Wiki source code of 04 Program flow instructions

Version 2.1 by Stone Wu on 2022/06/15 11:26

Show last authors
1 = **Program jump** =
2
3 == {{id name="_Toc102982428"/}}{{id name="_Toc17621"/}}{{id name="_Toc871"/}}{{id name="_Toc23743"/}}**CJ/Conditional jump** ==
4
5 When the jump instruction is ON, the program with the specified pointer number in the same program file is executed.
6
7 -[CJ (P) (P)]
8
9 **Content, range and data type**
10
11 (% class="table-bordered" %)
12 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
13 |(P)|The pointer number of the jump target|P0 to P4095|Device name|POINTER
14
15 **Device used**
16
17 (% class="table-bordered" %)
18 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(((
19 **Offset modification**
20 )))|(((
21 **Pulse extension**
22 )))|**other**
23 |**[D]**|**XXP**|**P**
24 |CJ|Parameter 1| |●|●
25
26 **Features**
27
28 * CJ(P)
29
30 {{id name="OLE_LINK159"/}}When the execution instruction is ON, the program with the specified pointer number is executed.
31
32 When the execution instruction is OFF, execute the next program.
33
34 (% style="text-align:center" %)
35 [[image:4_html_a501306a22b46191.png||class="img-thumbnail"]]
36
37 1. Execute instructions.
38 1. Each scan is executed.
39 1. One scan is executed.
40
41 **✎Note: **
42
43 After turning ON the coil of the timer, if the timer whose coil is ON is jumped by the CJ(P) instruction, the measurement will not be performed normally.
44
45 When the OUT instruction is jumped by the CJ(P) instruction, the scan time will be shorter.
46
47 When the CJ(P) instruction is used to jump backward, the scan time will be longer.
48
49 For the CJ(P) instruction, you can jump to a step smaller than the step number being executed. However, in order to avoid the time limit of the watchdog timer, a method of jumping out of the loop during this period should be considered.
50
51 (((
52 (% style="text-align:center" %)
53 [[image:4-2.png||class="img-thumbnail"]]
54
55 (1) While X3 is ON, the loop is executed.
56
57 (2) When X7 is set to ON, it jumps out of the loop.
58 )))
59
60 • The device skipped by the CJ(P) instruction does not change.
61
62 (((
63 When X2 is ON, jump to the label of P19.
64
65 Even if X2 and X4 turn ON/OFF during CJ instruction execution, Y4 and Y5 will not change.
66
67 (% style="text-align:center" %)
68 [[image:1652258381961-360.png||class="img-thumbnail"]]
69
70 (1) When X2 is ON, jump to the label of P19.
71
72 (2) Even if X2 and X4 turn ON/OFF during CJ instruction execution, Y4 and Y5 will not change.
73 )))
74
75 • The label (P□) occupies 1 step.
76
77 (% style="text-align:center" %)
78 [[image:4_html_624bb12f51649fa1.gif||class="img-thumbnail"]]
79
80 The jump instruction can only specify the pointer number in the same program file.
81
82 When jumping to the pointer number within the jump range during jump operation, the program after the jump destination pointer number is executed.
83
84 The label procedure is shown below. When creating a loop program, move the cursor to the left of the bus bar of the Circuit program, and enter the label (P) at the beginning of the loop block.
85
86 (% style="text-align:center" %)
87 [[image:4_html_66293951b95227d4.png||class="img-thumbnail"]]
88
89 It is also possible to program the label at the position where the step number is less than the CJ instruction, but if the scan time becomes more than 200ms (default setting), a watchdog timer error will occur, which requires attention.
90
91 (% style="text-align:center" %)
92 [[image:1652258541371-747.png||class="img-thumbnail"]]
93
94 When the pointer number in the operand is the same and the label is one, the operation is as follows.
95
96 (((
97 (% style="text-align:center" %)
98 [[image:1652258590342-123.png||class="img-thumbnail"]]
99
100 (1) When X20 is ON, jump from the CJ instruction of X20 to label P9.
101
102 (2) When X20 is OFF and X21 is ON, jump from the CJ instruction of X21 to label P9.
103 )))
104
105 If the tag number is reused, it will become an error state.
106
107 (% style="text-align:center" %)
108 [[image:4_html_8fb019c9369040bb.gif||class="img-thumbnail"]]
109
110 SM100 is always ON during the operation of the CPU module, so the usage method shown below will jump unconditionally.
111
112 (% style="text-align:center" %)
113 [[image:4_html_595b9dbff9fae7fc.png||class="img-thumbnail"]]
114
115 The pointer number P63 of LX3V represents the jump to the END instruction. The P63 pointer of LX5V no longer provides this function. If you need to use this function, please use the GOEND instruction.
116
117 **Error code**
118
119 No error message
120
121 **Example**
122
123 **(1) The situation to jump after OFF processing**
124
125 After one operation cycle when X023 changes from OFF to ON, the CJ P7 instruction is valid.
126
127 With this method, the output between CJ P7 instruction and mark P7 can be turned off before jumping.
128
129 (% style="text-align:center" %)
130 [[image:4_html_e09161008c47ac30.png||class="img-thumbnail"]]
131
132 **(2) CJ instruction and action of contact coil**
133
134 In the following program example, when X000 is ON, jump from the CJ instruction of the first loop to the mark P8. When X000 is OFF, no jump is performed, but the program is executed in order from step 1, and the CJ instruction in the 11th loop jumps to mark P9. The jumped instruction is not executed.
135
136 (((
137 (% style="text-align:center" %)
138 [[image:4_html_e0d34198cc559166.png||class="img-thumbnail"]]
139
140 Double-coil action of Y001 output:
141
142 When X000=OFF, it will act through X001.
143
144 When X000=ON, it will act through X012.
145
146 Even if the program is distinguished by conditional jump, if the same coil (Y000) is programmed twice or more within or outside the jump, it will be treated as normal double coil processing.
147
148 The action of the subroutine timer (T192 to T199):
149
150 After the coil is driven, the action continues even if it jumps, and the output contact also operates.
151
152 If using the high-speed counter (HSC0 to HSC7) operation
153
154 After the coil is driven, the action continues even if it jumps, and the output contact also operates.
155 )))
156
157 In the above program, if each input changes during the jump, the action of each coil is shown in the following table.
158
159 (% class="table-bordered" %)
160 |(% style="width:235px" %)**Content**|(% style="width:292px" %)**Contact state before jump**|(% style="width:549px" %)**Coil action in jump**
161 |(% rowspan="2" style="width:235px" %)(((
162 Y,M,S (Y1, M1, S1)
163 )))|(% style="width:292px" %)X1, X2, X3 OFF|(% style="width:549px" %)Y1, M1, S1 OFF
164 |(% style="width:292px" %)X1, X2, X3 ON|(% style="width:549px" %)Y1, M1, S1 ON
165 |(% rowspan="2" style="width:235px" %)(((
166 1ms, 10ms, 100ms timer (T0)
167 )))|(% style="width:292px" %)X4 OFF|(% style="width:549px" %)Timer not working
168 |(% style="width:292px" %)X4 ON|(% style="width:549px" %)Timer interrupt (continue after X0 OFF)
169 |(% rowspan="2" style="width:235px" %)(((
170 Program timer (T192)
171 )))|(% style="width:292px" %)X5 OFF, X6 OFF|(% style="width:549px" %)Timer not working, but the timer is reset when X13 is ON
172 |(% style="width:292px" %)X5 OFF, X6 ON|(% style="width:549px" %)Timing continues (contact action after X0 OFF)
173 |(% rowspan="2" style="width:235px" %)(((
174 Counter (C0)
175 )))|(% style="width:292px" %)X7 OFF, X10 OFF|(% style="width:549px" %){{id name="OLE_LINK160"/}}Counting interrupt, but it is reset when X13 is ON
176 |(% style="width:292px" %)X7 OFF, X10 ON|(% style="width:549px" %)Count interruption (continue after X0 OFF)
177 |(% rowspan="2" style="width:235px" %)(((
178 Application instructions
179
180 (MOV)
181 )))|(% style="width:292px" %)X11 OFF|(% rowspan="2" style="width:549px" %)(((
182 Single-cycle application instructions are not executed in the jump
183
184 Multi-cycle application instructions are partially executable (such as high-speed pulse instructions)
185 )))
186 |(% style="width:292px" %)X11 ON
187
188 **(3) The relationship between CJ instruction and MC to MCR jump**
189
190 The relationship between the main control instruction and the jump instruction and the action content are as follows.
191
192 However, since the operation of ②, ④, and ⑤ will become complicated, please avoid using them.
193
194 (% style="text-align:center" %)
195 [[image:4_html_679b6b2848540f73.png||class="img-thumbnail"]]
196
197 = {{id name="_Toc23403"/}}**Subroutine jump** =
198
199 == {{id name="_Toc12697"/}}**{{id name="_Toc7169"/}}{{id name="_Toc17038"/}}{{id name="_Toc102982430"/}}CALL/Subroutine call** ==
200
201 When the jump instruction is ON, the program with the specified pointer number in the same program file is executed.
202
203 -[CALL (P) (P)]
204
205 **Content, range and data type**
206
207 (% class="table-bordered" %)
208 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
209 |(P)|Subroutine name|-|Pointer|POINTER
210
211 **Device used**
212
213 (% class="table-bordered" %)
214 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(((
215 **Offset modification**
216 )))|(((
217 **Pulse extension**
218 )))|**other**
219 |**[D]**|**XXP**|(((
220 **Subroutine**
221
222 **name**
223 )))
224 |CALL|Parameter 1| |●|●
225
226 Parameter 1 can only use the subroutine name.
227
228 **Features**
229
230 When the CALL(P) instruction is executed, the subroutine of the pointer (P) will be executed. (P) can only write the name of the newly created subprogram, if the program name does not exist, the Circuit program compilation fails.
231
232 (% style="text-align:center" %)
233 [[image:4_html_8924f686c859efa4.png||class="img-thumbnail"]]
234
235 (% style="text-align:center" %)
236 [[image:4_html_60fa80c6a001beb0.gif||class="img-thumbnail"]]
237
238 CALL(P) instructions can be nested up to 32 levels.
239
240 (% style="text-align:center" %)
241 [[image:4_html_29c8e378dfb34066.png||class="img-thumbnail"]]
242
243 **✎Note: **
244
245 • Multiple CALL(P) instructions can call the same subprogram, but subprograms with the same program name are not allowed.
246
247 • Use program timers in subroutines (the same applies to interrupt programs). This timer counts when the coil instruction or the END instruction is executed. If it reaches the timer setting value, the output contact will act when the coil instruction or END instruction is executed. Generally, the timer only counts when the coil instruction is executed, so if it is used in a subroutine that executes the coil instruction under certain conditions, it will not count.
248
249 • If the 1ms accumulative timer is used in a subroutine (the same in an interrupt program), when it reaches the set value, the output contact will act when the first coil instruction is executed (when the subroutine is executed), so be careful.
250
251 • The devices that are turned on in the subprogram (the same in the interrupt program) will be retained after the program ends. Therefore, these devices should be reset in the main program after the end of the program.
252
253 **Error code**
254
255 (% class="table-bordered" %)
256 |**Error code**|**Content**
257 |4102H|CALL(P) instruction exceeds 32 levels of nesting structure
258
259 **Example**
260
261 **(1) New subroutine**
262
263 Project management→Subroutine→ Scan→Right click to create
264
265 (% style="text-align:center" %)
266 [[image:4_html_3d0d21476f0bb476.png||class="img-thumbnail"]]
267
268 **(2) Subroutine call**
269
270 (% style="text-align:center" %)
271 [[image:4_html_474fbc929fb22b37.png||class="img-thumbnail"]]
272
273 In the scan program, turn on M10 to call the subroutine SUB0, execute the Circuit program in the subroutine SUB0, until the END instruction of the subroutine is executed, return to the scan program MAIN to execute LD M11.
274
275 **(3) Subroutine nesting**
276
277 (% style="text-align:center" %)
278 [[image:4_html_d7bf03e5f06b73a8.png||class="img-thumbnail"]]
279
280 In the above figure, the subroutine SUB0 is called in the scan program, and the subroutine SUB1 is called in SUB0. So when the scan program M10 is turned on, after the CALL instruction is executed, the subroutine SUB0 will be executed first.And after the CALL instruction of SUB0 is executed, SUB1 will be executed first. After executing the END instruction of SUB1, return to SUB0 for execution. After executing the END instruction of SUB0, return to the scan program MAIN. The program has only 2 levels of nesting, and the number of nesting levels cannot be greater than 32.
281
282 = {{id name="_Toc8930"/}}**Interrupt disable, interrupt enable** =
283
284 == {{id name="_Toc102982432"/}}**DI and EI/Interrupt prohibited and allowed** ==
285
286 The CPU module is usually interrupt disabled. This instruction can make the CPU module into the interrupt enabled state (EI instruction), and then become disabled again (DI instruction).
287
288 • DI: It is forbidden to interrupt program execution.
289
290 • EI: Release the interrupt prohibition state.
291
292 -[DI (s)]
293
294 -[EI]
295
296 **Content, range and data type**
297
298 (% class="table-bordered" %)
299 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
300 |(P)|Subroutine name|-|Pointer|POINTER
301
302 (% class="table-bordered" %)
303 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|**Offset modification**|**Pulse extension**
304 |**[D]**|**XXP**
305 |DI|Parameter 1| |●
306
307 **{{id name="OLE_LINK161"/}}Features**
308
309 * DI
310
311 • Even if the execution interrupt condition is triggered in the program, prohibit the interrupt program execution before executing the EI instruction.
312
313 • When the PLC is powered on or after STOP, it will become the state after DI instruction is executed, and the interrupt program cannot be executed.
314
315 • The DI instruction can choose whether to use parameters. When there is no parameter, it means that all interrupt programs are prohibited. With parameters, according to the value in parameter s1, interrupt programs with this priority and lower priority are prohibited.
316
317 • The priority of the interrupt ranges from 0 to 2. The smaller the value, the higher the response priority of the interrupt. That is, the interrupt with priority 0 is the fastest to be responded.
318
319 • If there is no EI instruction before the DI instruction, the DI instruction is invalid.
320
321 * EI
322
323 • Release the interrupt prohibition state when DI instruction is executed, and allow interrupt program to run.
324
325 • When the EI and DI instructions are not enabled, they all maintain the original enabled or forbidden interrupt program execution status. The currently disabled interrupt priority can be viewed in SD151.
326
327 (% class="table-bordered" %)
328 |SD151|Currently disabled interrupt priority|(((
329 According to the interrupt prohibition instruction (DI instruction), the interrupt prohibition instruction (DI instruction) below the specified priority, and the interrupt enable instruction (EI instruction), the priority of the interrupt prohibition will be stored.
330
331 0: All priority interrupts are disabled (default);
332
333 1: Priority 1 and 2 interrupts are prohibited;
334
335 2: Priority 2 interrupt is prohibited;
336
337 3: All priority interrupts are allowed
338 )))|R(read only)
339
340 A: Sequence control program
341
342 * DI, EI nested structure
343
344 (((
345 (1) Interrupt allowable intervals of all priority levels;
346
347 (2) Interrupt forbidden zone below priority 2 (interrupt allowable zone above priority 1);
348
349 (3) Interrupt forbidden interval below priority 1 (interrupt allowable interval above priority 0);
350
351 (4) Interrupt prohibition zone below priority 2 (interrupt enable zone above priority 1);
352
353 (5) Interrupt allowable intervals of all priority levels;
354
355 (6) EI paired with [DI K1];
356
357 (7) EI paired with [DI K2].
358
359 (% style="text-align:center" %)
360 [[image:4_html_a573e3db41c8e5e9.png||class="img-thumbnail"]]
361 )))
362
363 • Interrupts (requests) that occur after the DI instruction are processed after the EI instruction is executed.
364
365 • When the DI instruction is executed multiple times and the priority of the argument is specified to be higher than the priority currently being prohibited, interrupts below the priority of the argument are disabled.
366
367 • When the DI instruction is executed multiple times and the priority of the argument is specified to be lower than the priority currently being disabled, the interrupt disable status will not be changed.
368
369 • The nesting of DI instructions can be up to 16 levels.
370
371 • The interrupt priority of the interrupt pointer can be set by the properties of the interrupt program. Refer to the description of the interrupt program for details.
372
373 • The interrupt prohibition interval when DI instruction and EI instruction are executed is as follows.
374
375 **(1) When the DI instruction is executed multiple times (when the interrupt with priority higher than the currently prohibited interrupt priority is prohibited and specified)**
376
377 (% style="text-align:center" %)
378 [[image:4_html_c7e0f7f383d45a1b.png||class="img-thumbnail"]]
379
380 Scan execution type program
381
382 1. Interrupt allowable intervals of all priority levels;
383 1. Interrupt prohibition interval below priority 2 (interrupt allowable interval above priority 1);
384 1. Interrupt prohibition section below priority 1 (interrupt enable section above priority 0).
385
386 **(2) When the DI instruction is executed multiple times (when the interrupt priority is lower than the currently prohibited interrupt priority is prohibited and specified)**
387
388 (% style="text-align:center" %)
389 [[image:4_html_aad79b3250e8a24b.png||class="img-thumbnail"]]
390
391 Scan execution type program
392
393 1. Interrupt allowable intervals of all priority levels;
394 1. Interrupt prohibited interval below priority 1 (interrupt allowable interval above priority 0);
395 1. The interrupts below priority 1 are already in the disabled state, so the interrupt disable priority will not be changed.
396
397 **(3) When DI instruction is executed through interrupt program**
398
399 (% style="text-align:center" %)
400 [[image:4_html_a6d7521496fdd1f8.png||class="img-thumbnail"]]
401
402 A: Scan execution type program
403
404 B: interrupt program
405
406 1. Interrupt allowable intervals of all priority levels;
407 1. Interrupt prohibited interval below priority 3 (interrupt allowable interval above priority 1);
408 1. Interrupt prohibition section below priority 2 (interrupt enable section above priority 0).
409
410 **(4) When only DI instructions without arguments are executed**
411
412 (% style="text-align:center" %)
413 [[image:4_html_606dbe3d93909e42.png||class="img-thumbnail"]]
414
415 A: Scan execution type program
416
417 1. Interrupt allowable intervals of all priority levels;
418 1. Interrupt prohibition interval below priority 1 (all interrupt prohibition intervals);
419 1. Because the DI instruction with no argument is set to interrupt prohibition, by executing the EI instruction once, all priority interrupts are set to allow.
420
421 **(5) In the case of executing DI instructions with arguments and DI instructions without arguments (when executing in the order of DI instructions with arguments → DI instructions without arguments)**
422
423 (% style="text-align:center" %)
424 [[image:4_html_b9b528491258d0e4.png||class="img-thumbnail"]]
425
426 A: Scan execution type program
427
428 1. Interrupt allowable intervals of all priority levels;
429 1. Interrupt prohibition interval below priority 2 (interrupt allowable interval above priority 1);
430 1. Interrupt prohibition section below priority 1 (all interrupt prohibition sections).
431
432 **(6) In the case of executing DI instructions with arguments and DI instructions without arguments (in the case of execution in the order of DI instructions with no arguments → DI instructions with arguments)**
433
434 (% style="text-align:center" %)
435 [[image:4_html_622cf36b6bdc523.png||class="img-thumbnail"]]
436
437 {{id name="_Toc11636"/}}A: Scan execution type program
438
439 1. Interrupt allowable intervals of all priority levels;
440 1. Interrupt prohibition section below priority 1 (all interrupt prohibition sections).
441
442 **Error code**
443
444 (% class="table-bordered" %)
445 |**Error code**|**Content**
446 |4085H|(S) read address exceeds the device range
447 |4084H|The data set in (S) exceeds 0 to 2
448 |4185H|When the nesting of DI instructions exceeds 16 levels
449
450 **Example**
451
452 (((
453 (% style="text-align:center" %)
454 [[image:4_html_e068a061529263d1.png||class="img-thumbnail"]]
455
456 All interrupt programs can be triggered
457
458 Can trigger interrupt programs of priority 0 and priority 1
459
460 Can trigger interrupts with priority 0
461
462 Cannot trigger any interrupts
463
464 Can trigger an interrupt program with a priority of 0
465
466 Can trigger interrupt programs with priority 0 and priority 1
467 )))
468
469 == {{id name="_Toc2335"/}}**SIMASK/Interrupt mask** ==
470
471 Set interrupt pointer No. specified in (I) to the execution permission state/execution prohibition state according to the value of (s).
472
473 -[SIMASK (I) (s)]
474
475 **Content, range and data type**
476
477 (% class="table-bordered" %)
478 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
479 |(I)|Interrupt program name|-|Program name|POINTER
480 |(s)|Specify the enable/disable of interrupt|0: Allow. 1: Prohibited|Signed BIN 16 bit|ANY16
481
482 **Device used**
483
484 (% class="table-bordered" %)
485 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="12" %)**Devices**|(((
486 **Offset**
487
488 **modification**
489 )))|(((
490 **Pulse**
491
492 **extension**
493 )))
494 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP**
495 |(% rowspan="2" %)SIMASK|Parameter 1|(% colspan="12" %)Only support interrupt program name| |
496 |Parameter 2|●|●|●|●|●|●|●|●|●|●|●|●|●|
497
498 **Features**
499
500 • The interrupt program of the interrupt program name specified in (I) is set to the execution permission state/execution prohibited state according to the data specified in (s).
501
502 • When (s) is 0: Interrupt program execution permission status
503
504 • When (s) is 1, the execution of the interrupt program is prohibited
505
506 • Regarding the interrupt program when the power is turned on or after STOP→RUN, all interrupt programs will be executed.
507
508 • After setting interrupt prohibition, the prohibition state will be saved even if the instruction is disconnected. To restore it, write 0 to (S), turn on the instruction again, or execute STOP→RUN.
509
510 • The interrupted execution permission status/execution prohibition status will be stored in SM or SD, details as following:
511
512 **{{id name="_Toc10728"/}}(1) External interrupt**
513
514 (((
515 (% class="table-bordered" %)
516 |**Register**|**Content**|**Register**|**Content**|**Register**|**Content**|**Register**|**Content**
517 |SM352|X0 rising edge interrupt|SM356|X2 rising edge interrupt|SM360|X4 rising edge interrupt|SM364|X6 rising edge interrupt
518 |SM353|X0 falling edge interrupt|SM357|X2 falling edge interrupt|SM361|X4 falling edge interrupt|SM365|X6 falling edge interrupt
519 |SM354|X1 rising edge interrupt|SM358|X3 rising edge interrupt|SM362|X5 rising edge interrupt|SM366|X7 rising edge interrupt
520 |SM355|X1 falling edge interrupt|SM359|X3 falling edge interrupt|SM363|X5 falling edge interrupt|SM367|X7 falling edge interrupt
521 )))
522
523 **(2) Timer interrupt**
524
525 (% class="table-bordered" %)
526 |**Register**|**Content**
527 |SD350 to SD356|Timer interrupt mask, each bit represents an interrupt, a total of 100
528
529 **(3) High-speed counter interrupt**
530
531 (% class="table-bordered" %)
532 |**Register**|**Content**
533 |SD382 to SD388|high-speed counter interrupt mask, each bit represents an interrupt, a total of 100
534
535 **Error code**
536
537 (% class="table-bordered" %)
538 |**Error code**|**Content**
539 |4084H|Data beyond 0 and 1 is input in the application instruction(s)
540 |4085H|(S) in the read application instruction exceeds the device range
541 |4189H|The SIMASK instruction specifies an interrupt program name that is not set
542
543 **Example**
544
545 (((
546 (% style="text-align:center" %)
547 [[image:4_html_fd3e8efafb82209a.png||class="img-thumbnail"]]
548
549 As shown in the figure: when M10 is turned on, the three interrupt programs of INT10, INT91 and INT70 are prohibited from running.
550 )))
551
552 = {{id name="_Toc15333"/}}**Cycle instructions** =
553
554 == {{id name="_Toc102982435"/}}**FOR to NEXT/Cycle** ==
555
556 When the processing between the FOR to NEXT instruction is executed unconditionally (n) times, the next processing of the NEXT instruction will be performed.
557
558 (% style="text-align:center" %)
559 [[image:4_html_bdecdd2d7f545f5b.gif||class="img-thumbnail"]]
560
561 **Content, range and data type**
562
563 (% class="table-bordered" %)
564 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
565 |(n)|Number of repetitions between FOR to NEXT instructions|1 to 32767|Signed BIN 16 bit|ANY16
566
567 (% class="table-bordered" %)
568 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="12" %)**Devices**|(((
569 **Offset**
570
571 **modification**
572 )))|(((
573 **Pulse**
574
575 **extension**
576 )))
577 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP**
578 |FOR|Parameter 1|●|●|●|●|●|●|●|●|●|●|●|●|●|
579
580 **Features**
581
582 • When the processing between the FOR to NEXT instruction is executed unconditionally (n) times, the next processing of the NEXT instruction will be performed.
583
584 • (n) can be specified in the range of 1 to 32767. When specifying -32768 to 0, the same processing as (n)=1 will be performed.
585
586 • If you do not want to execute the processing between the FOR and NEXT instructions, use the CJ instruction to jump.
587
588 • The FOR instruction can be nested up to 5 levels.
589
590 **✎Note: **
591
592 • In the case of FOR to NEXT instruction programming with nesting between FOR to NEXT instructions, up to 5 levels can be achieved.
593
594 (% style="text-align:center" %)
595 [[image:4_html_df140146b29101ab.png||class="img-thumbnail"]]
596
597 • Do not use IRET, SRET, RET, FEND, END and other instructions to block between FOR to NEXT instructions.
598
599 • If the number of repetitions is too large, the cycle time (operation cycle) becomes longer and the watchdog timer error occurs, you need to change the watchdog timer time or reset the watchdog timer.
600
601 • The following program will become an error.
602
603 (% style="text-align:center" %)
604 [[image:4_html_3646fec26f307e30.gif||class="img-thumbnail"]]
605
606 • If the FOR to NEXT instruction is repeatedly executed and ends midway, use the BREAK instruction.
607
608 **Error code**
609
610 (% class="table-bordered" %)
611 |**Error code**|**Content**
612 |4085H|(s) read address exceeds the device range
613 |4100H|When the nesting of FOR to NEXT instructions exceeds 5 levels or the number of FOR to NEXT does not correspond
614
615 **Example**
616
617 (% style="text-align:center" %)
618 [[image:4_html_cf327fbe235812df.png||class="img-thumbnail"]]
619
620 The program INC D0 will be executed 10 times, and INC D1 will be executed 100 times.
621
622 After execution, D0 will be equal to 10 and D1 will be equal to 100.
623
624 == {{id name="_Toc102982436"/}}**BREAK/Break cycle** ==
625
626 When the processing between the FOR to NEXT instruction is executed unconditionally (n) times, the next processing of the NEXT instruction will be performed.
627
628 -[BREAK]
629
630 **Features**
631
632 • Forcibly end the repeated processing by FOR to NEXT instructions.
633
634 • This instruction can only be between FOR to NEXT, otherwise an operation error will be reported.
635
636 • The BREAK instruction can only jump out of the loop nesting structure where the instruction itself is located.
637
638 • When the contact is connected, the loop structure of the FOR to NEXT instruction where it is located is forced to end, as shown in the figure below.
639
640 (((
641 (% style="text-align:center" %)
642 [[image:4_html_c83826b59b86eb5a.png||class="img-thumbnail"]]
643
644 M0 turns ON, no matter how many cycles are left to execute, jump directly to step 35 to execute the program.
645
646 M4 turns ON, no matter how many loops are left to execute, jump directly to step 50 to execute the program.
647 )))
648
649 **Error code**
650
651 (% class="table-bordered" %)
652 |**Error code**|**Content**
653 |4186H|{{id name="OLE_LINK163"/}}BREAK instruction is not used between FOR to NEXT instructions
654
655 **Example**
656
657 (% style="text-align:center" %)
658 [[image:4_html_300cc2cbd41e93af.png||class="img-thumbnail"]]
659
660 The program INC D0 will be executed 10 times, and INC D1 will be executed 100 times.
661
662 When M0 is OFF, D0 will be equal to 10 and D1 will be equal to 100 after execution.
663
664 When M0 is ON, the BREAK instruction is executed, and the current loop is exited. The INC D1 instruction will not be executed, and the result D1=0.
665
666 = {{id name="_Toc21268"/}}**Master Control Instructions** =
667
668 == {{id name="_Toc102982438"/}}{{id name="_Toc25408"/}}{{id name="_Toc22131"/}}{{id name="_Toc6021"/}}**MC and MCR instructions** ==
669
670 • MC: Start main control.
671
672 • MCR: End the main control.
673
674 (% style="text-align:center" %)
675 [[image:4_html_6f51bb3cb7d2ba4f.png||class="img-thumbnail"]]
676
677 **Content, range and data type**
678
679 (% class="table-bordered" %)
680 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
681 |(N)|Nested ID N|0 to 7|Signed BIN 16 bit|ANY16
682 |(d)|Device number that is turned ON|-|Bit|ANY_BOOL
683
684 (% class="table-bordered" %)
685 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="12" %)**Devices**|**Offset modification**|**Pulse extension**
686 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP**
687 |(% rowspan="2" %)MC|Parameter1|(% colspan="12" %)Only use N0 to N7| |
688 |Parameter2|●|●|●|●|●|●|●|●|●|●|●|●| |
689 |MCR|Parameter1|(% colspan="12" %)Only use N0 to N7| |
690
691 **Features**
692
693 The main control instruction is used to create an efficient circuit program switching program by opening and closing the common bus of the circuit program.
694
695 The transition of ordinary Circuit program and master control Circuit program is as follows:
696
697 (((
698 (% style="text-align:center" %)
699 [[image:4_html_43089229889e1c0c.png||class="img-thumbnail"]]
700 )))
701
702 MC to MCR internal program, X0 must be open to execute
703
704 ■MC
705
706 • When the execution instruction of the MC instruction is turned on by the start of main control, the operation result from the start of the MC instruction to the MCR instruction is the execution result of the instruction (loop). When the MC execution instruction is OFF, the calculation results from the MC instruction to the MCR instruction are as follows.
707
708 (% class="table-bordered" %)
709 |**Devices**|**Device status**
710 |Timer|The count value becomes 0, and the coil and contact are all turned off.
711 |Counter, cumulative timer|The coil turns off, but the count value and contact remain in the current state.
712 |Devices in the OUT instruction|Forced to be OFF.
713 |(((
714 Devices in SET and RST instruction
715
716 Devices in basic and application instructions
717 )))|Keep the current state
718
719 • For MC instructions, the same nesting (N) number can be used multiple times by changing the device of (d).
720
721 • When the MC instruction is ON, the coil of the device specified in (d) will turn ON. In addition, when the same device is used in an OUT instruction, etc., it becomes a double coil. Therefore, the device specified in (d) must not be used in other instructions.
722
723 **Key points:**
724
725 If there are instructions that do not require contact (such as, FOR to NEXT instructions).If the instruction after MC can not affect the main CPU module, the instruction will execute.
726
727 ■MCR
728
729 • The release instruction of the main control indicates the end of the main control range.
730
731 • Do not add a contact instruction before the MCR instruction.
732
733 • When using, MC instruction and MCR instruction of the same nesting number should be used. However, when the MCR instruction has a nested structure concentrated in one position, all main controls can be terminated by the smallest number (N) number. (Refer to notes)
734
735 ■Nested structure
736
737 The main control instruction can be used through a nested structure. Each main control section is distinguished by nesting (N). N0 to N7 can be used for nesting.
738
739 By using the nested structure, it is possible to create a Circuit program that sequentially restricts the execution conditions of the program. The Circuit program using the nested structure is shown below.
740
741 (Left: Display of engineering tools, Right: Actual action loop)
742
743 (% style="text-align:center" %)
744 [[image:1652259670879-365.png||class="img-thumbnail"]]
745
746 1. Execute when A is ON;
747 1. Execute when A and B are ON;
748 1. Execute when A, B, C are ON;
749 1. It has nothing to do with A, B,
750
751 **✎Note: **
752
753 • If there is no instruction (LD, LDI, etc.) connected to the bus after the MC instruction, a program structure error occurs.
754
755 • MC to MCR instructions cannot be used in FOR to NEXT, STL to RET, subroutines, events, and interrupts. In addition, there cannot be instructions such as IRET, FEND, END, RET (SRET) inside MC to MCR to block.
756
757 • There can be up to 8 nests (N0 to N7). In the case of nesting, the MC instruction is used from the small number of nesting (N), while the MCR instruction is used from the old number. If the order is reversed, it does not become a nested structure, so the CPU module cannot operate normally.
758
759 • When the MCR instruction is a nested structure concentrated in one location, all main control can be ended by the smallest number (N) number.
760
761 **Error code**
762
763 No operation error
764
765 **Example**
766
767 (1) No nested structure
768
769 (((
770 (% style="text-align:center" %)
771 [[image:4_html_4f6cacf53f330135.png||class="img-thumbnail"]]
772
773 Main control program 1
774
775 Main control program 2
776 )))
777
778 The main control program 1 and the main control program 2 do not belong to the nested structure, so you can use N0 programming. There is no limit to the number of times N0 can be used in this case.
779
780 **(2) Nested structure**
781
782 When using the MC instruction, the number of nesting level N increases sequentially.(N0→ N1→ N2→ N3→ N4→ N5→ N6→ N7). When returning, use the MCR instruction to release from the larger nesting level. (N7→ N6→ N5→ N4→ N3→ N2→ N1 → N0).
783
784 For example, when MCR N6 and MCR N7 are not programmed, if MCR N5 is programmed, the nesting level will return to 5 at once.The nesting level can be programmed up to 8 levels (N7).
785
786 (((
787 (% style="text-align:center" %)
788 [[image:1652260093074-914.png||class="img-thumbnail"]]
789 )))
790
791 As shown above:
792
793 87 Walk: Level N0, Y0 will follow X1 state only when X0 is ON.
794
795 95 Walk: Level N1, Y1 will follow X3 state only when X0 and X2 are both ON.
796
797 103 Walk: Level N2, Y2 will follow X5 state only when X0, X2, and X4 are ON at the same time.
798
799 109 Walk: Level N1, use MCR N2 to return to level N1. Y3 will follow the state of X6 only when X0 and X2 are both ON.
800
801 115 walk: level N0, use MCR N1 to return to level N0. Y4 will follow the state of X7 only when X0 is ON.
802
803 121 Walk: Does not belong to the main control structure, has nothing to do with X0, X2, X4, Y5 follows the state change of X10.
804
805 = {{id name="_Toc16744"/}}**Watchdog reset** =
806
807 == {{id name="_Toc15927"/}}**WDT/watchdog timer** ==
808
809 The watchdog timer is reset by the program.
810
811 -[WDT]
812
813 **Features**
814
815 • Reset the watchdog timer through the program.
816
817 • Use when the scan time exceeds the set value of the watchdog timer depending on conditions.
818
819 • For t1 from step 0 to WDT instruction, and from WDT instruction to END instruction, do not exceed the set value of the watchdog timer.
820
821 (% style="text-align:center" %)
822 [[image:4_html_3341a4693ce1250c.png||class="img-thumbnail"]]
823
824 • The WDT instruction can be used more than twice in one scan.
825
826 **✎Note: **
827
828 • The watchdog timeout time can be set in the special register SD122. The default is 200ms.
829
830 • Use the special relay SM122 to control whether to turn on the watchdog timer function. The WDT instruction will be invalid after closing.
831
832 (% style="text-align:center" %)
833 [[image:4_html_21bc20f7ff159189.png||class="img-thumbnail"]]
834
835 (1) The watchdog timer time is set to 300ms;
836
837 (2)  Refresh the watchdog timer.
838
839 **Error code**
840
841 There is no operation error.
842
843 **Example**
844
845 (% style="text-align:center" %)
846 [[image:4_html_ceca3c411d993d90.png||class="img-thumbnail"]]
847
848 The FOR to NXET instruction loop takes a long scan period for many times, which may exceed the set watchdog timer 300ms, causing the PLC to report an error and cannot continue to run. After turning on M0, the WDT instruction will run, and the watchdog timer is updated every cycle , So that it will not report an error to execute the program normally.