Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -17 LX3V/5V/5S comparsion
1 +03 Difference between 3V, 5V and 5S
Parent
... ... @@ -1,1 +1,1 @@
1 -PLC Editor2.WebHome
1 +PLC Editor2.1 User manual.WebHome
Content
... ... @@ -1,59 +1,48 @@
1 -= **1 Basic differences** =
1 += **1 Basic difference between 5S and 5V** =
2 2  
3 -|=(% scope="row" %)Functions|=5V|=5S|=3V
4 -|=Running Mode|(% colspan="3" %)Cyclic scan /Interrupt
5 -|=Power supply|(% colspan="3" %)A:AC 220V;D:DC 24V
6 -|=Output type|MT:Transistor|MT:Transistor;MR:Relay|MT:Transistor;MR:Relay
7 -|=I/O|1212;1412;1616;2416;2424;3624;|0806;1208;1212;1412;
3 +|Functions|5V|5S|3V
4 +|Running Mode|(% colspan="3" %)Cyclic scan /Interrupt
5 +|Power supply|(% colspan="3" %)A:AC 220V;D:DC 24V
6 +|Output type|MT:Transistor|MT:Transistor;MR:Relay|MT:Transistor;MR:Relay
7 +|I/O|1212;1412;1616;2416;2424;3624;|0806;1208;1212;1412;
8 8  1616;2416;2424;3624;|0806;1208;1212;1412;
9 9  1616;2416;2424;3624;
10 -|=Programming|(% colspan="3" %)Ladder
11 -|=Type of instruction| | |
12 -|=Execute Time|Basic 0.01-0.03μs|Basic 0.03-0.08μs|Basic 0.06μs/Applied instruction:1-10us
13 -|=Program Capacity|(% colspan="2" %)512KB|16k
14 -|=High Speed Pulse Output|≤1412MT and smaller: 4*200KHz;
10 +|Programming|(% colspan="3" %)Ladder
11 +|Type of instruction| | |
12 +|Execute Time|Basic 0.01-0.03μs|Basic 0.03-0.08μs|Basic 0.06μs/Applied instruction:1-10us
13 +|Program Capacity|(% colspan="2" %)512KB|16k
14 +|High Speed Pulse Output|≤1412MT and smaller: 4*200KHz;
15 15  ≥1616MT and bigger:  8*200KHz。|MT/MR2H: 2* 200KHz;
16 16  MT4H: 4* 200KHz。|MT/2H: 2*100KHZ, or 4H: 4*100, single: 200kHZ
17 -|=High speed counter Interrupt|(% colspan="2" %)100 channels|21channels
18 -|=Timer Interrupt|(% colspan="2" %)100 channels,Support 0.1ms Interrupt|95 channels
19 -|=X Interrupt|X0-X7 Rising & Falling|X0-X5 Rising & Falling|X0-X5 Rising & Falling
20 -|=**High speed counter Single Phase**|**≤1412 and smaller: 4*150KHz
17 +|High speed counter Interrupt|(% colspan="2" %)100 channels|21channels
18 +|Timer Interrupt|(% colspan="2" %)100 channels,Support 0.1ms Interrupt|95 channels
19 +|X Interrupt|X0-X7 Rising & Falling|X0-X5 Rising & Falling|X0-X5 Rising & Falling
20 +|**High speed counter Single Phase**|**≤1412 and smaller: 4*150KHz
21 21  ≥1616 and bigger: 8*150KHz**|**≤1412 and smaller: 2*150KHz;4*10KHz
22 -≥1616 and bigger: 6*150KHz**|(((
23 -**Hardware counter for the first two channels:2*200KHz;**
24 -
25 -**Software counter for the first two channels:2*100KHz;**
26 -
27 -**Software counter for back four channels:4*10KHz**
28 -)))
29 -|=**High speed counter AB phase**|**≤1412 and smaller: 4*100KHz
22 +≥1616 and bigger: 6*150KHz**|**2*200KHz; 4*10KHz**
23 +|**High speed counter AB phase**|**≤1412 and smaller: 4*100KHz
30 30  ≥1616 and bigger: 8*100KHz**|**≤1412 and smaller: 1*100KHz+2*10KHz
31 -≥1616 and bigger: 3*100KHz**|(((
32 -**Hardware counter for the first two channels:2*100KHz;**
33 -
34 -**Software counter for the first two channels:2*50KHz;**
35 -
36 -**Software counter for back four channels:4*5KHz**
37 -)))
38 -|=Storage Type|(% colspan="3" %)FLASH
39 -|=Serial Communication|(((
25 +≥1616 and bigger: 3*100KHz**|**2*100KHz**
26 +|Storage Type|(% colspan="3" %)FLASH
27 +|Serial Communication|(((
40 40  COM1: RS422、RS485;COM2: RS485
41 41  )))|1208 and smaller: COM1: RS422;COM2: RS485;
42 42  1212 and bigger: COM1: RS422、RS485;COM2:RS485|1208 and smaller: COM1: RS422;COM2: RS485;
43 43  1212 and bigger: COM1: RS422、RS485;COM2: RS485
44 -|=BD board support|yes|yes|yes
45 -|=Communication BD board|(% colspan="2" %)support LX5V-2RS485-BD and LX5V-ETH-BD|RS485 BD support, 3vp supports ethernet bd board
46 -|=Expansion Module|(% colspan="2" %)yes √ (1212 and bigger can support)|yes √ (1212 and bigger can support)
47 -|=Electronic CAM|√(2 sheets for switch)|√(2 sheets for switch)|N/A
48 -|=S-type CAM|√|√|N/A
49 -|=N:N Comm|√|√|N/A
50 -|=Linear Interpolation|√|√|N/A
51 -|=Circular Interpolation|√|√|N/A
52 -|=sub-rotine|√|√|N/A
32 +|BD board support|yes|yes|yes
33 +|Communication BD board|(% colspan="2" %)inbuilt ethernet port series, RS485 BD board in developing |RS485 BD support, 3vp supports ethernet bd board
34 +|Expansion Module|(% colspan="2" %)yes √ (1212 and bigger can support)|yes √ (1212 and bigger can support)
35 +|Electronic CAM|√(2 sheets for switch)|√(2 sheets for switch)|N/A
36 +|S-type CAM|√|√|N/A
37 +|N:N Comm|√|√|N/A
38 +|Linear Interpolation|√|√|N/A
39 +|Circular Interpolation|√|√|N/A
40 +|sub-rotine|√|√|N/A
41 +| | | |
53 53  
54 -= **2 Software difference between 5S vs 5V** =
43 += **2 Software interface difference between 5S and 5V** =
55 55  
56 -== **High speed counter configuration** ==
45 +== **2.1 High speed counter configuration** ==
57 57  
58 58  **5V as below**
59 59  
... ... @@ -67,21 +67,23 @@
67 67  
68 68  = **3** **Functions that 3V has but 5V does not** =
69 69  
70 -== **BD board** ==
59 +== **3.1 BD board** ==
71 71  
72 -LX5V does not support LX3V-2RS485-BD
61 +LX5V does not support RS485 BD
73 73  
74 -LX5V does not support LX3V-ETH-BD
63 +LX5V does not support Ethernet BD
75 75  
76 -== **Analog BD board expansion address** ==
65 +LX5V does not support CAN BD
77 77  
67 +== **3.2 Analog BD board expansion address** ==
68 +
78 78  Provides the function of analog board BD to modify parameters such as filtering. For specific functions, please refer to the BD board manual.
79 79  
80 -== **PLDID** ==
71 +== **3.3 PLDID** ==
81 81  
82 82  Program label function, when the label of the program corresponds to the label of the PLC, the ladder diagram can be uploaded and downloaded. Clearing the memory does not clear this tag either. It is mainly to limit the ladder diagram used by PLC.
83 83  
84 -== **Instructions** ==
75 +== **3.4 Instructions** ==
85 85  
86 86  (1) NOP instruction (null instruction)
87 87  
... ... @@ -105,55 +105,61 @@
105 105  
106 106  (11) CPAVL instruction(communication BD configuration)
107 107  
108 -== **Unsupported special register function (M8000, D8000)** ==
99 +== **3.5 Unsupported special register function (M8000, D8000)** ==
109 109  
110 -=== **Clock related** ===
101 +=== **3.5.1 Clock related** ===
111 111  
112 112  Clock function not supported by LX5V
113 113  
114 -|=M8014|Oscillation clock with 1 minute clock period
115 -|=M8015|Clock stop and preset
116 -|=M8016|Stop time to read the display
117 -|=M8017|±30 seconds correction
118 -|=M8018|install and examine
119 -|=M8019|Real-time clock (RTC) error
105 +(% class="table-bordered" %)
106 +|M8014|Oscillation clock with 1 minute clock period
107 +|M8015|Clock stop and preset
108 +|M8016|Stop time to read the display
109 +|M8017|±30 seconds correction
110 +|M8018|install and examine
111 +|M8019|Real-time clock (RTC) error
120 120  
121 -=== **High-speed counter ring counting function** ===
113 +=== **3.5.2 High-speed counter ring counting function** ===
122 122  
123 -|=M8099|High-speed ring counter count start
124 -|=M8099|Ring count configuration
115 +(% class="table-bordered" %)
116 +|M8099|High-speed ring counter count start
117 +|M8099|Ring count configuration
125 125  
126 -=== **X0~~X5 pulse capture function** ===
119 +=== **3.5.3 X0~~X5 pulse capture function** ===
127 127  
128 -|=M8170|X000 pulse capture
129 -|=M8171|X001 pulse capture
130 -|=M8172|X002 pulse capture
131 -|=M8173|X003 pulse capture
132 -|=M8174|X004 pulse capture
133 -|=M8175|X005 pulse capture
121 +(% class="table-bordered" %)
122 +|M8170|X000 pulse capture
123 +|M8171|X001 pulse capture
124 +|M8172|X002 pulse capture
125 +|M8173|X003 pulse capture
126 +|M8174|X004 pulse capture
127 +|M8175|X005 pulse capture
134 134  
135 -= **4 3V and 5V incompatible functions** =
129 += **4. 5V function under development** =
136 136  
137 -(% class="wikigeneratedid" %)
138 -**(These can be automatically converted in the future)**
131 +N:N communication protocol
139 139  
140 -== **General register** ==
133 +Interpolation instructions (G90G01, G90G02, G90G03, G91G01, G91G02, G91G03)
141 141  
135 += **5. 3V and 5V incompatible functions (These can be automatically converted in the future)** =
136 +
137 +== **5.1 General register** ==
138 +
142 142  (% class="table-bordered" %)
143 -|=(% scope="row" %)**register**|=**LX3V**|=**LX5V**|=**Remarks**
144 -|=Input|X0~~X377|X0~~X1777|
145 -|=Output|Y0~~Y377|Y0~~Y1777|
146 -|=Auxiliary|M0~~M3071|M0~~M7999|
147 -|=Status|S0~~S999|S0~~S4095|
148 -|=Timer|T0~~T255|T0~~T511|
149 -|=counter|C0~~C199|C0~~C255|
150 -|=Double word counter|C200~~C219|LC0~~LC99|Non-power-down save
151 -|=Double word counter|C220~~C234|LC100~~LC255|Power-down save
152 -|=High-speed counter|C235~~C255|HSC0~~HSC7|Check the high-speed input function
153 -|=Data Register|D0~~D7999|D0~~D7999 (R0~~R29999)|
154 -|=Pointer P|P0~~P127|P0~~P4095|
155 -|=Instruction I|I0~~I8xx|None|
156 -|=constant|K, H, E|K, H, E|
140 +|**register**|**LX3V**|**LX5V**|**Remarks**
141 +|Input|X0~~X377|X0~~X1777|
142 +|Output|Y0~~Y377|Y0~~Y1777|
143 +|Auxiliary|M0~~M3071|M0~~M7999|
144 +|Status|S0~~S999|S0~~S4095|
145 +|Timer|T0~~T255|T0~~T511|
146 +|counter|C0~~C199|C0~~C255|
147 +|Double word counter|C200~~C219|LC0~~LC99|Non-power-down save
148 +|Double word counter|C220~~C234|LC100~~LC255|Power-down save
149 +|High-speed counter|C235~~C255|HSC0~~HSC7|Check the high-speed input function
150 +|Data Register|D0~~D7999|D0~~D7999 (R0~~R29999)|
151 +|Pointer P|P0~~P127|P0~~P4095|
152 +|Instruction I|I0~~I8xx|None|
153 +|constant|K, H, E|K, H, E|
157 157  
158 158  **Incompatible part**
159 159  
... ... @@ -167,13 +167,10 @@
167 167  
168 168  5. Pointer I is cancelled in LX5V, please check the programming mode for details.
169 169  
170 -== **Programming method** ==
167 +== **5.2 Programming method** ==
171 171  
172 -=== **Subroutine** ===
169 +=== **5.2.1 Subroutine (For details, please refer to LX5V Programming Manual Chapter 1.4-Subroutine Branch)** ===
173 173  
174 -(% class="wikigeneratedid" %)
175 -**(For details, please refer to LX5V Programming Manual Chapter 1.4-Subroutine Branch)**
176 -
177 177  **Use of LX3V subroutines**
178 178  [[image:1652684087594-147.png]]
179 179  
... ... @@ -187,11 +187,8 @@
187 187  
188 188  [[image:1652684829740-769.png]]
189 189  
190 -=== **Interrupt** ===
184 +=== **5.2.2 Interrupt (For details, please refer to LX5V Programming Manual Chapter 1.4-Branch)** ===
191 191  
192 -(% class="wikigeneratedid" %)
193 -**(For details, please refer to LX5V Programming Manual Chapter 1.4-Branch)**
194 -
195 195  **LX3V interrupt**
196 196  
197 197  The interrupt program is under FEND and returns with IRET. The meaning of the specific interrupt is distinguished by the pointer I number.(Refer to EI/DI instruction in 3V)
... ... @@ -210,9 +210,9 @@
210 210  
211 211  [[image:1652685809566-630.png]]
212 212  
213 -=== **Instructions** ===
204 +=== **5.2.3 Instructions** ===
214 214  
215 -**OUT instruction**
206 +**OUT command**
216 216  
217 217  Double word counter[[image:file:///C:\Users\ANNAXU~~1\AppData\Local\Temp\ksohtml14432\wps28.png]]
218 218  
... ... @@ -278,9 +278,9 @@
278 278  
279 279  [[image:1652689626279-240.png]]
280 280  
281 -= **5 High-speed input function** =
272 += **6. High-speed input function** =
282 282  
283 -== **Use on LX3V** ==
274 +== **6.1 Use on LX3V** ==
284 284  
285 285  Find the high-speed input counter you need to use according to the following table:
286 286  
... ... @@ -292,7 +292,7 @@
292 292  
293 293  [[image:1652690126303-800.png]]
294 294  
295 -== **Use on LX5V** ==
286 +== **6.2 Use on LX5V** ==
296 296  
297 297  According to channel, select the HSC register to use:
298 298  
... ... @@ -306,10 +306,11 @@
306 306  
307 307  [[image:1652692388207-617.png]]
308 308  
309 -== **Difference between high-speed counters on LX5V and LX3V** ==
300 +== **6.3 Difference between high-speed counters on LX5V and LX3V** ==
310 310  
311 311  LX3V updates the count value when the OUT instruction is executed, which is affected by the scan cycle.
312 312  
304 +
313 313  LX5V is updated in the 100us interrupt, not affected by the scan cycle, and provides the REF instruction to refresh the current high-speed counter value immediately.
314 314  
315 315  LX5V single-phase high-speed counter supports filtering function, configurable 0~~17us.
... ... @@ -316,20 +316,20 @@
316 316  
317 317  LX5V high-speed input counter will update the input frequency in the special soft element (SD) every 100us.
318 318  
319 -= **6 High-speed output function** =
311 += **7. High-speed output function** =
320 320  
321 321  **High-speed pulse commands are the same in the use of commands.**
322 322  
323 323  (% class="table-bordered" %)
324 -|=(% scope="row" %) |=LX3V|=LX5V
325 -|=DRVI|√|√
326 -|=DRVA|√|√
327 -|=PLSR|√|√
328 -|=PLSV|√|√
329 -|=PLSY|√|√
330 -|=DVIT|√|√
331 -|=ZRN|√|√
332 -|=PLSR2|√|√
316 +| |LX3V|LX5V
317 +|DRVI|√|√
318 +|DRVA|√|√
319 +|PLSR|√|√
320 +|PLSV|√|√
321 +|PLSY|√|√
322 +|DVIT|√|√
323 +|ZRN|√|√
324 +|PLSR2|√|√
333 333  
334 334  **High-speed pulse command difference.**
335 335  
... ... @@ -342,16 +342,16 @@
342 342  2. Comparison of bit devices
343 343  
344 344  (% class="table-bordered" %)
345 -|=(% scope="row" %)**3V**|=**Description**|=**5V**|=**Description**
346 -|=M8145|Y000 pulse output stop|SM898|Y000 pulse output stop
347 -|=M8146|Y001 Pulse output stop|SM958|Y001 Pulse output stop
348 -|=M8152|Y002 pulse output stop|SM1018|Y002 pulse output stop
349 -|=M8153|Y003 Pulse output stop|SM1078|Y003 Pulse output stop
350 -|=M8147|Y000 monitoring during pulse output|SM880|Y000 monitoring during pulse output
351 -|=M8148|Y001 Monitoring during pulse output|SM940|Y001 Monitoring during pulse output
352 -|=M8149|Y002 Monitoring during pulse output|SM1000|Y002 Monitoring during pulse output
353 -|=M8150|Y003 Monitoring during pulse output|SM1060|Y003 Monitoring during pulse output
354 -|=(% rowspan="4" %)(((
337 +|**3V**|**Description**|**5V**|**Description**
338 +|M8145|Y000 pulse output stop|SM898|Y000 pulse output stop
339 +|M8146|Y001 Pulse output stop|SM958|Y001 Pulse output stop
340 +|M8152|Y002 pulse output stop|SM1018|Y002 pulse output stop
341 +|M8153|Y003 Pulse output stop|SM1078|Y003 Pulse output stop
342 +|M8147|Y000 monitoring during pulse output|SM880|Y000 monitoring during pulse output
343 +|M8148|Y001 Monitoring during pulse output|SM940|Y001 Monitoring during pulse output
344 +|M8149|Y002 Monitoring during pulse output|SM1000|Y002 Monitoring during pulse output
345 +|M8150|Y003 Monitoring during pulse output|SM1060|Y003 Monitoring during pulse output
346 +|(% rowspan="4" %)(((
355 355  
356 356  
357 357  
... ... @@ -361,35 +361,35 @@
361 361  
362 362  Some instructions (PLSR, etc.) instruction execution completed (Y0-Y3)
363 363  )))|SM882|Y0 pulse sending completed
364 -|=SM942|Y1 pulse sending completed
365 -|=SM1002|Y2 pulse transmission completed
366 -|=SM1062|Y3 pulse transmission completed
367 -|=M8134|Y0's thousandth control bit|SM897|Y0's thousandth control bit
368 -|=M8135|(((
356 +|SM942|Y1 pulse sending completed
357 +|SM1002|Y2 pulse transmission completed
358 +|SM1062|Y3 pulse transmission completed
359 +|M8134|Y0's thousandth control bit|SM897|Y0's thousandth control bit
360 +|M8135|(((
369 369  The acceleration and deceleration time between each axis of Y1's thousandth control position positioning command is separated
370 370  )))|(((
371 371  SM957
372 372  )))|Y1 Perimeter control bit
373 -|=M8136|Y2 Perimeter control bit|SM1017|Y2 Perimeter control bit
374 -|=M8137|Y3 Perimeter control bit|SM1077|Y3 Perimeter control bit
365 +|M8136|Y2 Perimeter control bit|SM1017|Y2 Perimeter control bit
366 +|M8137|Y3 Perimeter control bit|SM1077|Y3 Perimeter control bit
375 375  
376 376  3. Comparison of word devices
377 377  
378 378  (% class="table-bordered" %)
379 -|=(% scope="row" %)**3V**|=**Description**|=**5V**|=**Description**
380 -|=D8104|Y0 acceleration and deceleration time (open M8135)|SD902/SD962|Y0 acceleration/deceleration time
381 -|=D8105|Y1 acceleration and deceleration time (open M8135)|SD1022/SD1082|Y1 acceleration/deceleration time
382 -|=D8106|Y2 acceleration and deceleration time (open M8135)|SD1142/SD1202|Y2 acceleration/deceleration time
383 -|=D8107|Y3 acceleration and deceleration time (open M8135)|SD1262/SD1322|Y3 acceleration/deceleration time
384 -|=D8140|Y000 Current position low|SD880|Y000 Current position low
385 -|=D8141|Y000 current position high|SD881|Y000 current position high
386 -|=D8142|Y001 Current position low|SD940|Y001 Current position low
387 -|=D8143|Y001 Current position high|SD941|Y001 Current position high
388 -|=D8150|Y002 current position low|SD1000|Y002 current position low
389 -|=D8151|Y002 current position high|SD1001|Y002 current position high
390 -|=D8152|Y003 Current position low|SD1060|Y003 Current position low
391 -|=D8153|Y003 Current position high|SD1061|Y003 Current position high
392 -|=(% rowspan="4" %)(((
371 +|**3V**|**Description**|**5V**|**Description**
372 +|D8104|Y0 acceleration and deceleration time (open M8135)|SD902/SD962|Y0 acceleration/deceleration time
373 +|D8105|Y1 acceleration and deceleration time (open M8135)|SD1022/SD1082|Y1 acceleration/deceleration time
374 +|D8106|Y2 acceleration and deceleration time (open M8135)|SD1142/SD1202|Y2 acceleration/deceleration time
375 +|D8107|Y3 acceleration and deceleration time (open M8135)|SD1262/SD1322|Y3 acceleration/deceleration time
376 +|D8140|Y000 Current position low|SD880|Y000 Current position low
377 +|D8141|Y000 current position high|SD881|Y000 current position high
378 +|D8142|Y001 Current position low|SD940|Y001 Current position low
379 +|D8143|Y001 Current position high|SD941|Y001 Current position high
380 +|D8150|Y002 current position low|SD1000|Y002 current position low
381 +|D8151|Y002 current position high|SD1001|Y002 current position high
382 +|D8152|Y003 Current position low|SD1060|Y003 Current position low
383 +|D8153|Y003 Current position high|SD1061|Y003 Current position high
384 +|(% rowspan="4" %)(((
393 393  
394 394  
395 395  
... ... @@ -400,10 +400,10 @@
400 400  
401 401  Y0-Y3 Paranoid speed (single word)
402 402  )))|SD900, SD901|Y0 Paranoid speed (double word)
403 -|=SD960, SD961|Y1 Paranoid speed (double word)
404 -|=SD1020, SD1021|Y2 Paranoid speed (double word)
405 -|=SD1080, SD1081|Y3 Paranoid speed (double word)
406 -|=(% rowspan="8" %)(((
395 +|SD960, SD961|Y1 Paranoid speed (double word)
396 +|SD1020, SD1021|Y2 Paranoid speed (double word)
397 +|SD1080, SD1081|Y3 Paranoid speed (double word)
398 +|(% rowspan="8" %)(((
407 407  
408 408  
409 409  
... ... @@ -418,14 +418,14 @@
418 418  
419 419  Y0-Y3 maximum frequency (double word)
420 420  )))|SD898|Y0 Maximum speed low
421 -|=SD899|Y0 Highest speed
422 -|=SD958|Y1 Maximum speed low
423 -|=SD959|Y1 Highest speed
424 -|=SD1018|Y2 Maximum speed low
425 -|=SD1019|Y2 Highest speed
426 -|=SD1078|Y3 Maximum speed low
427 -|=SD1079|Y3 Highest speed
428 -|=(% rowspan="4" %)(((
413 +|SD899|Y0 Highest speed
414 +|SD958|Y1 Maximum speed low
415 +|SD959|Y1 Highest speed
416 +|SD1018|Y2 Maximum speed low
417 +|SD1019|Y2 Highest speed
418 +|SD1078|Y3 Maximum speed low
419 +|SD1079|Y3 Highest speed
420 +|(% rowspan="4" %)(((
429 429  
430 430  
431 431  
... ... @@ -435,9 +435,9 @@
435 435  
436 436  4-axis acceleration/deceleration time (when M8135 is not turned on)
437 437  )))|SD902/SD962|Y0 acceleration/deceleration time
438 -|=SD1022/SD1082|Y1 acceleration/deceleration time
439 -|=SD1142/SD1202|Y2 acceleration/deceleration time
440 -|=SD1262/SD1322|Y3 acceleration/deceleration time
430 +|SD1022/SD1082|Y1 acceleration/deceleration time
431 +|SD1142/SD1202|Y2 acceleration/deceleration time
432 +|SD1262/SD1322|Y3 acceleration/deceleration time
441 441  
442 442   4. New features of high-speed pulse instructions on LX5V
443 443  
... ... @@ -463,7 +463,7 @@
463 463  
464 464  ⑨Support direction reversal (can set the forward direction to low level)
465 465  
466 -= **7 Communication function** =
458 += **8. Communication function** =
467 467  
468 468  **~1. Communication parameter configuration**
469 469  
... ... @@ -474,27 +474,27 @@
474 474  3V settings:
475 475  
476 476  (% class="table-bordered" %)
477 -|=(% scope="row" %)**protocol**|=**D8126 value setting**
478 -|=RS instruction (custom protocol)|00H
479 -|=HMI monitoring protocol (PLC protocol)|01H
480 -|=MODBUS-RTU slave|02H
481 -|=MODBUS-ASCII slave|03H
482 -|=N:N network communication protocol slave|04H
483 -|=RS instruction (custom protocol)|10H
484 -|=MODBUS-RTU master station|20H
485 -|=MODBUS-ASCII master station|30H
486 -|=N:N network communication protocol master station|40H
469 +|**protocol**|**D8126 value setting**
470 +|RS instruction (custom protocol)|00H
471 +|HMI monitoring protocol (PLC protocol)|01H
472 +|MODBUS-RTU slave|02H
473 +|MODBUS-ASCII slave|03H
474 +|N:N network communication protocol slave|04H
475 +|RS instruction (custom protocol)|10H
476 +|MODBUS-RTU master station|20H
477 +|MODBUS-ASCII master station|30H
478 +|N:N network communication protocol master station|40H
487 487  
488 488  5V settings:
489 489  
490 490  (% class="table-bordered" %)
491 -|=(% scope="row" %)**SD2592 value setting**|=**Protocol**
492 -|=0 H|Wecon Modbus slave
493 -|=2 H|ModbusRTU slave
494 -|=3 H|ModbusASCII slave
495 -|=10 H|User-defined protocol
496 -|=20 H|ModbusRTU master station
497 -|=30 H|(((
483 +|**SD2592 value setting**|**Protocol**
484 +|0 H|Wecon Modbus slave
485 +|2 H|ModbusRTU slave
486 +|3 H|ModbusASCII slave
487 +|10 H|User-defined protocol
488 +|20 H|ModbusRTU master station
489 +|30 H|(((
498 498  ModbusASCII master
499 499  
500 500  
... ... @@ -511,31 +511,34 @@
511 511  5V address:
512 512  
513 513  (% class="table-bordered" %)
514 -|=(% scope="row" %)Port|=Occupy|=(% style="width: 240px;" %)Address range|=(% style="width: 221px;" %)(((
506 +|Port|Occupy|(% style="width:240px" %)Address range|(% style="width:221px" %)(((
515 515  10 hex Register
516 -)))|=(((
508 +)))|(((
517 517  Total reserved land Address size
518 518  )))
519 -|=**Word address**| |(% style="width:240px" %) |(% style="width:221px" %) |
520 -|=T0~~T511|512 WORD|(% style="width:240px" %)0x0000-0x01ff|(% style="width:221px" %)0|1536
521 -|=C0~~C255|256 WORD|(% style="width:240px" %)0x0600-0x06ff|(% style="width:221px" %)1536|1024
522 -|=LC0~~LC255|512 WORD|(% style="width:240px" %)0x0A00-0x0BFF|(% style="width:221px" %)2560|1024
523 -|=HSC0~~HSC15|128 WORD|(% style="width:240px" %)0x0E00-0x0E1F|(% style="width:221px" %)3584|512
524 -|=D0~~D7999|8000 WORD|(% style="width:240px" %)0x1000-0x2F3F|(% style="width:221px" %)4096|16384
525 -|=SD0~~SD4095|4096 WORD|(% style="width:240px" %)0x5000-0x5FFF|(% style="width:221px" %)20480|12288
526 -|=R0~~R30000|30000 WORD|(% style="width:240px" %)0x8000-0xF52F|(% style="width:221px" %)32768|30000
527 -|=**Bit address**| |(% style="width:240px" %) |(% style="width:221px" %) |
528 -|=T0~~T511|512 bit|(% style="width:240px" %)0x0000-0x01ff|(% style="width:221px" %) |1536
529 -|=C0~~C255|256 bit|(% style="width:240px" %)0x0600-0x06ff|(% style="width:221px" %)1536|1024
530 -|=LC0~~LC255|256 bit|(% style="width:240px" %)0x0A00-0x0AFF|(% style="width:221px" %)2560|1024
531 -|=HSC0~~HSC15|64 bit|(% style="width:240px" %)0x0E00-0x0E0F|(% style="width:221px" %)3584|512
532 -|=M0~~M8000|8192bit|(% style="width:240px" %)0x1000-0x2F3F|(% style="width:221px" %)4096|16384
533 -|=SM0~~SM4095|4096bit|(% style="width:240px" %)0x5000-0x5FFF|(% style="width:221px" %)20480|12288
534 -|=Reserved| |(% style="width:240px" %)0x8000-0xBFFF|(% style="width:221px" %) |16383
535 -|=S0~~S4095|4096bit|(% style="width:240px" %)0xC000-0xCFFF|(% style="width:221px" %)49152|8192
536 -|=X0~~X1023|1024bit|(% style="width:240px" %)0xE000-0xE3FF|(% style="width:221px" %)57344|4096
537 -|=Y0~~Y1023|1024bit|(% style="width:240px" %)0xF000-0xF3FF|(% style="width:221px" %)61440|4096
511 +|**Word address**| |(% style="width:240px" %) |(% style="width:221px" %) |
512 +|T0~~T511|512 WORD|(% style="width:240px" %)0x0000-0x01ff|(% style="width:221px" %)0|1536
513 +|C0~~C255|256 WORD|(% style="width:240px" %)0x0600-0x06ff|(% style="width:221px" %)1536|1024
514 +|LC0~~LC255|512 WORD|(% style="width:240px" %)0x0A00-0x0BFF|(% style="width:221px" %)2560|1024
515 +|HSC0~~HSC15|128 WORD|(% style="width:240px" %)0x0E00-0x0E1F|(% style="width:221px" %)3584|512
516 +|D0~~D7999|8000 WORD|(% style="width:240px" %)0x1000-0x2F3F|(% style="width:221px" %)4096|16384
517 +|SD0~~SD4095|4096 WORD|(% style="width:240px" %)0x5000-0x5FFF|(% style="width:221px" %)20480|12288
518 +|R0~~R30000|30000 WORD|(% style="width:240px" %)0x8000-0xF52F|(% style="width:221px" %)32768|30000
519 +|**Bit address**| |(% style="width:240px" %) |(% style="width:221px" %) |
520 +|T0~~T511|512 bit|(% style="width:240px" %)0x0000-0x01ff|(% style="width:221px" %) |1536
521 +|C0~~C255|256 bit|(% style="width:240px" %)0x0600-0x06ff|(% style="width:221px" %)1536|1024
522 +|LC0~~LC255|256 bit|(% style="width:240px" %)0x0A00-0x0AFF|(% style="width:221px" %)2560|1024
523 +|HSC0~~HSC15|64 bit|(% style="width:240px" %)0x0E00-0x0E0F|(% style="width:221px" %)3584|512
524 +|M0~~M8000|8192bit|(% style="width:240px" %)0x1000-0x2F3F|(% style="width:221px" %)4096|16384
525 +|SM0~~SM4095|4096bit|(% style="width:240px" %)0x5000-0x5FFF|(% style="width:221px" %)20480|12288
526 +|Reserved| |(% style="width:240px" %)0x8000-0xBFFF|(% style="width:221px" %) |16383
527 +|S0~~S4095|4096bit|(% style="width:240px" %)0xC000-0xCFFF|(% style="width:221px" %)49152|8192
528 +|X0~~X1023|1024bit|(% style="width:240px" %)0xE000-0xE3FF|(% style="width:221px" %)57344|4096
529 +|Y0~~Y1023|1024bit|(% style="width:240px" %)0xF000-0xF3FF|(% style="width:221px" %)61440|4096
538 538  
539 539  **5. LX5V added functions**
540 540  
541 541  Modify serial communication parameters during RUN. For example, use PROTOCOL instruction to modify the protocol during run. The corresponding instruction description can also find the method of setting without instruction. For details, please refer to the relevant instructions of the instruction. Commands are PROTOCOL (set serial port protocol), PROTPARA (set serial port parameters), STATION (set station number)
534 +
535 +
536 +