... ... @@ -1,3 +1,388 @@
1 += **Contact comparison instruction** =
2 +
3 +== **Signed 16-bit contact comparison instruction** ==
4 +
5 +**LD £, AND £, OR £**
6 +
7 +The BIN 16-bit data of the device specified in (s1) and the BIN 16-bit data of the device specified in (s2) are compared by normal open contact processing.
8 +
9 +LD£: Normally open contact comparison instruction
10 +
11 +AND£: Normally open contact series connection comparison instruction
12 +
13 +OR£: Normally open contact parallel connection comparison instruction
14 +
15 +**Ladder diagram**
16 +
17 +(% style="text-align:center" %)
18 +[[image:07-5 Basic instructions_html_63210db6b7e1512f.png]]
19 +
20 +(You can enter "=", "<>", ">", "<", ">=", "<=" in "£")
21 +
22 +**Content, range and data type**
23 +
24 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
25 +|(s1)|Comparison data or device storing comparison data|-32768 to 32767|Signed BIN 16 bit|ANY16_S
26 +|(s2)|Comparison data or device storing comparison data|-32768 to 32767|Signed BIN 16 bit|ANY16_S
27 +
28 +**Device used**
29 +
30 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="11" %)**Devices**|(((
31 +**Offset modification**
32 +)))|(((
33 +**Pulse extension**
34 +)))
35 +|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**[D]**|**XXP**
36 +|LD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
37 +|LD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
38 +|LD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
39 +|LD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
40 +|LD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
41 +|LD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
42 +|AND=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
43 +|AND>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
44 +|AND<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
45 +|AND>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
46 +|AND<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
47 +|AND<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
48 +|OR=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
49 +|OR>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
50 +|OR<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
51 +|OR>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
52 +|OR<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
53 +|OR<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
54 +
55 +**Features**
56 +
57 +The BIN 16-bit data of the device specified in (s1) and the BIN 16-bit data of the device specified in (s2) are compared by normal open contact processing.
58 +
59 +The comparison operation result of each instruction is shown below.
60 +
61 +|**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result**
62 +|==|(s1)=(s2)|(% rowspan="6" %)On state|==|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state
63 +|<>|(s1)≠(s2)|<>|(s1)=(s2)
64 +|>|(s1)>(s2)|>|(s1)≤(s2)
65 +|<|(s1)<(s2)|<|(s1)≥(s2)
66 +|>=|(s1)≥(s2)|>=|(s1)<(s2)
67 +|<=|(s1)≤(s2)|<=|(s1)>(s2)
68 +
69 +**Error code**
70 +
71 +|**Error code**|**Content**
72 +|4085H|(s) read address exceeds the device range
73 +
74 +**Example**
75 +
76 +(((
77 +(1) LD£ instruction:
78 +
79 +(% style="text-align:center" %)
80 +[[image:07-5 Basic instructions_html_1309199eccc7134.png]]
81 +)))
82 +
83 +When the current value of counter C10 is 200, Y10 is set
84 +
85 +When the content of D200 is above -29, and X1 is ON, Y11 is set
86 +
87 +(2) AND£ instruction:
88 +
89 +(% style="text-align:center" %)
90 +[[image:07-5 Basic instructions_html_1c966f74b0bd808e.png]]
91 +
92 +(((
93 +When X0 is ON, or when the current value of counter C10 is 200, Y10 is set
94 +
95 +When X1 is OFF, and the content of data counter D0 is not -10, Y11 is set
96 +
97 +
98 +)))
99 +
100 +(3) OR£ instruction:
101 +
102 +(% style="text-align:center" %)
103 +[[image:07-5 Basic instructions_html_8b000809015ea436.png]]
104 +
105 +(((
106 +When X1 is ON, or when the current value of counter C10 is 200, Y0 is set
107 +
108 +When X2 and M30 are ON, or the content of register D100 is K10000 and above, M60 is set
109 +)))
110 +
111 +== **Signed 32-bit contact comparison instruction** ==
112 +
113 +**LDD £, ANDD £, ORD £**
114 +
115 +The BIN 32-bit data of the device specified in (s1) and the BIN 32-bit data of the device specified in (s2) are compared by normal open contact processing.
116 +
117 +LDD£: Normally open contact comparison command
118 +
119 +ANDD£: Normally open contact series link comparison instruction
120 +
121 +ORD£: Normally open contact parallel link comparison instruction
122 +
123 +**Ladder diagram**
124 +
125 +(% style="text-align:center" %)
126 +[[image:07-5 Basic instructions_html_63210db6b7e1512f.png]]
127 +
128 +“=”, “<>”, “>”, “<”, “>=”, “<=” can be input in “£”
129 +
130 +**Content, range and data type**
131 +
132 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
133 +|(s1)|Comparison data or device storing comparison data|-2147483648 to 2147483647|Signed BIN 32 bit|ANY32_S
134 +|(s2)|Comparison data or device storing comparison data|-2147483648 to 2147483647|Signed BIN 32 bit|ANY32_S
135 +
136 +**Device used**
137 +
138 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="13" %)**Devices**|(((
139 +**Offset modification**
140 +)))|(((
141 +**Pulse extension**
142 +)))
143 +|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**[D]**|**XXP**
144 +|LDD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
145 +|LDD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
146 +|LDD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
147 +|LDD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
148 +|LDD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
149 +|LDD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
150 +|ANDD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
151 +|ANDD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
152 +|ANDD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
153 +|ANDD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
154 +|ANDD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
155 +|ANDD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
156 +|ORD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
157 +|ORD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
158 +|ORD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
159 +|ORD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
160 +|ORD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
161 +|ORD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●|
162 +
163 +**Features**
164 +
165 +The BIN 32-bit data of the device specified in (s1) and the BIN 32-bit data of the device specified in (s2) are compared by normal open contact processing.
166 +
167 +The comparison operation result of each instruction is shown below.
168 +
169 +|**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result**
170 +|==|(s1)=(s2)|(% rowspan="6" %)On state|==|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state
171 +|<>|(s1)≠(s2)|<>|(s1)=(s2)
172 +|>|(s1)>(s2)|>|(s1)≤(s2)
173 +|<|(s1)<(s2)|<|(s1)≥(s2)
174 +|>=|(s1)≥(s2)|>=|(s1)<(s2)
175 +|<=|(s1)≤(s2)|<=|(s1)>(s2)
176 +
177 +**Error code**
178 +
179 +|**Error code**|**Content**
180 +|4085H|(S) read address exceeds the device range
181 +
182 +**Example**
183 +
184 +(1) LDD£ instruction:
185 +
186 +(% style="text-align:center" %)
187 +[[image:07-5 Basic instructions_html_8acf0d489297c561.png]]
188 +
189 +When the data of LC10 is 200000, Y10 is set, otherwise Y10 is reset.
190 +
191 +When the 32-bit data composed of D201 and D200 exceeds -5000, and X1 is ON, Y11 is turned ON.
192 +
193 +(2) ANDD£ instruction:
194 +
195 +(% style="text-align:center" %)
196 +[[image:07-5 Basic instructions_html_38be93eec0ced6c.png]]
197 +
198 +When X0 is ON and the value of LC10 is 200000, Y10 is set, otherwise it is reset.
199 +
200 +When X1 is OFF and the 32-bit data composed of D1 and D0 is not equal to K-50000, Y11 is set.
201 +
202 +(3) ORD£ instruction:
203 +
204 +(% style="text-align:center" %)
205 +[[image:07-5 Basic instructions_html_8ebfc7b0562cf370.png]]
206 +
207 +When X1 is ON, or the data of LC10 is equal to the data of LC10 is equal to 200000, Y0 is set.
208 +
209 +When X2 and M30 are set, or the double word data composed of D101 and D100 is greater than or equal to 100000, M60 is set.
210 +
211 +== **Single precision real number contact comparison instruction** ==
212 +
213 +**LDE £, ANDE £, ORE £**
214 +
215 +The single precision real number of the device specified in (s1) and the single precision real number of the device specified in (s2) are compared by normal open contact processing.
216 +
217 +LDE£: Normally open contact comparison command
218 +
219 +ANDE£: Normally open contact series link comparison instruction
220 +
221 +ORE£: Normally open contact parallel link comparison instruction
222 +
223 +**Ladder diagram**
224 +
225 +(% style="text-align:center" %)
226 +[[image:07-5 Basic instructions_html_6ac28f30e24ad296.png||height="352" width="550"]]
227 +
228 +“=”, “<>”, “>”, “<”, “>=”, “<=” can be input in “£”
229 +
230 +**Content, range and data type**
231 +
232 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
233 +|(s1)|Comparison data or the device start number storing the comparison data|0, 2^^-126^^ ≤~|(s)~|< 2^^128^^|Single precision real number|ANYREAL_32
234 +|(s2)|Comparison data or the device start number storing the comparison data|0, 2^^-126^^ ≤~|(s)~|< 2^^128^^|Single precision real number|ANYREAL_32
235 +
236 +**Device used**
237 +
238 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="8" %)**Devices**|(((
239 +**Offset modification**
240 +)))|(((
241 +**Pulse extension**
242 +)))
243 +|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**E**|**[D]**|**XXP**
244 +|LDE=|s1, s2|●|●|●|●|●|●|●|●|●|
245 +|LDE>|s1, s2|●|●|●|●|●|●|●|●|●|
246 +|LDE<|s1, s2|●|●|●|●|●|●|●|●|●|
247 +|LDE>=|s1, s2|●|●|●|●|●|●|●|●|●|
248 +|LDE<=|s1, s2|●|●|●|●|●|●|●|●|●|
249 +|LDE<>|s1, s2|●|●|●|●|●|●|●|●|●|
250 +|ANDE=|s1, s2|●|●|●|●|●|●|●|●|●|
251 +|ANDE>|s1, s2|●|●|●|●|●|●|●|●|●|
252 +|ANDE<|s1, s2|●|●|●|●|●|●|●|●|●|
253 +|ANDE>=|s1, s2|●|●|●|●|●|●|●|●|●|
254 +|ANDE<=|s1, s2|●|●|●|●|●|●|●|●|●|
255 +|ANDE<>|s1, s2|●|●|●|●|●|●|●|●|●|
256 +|ORE=|s1, s2|●|●|●|●|●|●|●|●|●|
257 +|ORD>|s1, s2|●|●|●|●|●|●|●|●|●|
258 +|ORE<|s1, s2|●|●|●|●|●|●|●|●|●|
259 +|ORE>=|s1, s2|●|●|●|●|●|●|●|●|●|
260 +|ORE<=|s1, s2|●|●|●|●|●|●|●|●|●|
261 +|ORE<>|s1, s2|●|●|●|●|●|●|●|●|●|
262 +
263 +**Features**
264 +
265 +The single precision real number of the device specified in (s1) and the single precision real number of the device specified in (s2) are compared by normal open contact processing.
266 +
267 +The comparison operation result of each instruction is shown below.
268 +
269 +|**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result**
270 +|E=|(s1)=(s2)|(% rowspan="6" %)On state|E=|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state
271 +|E<>|(s1)≠(s2)|E<>|(s1)=(s2)
272 +|E>|(s1)>(s2)|E>|(s1)≤(s2)
273 +|E<|(s1)<(s2)|E<|(s1)≥(s2)
274 +|E>=|(s1)≥(s2)|E>=|(s1)<(s2)
275 +|E<=|(s1)≤(s2)|E<=|(s1)>(s2)
276 +
277 +**Error code**
278 +
279 +|**Error code**|**Content**
280 +|4084H|When the content of the specified device by (s1) and (s2) is an irregular number, a non-number, or ±∞
281 +|4085H|The read address of (s1) and (s2exceeds the device range
282 +
283 +**Example**
284 +
285 +(1) LDE£ instruction:
286 +
287 +(% style="text-align:center" %)
288 +[[image:07-5 Basic instructions_html_c4c820cf59601493.png]]
289 +
290 +When the real number input in D0 is equal to E1.23, Y10 is ON, otherwise Y10 is OFF.
291 +
292 +When the real number in R0 is greater than or equal to the real number in LC0, Y11 is ON, otherwise it is OFF.
293 +
294 +If the input in D0, R0, LC0 is not a real number, it will report H4084 error.
295 +
296 +(2) ANDE£ instruction:
297 +
298 +(% style="text-align:center" %)
299 +[[image:07-5 Basic instructions_html_7cdd2117360e179b.png]]
300 +
301 +Only when M0 is ON and D2 real number is not equal to E1.23 and R2 real number is less than real number LC2 , Y12 is ON, otherwise all are OFF.
302 +
303 +(3) ORE£ instruction:
304 +
305 +(% style="text-align:center" %)
306 +[[image:07-5 Basic instructions_html_3eba0bd56176441d.png]]
307 +
308 +When the real number of R4 is less than or equal to the real number of R15, or the real number R6 is equal to the real number R20, Y13 is ON, otherwise Y13 is OFF.
309 +
310 +== **String comparison** ==
311 +
312 +**LDS£、ANDS£、 ORS£**
313 +
314 +Compare the string stored after the device number specified in (s1) with the string stored after the device number specified in (s2).
315 +
316 +LDS£: String comparison instruction
317 +
318 +ANDS£: String serial connection comparison instruction
319 +
320 +ORS£: String parallel connection comparison instruction
321 +
322 +**Ladder diagram**
323 +
324 +(% style="text-align:center" %)
325 +[[image:07-5 Basic instructions_html_5fb3b3b70645fef5.png||height="371" width="550"]]
326 +
327 +“=” and “<>” could be entered in “£”
328 +
329 +**Content, range and data type**
330 +
331 +|**Parameter**|**Content**|**Range**|**Date type**|**Date type(label)**
332 +|(S1)|Connection data or the device start number storing the data or the string specified directly|-|String|ANYSTRING_SINGLE
333 +|(S1)|Connection data or the device start number storing the data or the string specified directly|-|String|ANYSTRING_SINGLE
334 +
335 +**Device used**
336 +
337 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|(((
338 +**Offset modification**
339 +)))|(((
340 +**Pulse extension**
341 +)))
342 +|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
343 +|LDS=|s1、s2|●|●|●|●|●|●|●|●|●|●|
344 +|LDS<>|s1、s2|●|●|●|●|●|●|●|●|●|●|
345 +|ANDS=|s1、s2|●|●|●|●|●|●|●|●|●|●|
346 +|ANDS<>|s1、s2|●|●|●|●|●|●|●|●|●|●|
347 +|ORS=|s1、s2|●|●|●|●|●|●|●|●|●|●|
348 +|ORS<>|s1、s2|●|●|●|●|●|●|●|●|●|●|
349 +
350 +**Features**
351 +
352 +• Compare the string stored after the device number specified in (s1) with the string stored after the device number specified in (s2).
353 +
354 +• The comparison operation result of each instruction is shown below.
355 +
356 +|**Instruction sign**|**Condition**|**Comparison operation result**|**Instruction sign**|**Condition**|**Comparison operation result**
357 +|==|(s1)=(s2)|(% rowspan="2" %)On stat|==|(s1)≠(s2)|(% rowspan="2" %)Non-conduction state
358 +|<>|(s1)≠(s2)|<>|(s1)=(s2)
359 +
360 +**Error code**
361 +
362 +|**Error code**|**Content**
363 +|4085H|The read address of (s1) or (s2) exceeds the device range
364 +|408AH|The length of the read string of (s1) or (s2) exceeds, and the continuous length of the string exceeds 400 characters.
365 +|408BH|When (s1) or (s2) reading the string, the maximum range of the device is read but 00H is not found as the end.
366 +
367 +**Example**
368 +
369 +(1) LDS£ instruction:
370 +
371 +(% style="text-align:center" %)
372 +[[image:07-5 Basic instructions_html_449a071f61ff5b58.png]]
373 +
374 +(2) ANDS£ instruction:
375 +
376 +(% style="text-align:center" %)
377 +[[image:07-5 Basic instructions_html_dd6aa995d193bdd2.png]]
378 +
379 +(3) ORS£ instruction:
380 +
381 +(% style="text-align:center" %)
382 +[[image:07-5 Basic instructions_html_4f8fb7c94f87c58d.png]]
383 +
384 += **Clock operation instruction** =
385 +
1 1  == **TADD/The addition of clock data** ==
2 2  
3 3  **TADD(P)**
... ... @@ -274,7 +274,7 @@
274 274  
275 275  == **TWR/Clock data writing** ==
276 276  
277 -**TWR(P)**
662 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TWR(P)**
278 278  
279 279  Write the clock data of the built-in real-time clock of the CPU module.
280 280  
... ... @@ -287,13 +287,17 @@
287 287  
288 288  **Device used**
289 289  
290 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="4" %)**Devices**|(((
291 -**Offset modification**
675 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
676 +**Offset**
677 +
678 +**modification**
292 292  )))|(((
293 -**Pulse extension**
680 +**Pulse**
681 +
682 +**extension**
294 294  )))
295 -|**T**|**C**|**D**|**R**|**[D]**|**XXP**
296 -|TWR|Parameter 1|●|●|●|●|●|●
684 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
685 +|TWR|Parameter 1| | | | | | | | | | | | | | |●|●|●|●| | | | | | |●|●
297 297  
298 298  **Features**
299 299  
... ... @@ -328,7 +328,7 @@
328 328  |SD105|The year data of the clock data is stored in a 4-digit BIN code of the Gregorian calendar.
329 329  |SD106|The week data of the clock data is stored in BIN code. (0: day, 1: one, ..., 6: six) are stored in BIN code.
330 330  
331 -✎**Note:**
720 +✎**Note**
332 332  
333 333  The device specified in (s) occupies 7 points. Be careful not to overlap with the device used for machine control.
334 334  
... ... @@ -341,15 +341,13 @@
341 341  
342 342  Set D0 date and time to 2020-2-19 12:36:00 in advance
343 343  
344 -(% style="text-align:center" %)
345 -[[image:07-5 Basic instructions_html_994c66d1a4cbd45f.png||height="57" width="305"]]
733 +[[image:07-5 Basic instructions_html_994c66d1a4cbd45f.png]]
346 346  
347 347  At the moment when the time 12:36:00 arrives, turn on the M0 coil and write the time.
348 348  
349 -(% style="text-align:center" %)
350 -[[image:07-5 Basic instructions_html_bf3e906ee5265598.png||height="42" width="586"]]
737 +[[image:07-5 Basic instructions_html_bf3e906ee5265598.png]]
351 351  
352 -== **HTOS/16-bit data conversion of time data (hour, minute, second → second)** ==
739 +{{id name="_Toc5357"/}}{{id name="_Toc6196"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **HTOS/16-bit data conversion of time data (hour, minute, second → second)**
353 353  
354 354  **HTOS(P)**
355 355  
... ... @@ -365,26 +365,26 @@
365 365  
366 366  **Device used**
367 367  
368 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|**Offset modification**|(((
369 -**Pulse extension**
755 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
756 +**Pulse**
757 +
758 +**extension**
370 370  )))
371 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
372 -|(% rowspan="2" %)HTOS|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
373 -|Parameter 2| |●|●|●|●|●|●|●|●|●|●
760 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
761 +|(% rowspan="2" %)HTOS|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
762 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
374 374  
375 375  **Features**
376 376  
377 377  Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d).
378 378  
379 -(% style="text-align:center" %)
380 -[[image:07-5 Basic instructions_html_a84b7741fd5bef2f.png||height="130" width="550"]]
768 +[[image:07-5 Basic instructions_html_a84b7741fd5bef2f.png]]
381 381  
382 382  **Example**
383 383  
384 384  When 4 hours, 29 minutes and 31 seconds are specified in (s)
385 385  
386 -(% style="text-align:center" %)
387 -[[image:07-5 Basic instructions_html_5effb7bc9b8e5cf7.png||height="162" width="550"]]
774 +[[image:07-5 Basic instructions_html_5effb7bc9b8e5cf7.png]]
388 388  
389 389  **Error code**
390 390  
... ... @@ -392,7 +392,7 @@
392 392  |4085H|When reading the specified device range exceeds the corresponding device range
393 393  |4086H|When writing the specified device range exceeds the corresponding device range
394 394  |4084H|(((
395 -When the calculation result is not in the range of 0 to 32767
782 +{{id name="OLE_LINK348"/}}When the calculation result is not in the range of 0 to 32767
396 396  
397 397  When the value specified in (s) is not in the range of 0 to 9
398 398  
... ... @@ -401,22 +401,19 @@
401 401  
402 402  **Example**
403 403  
404 -(% style="text-align:center" %)
405 -[[image:07-5 Basic instructions_html_e23e38c4ba4c34bb.png||height="43" width="338"]]
791 +[[image:07-5 Basic instructions_html_e23e38c4ba4c34bb.png]]
406 406  
407 407  D0 time is set to 5:36:53
408 408  
409 -(% style="text-align:center" %)
410 410  [[image:07-5 Basic instructions_html_2866a121e5ca5713.png]]
411 411  
412 412  The time of D10 after the M0 coil is turned on is as below.
413 413  
414 -(% style="text-align:center" %)
415 415  [[image:07-5 Basic instructions_html_1dd6c5de05890797.png]]
416 416  
417 -== **DHTOS/32-bit data conversion of time data (hour, minute, second → second)** ==
801 +{{id name="_Toc13431"/}}{{id name="_Toc5278"/}}**DHTOS/32-bit data conversion of time data (hour, minute, second → second)**
418 418  
419 -**DHTOS(P)**
803 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DHTOS(P)**
420 420  
421 421  Convert the time data stored after the device number specified in (s) into seconds and store the conversion result as BIN 32-bit data in the device specified in (d).
422 422  
... ... @@ -430,28 +430,30 @@
430 430  
431 431  **Device used**
432 432  
433 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|(((
434 -**Offset modification**
817 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
818 +**Offset**
819 +
820 +**modification**
435 435  )))|(((
436 -**Pulse extension**
822 +**Pulse**
823 +
824 +**extension**
437 437  )))
438 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
439 -|(% rowspan="2" %)DHTOS|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
440 -|Parameter 2| |●|●|●|●|●|●|●|●|●|●
826 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
827 +|(% rowspan="2" %)DHTOS|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
828 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
441 441  
442 442  **Features**
443 443  
444 444  Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d).
445 445  
446 -(% style="text-align:center" %)
447 -[[image:07-5 Basic instructions_html_f4be08508575ea01.png||height="99" width="550"]]
834 +[[image:07-5 Basic instructions_html_f4be08508575ea01.png]]
448 448  
449 449  **Example**
450 450  
451 451  When 35 hours, 10 minutes and 58 seconds are specified in (s)
452 452  
453 -(% style="text-align:center" %)
454 -[[image:07-5 Basic instructions_html_5b9ad230ed5e1fd0.png||height="125" width="550"]]
840 +[[image:07-5 Basic instructions_html_5b9ad230ed5e1fd0.png]]
455 455  
456 456  **Error code**
457 457  
... ... @@ -466,20 +466,17 @@
466 466  
467 467  **Example**
468 468  
469 -(% style="text-align:center" %)
470 -[[image:07-5 Basic instructions_html_ae8ab4379e8bdb91.png||height="45" width="263"]]
855 +[[image:07-5 Basic instructions_html_ae8ab4379e8bdb91.png]]
471 471  
472 472  D0 time is set to 15:33:24
473 473  
474 -(% style="text-align:center" %)
475 -[[image:07-5 Basic instructions_html_57a15d9e1045e93e.png||height="41" width="313"]]
859 +[[image:07-5 Basic instructions_html_57a15d9e1045e93e.png]]
476 476  
477 477  The second of D10 after the M0 coil is turned on is
478 478  
479 -(% style="text-align:center" %)
480 -[[image:07-5 Basic instructions_html_194e906b1dc12078.png||height="64" width="365"]]
863 +[[image:07-5 Basic instructions_html_194e906b1dc12078.png]]
481 481  
482 -**HOUR/Hour measuring 16-bit**
865 +{{id name="_Ref22686"/}}{{id name="_Toc11231"/}}{{id name="_Toc7401"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **HOUR/Hour measuring 16-bit**
483 483  
484 484  **HOUR(P)**
485 485  
... ... @@ -504,15 +504,19 @@
504 504  
505 505  **Device used**
506 506  
507 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="17" %)**Devices**|(((
508 -**Offset modification**
890 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
891 +**Offset**
892 +
893 +**modification**
509 509  )))|(((
510 -**Pulse extension**
895 +**Pulse**
896 +
897 +**extension**
511 511  )))
512 -|**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP**
513 -|(% rowspan="3" %)HOUR|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
514 -|Parameter 2| | | | | | | | | | | |●|●|●| | | |●|●
515 -|Parameter 3|●|●|●|●|●| | | | | | | | | | | | |●|●
899 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
900 +|(% rowspan="3" %)HOUR|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
901 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
902 +|Parameter 3| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
516 516  
517 517  **Features**
518 518  
... ... @@ -534,7 +534,7 @@
534 534  
535 535  • The measurement stops when the current value reaches the 16-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+1.
536 536  
537 -✎**Note:**
924 +✎**Note**
538 538  
539 539  • The device specified in (d1) occupies 2 points. Be careful not to overlap with the device used for machine control.
540 540  
... ... @@ -547,14 +547,15 @@
547 547  |4086H|When writing the specified device range exceeds the corresponding device range
548 548  |4084H|When the value of (s) is negative
549 549  
937 +
938 +
550 550  **Example**
551 551  
552 -(% style="text-align:center" %)
553 -[[image:07-5 Basic instructions_html_7570f8c392470a9f.png||height="45" width="320"]]
941 +[[image:07-5 Basic instructions_html_7570f8c392470a9f.png]]
554 554  
555 555  When M0 = ON, the duration of the state is accumulated, the time is recorded in D0, and the seconds less than 1 hour are recorded in D1. When the accumulated time of D0 reaches 98 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K98), the accumulated timing will continue and the reading will continue to increase; the current time value D0 reaches the maximum value of 32767 hours and D1 reaches 3599 seconds, the timing measurement will stop. The current time values D0 and D1 are cleared to 0.
556 556  
557 -== **DHOUR/Hour measuring 32 bits** ==
945 +{{id name="_Toc8523"/}}{{id name="_Toc9364"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DHOUR/Hour measuring 32 bits**
558 558  
559 559  **DHOUR(P)**
560 560  
... ... @@ -566,7 +566,9 @@
566 566  
567 567  |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
568 568  |(s)|(((
569 -The time when the alarm (d2) is turned ON (set by one hour)
957 +The time when the alarm (d2) is turned ON
958 +
959 +(set by one hour)
570 570  )))|0 to 2147483647|Signed BIN 32 bit|ANY32
571 571  |(d1)|Device that stores the current value of measurement (specified data register for power failure retention)|-|Unsigned BIN 32 bit|(((
572 572  ANY32_ARRAY
... ... @@ -577,15 +577,19 @@
577 577  
578 578  **Device used**
579 579  
580 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="18" %)**Devices**|(((
581 -**Offset modification**
970 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
971 +**Offset**
972 +
973 +**modification**
582 582  )))|(((
583 -**Pulse extension**
975 +**Pulse**
976 +
977 +**extension**
584 584  )))
585 -|**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**[D]**|**XXP**
586 -|(% rowspan="3" %)DHOUR|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●|●|●
587 -|Parameter 2| | | | | | | | | | | |●|●|●| | | | |●|●
588 -|Parameter 3|●|●|●|●|●| | | | | | | | | | | | | |●|●
979 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
980 +|(% rowspan="3" %)DHOUR|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
981 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
982 +|Parameter 3| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
589 589  
590 590  **Features**
591 591  
... ... @@ -607,7 +607,7 @@
607 607  
608 608  • The measurement stops when the current value reaches the 32-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+2.
609 609  
610 -✎**Note:**
1004 +✎**Note**
611 611  
612 612  • The device specified in (d1) occupies 3 points. Be careful not to overlap with the device used for machine control.
613 613  
... ... @@ -620,16 +620,17 @@
620 620  |4086H|When writing the specified device range exceeds the corresponding device range
621 621  |4084H|When the value of (s) is negative
622 622  
1017 +
1018 +
623 623  **Example**
624 624  
625 -(% style="text-align:center" %)
626 -[[image:07-5 Basic instructions_html_3f1ef5ecc835de30.png||height="43" width="448"]]
1021 +[[image:07-5 Basic instructions_html_3f1ef5ecc835de30.png]]
627 627  
628 628  When M0=ON, the duration of this state is accumulated, the time is recorded in D1, D0, and the seconds less than 1 hour are recorded in D2. When the accumulated time of D1, D0 reaches 1000 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K1000), the accumulated timing will continue, and the reading will continue to increase; the current time values D1 and D0 reach the maximum value of 2147483647 hours, and when D2 reaches 3599 seconds, the timing measurement will stop and the timing should be restarted. The current time values D0, D1, and D2 must be cleared to 0.
629 629  
630 -== **STOH/16-bit data conversion of time data (second → hour, minute, second)** ==
1025 +**{{id name="_Toc11629"/}}STOH/16-bit data conversion of time data (second → hour, minute, second)**
631 631  
632 -**STOH(P)**
1027 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **STOH(P)**
633 633  
634 634  Convert the second 16-bit data stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
635 635  
... ... @@ -638,35 +638,39 @@
638 638  **Content, range and data type**
639 639  
640 640  |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
641 -|(s)|The device start number that stores the clock data before conversion|0 to 32767|Signed BIN 16 bit|ANY16
1036 +|(s)|{{id name="OLE_LINK353"/}}The device start number that stores the clock data before conversion|0 to 32767|Signed BIN 16 bit|ANY16
642 642  |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|(((
643 -ANY16_ARRAY (number of elements: 3)
1038 +ANY16_ARRAY
1039 +
1040 +(number of elements: 3)
644 644  )))
645 645  
646 646  **Device used**
647 647  
648 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|(((
649 -**Offset modification**
1045 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1046 +**Offset**
1047 +
1048 +**modification**
650 650  )))|(((
651 -**Pulse extension**
1050 +**Pulse**
1051 +
1052 +**extension**
652 652  )))
653 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
654 -|(% rowspan="2" %)STOH|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
655 -|Parameter 2| |●|●|●|●|●|●|●|●|●|●
1054 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1055 +|(% rowspan="2" %)STOH|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1056 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
656 656  
657 657  **Features**
658 658  
659 659  Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
660 660  
661 -(% style="text-align:center" %)
662 -[[image:07-5 Basic instructions_html_1f5f3f1d80af2a34.png||height="110" width="550"]]
1062 +[[image:07-5 Basic instructions_html_1f5f3f1d80af2a34.png]]
663 663  
664 664  **Example**
665 665  
666 666  When 29,011 seconds are specified in (s)
667 667  
668 -(% style="text-align:center" %)
669 -[[image:07-5 Basic instructions_html_682516cbf773f515.png||height="163" width="550"]]
1068 +[[image:07-5 Basic instructions_html_682516cbf773f515.png]]
670 670  
671 671  **Error code**
672 672  
... ... @@ -677,19 +677,17 @@
677 677  
678 678  **Example**
679 679  
680 -(% style="text-align:center" %)
681 -[[image:07-5 Basic instructions_html_e783349d57adf7d2.png||height="47" width="350"]]
1079 +[[image:07-5 Basic instructions_html_e783349d57adf7d2.png]]
682 682  
683 683  Set D0 seconds to 12537
684 684  
685 685  The hour, minute and second of D10 after the M0 coil is turned on are
686 686  
687 -(% style="text-align:center" %)
688 -[[image:07-5 Basic instructions_html_d3c33949e8684891.png||height="52" width="645"]]
1085 +[[image:07-5 Basic instructions_html_d3c33949e8684891.png]]
689 689  
690 -== **DSTOH/32-bit data conversion of time data (second → hour, minute, second)** ==
1087 +{{id name="_Toc10764"/}}{{id name="_Toc30243"/}}**DSTOH/32-bit data conversion of time data (second → hour, minute, second)**
691 691  
692 -**DSTOH(P)**
1089 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSTOH(P)**
693 693  
694 694  Convert the second 32-bit data of second stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
695 695  
... ... @@ -700,33 +700,37 @@
700 700  |**Parameter**|**Content**|**Range**|**Data type**|**Data &nbsp;&nbsp;&nbsp;&nbsp;type (label)**
701 701  |(s)|The device start number that stores the clock data before conversion|0 to 117964799|Signed BIN 32 bit|ANY32
702 702  |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|(((
703 -ANY16_ARRAY (number of elements: 3)
1100 +ANY16_ARRAY
1101 +
1102 +(number of elements: 3)
704 704  )))
705 705  
706 706  **Device used**
707 707  
708 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|(((
709 -**Offset modification**
1107 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1108 +**Offset**
1109 +
1110 +**modification**
710 710  )))|(((
711 -**Pulse extension**
1112 +**Pulse**
1113 +
1114 +**extension**
712 712  )))
713 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
714 -|(% rowspan="2" %)DSTOH|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
715 -|Parameter 2| |●|●|●|●|●|●|●|●|●|●
1116 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1117 +|(% rowspan="2" %)DSTOH|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1118 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
716 716  
717 717  **Features**
718 718  
719 719  Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
720 720  
721 -(% style="text-align:center" %)
722 -[[image:07-5 Basic instructions_html_cbf13fc3d10fbe61.png||height="99" width="600"]]
1124 +[[image:07-5 Basic instructions_html_cbf13fc3d10fbe61.png]]
723 723  
724 724  **Example**
725 725  
726 726  When 45,325 seconds is specified in (s)
727 727  
728 -(% style="text-align:center" %)
729 -[[image:07-5 Basic instructions_html_d6045506b13275a0.png||height="135" width="600"]]
1130 +[[image:07-5 Basic instructions_html_d6045506b13275a0.png]]
730 730  
731 731  **Error code**
732 732  
... ... @@ -737,17 +737,15 @@
737 737  
738 738  **Example**
739 739  
740 -(% style="text-align:center" %)
741 -[[image:07-5 Basic instructions_html_e7dd49d953db6da4.png||height="39" width="316"]]
1141 +[[image:07-5 Basic instructions_html_e7dd49d953db6da4.png]]
742 742  
743 743  Set D0 seconds to 2152537
744 744  
745 745  The hour, minute and second of D10 after the M0 coil is turned on are
746 746  
747 -(% style="text-align:center" %)
748 -[[image:07-5 Basic instructions_html_10d57bde1ac0a218.png||height="52" width="661"]]
1147 +[[image:07-5 Basic instructions_html_10d57bde1ac0a218.png]]
749 749  
750 -== **TCMP/Clock data comparison** ==
1149 +{{id name="_Toc2937"/}}{{id name="_Toc24209"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TCMP/Clock data comparison**
751 751  
752 752  **TCMP(P)**
753 753  
... ... @@ -766,26 +766,29 @@
766 766  
767 767  **Device used**
768 768  
769 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="17" %)**Devices**|(((
770 -**Offset modification**
1168 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1169 +**Offset**
1170 +
1171 +**modification**
771 771  )))|(((
772 -**Pulse extension**
1173 +**Pulse**
1174 +
1175 +**extension**
773 773  )))
774 -|**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP**
775 -|(% rowspan="5" %)TCMP|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
776 -|Parameter 2| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
777 -|Parameter 3| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
778 -|Parameter 4| | | | | | | | | |●|●|●|●|●| | | |●|●
779 -|Parameter 5|●|●|●|●|●| | | | | | | | | | | | |●|●
1177 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1178 +|(% rowspan="5" %)TCMP|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1179 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1180 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1181 +|Parameter 4| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1182 +|Parameter 5| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
780 780  
781 781  **Features**
782 782  
783 783  Compare the time of the reference time (hour, minute, second) [(s1), (s2), (s3)] with the time data (hour, minute, second) [(s4), (s4)+1, (s4) +2] Compare the size and turn on/off the 3 points from (d) according to the result of the same size.
784 784  
785 -(% style="text-align:center" %)
786 -[[image:07-5 Basic instructions_html_5df7ad3057fada12.png||height="385" width="750"]]
1188 +[[image:07-5 Basic instructions_html_5df7ad3057fada12.png]]
787 787  
788 -✎**Note:**
1190 +✎**Note**
789 789  
790 790  The device specified in (s4) and (d) occupies 3 points. Be careful not to overlap with the device used for machine control.
791 791  
... ... @@ -799,29 +799,26 @@
799 799  |4084H|(((
800 800  When the value specified in (s) and (s4) is not in the range of 0 to 23
801 801  
802 -When the value specified in (s2),(s3) (s4)+1 and (s4)+2 is not in the range of 0 to 59
1204 +{{id name="OLE_LINK355"/}}When the value specified in (s2),(s3) (s4)+1 and (s4)+2 is not in the range of 0 to 59
803 803  )))
804 804  
805 805  **Example**
806 806  
807 -(% style="text-align:center" %)
808 -[[image:07-5 Basic instructions_html_fcc16317cf7c0700.png||height="68" width="359"]]
1209 +[[image:07-5 Basic instructions_html_fcc16317cf7c0700.png]]
809 809  
810 810  Set D10 to 1, D11 to 30, D12 to 0
811 811  
812 812  When M0 is turned on, the time that D23 will come is 0:31:27
813 813  
814 -(% style="text-align:center" %)
815 -[[image:07-5 Basic instructions_html_de97dd7a612b2323.png||height="50" width="653"]]
1215 +[[image:07-5 Basic instructions_html_de97dd7a612b2323.png]]
816 816  
817 817  M10 is turned ON
818 818  
819 -(% style="text-align:center" %)
820 -[[image:07-5 Basic instructions_html_56e2d606adc09fd.png||height="52" width="239"]]
1219 +[[image:07-5 Basic instructions_html_56e2d606adc09fd.png]]
821 821  
822 -== **TZCP/Clock data bandwidth comparison** ==
1221 +{{id name="_Toc29031"/}}{{id name="_Toc22923"/}}**TZCP/Clock data bandwidth comparison**
823 823  
824 -**TZCP(P)**
1223 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TZCP(P)**
825 825  
826 826  Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth.
827 827  
... ... @@ -831,37 +831,46 @@
831 831  
832 832  |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
833 833  |(s1)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|(((
834 -ANY16_ARRAY (number of elements: 3)
1233 +ANY16_ARRAY
1234 +
1235 +(number of elements: 3)
835 835  )))
836 836  |(s2)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|(((
837 -ANY16_ARRAY (number of elements: 3)
1238 +ANY16_ARRAY
1239 +
1240 +(number of elements: 3)
838 838  )))
839 839  |(s3)|Specify "hour" of time data (hour, minute, second)|-|Signed BIN 16 bit|(((
840 -ANY16_ARRAY (number of elements: 3)
1243 +ANY16_ARRAY
1244 +
1245 +(number of elements: 3)
841 841  )))
842 842  |(d)|The bit device is turned ON/OFF according to the comparison result.|-|Bit|(((
843 -ANY16_ARRAY (number of elements: 3)
1248 +ANY16_ARRAY
1249 +
1250 +(number of elements: 3)
844 844  )))
845 845  
846 846  **Device used**
847 847  
848 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="10" %)**Devices**|**Offset modification**|(((
849 -**Pulse extension**
1255 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1256 +**Pulse**
1257 +
1258 +**extension**
850 850  )))
851 -|**Y**|**M**|**S**|**SM**|**D.b**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
852 -|(% rowspan="4" %)TZCP|Parameter 1| | | | | |●|●|●|●|●|●|●
853 -|Parameter 2| | | | | |●|●|●|●|●|●|●
854 -|Parameter 3| | | | | |●|●|●|●|●|●|●
855 -|Parameter 4|●|●|●|●|●| | | | | |●|●
1260 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1261 +|(% rowspan="4" %)TZCP|Parameter 1| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1262 +|Parameter 2| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1263 +|Parameter 3| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1264 +|Parameter 4| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
856 856  
857 857  **Features**
858 858  
859 859  Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth.
860 860  
861 -(% style="text-align:center" %)
862 -[[image:07-5 Basic instructions_html_844291270080313d.png||height="339" width="750"]]
1270 +[[image:07-5 Basic instructions_html_844291270080313d.png]]
863 863  
864 -✎**Note:**
1272 +✎**Note**
865 865  
866 866  • The devices specified in (s1), (s2), (s3), (d) occupy 3 points. Be careful not to overlap with the device used for machine control.
867 867  
... ... @@ -882,23 +882,1176 @@
882 882  
883 883  **Example**
884 884  
885 -(% style="text-align:center" %)
886 -[[image:07-5 Basic instructions_html_30027a2387c26c2e.png||height="46" width="439"]]
1293 +[[image:07-5 Basic instructions_html_30027a2387c26c2e.png]]
887 887  
888 888  Set D0 time to 16:30:00 and D10 time to 4:30:0
889 889  
890 -(% style="text-align:center" %)
891 -[[image:07-5 Basic instructions_html_c64e0faf2af172f8.png||height="49" width="626"]]
1297 +[[image:07-5 Basic instructions_html_c64e0faf2af172f8.png]]
892 892  
893 -(% style="text-align:center" %)
894 -[[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png||height="50" width="625"]]
1299 +[[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png]]
895 895  
896 896  After the coil is turned on, the reading time to D20 time is 8:30:00
897 897  
898 -(% style="text-align:center" %)
899 -[[image:07-5 Basic instructions_html_75c44dad07eaf80a.png||height="49" width="625"]]
1303 +[[image:07-5 Basic instructions_html_75c44dad07eaf80a.png]]
900 900  
901 901  M0/M12 is ON
902 902  
903 -(% style="text-align:center" %)
904 -[[image:07-5 Basic instructions_html_f512f36261705953.png||height="48" width="218"]]
1307 +[[image:07-5 Basic instructions_html_f512f36261705953.png]]
1308 +
1309 +{{id name="_Toc6129"/}}[[image:07-5 Basic instructions_html_a2e3294e01b2f206.gif]] **7.13 Data control instructions**
1310 +
1311 +{{id name="_Toc3339"/}}{{id name="_Toc27829"/}}{{id name="_Toc9204"/}}**BAND/BIN 16-bit data dead zone control**
1312 +
1313 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **BAND(P)**
1314 +
1315 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2).
1316 +
1317 +-[BAND (s1) (s2) (S3) (d)]
1318 +
1319 +**Content, range and data type**
1320 +
1321 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1322 +|(s1)|Lower limit of dead zone (no output zone)|-32,768 to +32,767|Signed BIN 16 bit|ANY16_S
1323 +|(s2)|Upper limit of dead zone (no output zone)|-32,768 to +32,767|Signed BIN 16 bit|ANY16_S
1324 +|(S3)|Input value controlled by dead zone control|-32768 to +32,767|Signed BIN 16 bit|ANY16_S
1325 +|(D)|The start number of the device that stores the output value controlled by the dead zone control|-|Signed BIN 16 bit|ANY16_S
1326 +
1327 +**Device used**
1328 +
1329 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1330 +**Offset**
1331 +
1332 +**modification**
1333 +)))|(((
1334 +**Pulse**
1335 +
1336 +**extension**
1337 +)))
1338 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1339 +|(% rowspan="4" %)BAND|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1340 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1341 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1342 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1343 +
1344 +**Features**
1345 +
1346 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). The output value is controlled as follows.
1347 +
1348 +|**Condition**|**The value stored in the output value**
1349 +|When dead zone low limit (s1)> input value (s3)|Input value (s3)-Dead zone low limit (s1)
1350 +|When dead zone high limit (s1) <input value (s3)|Input value (s3)- Dead zone high limit (s2)
1351 +|When dead zone low limit (s1) ≤ input value (s3) ≤ dead zone low limit (s2)|0
1352 +
1353 +
1354 +(((
1355 +•When the output value stored in (d) is a signed BIN 16-bit value, and the operation result exceeds the range of -32768 to 32767, the situation is shown in the following example.
1356 +
1357 +For example, when (s1) is 10 and (s3) is -32768,
1358 +
1359 +the output value = -32768-10=8000H-000AH=7FFFH=32758.
1360 +
1361 +[[image:07-5 Basic instructions_html_6850e21a76b813c0.png]]
1362 +)))
1363 +
1364 +**Error code**
1365 +
1366 +|**Error code**|**Content**
1367 +|4085H|When the specified device range for reading exceeds the range of the corresponding device.
1368 +|4086H|When the specified device range for writing exceeds the range of the corresponding device.
1369 +|4084H|When the low limit specified in (s1) is greater than the high limit specified in (s2).
1370 +
1371 +**Example &nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;**
1372 +
1373 +[[image:07-5 Basic instructions_html_c0e65cfeed403ecf.png]]
1374 +
1375 +When X000 is ON, when D0<(-1,000), the value of ( D0)-(-1,000) is stored in (D1).
1376 +
1377 +• When -1,000≦ D0≦1,000, 0 is stored in D1.
1378 +
1379 +• When D0<1,000, the value of (D0)-1,000 is stored in D1.
1380 +
1381 +{{id name="_Toc1180"/}}{{id name="_Toc21657"/}}{{id name="_Toc27323"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DBAND/BIN 32-bit data dead zone control**
1382 +
1383 +**DBAND(P)**
1384 +
1385 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2).
1386 +
1387 +-[DBAND (s1) (s2) (S3) (d)]
1388 +
1389 +**Content, range and data type**
1390 +
1391 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1392 +|(s1)|Dead zone low limit (no output zone)|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
1393 +|(s2)|Dead zone high limit (no output zone)|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
1394 +|(S3)|Input value controlled by dead zone control|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
1395 +|(d)|The start number of the device that stores the output value controlled by the dead zone control|-|Signed BIN 32 bit|ANY32_S
1396 +
1397 +**Device used**
1398 +
1399 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1400 +**Pulse**
1401 +
1402 +**extension**
1403 +)))
1404 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1405 +|(% rowspan="4" %)DBAND|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1406 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1407 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|●
1408 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
1409 +
1410 +**Features**
1411 +
1412 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). The output value is controlled as follows.
1413 +
1414 +|**Condition**|**The value stored in the output value**
1415 +|When dead zone low limit ((s1), (s1)+1)> input value ((s3), (s3)+1)|{{id name="OLE_LINK42"/}}Input value ((s3), (s3)+1)-dead zone low limit ((s1), (s1)+1)
1416 +|When dead zone high limit ((s1), (s1)+1) <input value ((s3), (s3)+1)|{{id name="OLE_LINK357"/}}Input value ((s3), (s3)+1)-dead zone high limit ((s2), (s2)+1)
1417 +|When dead zone low limit ((s1), (s1)+1) ≤ input value ((s3), (s3)+1) ≤ dead zone high limit ((s2), (s2)+1)|0
1418 +
1419 +
1420 +(((
1421 +• When the output value stored in (d) is a signed BIN 32-bit value, and the operation result exceeds the range of -2,147,483,648 to 2,147,483,647, the situation is as the following example. For example,** &nbsp;**When (s1) and (s1)+1 are 1000, (s3) and (s3)+1 are -2,147,483,648, then the output value=
1422 +
1423 +-2,147,483,648-1000=80000000H-000003E8H=7FFFFC18H=2,147,482,648.
1424 +
1425 +[[image:07-5 Basic instructions_html_e0144674dad3e8fd.png]]
1426 +
1427 +
1428 +
1429 +)))
1430 +
1431 +**Error code**
1432 +
1433 +|**Error code**|**Content**
1434 +|4085H|When the specified device range for reading exceeds the range of the corresponding device.
1435 +|4086H|When the specified device range for writing exceeds the range of the corresponding device.
1436 +|4084H|When the low limit specified in (s1) is greater than the high limit specified in (s2).
1437 +
1438 +**Example**
1439 +
1440 +[[image:07-5 Basic instructions_html_88f3fe0fb4841bab.png]]
1441 +
1442 +• When (D1, D0)<(-10,000), the value of (D1, D0)-(-10,000) is stored in (D11, D10).
1443 +
1444 +• When -10,000≦(D1, D0)≦10,000, 0 is stored in (D11, D10).
1445 +
1446 +• When 10,000< (D1, D0), the value of (D1, D0)-10,000 is stored in D1.
1447 +
1448 +{{id name="_Toc21668"/}}{{id name="_Toc25056"/}}{{id name="_Toc17582"/}}{{id name="OLE_LINK165"/}}**BINDA/BIN 16-bit data → Decimal ASCII conversion**
1449 +
1450 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **BINDA(P)**
1451 +
1452 +Convert the BIN 16-bit data specified in (s) and the value of each digit in decimal numbers into ASCII codes and store them after the device number specified in (d).
1453 +
1454 +-[BINDA(s)(d)]
1455 +
1456 +**Content, range and data type**
1457 +
1458 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1459 +|(s)|BIN data for ASCII conversion|-32768 to +32767|Signed BIN 16 bit|ANY16_S
1460 +|(d)|The start number of the device storing the conversion result|-|String|ANYSTRING_SINGLE
1461 +
1462 +**Device used**
1463 +
1464 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1465 +**Pulse**
1466 +
1467 +**extension**
1468 +)))
1469 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1470 +|(% rowspan="2" %)BINDA|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1471 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1472 +
1473 +**Features**
1474 +
1475 +Convert the BIN 16-bit data specified in (s) and the value of each digit in decimal numbers into ASCII codes and store them after the device number specified in (d).
1476 +
1477 +
1478 +
1479 +(((
1480 +←Only store 0 when SM191 is OFF
1481 +
1482 +[[image:07-5 Basic instructions_html_57bda5f08026449d.png]]
1483 +)))
1484 +
1485 +For example, when -12,345 is specified in (s) (in the case of specifying signed)
1486 +
1487 +[[image:07-5 Basic instructions_html_f346102467b9bef9.png]]
1488 +
1489 +The calculation result stored in (d) will be as below.
1490 +
1491 +• In "Sign", 20H is stored when the BIN data is positive, and 2DH is stored when it is negative.
1492 +
1493 +• In the 0 to the left of the effective digit, 20H is stored. (Suppress 0.) For example, in the case of "00325", "00" becomes 20H, and "325" becomes the effective digit.
1494 +
1495 +• When storing data to the device specified in (d)+3, when SM191 (output character number switching signal) is OFF, 0 is stored, and it does not change when it is ON.
1496 +
1497 +✎**Note: **The number of occupied points of (d) is 3 when SM191 is ON, and it is 4 when SM191 is OFF.
1498 +
1499 +**Error code**
1500 +
1501 +|**Error code**|**Content**
1502 +|4085H|The read address of (s) exceeds the device range.
1503 +|4086H|The write address of (d) exceeds the device range.
1504 +
1505 +**Example**
1506 +
1507 +
1508 +
1509 +(((
1510 +When X000 is ON, convert the value of 16-bit data (BIN) D1000 into decimal ASCII code, and then use PR instruction to output the
1511 +
1512 +converted ASCII code character by character to the program of Y040 to Y057.
1513 +
1514 +[[image:07-5 Basic instructions_html_c598806a42484ed.png]]
1515 +)))
1516 +
1517 +{{id name="_Toc12255"/}}{{id name="_Toc8216"/}}{{id name="_Toc470"/}}**DBINDA/BIN 32-bit data → Decimal ASCII conversion**
1518 +
1519 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DBINDA(P)**
1520 +
1521 +Convert the BIN 32-bit data specified in (s) and the value of each bit in decimal numbers into ASCII codes and store them after the device number specified in (d).
1522 +
1523 +-[DBINDA(s)(d)]
1524 +
1525 +**Content, range and data type**
1526 +
1527 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1528 +|(s)|BIN data for ASCII conversion|-2,147483648 to 2147483647|Signed BIN 32 bit|ANY32_S
1529 +|(d)|{{id name="OLE_LINK2"/}}The start number of the device storing the conversion result|-|String|ANYSTRING_SINGLE
1530 +
1531 +**Device used**
1532 +
1533 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1534 +**Offset**
1535 +
1536 +**modification**
1537 +)))|(((
1538 +**Pulse**
1539 +
1540 +**extension**
1541 +)))
1542 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1543 +|(% rowspan="2" %)DBINDA|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1544 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1545 +
1546 +**Features**
1547 +
1548 +Convert the BIN 32-bit data specified in (s) and the value of each bit when expressed in decimal numbers into ASCII codes, and store them after the device number specified in (d).
1549 +
1550 +For example, when -12345678 is specified in (s). (in the case of specifying signed)
1551 +
1552 +[[image:07-5 Basic instructions_html_4d939462838cf09b.gif]] The calculation result stored in (d) will be as below.
1553 +
1554 +• In "Sign", 20H is stored when the BIN data is positive, and 2DH is stored when it is negative.
1555 +
1556 +• 20H is stored at 0 to the left of the effective number of digits. (Suppress 0.) For example, in the case of "0012034560", "00" becomes 20H, and "12034560" becomes effective digits.
1557 +
1558 +• For the data stored in the upper 8 bits of the device specified in (d)+5, 0 will be stored when SM191 (output character switching signal) is OFF, and 20H will be stored when it is ON.
1559 +
1560 +✎**Note: **(d) Occupies 6 points.
1561 +
1562 +**Error code**
1563 +
1564 +|**Error code**|**Content**
1565 +|4085H|(s) read address exceeds the device range
1566 +|4086H|(d) write address exceeds the device range
1567 +
1568 +**Example**
1569 +
1570 +[[image:07-5 Basic instructions_html_ec8ac32d748a991c.png]]
1571 +
1572 +When X000 is ON, convert the value of 32-bit data (BIN) D1000 into decimal ASCII code, and then use PR (FNC 77) instruction to output the converted ASCII code character by character to the program in Y040 to Y051 in time and time division.
1573 +
1574 +{{id name="_Toc19693"/}}{{id name="_Toc18078"/}}{{id name="_Toc5726"/}}**DABIN/Decimal ASCII → BIN conversion**
1575 +
1576 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DABIN(P)**
1577 +
1578 +Digital ASCII code (30H to 39H) is a instruction to convert real data into BIN data.
1579 +
1580 +-[DABIN (s) (d)]
1581 +
1582 +**Content, range and data type**
1583 +
1584 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1585 +|(s)|The start number of the device that stores the data (ASCII code) to be converted into a BIN value|-|String|ANYSTRING_SINGLE
1586 +|(d)|The device number for storing conversion result|-|BIN16 bit|ANY16_S
1587 +
1588 +**Device used**
1589 +
1590 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1591 +**Pulse**
1592 +
1593 +**extension**
1594 +)))
1595 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1596 +|(% rowspan="2" %)DABIN|Parameter 1| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1597 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1598 +
1599 +**Features**
1600 +
1601 +The decimal ASCII data stored after the device number specified in (s) is converted into BIN 16-bit data and stored in the device specified in (d).
1602 +
1603 +[[image:07-5 Basic instructions_html_22c5cb32a0a32214.png]]
1604 +
1605 +|**ASCII S**|**ASCII 10^^0^^**|**ASCII 10^^1^^**|**ASCII 10^^2^^**|**ASCII 10^^3^^**|**ASCII 10^^4^^**
1606 +|**ASCII code**|(((
1607 +{{id name="OLE_LINK36"/}}Units of
1608 +
1609 +ASCII code
1610 +)))|(((
1611 +Tens of
1612 +
1613 +ASCII code
1614 +)))|(((
1615 +Hundreds of
1616 +
1617 +ASCII code
1618 +)))|(((
1619 +Thousands of
1620 +
1621 +ASCII code
1622 +)))|(((
1623 +Ten thousands
1624 +
1625 +of ASCII code
1626 +)))
1627 +
1628 +For example, When -25,108 is specified in (s)
1629 +
1630 +[[image:07-5 Basic instructions_html_10fb2792e37dbf23.png]]
1631 +
1632 +• The ASCII data specified in (s) to (s)+2 is within the range of -32,768 to +32,767.
1633 +
1634 +• In “Sign”, set 20H when the converted data is positive, and set 2DH when it is negative. (When other than 20H or 2DH is set, it will be treated as positive data. (DABIN(P))
1635 +
1636 +• The range of the ASCII code set in each digit is 30H to 39H.
1637 +
1638 +• When the ASCII code set in each bit is 20H or 00H, it will be treated as 30H.
1639 +
1640 +**Error code**
1641 +
1642 +|**Error code**|**Content**
1643 +|4084H|(((
1644 +When the Sign data exceeds the range of 30H to 39H, 20H, 00H, 2DH;
1645 +
1646 +When the ASCII code of each bit specified in (s) to (s)+2 exceeds the range of 30H to 39H, 20H, 00H;
1647 +
1648 +When the ASCII data specified in (s) to (s)+2 is other than -32,768 to +32,767.
1649 +)))
1650 +|4085H|The read address of (s) exceeds the device range.
1651 +|4086H|The write address of (d) exceeds the device range.
1652 +
1653 +
1654 +(((
1655 +When X000 is ON, the Signs set in D20 to D22 and the ASCII code data of 5-digit decimal numbers are converted into BIN values, and then stored in the program of D0.
1656 +
1657 +**Example**
1658 +)))
1659 +
1660 +[[image:07-5 Basic instructions_html_bec2bea131b58c03.png]]
1661 +
1662 +{{id name="_Toc3351"/}}{{id name="_Toc26383"/}}{{id name="_Toc26233"/}}**DDABIN/Decimal ASCII → BIN32-bit data conversion**
1663 +
1664 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DDABIN(P)**
1665 +
1666 +The decimal ASCII data stored after the device number specified in (s) is converted into BIN 32-bit data and stored in the device number specified in (d).
1667 +
1668 +-[DDABIN (s) (d) ]
1669 +
1670 +**Content, range and data type**
1671 +
1672 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1673 +|(s)|The start number of the device that stores data (ASCII code) to be converted into a BIN value|-|String|ANYSTRING_SINGLE
1674 +|(d)|The device number for storing conversion result|-|Signed BIN 32 bit|ANY32_S
1675 +
1676 +**Device used**
1677 +
1678 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1679 +**Pulse**
1680 +
1681 +**extension**
1682 +)))
1683 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1684 +|(% rowspan="2" %)DDABIN|Parameter 1| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1685 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
1686 +
1687 +**Features**
1688 +
1689 +The decimal ASCII data stored after the device number specified in (s) is converted into BIN 32-bit data and stored in the device specified in (d).
1690 +
1691 +[[image:07-5 Basic instructions_html_c444110b273f33b7.gif]]
1692 +
1693 +|**ASCII S**|**ASCII code**|**ASCII S**|**ASCII code**
1694 +|ASCII 10^^0^^|Units of ASCII code|ASCII 10^^5^^|{{id name="OLE_LINK38"/}}Hundred thousands of ASCII code
1695 +|ASCII 10^^1^^|Tens of ASCII code|ASCII 10^^6^^|Millions of ASCII code
1696 +|ASCII 10^^2^^|Hundreds of ASCII code|ASCII 10^^7^^|Ten millions of ASCII code
1697 +|ASCII 10^^3^^|{{id name="OLE_LINK37"/}}Thousands of ASCII code|ASCII 10^^8^^|Hundred millions of ASCII code
1698 +|ASCII 10^^4^^|Tens thousands of ASCII code|ASCII 10^^9^^|billions of ASCII code
1699 +
1700 +When -1234543210 is specified in (s) (When signed is specified)
1701 +
1702 +[[image:07-5 Basic instructions_html_1b4c7e1c663a4399.png]]
1703 +
1704 +• The ASCII data specified in (s) to (s)+5 is within the range of -2,147,483,648 to +2,147,483,647. In addition, the data stored in the high byte of (s)+5 will be ignored.
1705 +
1706 +• In the Sign data, set 20H when the converted data is positive, and set 2DH when it is negative. (When other than 20H or 2DH is set, it will be treated as positive data. (DABIN(P))
1707 +
1708 +• The range of ASCII code set in each digit is 30H to 39H.
1709 +
1710 +• When the ASCII code set in each bit is 20H or 00H, it will be treated as 30H.
1711 +
1712 +**Error code**
1713 +
1714 +|**Error code**|**Content**
1715 +|4084H|(((
1716 +When the Sign data exceeds the range of 30H to 39H, 20H, 00H and 2DH;
1717 +
1718 +{{id name="OLE_LINK39"/}}When the ASCII code of each bit specified in (s) to (s)+5 exceeds the range of 30H to 39H, 20H and 00H;
1719 +
1720 +When the ASCII data specified in (s) to (s)+5 exceeds the range of -2,147,483,648 to +2,147,483,647
1721 +)))
1722 +|4085H|The read address of (s) exceeds the device range.
1723 +|4086H|The write address of (d) exceeds the device range.
1724 +
1725 +**Example**
1726 +
1727 +[[image:07-5 Basic instructions_html_feea438c943ea9dd.png]]
1728 +
1729 +When X000 is ON, the Signs set in to D20 to D25 and the ASCII code data of 10-digit decimal numbers are converted into BIN values and then saved to the program in D0 to D1.
1730 +
1731 +{{id name="_Toc26556"/}}{{id name="_Toc12799"/}}{{id name="_Toc23863"/}}**LIMIT/ BIN 16-bit data high and low limit control**
1732 +
1733 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **LIMIT(P)**
1734 +
1735 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limit value ranges specified in (s1) and (s2).
1736 +
1737 +-[LIMIT (s1) (s2) (s3) (d)]
1738 +
1739 +**Content, range and data type**
1740 +
1741 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1742 +|s1|Low limit value (minimum output limit value)|-32,768 to 32,767|BIN16 bit|ANY16_S
1743 +|s2|High limit value (maximum output limit value)|-32,768 to 32,767|BIN16 bit|ANY16_S
1744 +|s3|Input value controlled by high and low limit control|-32,768 to 32,767|BIN16 bit|ANY16_S
1745 +|d|The start number of device that stores the output value controlled by high and low limit control|-|BIN16 bit|ANY16_S
1746 +
1747 +**Device used**
1748 +
1749 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1750 +**Pulse**
1751 +
1752 +**extension**
1753 +)))
1754 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1755 +|(% rowspan="4" %)LIMIT|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1756 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1757 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1758 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1759 +
1760 +**Features**
1761 +
1762 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the high and low limit value ranges specified in (s1) and (s2). The output value is controlled as follows.
1763 +
1764 +|**Condition**|**The value stored in the output value**
1765 +|Low limit value (s1)>input value (s3)|Low limit value (s1)
1766 +|High limit value (s1) <input value (s3)|High limit value (s2)
1767 +|Low limit value (s1) ≤ input value (s3) ≤ high limit value (s2)|Input value (s3)
1768 +
1769 +
1770 +(((
1771 +•Only in the case of controlling high limit value, set the minimum value of data range in the low limit value specified in (s1).
1772 +
1773 +• Only in the case of controlling low limit value, set the maximum value of data range in the high limit value specified in (s2).
1774 +
1775 +[[image:07-5 Basic instructions_html_50eb5229b027aa14.png]]
1776 +)))
1777 +
1778 +**Error code**
1779 +
1780 +|**Error code**|**Content**
1781 +|4085H|The read address exceeds the device range
1782 +|4086H|The write address exceeds the device range
1783 +|4084H|High limit <low limit
1784 +
1785 +**Example**
1786 +
1787 +[[image:07-5 Basic instructions_html_d67a2e740d4fc738.png]]
1788 +
1789 +When X000 is ON
1790 +
1791 +• When D0 <500, D1 is 500.
1792 +
1793 +• When 500 ≤ D0 ≤ 5,000, D1 is the value of D0.
1794 +
1795 +• When 5,000 <D0, D1 is 5,000.
1796 +
1797 +{{id name="_Toc32553"/}}{{id name="_Toc9981"/}}{{id name="_Toc9158"/}}**DLIMIT/BIN 32-bit data high and low limit control**
1798 +
1799 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DLIMIT(P)**
1800 +
1801 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the range of high and low limit values specified in (s1) and (s2).
1802 +
1803 +-[DLIMIT (s1) (s2) (s3) (d)]
1804 +
1805 +**Content, range and data type**
1806 +
1807 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1808 +|s1|Low limit value (minimum output limit value)|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S
1809 +|s2|High limit value (maximum output limit value)|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S
1810 +|s3|Input value controlled by high and low limit control|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S
1811 +|d|The start number of the device that stores the output value controlled by high and low limit control|-|BIN32 bit|ANY32_S
1812 +
1813 +**Device used**
1814 +
1815 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1816 +**Pulse**
1817 +
1818 +**extension**
1819 +)))
1820 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1821 +|(% rowspan="4" %)DLIMIT|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1822 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1823 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|●
1824 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
1825 +
1826 +**Features**
1827 +
1828 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the range of high and low limit values specified in (s1) and (s2). The output value is controlled as follows.
1829 +
1830 +|**Condition**|**The value stored in the output value**
1831 +|Low limit value ((s1), (s1)+1)> input value ((s3), (s3)+1)|Low limit value ((s1), (s1)+1)
1832 +|High limit value ((s2), (s2)+1) <input value ((s3), (s3)+1)|High limit value ((s2), (s2)+1)
1833 +|Low limit value ((s1), (s1)+1) ≤ input value ((s3), (s3)+1) ≤ high limit value ((s2), (s2)+1)|Input value ((s3), (s3)+1)
1834 +
1835 +{{id name="OLE_LINK43"/}}{{id name="OLE_LINK40"/}}•Only in the case of controlling high limit value, set the minimum value of data range in the low limit value specified in (s1).
1836 +
1837 +• Only in the case of controlling low limit value, set the maximum value of data range in the high limit value specified in (s2).
1838 +
1839 +**Error code**
1840 +
1841 +|**Error code**|**Content**
1842 +|4085H|The read address exceeds the device range
1843 +|4086H|The write address exceeds the device range
1844 +|4084H|High limit <low limit
1845 +
1846 +**Example**
1847 +
1848 +[[image:07-5 Basic instructions_html_217355b90f4b4e16.png]]
1849 +
1850 +Operation:
1851 +
1852 +• When (D1, D0) <10,000, (D11, D10) is 10,000.
1853 +
1854 +• When 10,000 ≤ (D1, D0) ≤ 1,000,000, (D11, D10) is the value of (D1, D0).
1855 +
1856 +• When 1,000,000 <(D1, D0), (D11, D10) is 1,000,000.
1857 +
1858 +{{id name="_Toc12534"/}}{{id name="_Toc28213"/}}{{id name="_Toc24591"/}}**SCL/BIN 16-bit unit scale (coordinate data of each point)**
1859 +
1860 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **SCL(P)**
1861 +
1862 +The scaling conversion data (16-bit data unit) specified in (s2) is scaled from the input value specified in (s1), and the calculation result is stored in the device specified in (d).
1863 +
1864 +-[SCL (s1) (s2) (d)]
1865 +
1866 +**Content, range and data type**
1867 +
1868 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1869 +|(s1)|The input value for scaling or the start number of device storing the input value|-32,768 to 32,767|Signed BIN 16 bit|ANY16_S
1870 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 16 bit|ANY16_S
1871 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 16 bit|ANY16_S
1872 +
1873 +**Device used**
1874 +
1875 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1876 +**Pulse**
1877 +
1878 +**extension**
1879 +)))
1880 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1881 +|(% rowspan="3" %)SCL|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1882 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1883 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1884 +
1885 +**Features**
1886 +
1887 +For the scale conversion data (16-bit data unit) specified in (s2), scale by the input value specified in (s1), and store the operation result in the device specified in (d). Scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
1888 +
1889 +|(% colspan="2" %)**Setting items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
1890 +|(% colspan="2" %)Coordinate points|(s2)
1891 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+1
1892 +|Y coordinate|(s2)+2
1893 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+3
1894 +|Y coordinate|(s2)+4
1895 +|(% colspan="3" %)........
1896 +|(% rowspan="2" %)Point n|X coordinate|(s2)+2n-1
1897 +|Y coordinate|(s2)+2n
1898 +
1899 +[[image:07-5 Basic instructions_html_80185ccddb878234.png]]
1900 +
1901 +• If the operation result is not an integer value, round the first digit below the decimal point.
1902 +
1903 +• The X coordinate data of the conversion data for scaling should be set in ascending order.
1904 +
1905 +• (s1) should be set within the range of conversion data for scaling (device value of (s2)).
1906 +
1907 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
1908 +
1909 +• Set the number of coordinate points of the conversion data for scaling within the range of 1 to 32,767.
1910 +
1911 +• Setting example of conversion table for scaling.
1912 +
1913 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
1914 +
1915 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
1916 +
1917 +|(% colspan="2" rowspan="2" %)**Set &nbsp;&nbsp;&nbsp;&nbsp;items**|(% colspan="3" %)**Sett &nbsp;&nbsp;&nbsp;&nbsp;device and content**|(% rowspan="2" %)**Remarks**
1918 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set &nbsp;&nbsp;&nbsp;&nbsp;content**
1919 +|(% colspan="2" %)Coordinate points|(s2)|R0|K10|
1920 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+1|R1|K5|
1921 +|Y coordinate|(s2)+2|R2|K20|
1922 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+3|R3|K30|
1923 +|Y coordinate|(s2)+4|R4|K50|
1924 +|(% rowspan="2" %)Point 3|X coordinate|(s2)+5|R5|K100|
1925 +|Y coordinate|(s2)+6|R6|K200|
1926 +|(% rowspan="2" %)Point 4|X coordinate|(s2)+7|R7|K25|(% rowspan="6" %)(((
1927 +If the coordinates are specified by 3 points, the intermediate value could be the output value.
1928 +
1929 +In this example, the output value (median value) is specified by the Y coordinate of point 5.
1930 +
1931 +When the X coordinate is the same at 3 points or more, the value of the 2nd point is also output.
1932 +)))
1933 +|Y coordinate|(s2)+8|R8|K200
1934 +|(% rowspan="2" %)Point 5|X coordinate|(s2)+9|R9|K70
1935 +|Y coordinate|(s2)+10|R10|K200
1936 +|(% rowspan="2" %)Point 6|X coordinate|(s2)+11|R11|K250
1937 +|Y coordinate|(s2)+12|R12|K250
1938 +|(% rowspan="2" %)Point 7|X coordinate|(s2)+13|R13|K250|
1939 +|Y coordinate|(s2)+14|R14|K90|
1940 +|(% rowspan="2" %)Point 8|X coordinate|(s2)+15|R15|K350|(% rowspan="4" %)(((
1941 +If the coordinates are specified by two points, the output value is the value of the Y coordinate of the next point.
1942 +
1943 +In this example, the output value is specified by the Y coordinate of point 9.
1944 +)))
1945 +|Y coordinate|(s2)+16|R16|K90
1946 +|(% rowspan="2" %)Point 9|X coordinate|(s2)+17|R17|K350
1947 +|Y coordinate|(s2)+18|R18|K30
1948 +|(% rowspan="2" %)Point 10|X coordinate|(s2)+19|R19|K400|
1949 +|Y coordinate|(s2)+20|R20|K7|
1950 +
1951 +**Error code**
1952 +
1953 +|**Error code**|**Content**
1954 +|4085H|When the specified device range for reading exceeds the range of the corresponding device.
1955 +|4086H|When the specified device range for writing exceeds the range of the corresponding device.
1956 +|4084H|(((
1957 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
1958 +
1959 +When the input value specified in (s1) exceeds the range of the set scale conversion data;
1960 +
1961 +When the number of start coordinate points of device (s2) is less than 0.
1962 +)))
1963 +
1964 +**Example**
1965 +
1966 +[[image:07-5 Basic instructions_html_5519d7b41f15b6d6.png]]
1967 +
1968 +[[image:07-5 Basic instructions_html_ace075fb7675de8e.gif]] When -100 ≤ D0(X) < 0, D100(Y)=
1969 +
1970 +[[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] when D0(X)=0, D100(Y)=0;
1971 +
1972 +when 0< D0(X) ≤ 100, D100(Y)=
1973 +
1974 +[[image:07-5 Basic instructions_html_e35e13160c08a133.png]]
1975 +
1976 +
1977 +
1978 +{{id name="_Toc4862"/}}{{id name="_Toc11340"/}}{{id name="_Toc25383"/}}**DSCL/32-bit unit scale (coordinate data of each point)**
1979 +
1980 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSCL(P)**
1981 +
1982 +The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d).
1983 +
1984 +-[DSCL (s1) (s2) (d)]
1985 +
1986 +**Content, range and data type**
1987 +
1988 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1989 +|(s1)|The input value for scaling or the start number of the device storing the input value|-2,147,483,648 to 2,147,483,647|Signed BIN 32 bit|ANY32_S
1990 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 32 bit|ANY32_S
1991 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 32 bit|ANY32_S
1992 +
1993 +**Device used**
1994 +
1995 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Device**|**Offset modification**|(((
1996 +**Pulse**
1997 +
1998 +**extension**
1999 +)))
2000 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2001 +|(% rowspan="3" %)DSCL|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
2002 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
2003 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
2004 +
2005 +**Features**
2006 +
2007 +{{id name="OLE_LINK41"/}}The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
2008 +
2009 +|(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
2010 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2)
2011 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+3, (s2)+2
2012 +|Y coordinate|(s2)+5, (s2)+4
2013 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+7, (s2)+6
2014 +|Y coordinate|(s2)+9, (s2)+8
2015 +|(% colspan="3" %)........
2016 +|(% rowspan="2" %)Point n|X coordinate|(s2)+4n-1, (s2)+4n-2
2017 +|Y coordinate|(s2)+4n+1, (s2)+4n
2018 +
2019 +[[image:07-5 Basic instructions_html_6633ca18cee1218c.png]]
2020 +
2021 +• If the calculation result is not an integer value, round the first digit below the decimal point.
2022 +
2023 +• The X coordinate data of the conversion data for scaling should be set in ascending order.
2024 +
2025 +• For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value).
2026 +
2027 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
2028 +
2029 +• Set the number of coordinate points of conversion data for scaling within the range of 1 to 2,147,483,647.
2030 +
2031 +• Setting example of conversion table for scaling.
2032 +
2033 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
2034 +
2035 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
2036 +
2037 +|(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Set &nbsp;&nbsp;&nbsp;&nbsp;device and content**|(% rowspan="2" %)**Remarks**
2038 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set &nbsp;&nbsp;&nbsp;&nbsp;content**
2039 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2)|R1, R0|K10|
2040 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+3, (s2)+2|R3, R2|K5|
2041 +|Y coordinate|(s2)+5, (s2)+4|R5, R4|K7|
2042 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+7, (s2)+6|R7, R6|K20|
2043 +|Y coordinate|(s2)+9, (s2)+8|R9, R8|K30|
2044 +|(% rowspan="2" %)Point 3|X coordinate|(s2)+11, (s2)+10|R10, R11|K50|
2045 +|Y coordinate|(s2)+13, (s2)+12|R13, R12|K100|
2046 +|(% rowspan="2" %)Point 4|X coordinate|(s2)+15, (s2)+14|R15, R14|K200|(% rowspan="6" %)(((
2047 +if the coordinates are specified by 3 points, the intermediate value could be the output value.
2048 +
2049 +In this example, the output value (median value) is specified by the Y coordinate of point 5.
2050 +
2051 +When the X coordinate is the same at 3 points or more, the value of the 2nd point is also output.
2052 +)))
2053 +|Y coordinate|(s2)+17, (s2)+16|R17, R16|K25
2054 +|(% rowspan="2" %)Point 5|X coordinate|(s2)+19, (s2)+18|R19, R18|K200
2055 +|Y coordinate|(s2)+21, (s2)+20|R21, R20|K70
2056 +|(% rowspan="2" %)Point 6|X coordinate|(s2)+23, (s2)+22|R23, R22|K200
2057 +|Y coordinate|(s2)+25, (s2)+24|R25, R24|K250
2058 +|(% rowspan="2" %)Point 7|X coordinate|(s2)+27, (s2)+26|R27, R26|K250|
2059 +|Y coordinate|(s2)+29, (s2)+28|R29, R28|K90|
2060 +|(% rowspan="2" %)Point 8|X coordinate|(s2)+31, (s2)+30|R31, R30|K350|(% rowspan="4" %)(((
2061 +If the coordinates are specified by two points, the output value is the value of the Y coordinate of the next point.
2062 +
2063 +In this example, the output value is specified by the Y coordinate of point 9.
2064 +)))
2065 +|Y coordinate|(s2)+33, (s2)+32|R33, R32|K90
2066 +|(% rowspan="2" %)Point 9|X coordinate|(s2)+35, (s2)+34|R35, R34|K350
2067 +|Y coordinate|(s2)+37, (s2)+36|R37, R36|K30
2068 +|(% rowspan="2" %)Point 10|X coordinate|(s2)+39, (s2)+38|R39, R38|K400|
2069 +|Y coordinate|(s2)+41, (s2)+40|R41, R40|K7|
2070 +
2071 +**Error code**
2072 +
2073 +|**Error code**|**Content**
2074 +|4085H|When the specified device range for reading exceeds the range of the corresponding device.
2075 +|4086H|When the specified device range for writing exceeds the range of the corresponding device.
2076 +|4084H|(((
2077 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
2078 +
2079 +When the input value specified in (s1) exceeds the range of the set scale conversion data;
2080 +
2081 +When the number of start coordinate points of device (s2) is less than 0.
2082 +)))
2083 +
2084 +**Example**
2085 +
2086 +[[image:07-5 Basic instructions_html_ba95b2d50d8d1d3e.png]]
2087 +
2088 +[[image:07-5 Basic instructions_html_1de79c7d87d51f78.gif]] When -100 ≤ D0(X) < 0, D100(Y)=
2089 +
2090 +[[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] When D0(X)=0, D100(Y)=0;
2091 +
2092 +When 0 < D0(X) ≤ 100, D100(Y)=
2093 +
2094 +[[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]]
2095 +
2096 +{{id name="_Toc3776"/}}{{id name="_Toc11170"/}}{{id name="_Toc2957"/}}**SCL2/BIN 16-bit unit scale (X/Y coordinate data)**
2097 +
2098 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **SCL2(P)**
2099 +
2100 +The conversion data (16-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d).
2101 +
2102 +-[SCL2 (s1) (s2) (d)]
2103 +
2104 +**Content, range and data type**
2105 +
2106 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2107 +|(s1)|The input value for scaling or the start number of the device storing the input value|-32,768 to 32,767|Signed BIN 16 bit|ANY16_S
2108 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 16 bit|ANY16_S
2109 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 16 bit|ANY16_S
2110 +
2111 +**Device used**
2112 +
2113 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2114 +**Pulse**
2115 +
2116 +**extension**
2117 +)))
2118 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2119 +|(% rowspan="3" %)SCL2|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
2120 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
2121 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
2122 +
2123 +**Features**
2124 +
2125 +The conversion data (16-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
2126 +
2127 +|(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
2128 +|(% colspan="2" %)Coordinate points|(s2)
2129 +|(% rowspan="4" %)X coordinate|Point 1|(s2)+1
2130 +|Point 2|(s2)+2
2131 +|.....|......
2132 +|Point n|(s2)+n
2133 +|(% rowspan="4" %)Y coordinate|Point 1|(s2)+n+1
2134 +|Point 2|(s2)+n+2
2135 +|.....|.....
2136 +|Point n|(s2)+2n
2137 +
2138 +[[image:07-5 Basic instructions_html_80185ccddb878234.png]]
2139 +
2140 +• If the operation result is not an integer value, round the first digit below the decimal point.
2141 +
2142 +• The X coordinate data of the conversion data for scaling should be set in ascending order.
2143 +
2144 +• For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value).
2145 +
2146 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
2147 +
2148 +• Set the number of coordinate points of conversion data for scaling within the range of 1 to 32,767.
2149 +
2150 +• Setting example of conversion table for scaling.
2151 +
2152 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
2153 +
2154 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
2155 +
2156 +|(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Set device and content**|(% rowspan="2" %)**Remarks**
2157 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set content**
2158 +|(% colspan="2" %)Coordinate points|(s2)|R0|K10|
2159 +|(% rowspan="10" %)X coordinate|Point 1|(s2)+1|R1|K5|
2160 +|Point 2|(s2)+2|R2|K20|
2161 +|Point 3|(s2)+3|R3|K50|
2162 +|Point 4|(s2)+4|R4|K200|(% rowspan="3" %)Refer to** ✎1**
2163 +|Point 5|(s2)+5|R5|K200
2164 +|Point 6|(s2)+6|R6|K200
2165 +|Point 7|(s2)+7|R7|K250|
2166 +|Point 8|(s2)+8|R8|K350|(% rowspan="2" %)Refer to** ✎2**
2167 +|Point 9|(s2)+9|R9|K350
2168 +|Point 10|(s2)+10|R10|K400|
2169 +|(% rowspan="10" %)Y coordinate|Point 1|(s2)+11|R11|K7|
2170 +|Point 2|(s2)+12|R12|K30|
2171 +|Point 3|(s2)+13|R13|K100|
2172 +|Point 4|(s2)+14|R14|K25|(% rowspan="3" %)Refer to**✎1**
2173 +|Point 5|(s2)+15|R15|K70
2174 +|Point 6|(s2)+16|R16|K250
2175 +|Point 7|(s2)+17|R17|K90|
2176 +|Point 8|(s2)+18|R18|K90|(% rowspan="2" %)Refer to** ✎2**
2177 +|Point 9|(s2)+19|R19|K30
2178 +|Point 10|(s2)+20|R20|K7|
2179 +
2180 +✎**1** Like points 4, 5, and 6, if the coordinates are specified by 3 points, the intermediate value could be the output value.
2181 +
2182 +In this example, the output value (median value) is specified by the Y coordinate of point 5.
2183 +
2184 +When the X coordinate is the same at 3 or more points, the value of the second point is also output.
2185 +
2186 +✎**2** Like points 8 and 9, if the coordinates are specified by 2 points, the output value is the value of the Y coordinate of next point.
2187 +
2188 +In this example, the output value is specified by the Y coordinate of point 9.
2189 +
2190 +**Error code**
2191 +
2192 +|**Error code**|**Content**
2193 +|4085H|When the specified device range for reading exceeds the range of the corresponding device.
2194 +|4086H|When the specified device range for writing exceeds the range of the corresponding device.
2195 +|4084H|(((
2196 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
2197 +
2198 +When the input value specified in (s1) exceeds the range of the set scale conversion data;
2199 +
2200 +When the number of start coordinate points of device (s2) is less than 0.
2201 +)))
2202 +
2203 +**Example**
2204 +
2205 +[[image:07-5 Basic instructions_html_ace075fb7675de8e.gif]] [[image:07-5 Basic instructions_html_de529c9a16a62ef0.png]]
2206 +
2207 +When -100 ≤D0 (X) < 0, D100(Y)=
2208 +
2209 +[[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] when D0(X)=0, D100(Y)=0;
2210 +
2211 +when 0 < D0(X) ≤ 100, D100(Y)=
2212 +
2213 +[[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]]
2214 +
2215 +{{id name="_Toc5608"/}}{{id name="_Toc1756"/}}{{id name="_Toc21402"/}}**DSCL2/BIN 32-bit unit scale (X/Y coordinate data)**
2216 +
2217 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSCL2(P)**
2218 +
2219 +The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d).
2220 +
2221 +-[DSCL2 (s1) (s2) (d)]
2222 +
2223 +**Content, range and data type**
2224 +
2225 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2226 +|(s1)|The input value for scaling or the start number of the device storing the input value|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
2227 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 32 bit|ANY32_S
2228 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 32 bit|ANY32_S
2229 +
2230 +**Device used**
2231 +
2232 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2233 +**Pulse**
2234 +
2235 +**extension**
2236 +)))
2237 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2238 +|(% rowspan="3" %)DSCL2|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
2239 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
2240 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
2241 +
2242 +**Features**
2243 +
2244 +The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
2245 +
2246 +|(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
2247 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2)
2248 +|(% rowspan="4" %)X coordinate|Point 1|(s2)+3, (s2)+2
2249 +|Point 2|(s2)+5, (s2)+4
2250 +|.....|......
2251 +|Point n|(s2)+2n+1, (s2)+2n
2252 +|(% rowspan="4" %)Y coordinate|Point 1|(s2)+2n+3, (s2)+2n+2
2253 +|Point 2|(s2)+2n+5, (s2)+2n+4
2254 +|.....|.....
2255 +|Point n|(s2)+4n+1, (s2)+4n
2256 +
2257 +[[image:07-5 Basic instructions_html_6633ca18cee1218c.png]]
2258 +
2259 +• If the operation result is not an integer value, round the first digit below the decimal point.
2260 +
2261 +• The X coordinate data of the conversion data for scaling should be set in ascending order.
2262 +
2263 +• For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value).
2264 +
2265 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
2266 +
2267 +• Set the number of coordinate points of conversion data for scaling within the range of 1 to 2,147,483,647.
2268 +
2269 +• Setting example of conversion table for scaling.
2270 +
2271 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
2272 +
2273 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
2274 +
2275 +|(% colspan="2" rowspan="2" %)**Set &nbsp;&nbsp;&nbsp;&nbsp;items**|(% colspan="3" %)**Set device and content**|(% rowspan="2" %)**Remarks**
2276 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set content**
2277 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2)|R1, R0|K10|
2278 +|(% rowspan="10" %)X|Point 1|(s2)+3, (s2)+2|R3, R2|K5|
2279 +|Point 2|(s2)+5, (s2)+4|R5, R4|K20|
2280 +|Point 3|(s2)+7, (s2)+6|R7, R6|K50|
2281 +|Point 4|(s2)+9, (s2)+8|R9, R8|K200|(% rowspan="3" %)Refer to** ✎1**
2282 +|Point 5|(s2)+11, (s2)+10|R10, R11|K200
2283 +|Point 6|(s2)+13, (s2)+12|R13, R12|K200
2284 +|Point 7|(s2)+15, (s2)+14|R15, R14|K250|
2285 +|Point 8|(s2)+17, (s2)+16|R17, R16|K350|(% rowspan="2" %)Refer to** ✎2**
2286 +|Point 9|(s2)+19, (s2)+18|R19, R18|K350
2287 +|Point 10|(s2)+21, (s2)+20|R21, R20|K400|
2288 +|(% rowspan="10" %)Y coordinate|Point 1|(s2)+23, (s2)+22|R23, R22|K7|
2289 +|Point 2|(s2)+25, (s2)+24|R25, R24|K30|
2290 +|Point 3|(s2)+27, (s2)+26|R27, R26|K100|
2291 +|Point 4|(s2)+29, (s2)+28|R29, R28|K25|(% rowspan="3" %)Refer to** ✎1**
2292 +|Point 5|(s2)+31, (s2)+30|R31, R30|K70
2293 +|Point 6|(s2)+33, (s2)+32|R33, R32|K250
2294 +|Point 7|(s2)+35, (s2)+34|R35, R34|K90|
2295 +|Point 8|(s2)+37, (s2)+36|R37, R36|K90|(% rowspan="2" %)Refer to** ✎2**
2296 +|Point 9|(s2)+39, (s2)+38|R39, R38|K30
2297 +|Point 10|(s2)+41, (s2)+40|R41, R40|K7|
2298 +
2299 +✎**1** Like points 4, 5, and 6, if the coordinates are specified by 3 points, the intermediate value could be the output value.
2300 +
2301 +In this example, the output value (median value) is specified by the Y coordinate of point 5.
2302 +
2303 +When the X coordinate is the same at 3 or more points, the value of the second point is also output.
2304 +
2305 +✎**2** Like points 8 and 9, if the coordinates are specified by 2 points, the output value is the value of the Y coordinate of the next point.
2306 +
2307 +In this example, the output value is specified by the Y coordinate of point 9.
2308 +
2309 +**Error code**
2310 +
2311 +|**Error code**|**Content**
2312 +|4085H|When the specified device range for reading exceeds the range of the corresponding device.
2313 +|4086H|When the specified device range for writing exceeds the range of the corresponding device.
2314 +|4084H|(((
2315 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
2316 +
2317 +When the input value specified in (s1) exceeds the range of the set scale conversion data;
2318 +
2319 +When the number of start coordinate points of device (s2) is less than 0.
2320 +)))
2321 +
2322 +**Example**
2323 +
2324 +[[image:07-5 Basic instructions_html_91dbc16faa9d2ec3.png]]
2325 +
2326 +When -100 ≤D0(X) < 0, D100(Y)=[[image:/xwiki/bin/download/PLC%20Editor2/1%20User%20manual/2.1%20LX5V%20user%20manual/07-5%20Basic%20instruction/WebHome/07-5%20Basic%20instructions_html_2c96d630f666e72c.gif?rev=1.1||alt="07-5 Basic instructions_html_2c96d630f666e72c.gif"]],,[[image:07-5 Basic instructions_html_2c96d630f666e72c.gif]] ,,;
2327 +
2328 +when D0(X)=0, D100(Y)=0;
2329 +
2330 +when 0< D0(X) ≤ 100, D100(Y)=[[image:/xwiki/bin/download/PLC%20Editor2/1%20User%20manual/2.1%20LX5V%20user%20manual/07-5%20Basic%20instruction/WebHome/07-5%20Basic%20instructions_html_47ebf5cc7733fccc.gif?rev=1.1||alt="07-5 Basic instructions_html_47ebf5cc7733fccc.gif"]],,[[image:07-5 Basic instructions_html_47ebf5cc7733fccc.gif]] ,,.
2331 +
2332 +[[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]]
2333 +
2334 +{{id name="_Toc32057"/}}{{id name="_Toc9941"/}}{{id name="_Toc6492"/}}**ZONE/BIN 16-bit data zone control**
2335 +
2336 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **ZONE(P)**
2337 +
2338 +After adding the offset value specified in (s1) or (s2) to the input value specified in (s3), it is stored in the device number specified in (d).
2339 +
2340 +-[ZONE (s1) (s2) (s3) (d)]
2341 +
2342 +**Content, range and data type**
2343 +
2344 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2345 +|s1|The negative offset value for addition in the input value|-32,768 to 32,767|BIN16 bit|ANY16_S
2346 +|s2|The positive offset value for addition in the input value|-32,768 to 32,767|BIN16 bit|ANY16_S
2347 +|s3|Input value for zone control`|-32,768 to 32,767|BIN16 bit|ANY16_S
2348 +|d|The start number of the device storing the output value controlled by zone control|-|BIN16 bit|ANY16_S
2349 +
2350 +**Device used**
2351 +
2352 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2353 +**Pulse**
2354 +
2355 +**extension**
2356 +)))
2357 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2358 +|(% rowspan="4" %)ZONE|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
2359 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
2360 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
2361 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
2362 +
2363 +**Features**
2364 +
2365 +After adding the offset value specified in (s1) or (s2) to the input value (BIN 16-bit value) specified in (s3), it is stored in the device number specified in (d). The offset value is controlled as follows.
2366 +
2367 +|**Condition**|**The value stored in the output value**
2368 +|When input value (s3)<0|Input value (s3) + negative offset value (s1)
2369 +|When input value (s3)=0|0
2370 +|When input value (s3)>0|Input value (s3) + positive offset value (s2)
2371 +
2372 +
2373 +(((
2374 +• When the output value stored in (d) is a signed BIN 16-bit value, and the operation result exceeds the range of -32,768 to 32,767, the situation is shown in the following example.
2375 +
2376 +For example, when (s1) is -100 and (s3) is -32,768,
2377 +
2378 +the output value = -32768+(-100)=8000H-FF9CH=7F9CH=32668.
2379 +
2380 +[[image:07-5 Basic instructions_html_a2adbf9ccf8f839.png]]
2381 +
2382 +
2383 +
2384 +)))
2385 +
2386 +**Error code**
2387 +
2388 +|**Error code**|**Content**
2389 +|4085H|When the specified device range for reading exceeds the range of the corresponding device
2390 +|4086H|When the specified device range for writing exceeds the range of the corresponding device
2391 +
2392 +**Example**
2393 +
2394 +[[image:07-5 Basic instructions_html_5da523c7765bf5be.png]]
2395 +
2396 +When X000 is ON
2397 +
2398 +• When D0<0, the value of (D0)+(-1,000) is stored in D1.
2399 +
2400 +• When D0=0, 0 is stored in D1.
2401 +
2402 +• When 0<D0, the value of (D0)+(1,000) is stored in D1.
2403 +
2404 +{{id name="_Toc28351"/}}{{id name="_Toc11023"/}}{{id name="_Toc30269"/}}**DZONE/BIN 32-bit data zone control**
2405 +
2406 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] DZONE(P)
2407 +
2408 +After adding the offset value specified in (s1) or (s2) to the input value specified in (s3), it is stored in the device number specified in (d).
2409 +
2410 +-[DZONE (s1) (s2) (s3) (d)]
2411 +
2412 +**Content, range and data type**
2413 +
2414 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2415 +|(s1)|The negative offset value for addition in the input value|-2147483648 to 2147483647|BIN32 bit|ANY32_S
2416 +|(s2)|The positive offset value for addition in the input value|-2147483648 to 2147483647|BIN32 bit|ANY32_S
2417 +|(s3)|Input value for zone control|-2147483648 to 2147483647|BIN32 bit|ANY32_S
2418 +|(d)|The start number of the device storing the output value controlled by zone control|-|BIN32 bit|ANY32_S
2419 +
2420 +**Device used**
2421 +
2422 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2423 +**Pulse**
2424 +
2425 +**extension**
2426 +)))
2427 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2428 +|(% rowspan="4" %)DZONE|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
2429 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
2430 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|●
2431 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
2432 +
2433 +**Features**
2434 +
2435 +After adding the offset value specified in (s1) or (s2) to the input value (BIN 32-bit value) specified in (s3), it is stored in the device number specified in (d). The offset value is controlled as follows.
2436 +
2437 +|**Condition**|**The value stored in the output value**
2438 +|When input value ((s3), (s3)+1)<0|Input value ((s3), (s3)+1) + negative offset value (s1), (s1)+1
2439 +|When input value ((s3), (s3)+1)=0|0
2440 +|When input value ((s3), (s3)+1)>0|Input value ((s3), (s3)+1) + positive offset value (s2), (s2)+1
2441 +
2442 +
2443 +(((
2444 +• When the output value stored in (d) and (d)+1 is a signed BIN 32-bit value, and the operation result exceeds the range of -2,147,483,648 to 2,147,483,647, the situation is shown in the following example.
2445 +
2446 +For example, (s1), (s1)+1 is -1,000, (s3), (s3)+1 is -2,147,483,648, then the output value=-2,147,483,648+(-1000)=80000000H+FFFFFC18H=2,147,482,648.
2447 +
2448 +[[image:07-5 Basic instructions_html_2f3a96a2565c75c7.png]]
2449 +)))
2450 +
2451 +**Error code**
2452 +
2453 +|**Error code**|**Content**
2454 +|4085H|When the specified device range for reading exceeds the range of the corresponding device
2455 +|4086H|When the specified device range for writing exceeds the range of the corresponding device
2456 +
2457 +**Example**
2458 +
2459 +[[image:07-5 Basic instructions_html_b831b14748df07ab.png]]
2460 +
2461 +• When (D1, D0)<0, the value of (D1, D0)+(-10,000) is stored in (D11, D10).
2462 +
2463 +• When (D1, D0)=0, 0 is stored in (D11, D10).
2464 +
2465 +• When 0<(D1, D0), the value of (D1, D0)+10,000 is stored in (D11, D10).