or the DC power supply terminal, the programmable controller will be burnt out.
77 -* Please do not supply power to the 24+ terminal of the basic unit from the external power supply, and to the empty terminal    . Do not wire from the outside, otherwise the product will be damaged.
78 -* Please ground the ground terminal of the basic unit according to the third method. But please do not share the ground with the strong current system.
79 -
80 -**Attached**
81 -
82 -The programmable controller will continue to work if there is an instantaneous power failure of less than 10ms.
83 -
84 -When the power is cut for a long time or the voltage is low, the programmable controller will stop working and the output will turn OFF, but once the power supply is restored, it will automatically restart.
85 -
86 -== Startup and maintenance ==
87 -
88 -(% class="table-bordered" %)
89 -(% class="warning" %)|=**Danger**
90 -|(((
91 -Please do not touch the terminals when the power is on, otherwise it may cause electric shock or misoperation.
92 -
93 -Please clean and disassemble the terminal after the power is turned off. Performing it while the power is on may cause electric shock.
94 -
95 -Please read the manual thoroughly and fully confirm the safety before proceeding with program changes, forced output, RUN/STOP, etc. during machine operation.
96 -
97 -Operation errors can damage the machine and cause accidents.
98 -)))
99 -
100 -(% class="table-bordered" %)
101 -(% class="warning" %)|=**Caution**
102 -|(((
103 -Please do not disassemble or modify, otherwise it may cause malfunction, malfunction, fire.
104 -
105 -※For repair matters, please contact Fuzhou Wecon Electronic Technology Co., Ltd.
106 -
107 -After the power is turned off, perform the installation and disassembly of the extension cables and other connecting cables, otherwise it may cause malfunctions and malfunctions.
108 -)))
109 -
110 -== **Maintenance** ==
111 -
112 -Regular inspection: Whether the programmable controller is equipped with consumables with a shorter life.
113 -
114 -For relay output type, if the output relay works abnormally at a high frequency or drives a large-capacity load, you must pay attention to its impact on the service life.
115 -
116 -Check with other equipment, please pay attention to the following points:
117 -
118 -* Whether there is an abnormal increase in the temperature inside the machine due to other heating elements or direct sunlight.
119 -* Whether dust or conductive dust has penetrated into the machine.
120 -* Whether there are loose wiring and terminals or other abnormalities
121 -
122 122  = Scan structure =
123 123  
124 124  The scan configuration of the CPU module is as follows.
... ... @@ -130,12 +130,11 @@
130 130  
131 131  The initialization based on the status of the CPU module is as follows.
132 132  
133 -* **√**: execute
134 -* **×**: not execute
12 +**√**: execute. **×**: not execute
135 135  
136 136  (% class="table-bordered" %)
137 -|=(% rowspan="2" %)**Processing item**|=(% colspan="3" %)**Status of the CPU module**
138 -|=**When the power is ON**|=**STOP**|=**When STOP RUN**
15 +|(% rowspan="2" %)**Processing item**|(% colspan="3" %)**Status of the CPU module**
16 +|**When the power is ON**|**STOP**|**When STOP RUN**
139 139  |Initialization of input and output modules|√|×|×
140 140  |CPU parameter check|√|×|×
141 141  |Check of system parameters|√|×|×
... ... @@ -146,11 +146,11 @@
146 146  
147 147  Perform the following before starting program calculation.      
148 148  
149 -* Update the actual input point of the PLC to the input relay X.
27 +Update the actual input point of the PLC to the input relay X.
150 150  
151 151  The following is executed after the END instruction is executed.
152 152  
153 -* Update the PLC output relay Y to the actual output point.
31 +Update the PLC output relay Y to the actual output point.
154 154  
155 155  **Key points**
156 156  
... ... @@ -182,8 +182,10 @@
182 182  
183 183  It is the first scan time of the CPU module in RUN.
184 184  
185 -Process as the following way: The value stored in SD134 (initial scan time (ms unit)) and SD135 (initial scan time (s unit)).
63 +Process as the following way:
186 186  
65 +The value stored in SD134 (initial scan time (ms unit)) and SD135 (initial scan time (s unit)).
66 +
187 187  = The flow of each procedure =
188 188  
189 189  When the CPU module changes to the RUN state, the programs are executed in sequence according to the program execution type and execution sequence settings.
... ... @@ -195,11 +195,10 @@
195 195  
196 196  When the execution types of the programs are the same, they are executed in the order set in the execution order.
197 197  
198 -(% class="box infomessage" %)
199 -(((
200 -**✎Note:** When executing instructions that can be completed with multiple cycles (such as OUT T, RAMP, RS, etc.), they should be programmed in the scan program. If it is used in event execution type programs and mid-stage execution type programs, these instructions may not be executed in multiple scan cycles, causing actual results to be different from the ideal results. Therefore, unless events, interrupts and subroutines can be executed in each scan cycle. It is not recommended to use multi-cycle execution instructions in other situations.
201 -)))
78 +**✎Note:**
202 202  
80 +When executing instructions that can be completed with multiple cycles (such as OUT T, RAMP, RS, etc.), they should be programmed in the scan program. If it is used in event execution type programs and mid-stage execution type programs, these instructions may not be executed in multiple scan cycles, causing actual results to be different from the ideal results. Therefore, unless events, interrupts and subroutines can be executed in each scan cycle. It is not recommended to use multi-cycle execution instructions in other situations.
81 +
203 203  = Types of program execution =
204 204  
205 205  == Scan execution program ==
... ... @@ -218,11 +218,11 @@
218 218  (% style="text-align:center" %)
219 219  [[image:1-5.png||height="372" width="300" class="img-thumbnail"]]
220 220  
221 -1. Scan the program name: the program name requires to match case, and the program name cannot use the same name with device name (the device name does not match case).
222 -1. The input of /%$@&=~~`^<>?:{}[],;!*.~\~\'" is not supported. It cannot exceed 64 characters. The default name is MAINx.
223 -1. The number of scan programs that can be built is limited to 100.
224 -1. Each scan program has been END ended, but only the last END instruction is completed to calculate a scan cycle.
225 -1. The execution sequence runs from top to bottom in the order of creation.
100 +* Scan the program name: the program name requires to match case, and the program name cannot use the same name with device name (the device name does not match case).
101 +* The input of /%$@&=to`^<>?:{}[],;!*.~\~\'" is not supported. It cannot exceed 64 characters. The default name is MAINx.
102 +* The number of scan programs that can be built is limited to 100.
103 +* Each scan program has been END ended, but only the last END instruction is completed to calculate a scan cycle.
104 +* The execution sequence runs from top to bottom in the order of creation.
226 226  
227 227  (% style="text-align:center" %)
228 228  [[image:1-6.png||class="img-thumbnail"]]
... ... @@ -238,7 +238,7 @@
238 238  
239 239  The trigger of event execution type program is as follows.
240 240  
241 -**ON event of bit data (TRUE)**
120 +**(1) ON event of bit data (TRUE)**
242 242  
243 243  * After the ON event is specified, if the contact that sets the trigger condition in the ON event is turned ON during the scan program, the ON event program will be executed in the scan program page*1 or before the END instruction is executed.
244 244  * The ON event program will only be executed once in a single scan cycle.
... ... @@ -254,13 +254,13 @@
254 254  The devices that can be specified are as follows.
255 255  
256 256  (% class="table-bordered" %)
257 -|=(% colspan="2" %)**Project**|=**Content**
136 +|(% colspan="2" %)**Project**|**Content**
258 258  |(% rowspan="2" %)Device *1|Bit Device|X, Y, M, SM
259 259  |Bit specification of word device|D.b
260 260  
261 261  *1 The indexed device cannot be specified.
262 262  
263 -**TIME event**
142 +**(2) TIME event**
264 264  
265 265  After the program is to RUN state and the specified time has elapsed, event is executed one time when it comes to the execution sequence of the first corresponding program. For the second and subsequent executions, the time is re-measured from the start of the last event execution type program. After the specified time has elapsed, the program is executed repeatedly when it comes to the execution sequence of the first corresponding program. In addition, in the next scan after the corresponding program is executed, the current value of the output (Y) and timer (T) used in the corresponding program can be cleared. It can be used for programs that do not need to respond in a fixed period of time.
266 266  
... ... @@ -285,7 +285,7 @@
285 285  Event program name:
286 286  
287 287  * The program name requires to match case, and the program name with the same name as the device cannot be used (the device name does not match case).
288 -* The program name does not support /%$@&=~~`^<>?:{}[],;!*.~\~\'" character input.
167 +* The program name does not support /%$@&=to`^<>?:{}[],;!*.~\~\'" character input.
289 289  * The length of the program name cannot exceed 64 characters. The default name is EVENTx.
290 290  
291 291  A maximum of 100 new event programs could be created.
... ... @@ -300,26 +300,26 @@
300 300  (% style="text-align:center" %)
301 301  [[image:1-11.png||height="419" width="500" class="img-thumbnail"]]
302 302  
303 -**Configuration instructions:**
182 +Configuration instructions:
304 304  
305 - Configuration interface
184 + 1) Configuration interface
306 306  
307 307  (% style="text-align:center" %)
308 308  [[image:1-12.png||height="372" width="300" class="img-thumbnail"]]
309 309  
310 -Parameter content:
189 +2) Parameter content:
311 311  
312 312  (% class="table-bordered" %)
313 -|=(% colspan="2" %)**Project**|=(% style="width: 654px;" %)**Content**|=(% style="width: 190px;" %)**Setting range**|=**Default**
314 -|(% colspan="2" %)Execution type|(% style="width:654px" %)Select event type|(% style="width:190px" %)Not set/ON event/TIME event|Not set
315 -|(% rowspan="2" %)ON event|Contact|(% style="width:654px" %)The event type can be set when ON event is selected. Set the bit device as the trigger condition.|(% style="width:190px" %)X/Y/M/SM/D.b|
316 -|Whether to clear|(% style="width:654px" %)When the bit device of the trigger condition set by the ON event is turned OFF, whether to clear the current value of the output (Y) and timer (T) used in the execution program of the ON event in the next cycle.|(% style="width:190px" %)(((
192 +|(% colspan="2" %)**Project**|**Content**|**Setting range**|**Default**
193 +|(% colspan="2" %)Execution type|Select event type|Not set/ON event/TIME event|Not set
194 +|(% rowspan="2" %)ON event|Contact|The event type can be set when ON event is selected. Set the bit device as the trigger condition.|X/Y/M/SM/D.b|
195 +|Whether to clear|When the bit device of the trigger condition set by the ON event is turned OFF, whether to clear the current value of the output (Y) and timer (T) used in the execution program of the ON event in the next cycle.|(((
317 317  True
318 318  
319 319  False
320 320  )))|False
321 -|(% rowspan="2" %)TIME event|Time|(% style="width:654px" %)Set how long to execute the event program once.|(% style="width:190px" %)1 to 2147483647 (100us unit)|
322 -|Whether to clear|(% style="width:654px" %)When the TIME event is executed, if the event is not executed in the next scan cycle, select whether to clear the output (Y) used in the TIME event execution program and the current value of the timer (T).|(% style="width:190px" %)(((
200 +|(% rowspan="2" %)TIME event|Time|Set how long to execute the event program once.|1 to 2147483647 (100us unit)|
201 +|Whether to clear|When the TIME event is executed, if the event is not executed in the next scan cycle, select whether to clear the output (Y) used in the TIME event execution program and the current value of the timer (T).|(((
323 323  True
324 324  
325 325  False
... ... @@ -333,61 +333,78 @@
333 333  
334 334  In the process of executing the scan program, the program that can interrupt the priority execution of the scan program is called an interrupt execution program.
335 335  
336 -* When an interrupt cause occurs, the interrupt program corresponding to the interrupt pointer number will be executed. However, the execution needs to be set to the interrupt enabled state by the EI instruction.
215 + ~1. When an interrupt cause occurs, the interrupt program corresponding to the interrupt pointer number will be executed. However, the execution needs to be set to the interrupt enabled state by the EI instruction.
337 337  
338 338  (% style="text-align:center" %)
339 339  [[image:1652249587490-678.png||class="img-thumbnail"]]
340 340  
341 341  
342 -* An interrupt name corresponds to an interrupt program, and the interrupt name cannot be repeated. Each interrupt has its own trigger condition and execution program, and each interrupt program ends with END.
343 -* Interrupt has the characteristic of interrupting the original execution program and executing the interrupt first, but it cannot interrupt the interrupt program being executed.
344 -* The interrupt program has the concept of priority. The smaller the priority value, the more priority the response. The priority setting range is 0 to 2.
221 + 2. An interrupt name corresponds to an interrupt program, and the interrupt name cannot be repeated. Each interrupt has its own trigger condition and execution program, and each interrupt program ends with END.
345 345  
346 -**The actions when an interruption cause occurs are as follows:**
223 + 3. Interrupt has the characteristic of interrupting the original execution program and executing the interrupt first, but it cannot interrupt the interrupt program being executed.
347 347  
348 -* Interrupt prohibition (DI) when an interruption cause occurs.
349 -** If the interrupt execution condition is triggered in a program that is forbidden by DI, the interrupt will not be executed. Even if the subsequent program uses the EI instruction to allow interruption, the previously shielded interrupt program will not be executed. Only the interrupt execution condition is triggered again. The interrupt program will be executed.
350 -* When multiple interrupt causes occur simultaneously in the interrupt enabled state.
351 -** The interrupt program with higher priority will be executed sequentially. In addition, when multiple interrupts with the same priority occur at the same time, the actions are executed in the order of interrupt priority.
352 -** If three interrupt programs I0, I10, I16 are created, the priority of I0 is 1, the priority of I10 is 0, and the priority of I16 is 1. The execution logic is shown in the figure below: I10 has the smallest priority and is executed first; I0 and I16 have the same priority and are executed in the order of program establishment.
225 + 4. The interrupt program has the concept of priority. The smaller the priority value, the more priority the response. The priority setting range is 0 to 2.
353 353  
227 +The actions when an interruption cause occurs are as follows:
228 +
229 +1. Interrupt prohibition (DI) when an interruption cause occurs.
230 +
231 +If the interrupt execution condition is triggered in a program that is forbidden by DI, the interrupt will not be executed. Even if the subsequent program uses the EI instruction to allow interruption, the previously shielded interrupt program will not be executed. Only the interrupt execution condition is triggered again. The interrupt program will be executed.
232 +
233 + 2.When multiple interrupt causes occur simultaneously in the interrupt enabled state.
234 +
235 +The interrupt program with higher priority will be executed sequentially. In addition, when multiple interrupts with the same priority occur at the same time, the actions are executed in the order of interrupt priority.
236 +
237 +If three interrupt programs I0, I10, I16 are created, the priority of I0 is 1, the priority of I10 is 0, and the priority of I16 is 1. The execution logic is shown in the figure below: I10 has the smallest priority and is executed first; I0 and I16 have the same priority and are executed in the order of program establishment.
238 +
354 354  (% style="text-align:center" %)
355 355  [[image:1652249553246-688.png||class="img-thumbnail"]]
356 356  
357 -* When an interrupt occurs during the waiting time when performing constant scan.
358 -** Execute the interrupt program for this interrupt.
359 -* When other interrupts occur during the execution of the interrupt program.
360 -** In the interrupt program (including the specification when the interrupt occurs in the event execution program), when other interrupts occur, the original interrupt execution program will not be interrupted. After the original interrupt execution program is completed, the new interrupt program is executed. After the execution is completed Then return to the scanning procedure.
361 -* During the execution of the interrupt program, when an interrupt cause with a low priority or the same priority occurs.
362 -** The interruption cause that occurred is stored, and after the interrupt program in execution ends, the interrupt program corresponding to the stored interruption cause is executed. Even if the same interruption cause occurs multiple times, the interruption cause is stored only once.
242 + 3. When an interrupt occurs during the waiting time when performing constant scan.
363 363  
244 +Execute the interrupt program for this interrupt.
364 364  
246 + 4.When other interrupts occur during the execution of the interrupt program.
247 +
248 +In the interrupt program (including the specification when the interrupt occurs in the event execution program), when other interrupts occur, the original interrupt execution program will not be interrupted. After the original interrupt execution program is completed, the new interrupt program is executed. After the execution is completed Then return to the scanning procedure.
249 +
250 + 5. During the execution of the interrupt program, when an interrupt cause with a low priority or the same priority occurs.
251 +
252 +The interruption cause that occurred is stored, and after the interrupt program in execution ends, the interrupt program corresponding to the stored interruption cause is executed. Even if the same interruption cause occurs multiple times, the interruption cause is stored only once.
253 +
254 +
365 365  (% style="text-align:center" %)
366 366  [[image:1652249673420-476.png||class="img-thumbnail"]]
367 367  
368 -* When the same interruption cause occurs during the execution of the interrupt program;
369 -** The interruption cause that occurred is stored, and after the interrupt program in execution ends, the interrupt program corresponding to the stored interruption cause is executed. Even if the same interruption cause occurs multiple times, the interruption cause is stored only once.
258 + 6. When the same interruption cause occurs during the execution of the interrupt program;
370 370  
260 +The interruption cause that occurred is stored, and after the interrupt program in execution ends, the interrupt program corresponding to the stored interruption cause is executed. Even if the same interruption cause occurs multiple times, the interruption cause is stored only once.
261 +
371 371  **Interrupt trigger condition classification**
372 372  
373 -* **External input (X) interrupt**
374 -** Description of external input interrupt
375 -*** The external input interrupt is triggered by the rising or falling edge of the fixed X point input.
376 -*** Supports the rising and falling edge interrupts of a total of 8 input points of X0 to X7, and supports a total of 16 external input interrupts.
377 -*** The same interrupt trigger condition cannot create multiple interrupt programs.
378 -*** External input interrupt and high-speed counter cannot use the same X point.
379 -*** You must use EI in the scan program to allow interrupts before the interrupt execution program will be executed.
380 -* **External input interrupt steps.**
381 -** Project management→ Program→ Interrupt→ right click to create.
382 -** The interrupt program name requires to match case, and the program name with the same name as the device cannot be used (the device name does not match case),
383 -** The interrupt program name does not support the input of /%$@&=~~`^<>?:{}[],;!*.~\~\'" characters,
384 -** The length of the interrupt program name cannot exceed 64 characters and cannot be typed. The default name is INTx.
264 +1. **External input (X) interrupt**
385 385  
266 +**~ **1. Description of external input interrupt
267 +
268 +1. The external input interrupt is triggered by the rising or falling edge of the fixed X point input.
269 +1. Supports the rising and falling edge interrupts of a total of 8 input points of X0 to X7, and supports a total of 16 external input interrupts.
270 +1. The same interrupt trigger condition cannot create multiple interrupt programs.
271 +1. External input interrupt and high-speed counter cannot use the same X point.
272 +1. You must use EI in the scan program to allow interrupts before the interrupt execution program will be executed.
273 +
274 + 2. External input interrupt steps.
275 +
276 +Project management→ Program→ Interrupt→ right click to create
277 +
386 386  (% style="text-align:center" %)
387 387  [[image:1-16.png||class="img-thumbnail"]]
388 388  
389 -* Click Configure, and select external interrupt for execution type, as shown in the figure below (it can also be configured in "program parameters" in "parameters" in project management):
281 +1. The interrupt program name requires to match case, and the program name with the same name as the device cannot be used (the device name does not match case),
282 +1. The interrupt program name does not support the input of /%$@&=to`^<>?:{}[],;!*.~\~\'" characters,
283 +1. The length of the interrupt program name cannot exceed 64 characters and cannot be typed. The default name is INTx.
390 390  
285 +Click Configure, and select external interrupt for execution type, as shown in the figure below (it can also be configured in "program parameters" in "parameters" in project management):
286 +
391 391  (% style="text-align:center" %)
392 392  [[image:1-17.png||class="img-thumbnail"]]
393 393  
... ... @@ -407,7 +407,7 @@
407 407  Note: X rising edge interrupt and X falling edge interrupt use the same X filter, so after the filter setting is changed in the X rising edge configuration, the X falling edge will also change. If the filter time is set to 1000, you must ensure that the high level and low level of the input signal are maintained for more than 10 us before the interrupt can be triggered.
408 408  )))|0 to 1700|1
409 409  
410 -* Write interrupt execution program
306 +1. Write interrupt execution program
411 411  
412 412  (% style="text-align:center" %)
413 413  [[image:1-18.png||class="img-thumbnail"]]
... ... @@ -417,19 +417,19 @@
417 417  (% style="text-align:center" %)
418 418  [[image:1652250056160-117.png||height="215" width="500" class="img-thumbnail"]]
419 419  
420 -**Timer interrupt**
316 +**~ 2.Timer interrupt**
421 421  
422 -Timer interrupt description
318 +1. Timer interrupt description
423 423  
424 -* Timer interrupt is based on the set time, execute the interrupt program every this time, the minimum time interval can reach 100us.
425 -* Up to 100 timer interrupt execution programs can be created.
426 -* Each timer interrupt program is independent of each other and does not affect each other.
427 -* Each timer interrupt program should be configured with priority. When triggered at the same time, it is executed in the order of priority, but when the priority is the same, it is executed in the order of the established program.
428 -* The interrupt execution program is executed only after EI is used in the scanner to allow the interrupt
320 +1. Timer interrupt is based on the set time, execute the interrupt program every this time, the minimum time interval can reach 100us.
321 +1. Up to 100 timer interrupt execution programs can be created.
322 +1. Each timer interrupt program is independent of each other and does not affect each other.
323 +1. Each timer interrupt program should be configured with priority. When triggered at the same time, it is executed in the order of priority, but when the priority is the same, it is executed in the order of the established program.
324 +1. The interrupt execution program is executed only after EI is used in the scanner to allow the interrupt
429 429  
430 -Timer interrupt step
326 + 2. Timer interrupt step
431 431  
432 -* Project managementðProgramðInterruptðRight click to create. Enter the program name. The program name only supports the combination of English letters, numbers, and underscores, and must start with an English letter. The default is INTx. Click Configure and select Timer Interrupt as the execution type, as shown in the figure below (it can also be configured in "program parameters" in "parameters" in project management).
328 +Project managementðProgramðInterruptðRight click to create. Enter the program name. The program name only supports the combination of English letters, numbers, and underscores, and must start with an English letter. The default is INTx. Click Configure and select Timer Interrupt as the execution type, as shown in the figure below (it can also be configured in "program parameters" in "parameters" in project management).
433 433  
434 434  (% style="text-align:center" %)
435 435  [[image:1-20.png||class="img-thumbnail"]]
... ... @@ -440,35 +440,34 @@
440 440  |(% rowspan="2" %)Timer interrupt|Time|Set the interval time for interrupt triggering|1 to 2147483647 (100us unit)|
441 441  |priority|When multiple interrupts arrive at the same time, the order of priority execution, the smallest value is executed first|0 to 2|0
442 442  
443 -Write interrupt execution program
339 +1. Write interrupt execution program
444 444  
445 445  (% style="text-align:center" %)
446 446  [[image:1-21.png||class="img-thumbnail"]]
447 447  
448 -* Double-click the newly created timer interrupt program in the project management to start writing the interrupt execution program. As shown in the figure above, a newly created timer interrupt program is INT0, and the trigger condition is configured to execute the interrupt program every 10ms. If the main program uses EI to enable interrupts, all instruction programs in INT0 will be executed every 10ms, namely D0 It will add 1 to 10ms.
344 +Double-click the newly created timer interrupt program in the project management to start writing the interrupt execution program. As shown in the figure above, a newly created timer interrupt program is INT0, and the trigger condition is configured to execute the interrupt program every 10ms. If the main program uses EI to enable interrupts, all instruction programs in INT0 will be executed every 10ms, namely D0 It will add 1 to 10ms.
449 449  
450 450  (% style="text-align:center" %)
451 451  [[image:1652250294005-455.png||class="img-thumbnail"]]
452 452  
453 -**High-speed counter interrupt**
349 +**~ 3. High-speed counter interrupt**
454 454  
455 -Description of high-speed counter interrupt
351 +1. Description of high-speed counter interrupt
456 456  
457 -* The high-speed counter interrupt triggers an interrupt condition after the set value of the high-speed counter HSC0 to HSC7 provided by the PLC and executes the interrupt program.
458 -* It can support up to 100 high-speed counter interrupt programs, but the number that can be supported by each channel does not need to be fixed.
459 -* When using the high-speed counter interrupt, project must configure the high-speed counter and use the OUT HSC instruction to enable the corresponding counting channel to count before it can be used (see the high-speed counter description section for the specific configuration method).
460 -* Each high-speed counter interrupt program should be configured with priority. When triggered at the same time, it will be executed in the order of priority. When the priority is the same, it will be executed in the order of channels HSC0-HSC7. When the channel is also the same, it is executed in order according to the creation promise.
461 -* Project must use EI in the scan program to allow interrupts before the interrupt execution program will be executed.
353 +1. The high-speed counter interrupt triggers an interrupt condition after the set value of the high-speed counter HSC0 to HSC7 provided by the PLC and executes the interrupt program.
354 +1. It can support up to 100 high-speed counter interrupt programs, but the number that can be supported by each channel does not need to be fixed.
355 +1. When using the high-speed counter interrupt, project must configure the high-speed counter and use the OUT HSC instruction to enable the corresponding counting channel to count before it can be used (see the high-speed counter description section for the specific configuration method).
356 +1. Each high-speed counter interrupt program should be configured with priority. When triggered at the same time, it will be executed in the order of priority. When the priority is the same, it will be executed in the order of channels HSC0-HSC7. When the channel is also the same, it is executed in order according to the creation promise.
357 +1. Project must use EI in the scan program to allow interrupts before the interrupt execution program will be executed.
462 462  
463 -(% class="box infomessage" %)
464 -(((
465 -**✎Note: **Both the HSC channel and the external input interrupt channel must use the PLC input point X. It should be noted that it cannot be reused during configuration. For details, please refer to the configuration chapter of the high-speed counter.
466 -)))
359 +**✎Note: **Both the HSC channel and the external input interrupt channel must use the PLC input point X. It should be noted that it
467 467  
468 -High-speed counter interrupt steps
361 +cannot be reused during configuration. For details, please refer to the configuration chapter of the high-speed counter.
469 469  
470 -* “Project management”ð“Programð“Interrupt”ðRight click to create. Enter the program name. The program name only supports the combination of English letters, numbers, and underscores, and must start with an English letter. The default is INTx. Click Configure, select high-speed interrupt for execution type, as shown in the figure below (it can also be configured in "program parameters" in "parameters" in project management).
363 +1. high-speed counter interrupt step
471 471  
365 +“Project management”ð“Programð“Interrupt”ðRight click to create. Enter the program name. The program name only supports the combination of English letters, numbers, and underscores, and must start with an English letter. The default is INTx. Click Configure, select high-speed interrupt for execution type, as shown in the figure below (it can also be configured in "program parameters" in "parameters" in project management).
366 +
472 472  (% style="text-align:center" %)
473 473  [[image:1-23.png||class="img-thumbnail"]]
474 474  
... ... @@ -501,57 +501,56 @@
501 501  |Priority|When multiple interrupts arrive at the same time, the order of priority execution, the smallest value is executed first|0 to 2|0
502 502  |Contact|It is available when selecting high-speed comparison set and high-speed comparison reset. The contact is set or reset immediately after the trigger condition is reached.|Y/M/D.b|
503 503  
504 - Description of triggering rules
399 + 3. Description of triggering rules
505 505  
506 506  (% class="table-bordered" %)
507 -|(% style="width:135px" %)**Mode**|(% style="width:187px" %)**Configuration**|(% style="width:128px" %)**The current value**|(% style="width:324px" %)**Action**
508 -|(% rowspan="2" style="width:135px" %)High-speed compare interrupt (INT0)|(% rowspan="2" style="width:187px" %)Comparison value: 10000|(% style="width:128px" %)9999 → 10000|(% style="width:324px" %)Execute all programs in interrupt INT0
509 -|(% style="width:128px" %)10001 → 10000|(% style="width:324px" %)Execute all programs in interrupt INT0
510 -|(% rowspan="2" style="width:135px" %)High-speed comparison set (INT1)|(% rowspan="2" style="width:187px" %)(((
402 +|**Mode**|**Configuration**|**The current value**|**Action**
403 +|(% rowspan="2" %)High-speed compare interrupt (INT0)|(% rowspan="2" %)Comparison value: 10000|9999 → 10000|Execute all programs in interrupt INT0
404 +|10001 → 10000|Execute all programs in interrupt INT0
405 +|(% rowspan="2" %)High-speed comparison set (INT1)|(% rowspan="2" %)(((
511 511  Comparison value: -50,000
512 512  
513 513  Contact: Y10
514 -)))|(% style="width:128px" %)-50001 → -50000|(% style="width:324px" %)(((
409 +)))|-50001 → -50000|(((
515 515  Y10 is immediately set and mapped to the actual output (not affected by the scan period)
516 516  
517 517  The program in INT1 will not be executed
518 518  )))
519 -|(% style="width:128px" %)-49999 → -50000|(% style="width:324px" %)(((
414 +|-49999 → -50000|(((
520 520  Y10 is immediately set and mapped to the actual output (not affected by the scan period)
521 521  
522 522  The program in INT1 will not be executed
523 523  )))
524 -|(% rowspan="2" style="width:135px" %)High-speed comparison reset (INT2)|(% rowspan="2" style="width:187px" %)(((
419 +|(% rowspan="2" %)High-speed comparison reset (INT2)|(% rowspan="2" %)(((
525 525  Comparison value: 400000
526 526  
527 527  Contact: Y10
528 -)))|(% style="width:128px" %)399999 → 400000|(% style="width:324px" %)(((
423 +)))|399999 → 400000|(((
529 529  Y10 is reset immediately and mapped to the actual output (not affected by the scan period)
530 530  
531 531  The program in INT2 will not be executed
532 532  )))
533 -|(% style="width:128px" %)400001 → 400000|(% style="width:324px" %)(((
428 +|400001 → 400000|(((
534 534  Y10 is reset immediately and mapped to the actual output (not affected by the scan period)
535 535  
536 536  The program in INT2 will not be executed
537 537  )))
538 538  
539 -(% class="box infomessage" %)
540 -(((
541 541  **✎Note: **Both HSC channel and external input interrupt channel need to use the INPUT point X, so it should be noted that it cannot be reused in configuration. For details, please refer to the configuration section of high-speed counter.
542 -)))
543 543  
544 -Write interrupt execution program
436 +1. Write interrupt execution program
545 545  
546 546  * New interrupt program
547 -** Create three new interrupt programs under the interrupt of project management, namely HSC0_20000, HSC0_30000, HSC0_40000. Configure the interrupt program in the "program parameters", as shown in the figure below.
548 548  
440 +Create three new interrupt programs under the interrupt of project management, namely HSC0_20000, HSC0_30000, HSC0_40000. Configure the interrupt program in the "program parameters", as shown in the figure below.
441 +
549 549  (% style="text-align:center" %)
550 550  [[image:1-24.png||class="img-thumbnail"]]
551 551  
552 552  * High-speed counter configuration
553 -** Configure HSC0 for use in the high-speed counter configuration. After selecting the working mode, click the "Check” button. After the correct configuration box pops up, click Enter.
554 554  
447 +Configure HSC0 for use in the high-speed counter configuration. After selecting the working mode, click the "Check” button. After the correct configuration box pops up, click Enter.
448 +
555 555  (% style="text-align:center" %)
556 556  [[image:1-25.png||class="img-thumbnail"]]
557 557  
... ... @@ -561,23 +561,29 @@
561 561  
562 562  Program operation:
563 563  
564 -* Assuming that the High-speed counter channel 0 has been receiving pulses:
565 -** When the count value of HSC0 accumulates from 0 to 20000, all procedures of HSC0_20000 are executed.
566 -** When the count value of HSC0 is accumulated from 20000 to 30000, all procedures of HSC0_30000 are executed.
567 -** When the count value of HSC0 is accumulated from 30000 to 40000, all procedures of HSC0_40000 are executed.
458 +Assuming that the High-speed counter channel 0 has been receiving pulses:
568 568  
460 +When the count value of HSC0 accumulates from 0 to 20000, all procedures of HSC0_20000 are executed.
461 +
462 +When the count value of HSC0 is accumulated from 20000 to 30000, all procedures of HSC0_30000 are executed.
463 +
464 +When the count value of HSC0 is accumulated from 30000 to 40000, all procedures of HSC0_40000 are executed.
465 +
569 569  **Mask interrupt**
570 570  
571 -Mask through application instructions
468 +**~ 1. Mask through application instructions**
572 572  
573 -* The PLC interrupt is in the shielded state by default when it is powered on, and can only be used after the interrupt is allowed through the EI instruction.
574 -* The interrupt mask instruction DI masks all interrupts without parameters, and masks some priority interrupts with parameters (refer to the program flow instruction DI/EI for details).
470 +The PLC interrupt is in the shielded state by default when it is powered on, and can only be used after the interrupt is allowed through the EI instruction.
575 575  
576 -Mask through special registers SM and SD
472 +The interrupt mask instruction DI masks all interrupts without parameters, and masks some priority interrupts with parameters (refer to the program flow instruction DI/EI for details).
577 577  
474 +**~ 2. Mask through special registers SM and SD**
475 +
476 +1.External input interrupt mask register
477 +
578 578  (% class="table-bordered" %)
579 -|=(% colspan="4" %)**External input interrupt mask register**
580 -|=**Special register number**|=**Type of interrupt**|=**Instruction**|=**Defaults**
479 +|(% colspan="4" %)**External input interrupt mask register**
480 +|**Special register number**|**Type of interrupt**|**Instruction**|**Defaults**
581 581  |SM352|X0 rising edge interrupt|ON: Mask interrupt OFF: Enable interrupt|OFF
582 582  |SM353|X0 falling edge interrupt|ON: Mask interrupt OFF: Enable interrupt|OFF
583 583  |SM354|X1 rising edge interrupt|ON: Mask interrupt OFF: Enable interrupt|OFF
... ... @@ -595,6 +595,8 @@
595 595  |SM366|X7 rising edge interrupt|ON: Mask interrupt OFF: Enable interrupt|OFF
596 596  |SM367|X7 falling edge interrupt|ON: Mask interrupt OFF: Enable interrupt|OFF
597 597  
498 +2. Timer interrupt mask register
499 +
598 598  (% class="table-bordered" %)
599 599  |(% colspan="4" %)**Timer interrupt mask register**
600 600  |**Special register number**|**Type of interrupt**|**Instruction**|**Default**
0-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -40.3 KB
Content
1652145267405-613.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -4.0 KB
Content
1652145275238-798.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -1.6 KB
Content
1652145475206-244.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -19.7 KB
Content