Changes for page 12 Clock operation
Last modified by Mora Zhou on 2023/11/21 17:27
Summary
-
Page properties (4 modified, 0 added, 0 removed)
Details
- Page properties
-
- Title
-
... ... @@ -1,1 +1,0 @@ 1 -12 Clock operation instruction - Parent
-
... ... @@ -1,1 +1,1 @@ 1 -PLC Editor2.1 User manual.2\.1 LX5V user manual. 07.WebHome1 +PLC Editor2.1 User manual.2\.1 LX5V user manual.WebHome - Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki.J im1 +XWiki.Joey - Content
-
... ... @@ -1,3 +1,388 @@ 1 += **Contact comparison instruction** = 2 + 3 +== **Signed 16-bit contact comparison instruction** == 4 + 5 +**LD £, AND £, OR £** 6 + 7 +The BIN 16-bit data of the device specified in (s1) and the BIN 16-bit data of the device specified in (s2) are compared by normal open contact processing. 8 + 9 +LD£: Normally open contact comparison instruction 10 + 11 +AND£: Normally open contact series connection comparison instruction 12 + 13 +OR£: Normally open contact parallel connection comparison instruction 14 + 15 +**Ladder diagram** 16 + 17 +(% style="text-align:center" %) 18 +[[image:07-5 Basic instructions_html_63210db6b7e1512f.png]] 19 + 20 +(You can enter "=", "<>", ">", "<", ">=", "<=" in "£") 21 + 22 +**Content, range and data type** 23 + 24 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 25 +|(s1)|Comparison data or device storing comparison data|-32768 to 32767|Signed BIN 16 bit|ANY16_S 26 +|(s2)|Comparison data or device storing comparison data|-32768 to 32767|Signed BIN 16 bit|ANY16_S 27 + 28 +**Device used** 29 + 30 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="11" %)**Devices**|((( 31 +**Offset modification** 32 +)))|((( 33 +**Pulse extension** 34 +))) 35 +|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**[D]**|**XXP** 36 +|LD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 37 +|LD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 38 +|LD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 39 +|LD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 40 +|LD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 41 +|LD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 42 +|AND=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 43 +|AND>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 44 +|AND<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 45 +|AND>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 46 +|AND<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 47 +|AND<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 48 +|OR=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 49 +|OR>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 50 +|OR<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 51 +|OR>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 52 +|OR<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 53 +|OR<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●| 54 + 55 +**Features** 56 + 57 +The BIN 16-bit data of the device specified in (s1) and the BIN 16-bit data of the device specified in (s2) are compared by normal open contact processing. 58 + 59 +The comparison operation result of each instruction is shown below. 60 + 61 +|**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result** 62 +|==|(s1)=(s2)|(% rowspan="6" %)On state|==|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state 63 +|<>|(s1)≠(s2)|<>|(s1)=(s2) 64 +|>|(s1)>(s2)|>|(s1)≤(s2) 65 +|<|(s1)<(s2)|<|(s1)≥(s2) 66 +|>=|(s1)≥(s2)|>=|(s1)<(s2) 67 +|<=|(s1)≤(s2)|<=|(s1)>(s2) 68 + 69 +**Error code** 70 + 71 +|**Error code**|**Content** 72 +|4085H|(s) read address exceeds the device range 73 + 74 +**Example** 75 + 76 +((( 77 +(1) LD£ instruction: 78 + 79 +(% style="text-align:center" %) 80 +[[image:07-5 Basic instructions_html_1309199eccc7134.png]] 81 +))) 82 + 83 +When the current value of counter C10 is 200, Y10 is set 84 + 85 +When the content of D200 is above -29, and X1 is ON, Y11 is set 86 + 87 +(2) AND£ instruction: 88 + 89 +(% style="text-align:center" %) 90 +[[image:07-5 Basic instructions_html_1c966f74b0bd808e.png]] 91 + 92 +((( 93 +When X0 is ON, or when the current value of counter C10 is 200, Y10 is set 94 + 95 +When X1 is OFF, and the content of data counter D0 is not -10, Y11 is set 96 + 97 + 98 +))) 99 + 100 +(3) OR£ instruction: 101 + 102 +(% style="text-align:center" %) 103 +[[image:07-5 Basic instructions_html_8b000809015ea436.png]] 104 + 105 +((( 106 +When X1 is ON, or when the current value of counter C10 is 200, Y0 is set 107 + 108 +When X2 and M30 are ON, or the content of register D100 is K10000 and above, M60 is set 109 +))) 110 + 111 +== **Signed 32-bit contact comparison instruction** == 112 + 113 +**LDD £, ANDD £, ORD £** 114 + 115 +The BIN 32-bit data of the device specified in (s1) and the BIN 32-bit data of the device specified in (s2) are compared by normal open contact processing. 116 + 117 +LDD£: Normally open contact comparison command 118 + 119 +ANDD£: Normally open contact series link comparison instruction 120 + 121 +ORD£: Normally open contact parallel link comparison instruction 122 + 123 +**Ladder diagram** 124 + 125 +(% style="text-align:center" %) 126 +[[image:07-5 Basic instructions_html_63210db6b7e1512f.png]] 127 + 128 +“=”, “<>”, “>”, “<”, “>=”, “<=” can be input in “£” 129 + 130 +**Content, range and data type** 131 + 132 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 133 +|(s1)|Comparison data or device storing comparison data|-2147483648 to 2147483647|Signed BIN 32 bit|ANY32_S 134 +|(s2)|Comparison data or device storing comparison data|-2147483648 to 2147483647|Signed BIN 32 bit|ANY32_S 135 + 136 +**Device used** 137 + 138 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="13" %)**Devices**|((( 139 +**Offset modification** 140 +)))|((( 141 +**Pulse extension** 142 +))) 143 +|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**[D]**|**XXP** 144 +|LDD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 145 +|LDD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 146 +|LDD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 147 +|LDD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 148 +|LDD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 149 +|LDD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 150 +|ANDD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 151 +|ANDD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 152 +|ANDD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 153 +|ANDD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 154 +|ANDD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 155 +|ANDD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 156 +|ORD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 157 +|ORD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 158 +|ORD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 159 +|ORD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 160 +|ORD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 161 +|ORD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●|●| 162 + 163 +**Features** 164 + 165 +The BIN 32-bit data of the device specified in (s1) and the BIN 32-bit data of the device specified in (s2) are compared by normal open contact processing. 166 + 167 +The comparison operation result of each instruction is shown below. 168 + 169 +|**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result** 170 +|==|(s1)=(s2)|(% rowspan="6" %)On state|==|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state 171 +|<>|(s1)≠(s2)|<>|(s1)=(s2) 172 +|>|(s1)>(s2)|>|(s1)≤(s2) 173 +|<|(s1)<(s2)|<|(s1)≥(s2) 174 +|>=|(s1)≥(s2)|>=|(s1)<(s2) 175 +|<=|(s1)≤(s2)|<=|(s1)>(s2) 176 + 177 +**Error code** 178 + 179 +|**Error code**|**Content** 180 +|4085H|(S) read address exceeds the device range 181 + 182 +**Example** 183 + 184 +(1) LDD£ instruction: 185 + 186 +(% style="text-align:center" %) 187 +[[image:07-5 Basic instructions_html_8acf0d489297c561.png]] 188 + 189 +When the data of LC10 is 200000, Y10 is set, otherwise Y10 is reset. 190 + 191 +When the 32-bit data composed of D201 and D200 exceeds -5000, and X1 is ON, Y11 is turned ON. 192 + 193 +(2) ANDD£ instruction: 194 + 195 +(% style="text-align:center" %) 196 +[[image:07-5 Basic instructions_html_38be93eec0ced6c.png]] 197 + 198 +When X0 is ON and the value of LC10 is 200000, Y10 is set, otherwise it is reset. 199 + 200 +When X1 is OFF and the 32-bit data composed of D1 and D0 is not equal to K-50000, Y11 is set. 201 + 202 +(3) ORD£ instruction: 203 + 204 +(% style="text-align:center" %) 205 +[[image:07-5 Basic instructions_html_8ebfc7b0562cf370.png]] 206 + 207 +When X1 is ON, or the data of LC10 is equal to the data of LC10 is equal to 200000, Y0 is set. 208 + 209 +When X2 and M30 are set, or the double word data composed of D101 and D100 is greater than or equal to 100000, M60 is set. 210 + 211 +== **Single precision real number contact comparison instruction** == 212 + 213 +**LDE £, ANDE £, ORE £** 214 + 215 +The single precision real number of the device specified in (s1) and the single precision real number of the device specified in (s2) are compared by normal open contact processing. 216 + 217 +LDE£: Normally open contact comparison command 218 + 219 +ANDE£: Normally open contact series link comparison instruction 220 + 221 +ORE£: Normally open contact parallel link comparison instruction 222 + 223 +**Ladder diagram** 224 + 225 +(% style="text-align:center" %) 226 +[[image:07-5 Basic instructions_html_6ac28f30e24ad296.png||height="352" width="550"]] 227 + 228 +“=”, “<>”, “>”, “<”, “>=”, “<=” can be input in “£” 229 + 230 +**Content, range and data type** 231 + 232 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 233 +|(s1)|Comparison data or the device start number storing the comparison data|0, 2^^-126^^ ≤~|(s)~|< 2^^128^^|Single precision real number|ANYREAL_32 234 +|(s2)|Comparison data or the device start number storing the comparison data|0, 2^^-126^^ ≤~|(s)~|< 2^^128^^|Single precision real number|ANYREAL_32 235 + 236 +**Device used** 237 + 238 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="8" %)**Devices**|((( 239 +**Offset modification** 240 +)))|((( 241 +**Pulse extension** 242 +))) 243 +|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**E**|**[D]**|**XXP** 244 +|LDE=|s1, s2|●|●|●|●|●|●|●|●|●| 245 +|LDE>|s1, s2|●|●|●|●|●|●|●|●|●| 246 +|LDE<|s1, s2|●|●|●|●|●|●|●|●|●| 247 +|LDE>=|s1, s2|●|●|●|●|●|●|●|●|●| 248 +|LDE<=|s1, s2|●|●|●|●|●|●|●|●|●| 249 +|LDE<>|s1, s2|●|●|●|●|●|●|●|●|●| 250 +|ANDE=|s1, s2|●|●|●|●|●|●|●|●|●| 251 +|ANDE>|s1, s2|●|●|●|●|●|●|●|●|●| 252 +|ANDE<|s1, s2|●|●|●|●|●|●|●|●|●| 253 +|ANDE>=|s1, s2|●|●|●|●|●|●|●|●|●| 254 +|ANDE<=|s1, s2|●|●|●|●|●|●|●|●|●| 255 +|ANDE<>|s1, s2|●|●|●|●|●|●|●|●|●| 256 +|ORE=|s1, s2|●|●|●|●|●|●|●|●|●| 257 +|ORD>|s1, s2|●|●|●|●|●|●|●|●|●| 258 +|ORE<|s1, s2|●|●|●|●|●|●|●|●|●| 259 +|ORE>=|s1, s2|●|●|●|●|●|●|●|●|●| 260 +|ORE<=|s1, s2|●|●|●|●|●|●|●|●|●| 261 +|ORE<>|s1, s2|●|●|●|●|●|●|●|●|●| 262 + 263 +**Features** 264 + 265 +The single precision real number of the device specified in (s1) and the single precision real number of the device specified in (s2) are compared by normal open contact processing. 266 + 267 +The comparison operation result of each instruction is shown below. 268 + 269 +|**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result** 270 +|E=|(s1)=(s2)|(% rowspan="6" %)On state|E=|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state 271 +|E<>|(s1)≠(s2)|E<>|(s1)=(s2) 272 +|E>|(s1)>(s2)|E>|(s1)≤(s2) 273 +|E<|(s1)<(s2)|E<|(s1)≥(s2) 274 +|E>=|(s1)≥(s2)|E>=|(s1)<(s2) 275 +|E<=|(s1)≤(s2)|E<=|(s1)>(s2) 276 + 277 +**Error code** 278 + 279 +|**Error code**|**Content** 280 +|4084H|When the content of the specified device by (s1) and (s2) is an irregular number, a non-number, or ±∞ 281 +|4085H|The read address of (s1) and (s2exceeds the device range 282 + 283 +**Example** 284 + 285 +(1) LDE£ instruction: 286 + 287 +(% style="text-align:center" %) 288 +[[image:07-5 Basic instructions_html_c4c820cf59601493.png]] 289 + 290 +When the real number input in D0 is equal to E1.23, Y10 is ON, otherwise Y10 is OFF. 291 + 292 +When the real number in R0 is greater than or equal to the real number in LC0, Y11 is ON, otherwise it is OFF. 293 + 294 +If the input in D0, R0, LC0 is not a real number, it will report H4084 error. 295 + 296 +(2) ANDE£ instruction: 297 + 298 +(% style="text-align:center" %) 299 +[[image:07-5 Basic instructions_html_7cdd2117360e179b.png]] 300 + 301 +Only when M0 is ON and D2 real number is not equal to E1.23 and R2 real number is less than real number LC2 , Y12 is ON, otherwise all are OFF. 302 + 303 +(3) ORE£ instruction: 304 + 305 +(% style="text-align:center" %) 306 +[[image:07-5 Basic instructions_html_3eba0bd56176441d.png]] 307 + 308 +When the real number of R4 is less than or equal to the real number of R15, or the real number R6 is equal to the real number R20, Y13 is ON, otherwise Y13 is OFF. 309 + 310 +== **String comparison** == 311 + 312 +**LDS£、ANDS£、 ORS£** 313 + 314 +Compare the string stored after the device number specified in (s1) with the string stored after the device number specified in (s2). 315 + 316 +LDS£: String comparison instruction 317 + 318 +ANDS£: String serial connection comparison instruction 319 + 320 +ORS£: String parallel connection comparison instruction 321 + 322 +**Ladder diagram** 323 + 324 +(% style="text-align:center" %) 325 +[[image:07-5 Basic instructions_html_5fb3b3b70645fef5.png||height="371" width="550"]] 326 + 327 +“=” and “<>” could be entered in “£” 328 + 329 +**Content, range and data type** 330 + 331 +|**Parameter**|**Content**|**Range**|**Date type**|**Date type(label)** 332 +|(S1)|Connection data or the device start number storing the data or the string specified directly|-|String|ANYSTRING_SINGLE 333 +|(S1)|Connection data or the device start number storing the data or the string specified directly|-|String|ANYSTRING_SINGLE 334 + 335 +**Device used** 336 + 337 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|((( 338 +**Offset modification** 339 +)))|((( 340 +**Pulse extension** 341 +))) 342 +|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP** 343 +|LDS=|s1、s2|●|●|●|●|●|●|●|●|●|●| 344 +|LDS<>|s1、s2|●|●|●|●|●|●|●|●|●|●| 345 +|ANDS=|s1、s2|●|●|●|●|●|●|●|●|●|●| 346 +|ANDS<>|s1、s2|●|●|●|●|●|●|●|●|●|●| 347 +|ORS=|s1、s2|●|●|●|●|●|●|●|●|●|●| 348 +|ORS<>|s1、s2|●|●|●|●|●|●|●|●|●|●| 349 + 350 +**Features** 351 + 352 +• Compare the string stored after the device number specified in (s1) with the string stored after the device number specified in (s2). 353 + 354 +• The comparison operation result of each instruction is shown below. 355 + 356 +|**Instruction sign**|**Condition**|**Comparison operation result**|**Instruction sign**|**Condition**|**Comparison operation result** 357 +|==|(s1)=(s2)|(% rowspan="2" %)On stat|==|(s1)≠(s2)|(% rowspan="2" %)Non-conduction state 358 +|<>|(s1)≠(s2)|<>|(s1)=(s2) 359 + 360 +**Error code** 361 + 362 +|**Error code**|**Content** 363 +|4085H|The read address of (s1) or (s2) exceeds the device range 364 +|408AH|The length of the read string of (s1) or (s2) exceeds, and the continuous length of the string exceeds 400 characters. 365 +|408BH|When (s1) or (s2) reading the string, the maximum range of the device is read but 00H is not found as the end. 366 + 367 +**Example** 368 + 369 +(1) LDS£ instruction: 370 + 371 +(% style="text-align:center" %) 372 +[[image:07-5 Basic instructions_html_449a071f61ff5b58.png]] 373 + 374 +(2) ANDS£ instruction: 375 + 376 +(% style="text-align:center" %) 377 +[[image:07-5 Basic instructions_html_dd6aa995d193bdd2.png]] 378 + 379 +(3) ORS£ instruction: 380 + 381 +(% style="text-align:center" %) 382 +[[image:07-5 Basic instructions_html_4f8fb7c94f87c58d.png]] 383 + 384 += **Clock operation instruction** = 385 + 1 1 == **TADD/The addition of clock data** == 2 2 3 3 **TADD(P)** ... ... @@ -274,7 +274,7 @@ 274 274 275 275 == **TWR/Clock data writing** == 276 276 277 -**TWR(P)** 662 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TWR(P)** 278 278 279 279 Write the clock data of the built-in real-time clock of the CPU module. 280 280 ... ... @@ -287,13 +287,17 @@ 287 287 288 288 **Device used** 289 289 290 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="4" %)**Devices**|((( 291 -**Offset modification** 675 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 676 +**Offset** 677 + 678 +**modification** 292 292 )))|((( 293 -**Pulse extension** 680 +**Pulse** 681 + 682 +**extension** 294 294 ))) 295 -|**T**|**C**|**D**|**R**|**[D]**|**XXP** 296 -|TWR|Parameter 1|●|●|●|●|●|● 684 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 685 +|TWR|Parameter 1| | | | | | | | | | | | | | |●|●|●|●| | | | | | |●|● 297 297 298 298 **Features** 299 299 ... ... @@ -328,7 +328,7 @@ 328 328 |SD105|The year data of the clock data is stored in a 4-digit BIN code of the Gregorian calendar. 329 329 |SD106|The week data of the clock data is stored in BIN code. (0: day, 1: one, ..., 6: six) are stored in BIN code. 330 330 331 -✎**Note :**720 +✎**Note** 332 332 333 333 The device specified in (s) occupies 7 points. Be careful not to overlap with the device used for machine control. 334 334 ... ... @@ -341,15 +341,13 @@ 341 341 342 342 Set D0 date and time to 2020-2-19 12:36:00 in advance 343 343 344 -(% style="text-align:center" %) 345 -[[image:07-5 Basic instructions_html_994c66d1a4cbd45f.png||height="57" width="305"]] 733 +[[image:07-5 Basic instructions_html_994c66d1a4cbd45f.png]] 346 346 347 347 At the moment when the time 12:36:00 arrives, turn on the M0 coil and write the time. 348 348 349 -(% style="text-align:center" %) 350 -[[image:07-5 Basic instructions_html_bf3e906ee5265598.png||height="42" width="586"]] 737 +[[image:07-5 Basic instructions_html_bf3e906ee5265598.png]] 351 351 352 -== **HTOS/16-bit data conversion of time data (hour, minute, second → second)** ==739 +{{id name="_Toc5357"/}}{{id name="_Toc6196"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **HTOS/16-bit data conversion of time data (hour, minute, second → second)** 353 353 354 354 **HTOS(P)** 355 355 ... ... @@ -365,26 +365,26 @@ 365 365 366 366 **Device used** 367 367 368 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|**Offset modification**|((( 369 -**Pulse extension** 755 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 756 +**Pulse** 757 + 758 +**extension** 370 370 ))) 371 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP** 372 -|(% rowspan="2" %)HTOS|Parameter 1|●|●|●|●|●|●|●|●|●|●|● 373 -|Parameter 2| |●|●|●|●|●|●|●|●|●|● 760 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 761 +|(% rowspan="2" %)HTOS|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|● 762 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 374 374 375 375 **Features** 376 376 377 377 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d). 378 378 379 -(% style="text-align:center" %) 380 -[[image:07-5 Basic instructions_html_a84b7741fd5bef2f.png||height="130" width="550"]] 768 +[[image:07-5 Basic instructions_html_a84b7741fd5bef2f.png]] 381 381 382 382 **Example** 383 383 384 384 When 4 hours, 29 minutes and 31 seconds are specified in (s) 385 385 386 -(% style="text-align:center" %) 387 -[[image:07-5 Basic instructions_html_5effb7bc9b8e5cf7.png||height="162" width="550"]] 774 +[[image:07-5 Basic instructions_html_5effb7bc9b8e5cf7.png]] 388 388 389 389 **Error code** 390 390 ... ... @@ -392,7 +392,7 @@ 392 392 |4085H|When reading the specified device range exceeds the corresponding device range 393 393 |4086H|When writing the specified device range exceeds the corresponding device range 394 394 |4084H|((( 395 -When the calculation result is not in the range of 0 to 32767 782 +{{id name="OLE_LINK348"/}}When the calculation result is not in the range of 0 to 32767 396 396 397 397 When the value specified in (s) is not in the range of 0 to 9 398 398 ... ... @@ -401,22 +401,19 @@ 401 401 402 402 **Example** 403 403 404 -(% style="text-align:center" %) 405 -[[image:07-5 Basic instructions_html_e23e38c4ba4c34bb.png||height="43" width="338"]] 791 +[[image:07-5 Basic instructions_html_e23e38c4ba4c34bb.png]] 406 406 407 407 D0 time is set to 5:36:53 408 408 409 -(% style="text-align:center" %) 410 410 [[image:07-5 Basic instructions_html_2866a121e5ca5713.png]] 411 411 412 412 The time of D10 after the M0 coil is turned on is as below. 413 413 414 -(% style="text-align:center" %) 415 415 [[image:07-5 Basic instructions_html_1dd6c5de05890797.png]] 416 416 417 -= =**DHTOS/32-bit data conversion of time data (hour, minute, second → second)**==801 +{{id name="_Toc13431"/}}{{id name="_Toc5278"/}}**DHTOS/32-bit data conversion of time data (hour, minute, second → second)** 418 418 419 -**DHTOS(P)** 803 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DHTOS(P)** 420 420 421 421 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result as BIN 32-bit data in the device specified in (d). 422 422 ... ... @@ -430,28 +430,30 @@ 430 430 431 431 **Device used** 432 432 433 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|((( 434 -**Offset modification** 817 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 818 +**Offset** 819 + 820 +**modification** 435 435 )))|((( 436 -**Pulse extension** 822 +**Pulse** 823 + 824 +**extension** 437 437 ))) 438 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP** 439 -|(% rowspan="2" %)DHTOS|Parameter 1|●|●|●|●|●|●|●|●|●|●|● 440 -|Parameter 2| |●|●|●|●|●|●|●|●|●|● 826 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 827 +|(% rowspan="2" %)DHTOS|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|● 828 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 441 441 442 442 **Features** 443 443 444 444 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d). 445 445 446 -(% style="text-align:center" %) 447 -[[image:07-5 Basic instructions_html_f4be08508575ea01.png||height="99" width="550"]] 834 +[[image:07-5 Basic instructions_html_f4be08508575ea01.png]] 448 448 449 449 **Example** 450 450 451 451 When 35 hours, 10 minutes and 58 seconds are specified in (s) 452 452 453 -(% style="text-align:center" %) 454 -[[image:07-5 Basic instructions_html_5b9ad230ed5e1fd0.png||height="125" width="550"]] 840 +[[image:07-5 Basic instructions_html_5b9ad230ed5e1fd0.png]] 455 455 456 456 **Error code** 457 457 ... ... @@ -466,20 +466,17 @@ 466 466 467 467 **Example** 468 468 469 -(% style="text-align:center" %) 470 -[[image:07-5 Basic instructions_html_ae8ab4379e8bdb91.png||height="45" width="263"]] 855 +[[image:07-5 Basic instructions_html_ae8ab4379e8bdb91.png]] 471 471 472 472 D0 time is set to 15:33:24 473 473 474 -(% style="text-align:center" %) 475 -[[image:07-5 Basic instructions_html_57a15d9e1045e93e.png||height="41" width="313"]] 859 +[[image:07-5 Basic instructions_html_57a15d9e1045e93e.png]] 476 476 477 477 The second of D10 after the M0 coil is turned on is 478 478 479 -(% style="text-align:center" %) 480 -[[image:07-5 Basic instructions_html_194e906b1dc12078.png||height="64" width="365"]] 863 +[[image:07-5 Basic instructions_html_194e906b1dc12078.png]] 481 481 482 -**HOUR/Hour measuring 16-bit** 865 +{{id name="_Ref22686"/}}{{id name="_Toc11231"/}}{{id name="_Toc7401"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **HOUR/Hour measuring 16-bit** 483 483 484 484 **HOUR(P)** 485 485 ... ... @@ -504,15 +504,19 @@ 504 504 505 505 **Device used** 506 506 507 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="17" %)**Devices**|((( 508 -**Offset modification** 890 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 891 +**Offset** 892 + 893 +**modification** 509 509 )))|((( 510 -**Pulse extension** 895 +**Pulse** 896 + 897 +**extension** 511 511 ))) 512 -|**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP** 513 -|(% rowspan="3" %)HOUR|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|● 514 -|Parameter 2| | | | | | | | | | | |●|●|●| | | |●|● 515 -|Parameter 3|●|●|●|●|●| | | | | | | | | | | | |●|● 899 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 900 +|(% rowspan="3" %)HOUR|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 901 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 902 +|Parameter 3| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|● 516 516 517 517 **Features** 518 518 ... ... @@ -534,7 +534,7 @@ 534 534 535 535 • The measurement stops when the current value reaches the 16-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+1. 536 536 537 -✎**Note :**924 +✎**Note** 538 538 539 539 • The device specified in (d1) occupies 2 points. Be careful not to overlap with the device used for machine control. 540 540 ... ... @@ -547,14 +547,15 @@ 547 547 |4086H|When writing the specified device range exceeds the corresponding device range 548 548 |4084H|When the value of (s) is negative 549 549 937 + 938 + 550 550 **Example** 551 551 552 -(% style="text-align:center" %) 553 -[[image:07-5 Basic instructions_html_7570f8c392470a9f.png||height="45" width="320"]] 941 +[[image:07-5 Basic instructions_html_7570f8c392470a9f.png]] 554 554 555 555 When M0 = ON, the duration of the state is accumulated, the time is recorded in D0, and the seconds less than 1 hour are recorded in D1. When the accumulated time of D0 reaches 98 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K98), the accumulated timing will continue and the reading will continue to increase; the current time value D0 reaches the maximum value of 32767 hours and D1 reaches 3599 seconds, the timing measurement will stop. The current time values D0 and D1 are cleared to 0. 556 556 557 -== **DHOUR/Hour measuring 32 bits** ==945 +{{id name="_Toc8523"/}}{{id name="_Toc9364"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DHOUR/Hour measuring 32 bits** 558 558 559 559 **DHOUR(P)** 560 560 ... ... @@ -566,7 +566,9 @@ 566 566 567 567 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 568 568 |(s)|((( 569 -The time when the alarm (d2) is turned ON (set by one hour) 957 +The time when the alarm (d2) is turned ON 958 + 959 +(set by one hour) 570 570 )))|0 to 2147483647|Signed BIN 32 bit|ANY32 571 571 |(d1)|Device that stores the current value of measurement (specified data register for power failure retention)|-|Unsigned BIN 32 bit|((( 572 572 ANY32_ARRAY ... ... @@ -577,15 +577,19 @@ 577 577 578 578 **Device used** 579 579 580 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="18" %)**Devices**|((( 581 -**Offset modification** 970 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 971 +**Offset** 972 + 973 +**modification** 582 582 )))|((( 583 -**Pulse extension** 975 +**Pulse** 976 + 977 +**extension** 584 584 ))) 585 -|**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**[D]**|**XXP** 586 -|(% rowspan="3" %)DHOUR|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●|●|● 587 -|Parameter 2| | | | | | | | | | | |●|●|●| | | | |●|● 588 -|Parameter 3|●|●|●|●|●| | | | | | | | | | | | | |●|● 979 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 980 +|(% rowspan="3" %)DHOUR|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 981 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 982 +|Parameter 3| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|● 589 589 590 590 **Features** 591 591 ... ... @@ -607,7 +607,7 @@ 607 607 608 608 • The measurement stops when the current value reaches the 32-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+2. 609 609 610 -✎**Note :**1004 +✎**Note** 611 611 612 612 • The device specified in (d1) occupies 3 points. Be careful not to overlap with the device used for machine control. 613 613 ... ... @@ -620,16 +620,17 @@ 620 620 |4086H|When writing the specified device range exceeds the corresponding device range 621 621 |4084H|When the value of (s) is negative 622 622 1017 + 1018 + 623 623 **Example** 624 624 625 -(% style="text-align:center" %) 626 -[[image:07-5 Basic instructions_html_3f1ef5ecc835de30.png||height="43" width="448"]] 1021 +[[image:07-5 Basic instructions_html_3f1ef5ecc835de30.png]] 627 627 628 628 When M0=ON, the duration of this state is accumulated, the time is recorded in D1, D0, and the seconds less than 1 hour are recorded in D2. When the accumulated time of D1, D0 reaches 1000 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K1000), the accumulated timing will continue, and the reading will continue to increase; the current time values D1 and D0 reach the maximum value of 2147483647 hours, and when D2 reaches 3599 seconds, the timing measurement will stop and the timing should be restarted. The current time values D0, D1, and D2 must be cleared to 0. 629 629 630 - ==**STOH/16-bit data conversion of time data (second → hour, minute, second)**==1025 +**{{id name="_Toc11629"/}}STOH/16-bit data conversion of time data (second → hour, minute, second)** 631 631 632 -**STOH(P)** 1027 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **STOH(P)** 633 633 634 634 Convert the second 16-bit data stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later. 635 635 ... ... @@ -638,35 +638,39 @@ 638 638 **Content, range and data type** 639 639 640 640 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 641 -|(s)|The device start number that stores the clock data before conversion|0 to 32767|Signed BIN 16 bit|ANY16 1036 +|(s)|{{id name="OLE_LINK353"/}}The device start number that stores the clock data before conversion|0 to 32767|Signed BIN 16 bit|ANY16 642 642 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|((( 643 -ANY16_ARRAY (number of elements: 3) 1038 +ANY16_ARRAY 1039 + 1040 +(number of elements: 3) 644 644 ))) 645 645 646 646 **Device used** 647 647 648 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|((( 649 -**Offset modification** 1045 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 1046 +**Offset** 1047 + 1048 +**modification** 650 650 )))|((( 651 -**Pulse extension** 1050 +**Pulse** 1051 + 1052 +**extension** 652 652 ))) 653 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP** 654 -|(% rowspan="2" %)STOH|Parameter 1|●|●|●|●|●|●|●|●|●|●|● 655 -|Parameter 2| |●|●|●|●|●|●|●|●|●|● 1054 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1055 +|(% rowspan="2" %)STOH|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|● 1056 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 656 656 657 657 **Features** 658 658 659 659 Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later. 660 660 661 -(% style="text-align:center" %) 662 -[[image:07-5 Basic instructions_html_1f5f3f1d80af2a34.png||height="110" width="550"]] 1062 +[[image:07-5 Basic instructions_html_1f5f3f1d80af2a34.png]] 663 663 664 664 **Example** 665 665 666 666 When 29,011 seconds are specified in (s) 667 667 668 -(% style="text-align:center" %) 669 -[[image:07-5 Basic instructions_html_682516cbf773f515.png||height="163" width="550"]] 1068 +[[image:07-5 Basic instructions_html_682516cbf773f515.png]] 670 670 671 671 **Error code** 672 672 ... ... @@ -677,19 +677,17 @@ 677 677 678 678 **Example** 679 679 680 -(% style="text-align:center" %) 681 -[[image:07-5 Basic instructions_html_e783349d57adf7d2.png||height="47" width="350"]] 1079 +[[image:07-5 Basic instructions_html_e783349d57adf7d2.png]] 682 682 683 683 Set D0 seconds to 12537 684 684 685 685 The hour, minute and second of D10 after the M0 coil is turned on are 686 686 687 -(% style="text-align:center" %) 688 -[[image:07-5 Basic instructions_html_d3c33949e8684891.png||height="52" width="645"]] 1085 +[[image:07-5 Basic instructions_html_d3c33949e8684891.png]] 689 689 690 -= =**DSTOH/32-bit data conversion of time data (second → hour, minute, second)**==1087 +{{id name="_Toc10764"/}}{{id name="_Toc30243"/}}**DSTOH/32-bit data conversion of time data (second → hour, minute, second)** 691 691 692 -**DSTOH(P)** 1089 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSTOH(P)** 693 693 694 694 Convert the second 32-bit data of second stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later. 695 695 ... ... @@ -700,33 +700,37 @@ 700 700 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 701 701 |(s)|The device start number that stores the clock data before conversion|0 to 117964799|Signed BIN 32 bit|ANY32 702 702 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|((( 703 -ANY16_ARRAY (number of elements: 3) 1100 +ANY16_ARRAY 1101 + 1102 +(number of elements: 3) 704 704 ))) 705 705 706 706 **Device used** 707 707 708 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|((( 709 -**Offset modification** 1107 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 1108 +**Offset** 1109 + 1110 +**modification** 710 710 )))|((( 711 -**Pulse extension** 1112 +**Pulse** 1113 + 1114 +**extension** 712 712 ))) 713 -|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP** 714 -|(% rowspan="2" %)DSTOH|Parameter 1|●|●|●|●|●|●|●|●|●|●|● 715 -|Parameter 2| |●|●|●|●|●|●|●|●|●|● 1116 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1117 +|(% rowspan="2" %)DSTOH|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|● 1118 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 716 716 717 717 **Features** 718 718 719 719 Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later. 720 720 721 -(% style="text-align:center" %) 722 -[[image:07-5 Basic instructions_html_cbf13fc3d10fbe61.png||height="99" width="600"]] 1124 +[[image:07-5 Basic instructions_html_cbf13fc3d10fbe61.png]] 723 723 724 724 **Example** 725 725 726 726 When 45,325 seconds is specified in (s) 727 727 728 -(% style="text-align:center" %) 729 -[[image:07-5 Basic instructions_html_d6045506b13275a0.png||height="135" width="600"]] 1130 +[[image:07-5 Basic instructions_html_d6045506b13275a0.png]] 730 730 731 731 **Error code** 732 732 ... ... @@ -737,17 +737,15 @@ 737 737 738 738 **Example** 739 739 740 -(% style="text-align:center" %) 741 -[[image:07-5 Basic instructions_html_e7dd49d953db6da4.png||height="39" width="316"]] 1141 +[[image:07-5 Basic instructions_html_e7dd49d953db6da4.png]] 742 742 743 743 Set D0 seconds to 2152537 744 744 745 745 The hour, minute and second of D10 after the M0 coil is turned on are 746 746 747 -(% style="text-align:center" %) 748 -[[image:07-5 Basic instructions_html_10d57bde1ac0a218.png||height="52" width="661"]] 1147 +[[image:07-5 Basic instructions_html_10d57bde1ac0a218.png]] 749 749 750 -== **TCMP/Clock data comparison** ==1149 +{{id name="_Toc2937"/}}{{id name="_Toc24209"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TCMP/Clock data comparison** 751 751 752 752 **TCMP(P)** 753 753 ... ... @@ -766,26 +766,29 @@ 766 766 767 767 **Device used** 768 768 769 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="17" %)**Devices**|((( 770 -**Offset modification** 1168 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 1169 +**Offset** 1170 + 1171 +**modification** 771 771 )))|((( 772 -**Pulse extension** 1173 +**Pulse** 1174 + 1175 +**extension** 773 773 ))) 774 -|**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP** 775 -|(% rowspan="5" %)TCMP|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|● 776 -|Parameter 2| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|● 777 -|Parameter 3| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|● 778 -|Parameter 4| | | | | | | | | |●|●|●|●|●| | | |●|● 779 -|Parameter 5|●|●|●|●|●| | | | | | | | | | | | |●|● 1177 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1178 +|(% rowspan="5" %)TCMP|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1179 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1180 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1181 +|Parameter 4| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|● 1182 +|Parameter 5| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|● 780 780 781 781 **Features** 782 782 783 783 Compare the time of the reference time (hour, minute, second) [(s1), (s2), (s3)] with the time data (hour, minute, second) [(s4), (s4)+1, (s4) +2] Compare the size and turn on/off the 3 points from (d) according to the result of the same size. 784 784 785 -(% style="text-align:center" %) 786 -[[image:07-5 Basic instructions_html_5df7ad3057fada12.png||height="385" width="750"]] 1188 +[[image:07-5 Basic instructions_html_5df7ad3057fada12.png]] 787 787 788 -✎**Note :**1190 +✎**Note** 789 789 790 790 The device specified in (s4) and (d) occupies 3 points. Be careful not to overlap with the device used for machine control. 791 791 ... ... @@ -799,29 +799,26 @@ 799 799 |4084H|((( 800 800 When the value specified in (s) and (s4) is not in the range of 0 to 23 801 801 802 -When the value specified in (s2),(s3) (s4)+1 and (s4)+2 is not in the range of 0 to 59 1204 +{{id name="OLE_LINK355"/}}When the value specified in (s2),(s3) (s4)+1 and (s4)+2 is not in the range of 0 to 59 803 803 ))) 804 804 805 805 **Example** 806 806 807 -(% style="text-align:center" %) 808 -[[image:07-5 Basic instructions_html_fcc16317cf7c0700.png||height="68" width="359"]] 1209 +[[image:07-5 Basic instructions_html_fcc16317cf7c0700.png]] 809 809 810 810 Set D10 to 1, D11 to 30, D12 to 0 811 811 812 812 When M0 is turned on, the time that D23 will come is 0:31:27 813 813 814 -(% style="text-align:center" %) 815 -[[image:07-5 Basic instructions_html_de97dd7a612b2323.png||height="50" width="653"]] 1215 +[[image:07-5 Basic instructions_html_de97dd7a612b2323.png]] 816 816 817 817 M10 is turned ON 818 818 819 -(% style="text-align:center" %) 820 -[[image:07-5 Basic instructions_html_56e2d606adc09fd.png||height="52" width="239"]] 1219 +[[image:07-5 Basic instructions_html_56e2d606adc09fd.png]] 821 821 822 -= =**TZCP/Clock data bandwidth comparison**==1221 +{{id name="_Toc29031"/}}{{id name="_Toc22923"/}}**TZCP/Clock data bandwidth comparison** 823 823 824 -**TZCP(P)** 1223 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TZCP(P)** 825 825 826 826 Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth. 827 827 ... ... @@ -831,37 +831,46 @@ 831 831 832 832 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 833 833 |(s1)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|((( 834 -ANY16_ARRAY (number of elements: 3) 1233 +ANY16_ARRAY 1234 + 1235 +(number of elements: 3) 835 835 ))) 836 836 |(s2)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|((( 837 -ANY16_ARRAY (number of elements: 3) 1238 +ANY16_ARRAY 1239 + 1240 +(number of elements: 3) 838 838 ))) 839 839 |(s3)|Specify "hour" of time data (hour, minute, second)|-|Signed BIN 16 bit|((( 840 -ANY16_ARRAY (number of elements: 3) 1243 +ANY16_ARRAY 1244 + 1245 +(number of elements: 3) 841 841 ))) 842 842 |(d)|The bit device is turned ON/OFF according to the comparison result.|-|Bit|((( 843 -ANY16_ARRAY (number of elements: 3) 1248 +ANY16_ARRAY 1249 + 1250 +(number of elements: 3) 844 844 ))) 845 845 846 846 **Device used** 847 847 848 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="10" %)**Devices**|**Offset modification**|((( 849 -**Pulse extension** 1255 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1256 +**Pulse** 1257 + 1258 +**extension** 850 850 ))) 851 -|**Y**|**M**|**S**|**SM**|**D.b**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP** 852 -|(% rowspan="4" %)TZCP|Parameter 1| | | | | |●|●|●|●|●|●|● 853 -|Parameter 2| | | | | |●|●|●|●|●|●|● 854 -|Parameter 3| | | | | |●|●|●|●|●|●|● 855 -|Parameter 4|●|●|●|●|●| | | | | |●|● 1260 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1261 +|(% rowspan="4" %)TZCP|Parameter 1| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|● 1262 +|Parameter 2| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|● 1263 +|Parameter 3| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|● 1264 +|Parameter 4| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|● 856 856 857 857 **Features** 858 858 859 859 Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth. 860 860 861 -(% style="text-align:center" %) 862 -[[image:07-5 Basic instructions_html_844291270080313d.png||height="339" width="750"]] 1270 +[[image:07-5 Basic instructions_html_844291270080313d.png]] 863 863 864 -✎**Note :**1272 +✎**Note** 865 865 866 866 • The devices specified in (s1), (s2), (s3), (d) occupy 3 points. Be careful not to overlap with the device used for machine control. 867 867 ... ... @@ -882,23 +882,1176 @@ 882 882 883 883 **Example** 884 884 885 -(% style="text-align:center" %) 886 -[[image:07-5 Basic instructions_html_30027a2387c26c2e.png||height="46" width="439"]] 1293 +[[image:07-5 Basic instructions_html_30027a2387c26c2e.png]] 887 887 888 888 Set D0 time to 16:30:00 and D10 time to 4:30:0 889 889 890 -(% style="text-align:center" %) 891 -[[image:07-5 Basic instructions_html_c64e0faf2af172f8.png||height="49" width="626"]] 1297 +[[image:07-5 Basic instructions_html_c64e0faf2af172f8.png]] 892 892 893 -(% style="text-align:center" %) 894 -[[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png||height="50" width="625"]] 1299 +[[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png]] 895 895 896 896 After the coil is turned on, the reading time to D20 time is 8:30:00 897 897 898 -(% style="text-align:center" %) 899 -[[image:07-5 Basic instructions_html_75c44dad07eaf80a.png||height="49" width="625"]] 1303 +[[image:07-5 Basic instructions_html_75c44dad07eaf80a.png]] 900 900 901 901 M0/M12 is ON 902 902 903 -(% style="text-align:center" %) 904 -[[image:07-5 Basic instructions_html_f512f36261705953.png||height="48" width="218"]] 1307 +[[image:07-5 Basic instructions_html_f512f36261705953.png]] 1308 + 1309 +{{id name="_Toc6129"/}}[[image:07-5 Basic instructions_html_a2e3294e01b2f206.gif]] **7.13 Data control instructions** 1310 + 1311 +{{id name="_Toc3339"/}}{{id name="_Toc27829"/}}{{id name="_Toc9204"/}}**BAND/BIN 16-bit data dead zone control** 1312 + 1313 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **BAND(P)** 1314 + 1315 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). 1316 + 1317 +-[BAND (s1) (s2) (S3) (d)] 1318 + 1319 +**Content, range and data type** 1320 + 1321 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1322 +|(s1)|Lower limit of dead zone (no output zone)|-32,768 to +32,767|Signed BIN 16 bit|ANY16_S 1323 +|(s2)|Upper limit of dead zone (no output zone)|-32,768 to +32,767|Signed BIN 16 bit|ANY16_S 1324 +|(S3)|Input value controlled by dead zone control|-32768 to +32,767|Signed BIN 16 bit|ANY16_S 1325 +|(D)|The start number of the device that stores the output value controlled by the dead zone control|-|Signed BIN 16 bit|ANY16_S 1326 + 1327 +**Device used** 1328 + 1329 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 1330 +**Offset** 1331 + 1332 +**modification** 1333 +)))|((( 1334 +**Pulse** 1335 + 1336 +**extension** 1337 +))) 1338 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1339 +|(% rowspan="4" %)BAND|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1340 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1341 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|● 1342 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 1343 + 1344 +**Features** 1345 + 1346 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). The output value is controlled as follows. 1347 + 1348 +|**Condition**|**The value stored in the output value** 1349 +|When dead zone low limit (s1)> input value (s3)|Input value (s3)-Dead zone low limit (s1) 1350 +|When dead zone high limit (s1) <input value (s3)|Input value (s3)- Dead zone high limit (s2) 1351 +|When dead zone low limit (s1) ≤ input value (s3) ≤ dead zone low limit (s2)|0 1352 + 1353 + 1354 +((( 1355 +•When the output value stored in (d) is a signed BIN 16-bit value, and the operation result exceeds the range of -32768 to 32767, the situation is shown in the following example. 1356 + 1357 +For example, when (s1) is 10 and (s3) is -32768, 1358 + 1359 +the output value = -32768-10=8000H-000AH=7FFFH=32758. 1360 + 1361 +[[image:07-5 Basic instructions_html_6850e21a76b813c0.png]] 1362 +))) 1363 + 1364 +**Error code** 1365 + 1366 +|**Error code**|**Content** 1367 +|4085H|When the specified device range for reading exceeds the range of the corresponding device. 1368 +|4086H|When the specified device range for writing exceeds the range of the corresponding device. 1369 +|4084H|When the low limit specified in (s1) is greater than the high limit specified in (s2). 1370 + 1371 +**Example ** 1372 + 1373 +[[image:07-5 Basic instructions_html_c0e65cfeed403ecf.png]] 1374 + 1375 +When X000 is ON, when D0<(-1,000), the value of ( D0)-(-1,000) is stored in (D1). 1376 + 1377 +• When -1,000≦ D0≦1,000, 0 is stored in D1. 1378 + 1379 +• When D0<1,000, the value of (D0)-1,000 is stored in D1. 1380 + 1381 +{{id name="_Toc1180"/}}{{id name="_Toc21657"/}}{{id name="_Toc27323"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DBAND/BIN 32-bit data dead zone control** 1382 + 1383 +**DBAND(P)** 1384 + 1385 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). 1386 + 1387 +-[DBAND (s1) (s2) (S3) (d)] 1388 + 1389 +**Content, range and data type** 1390 + 1391 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1392 +|(s1)|Dead zone low limit (no output zone)|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S 1393 +|(s2)|Dead zone high limit (no output zone)|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S 1394 +|(S3)|Input value controlled by dead zone control|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S 1395 +|(d)|The start number of the device that stores the output value controlled by the dead zone control|-|Signed BIN 32 bit|ANY32_S 1396 + 1397 +**Device used** 1398 + 1399 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1400 +**Pulse** 1401 + 1402 +**extension** 1403 +))) 1404 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1405 +|(% rowspan="4" %)DBAND|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 1406 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 1407 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|● 1408 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|● 1409 + 1410 +**Features** 1411 + 1412 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). The output value is controlled as follows. 1413 + 1414 +|**Condition**|**The value stored in the output value** 1415 +|When dead zone low limit ((s1), (s1)+1)> input value ((s3), (s3)+1)|{{id name="OLE_LINK42"/}}Input value ((s3), (s3)+1)-dead zone low limit ((s1), (s1)+1) 1416 +|When dead zone high limit ((s1), (s1)+1) <input value ((s3), (s3)+1)|{{id name="OLE_LINK357"/}}Input value ((s3), (s3)+1)-dead zone high limit ((s2), (s2)+1) 1417 +|When dead zone low limit ((s1), (s1)+1) ≤ input value ((s3), (s3)+1) ≤ dead zone high limit ((s2), (s2)+1)|0 1418 + 1419 + 1420 +((( 1421 +• When the output value stored in (d) is a signed BIN 32-bit value, and the operation result exceeds the range of -2,147,483,648 to 2,147,483,647, the situation is as the following example. For example,** **When (s1) and (s1)+1 are 1000, (s3) and (s3)+1 are -2,147,483,648, then the output value= 1422 + 1423 +-2,147,483,648-1000=80000000H-000003E8H=7FFFFC18H=2,147,482,648. 1424 + 1425 +[[image:07-5 Basic instructions_html_e0144674dad3e8fd.png]] 1426 + 1427 + 1428 + 1429 +))) 1430 + 1431 +**Error code** 1432 + 1433 +|**Error code**|**Content** 1434 +|4085H|When the specified device range for reading exceeds the range of the corresponding device. 1435 +|4086H|When the specified device range for writing exceeds the range of the corresponding device. 1436 +|4084H|When the low limit specified in (s1) is greater than the high limit specified in (s2). 1437 + 1438 +**Example** 1439 + 1440 +[[image:07-5 Basic instructions_html_88f3fe0fb4841bab.png]] 1441 + 1442 +• When (D1, D0)<(-10,000), the value of (D1, D0)-(-10,000) is stored in (D11, D10). 1443 + 1444 +• When -10,000≦(D1, D0)≦10,000, 0 is stored in (D11, D10). 1445 + 1446 +• When 10,000< (D1, D0), the value of (D1, D0)-10,000 is stored in D1. 1447 + 1448 +{{id name="_Toc21668"/}}{{id name="_Toc25056"/}}{{id name="_Toc17582"/}}{{id name="OLE_LINK165"/}}**BINDA/BIN 16-bit data → Decimal ASCII conversion** 1449 + 1450 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **BINDA(P)** 1451 + 1452 +Convert the BIN 16-bit data specified in (s) and the value of each digit in decimal numbers into ASCII codes and store them after the device number specified in (d). 1453 + 1454 +-[BINDA(s)(d)] 1455 + 1456 +**Content, range and data type** 1457 + 1458 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1459 +|(s)|BIN data for ASCII conversion|-32768 to +32767|Signed BIN 16 bit|ANY16_S 1460 +|(d)|The start number of the device storing the conversion result|-|String|ANYSTRING_SINGLE 1461 + 1462 +**Device used** 1463 + 1464 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1465 +**Pulse** 1466 + 1467 +**extension** 1468 +))) 1469 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1470 +|(% rowspan="2" %)BINDA|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1471 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 1472 + 1473 +**Features** 1474 + 1475 +Convert the BIN 16-bit data specified in (s) and the value of each digit in decimal numbers into ASCII codes and store them after the device number specified in (d). 1476 + 1477 + 1478 + 1479 +((( 1480 +←Only store 0 when SM191 is OFF 1481 + 1482 +[[image:07-5 Basic instructions_html_57bda5f08026449d.png]] 1483 +))) 1484 + 1485 +For example, when -12,345 is specified in (s) (in the case of specifying signed) 1486 + 1487 +[[image:07-5 Basic instructions_html_f346102467b9bef9.png]] 1488 + 1489 +The calculation result stored in (d) will be as below. 1490 + 1491 +• In "Sign", 20H is stored when the BIN data is positive, and 2DH is stored when it is negative. 1492 + 1493 +• In the 0 to the left of the effective digit, 20H is stored. (Suppress 0.) For example, in the case of "00325", "00" becomes 20H, and "325" becomes the effective digit. 1494 + 1495 +• When storing data to the device specified in (d)+3, when SM191 (output character number switching signal) is OFF, 0 is stored, and it does not change when it is ON. 1496 + 1497 +✎**Note: **The number of occupied points of (d) is 3 when SM191 is ON, and it is 4 when SM191 is OFF. 1498 + 1499 +**Error code** 1500 + 1501 +|**Error code**|**Content** 1502 +|4085H|The read address of (s) exceeds the device range. 1503 +|4086H|The write address of (d) exceeds the device range. 1504 + 1505 +**Example** 1506 + 1507 + 1508 + 1509 +((( 1510 +When X000 is ON, convert the value of 16-bit data (BIN) D1000 into decimal ASCII code, and then use PR instruction to output the 1511 + 1512 +converted ASCII code character by character to the program of Y040 to Y057. 1513 + 1514 +[[image:07-5 Basic instructions_html_c598806a42484ed.png]] 1515 +))) 1516 + 1517 +{{id name="_Toc12255"/}}{{id name="_Toc8216"/}}{{id name="_Toc470"/}}**DBINDA/BIN 32-bit data → Decimal ASCII conversion** 1518 + 1519 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DBINDA(P)** 1520 + 1521 +Convert the BIN 32-bit data specified in (s) and the value of each bit in decimal numbers into ASCII codes and store them after the device number specified in (d). 1522 + 1523 +-[DBINDA(s)(d)] 1524 + 1525 +**Content, range and data type** 1526 + 1527 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1528 +|(s)|BIN data for ASCII conversion|-2,147483648 to 2147483647|Signed BIN 32 bit|ANY32_S 1529 +|(d)|{{id name="OLE_LINK2"/}}The start number of the device storing the conversion result|-|String|ANYSTRING_SINGLE 1530 + 1531 +**Device used** 1532 + 1533 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|((( 1534 +**Offset** 1535 + 1536 +**modification** 1537 +)))|((( 1538 +**Pulse** 1539 + 1540 +**extension** 1541 +))) 1542 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1543 +|(% rowspan="2" %)DBINDA|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 1544 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 1545 + 1546 +**Features** 1547 + 1548 +Convert the BIN 32-bit data specified in (s) and the value of each bit when expressed in decimal numbers into ASCII codes, and store them after the device number specified in (d). 1549 + 1550 +For example, when -12345678 is specified in (s). (in the case of specifying signed) 1551 + 1552 +[[image:07-5 Basic instructions_html_4d939462838cf09b.gif]] The calculation result stored in (d) will be as below. 1553 + 1554 +• In "Sign", 20H is stored when the BIN data is positive, and 2DH is stored when it is negative. 1555 + 1556 +• 20H is stored at 0 to the left of the effective number of digits. (Suppress 0.) For example, in the case of "0012034560", "00" becomes 20H, and "12034560" becomes effective digits. 1557 + 1558 +• For the data stored in the upper 8 bits of the device specified in (d)+5, 0 will be stored when SM191 (output character switching signal) is OFF, and 20H will be stored when it is ON. 1559 + 1560 +✎**Note: **(d) Occupies 6 points. 1561 + 1562 +**Error code** 1563 + 1564 +|**Error code**|**Content** 1565 +|4085H|(s) read address exceeds the device range 1566 +|4086H|(d) write address exceeds the device range 1567 + 1568 +**Example** 1569 + 1570 +[[image:07-5 Basic instructions_html_ec8ac32d748a991c.png]] 1571 + 1572 +When X000 is ON, convert the value of 32-bit data (BIN) D1000 into decimal ASCII code, and then use PR (FNC 77) instruction to output the converted ASCII code character by character to the program in Y040 to Y051 in time and time division. 1573 + 1574 +{{id name="_Toc19693"/}}{{id name="_Toc18078"/}}{{id name="_Toc5726"/}}**DABIN/Decimal ASCII → BIN conversion** 1575 + 1576 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DABIN(P)** 1577 + 1578 +Digital ASCII code (30H to 39H) is a instruction to convert real data into BIN data. 1579 + 1580 +-[DABIN (s) (d)] 1581 + 1582 +**Content, range and data type** 1583 + 1584 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1585 +|(s)|The start number of the device that stores the data (ASCII code) to be converted into a BIN value|-|String|ANYSTRING_SINGLE 1586 +|(d)|The device number for storing conversion result|-|BIN16 bit|ANY16_S 1587 + 1588 +**Device used** 1589 + 1590 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1591 +**Pulse** 1592 + 1593 +**extension** 1594 +))) 1595 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1596 +|(% rowspan="2" %)DABIN|Parameter 1| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 1597 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 1598 + 1599 +**Features** 1600 + 1601 +The decimal ASCII data stored after the device number specified in (s) is converted into BIN 16-bit data and stored in the device specified in (d). 1602 + 1603 +[[image:07-5 Basic instructions_html_22c5cb32a0a32214.png]] 1604 + 1605 +|**ASCII S**|**ASCII 10^^0^^**|**ASCII 10^^1^^**|**ASCII 10^^2^^**|**ASCII 10^^3^^**|**ASCII 10^^4^^** 1606 +|**ASCII code**|((( 1607 +{{id name="OLE_LINK36"/}}Units of 1608 + 1609 +ASCII code 1610 +)))|((( 1611 +Tens of 1612 + 1613 +ASCII code 1614 +)))|((( 1615 +Hundreds of 1616 + 1617 +ASCII code 1618 +)))|((( 1619 +Thousands of 1620 + 1621 +ASCII code 1622 +)))|((( 1623 +Ten thousands 1624 + 1625 +of ASCII code 1626 +))) 1627 + 1628 +For example, When -25,108 is specified in (s) 1629 + 1630 +[[image:07-5 Basic instructions_html_10fb2792e37dbf23.png]] 1631 + 1632 +• The ASCII data specified in (s) to (s)+2 is within the range of -32,768 to +32,767. 1633 + 1634 +• In “Sign”, set 20H when the converted data is positive, and set 2DH when it is negative. (When other than 20H or 2DH is set, it will be treated as positive data. (DABIN(P)) 1635 + 1636 +• The range of the ASCII code set in each digit is 30H to 39H. 1637 + 1638 +• When the ASCII code set in each bit is 20H or 00H, it will be treated as 30H. 1639 + 1640 +**Error code** 1641 + 1642 +|**Error code**|**Content** 1643 +|4084H|((( 1644 +When the Sign data exceeds the range of 30H to 39H, 20H, 00H, 2DH; 1645 + 1646 +When the ASCII code of each bit specified in (s) to (s)+2 exceeds the range of 30H to 39H, 20H, 00H; 1647 + 1648 +When the ASCII data specified in (s) to (s)+2 is other than -32,768 to +32,767. 1649 +))) 1650 +|4085H|The read address of (s) exceeds the device range. 1651 +|4086H|The write address of (d) exceeds the device range. 1652 + 1653 + 1654 +((( 1655 +When X000 is ON, the Signs set in D20 to D22 and the ASCII code data of 5-digit decimal numbers are converted into BIN values, and then stored in the program of D0. 1656 + 1657 +**Example** 1658 +))) 1659 + 1660 +[[image:07-5 Basic instructions_html_bec2bea131b58c03.png]] 1661 + 1662 +{{id name="_Toc3351"/}}{{id name="_Toc26383"/}}{{id name="_Toc26233"/}}**DDABIN/Decimal ASCII → BIN32-bit data conversion** 1663 + 1664 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DDABIN(P)** 1665 + 1666 +The decimal ASCII data stored after the device number specified in (s) is converted into BIN 32-bit data and stored in the device number specified in (d). 1667 + 1668 +-[DDABIN (s) (d) ] 1669 + 1670 +**Content, range and data type** 1671 + 1672 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1673 +|(s)|The start number of the device that stores data (ASCII code) to be converted into a BIN value|-|String|ANYSTRING_SINGLE 1674 +|(d)|The device number for storing conversion result|-|Signed BIN 32 bit|ANY32_S 1675 + 1676 +**Device used** 1677 + 1678 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1679 +**Pulse** 1680 + 1681 +**extension** 1682 +))) 1683 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1684 +|(% rowspan="2" %)DDABIN|Parameter 1| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 1685 +|Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|● 1686 + 1687 +**Features** 1688 + 1689 +The decimal ASCII data stored after the device number specified in (s) is converted into BIN 32-bit data and stored in the device specified in (d). 1690 + 1691 +[[image:07-5 Basic instructions_html_c444110b273f33b7.gif]] 1692 + 1693 +|**ASCII S**|**ASCII code**|**ASCII S**|**ASCII code** 1694 +|ASCII 10^^0^^|Units of ASCII code|ASCII 10^^5^^|{{id name="OLE_LINK38"/}}Hundred thousands of ASCII code 1695 +|ASCII 10^^1^^|Tens of ASCII code|ASCII 10^^6^^|Millions of ASCII code 1696 +|ASCII 10^^2^^|Hundreds of ASCII code|ASCII 10^^7^^|Ten millions of ASCII code 1697 +|ASCII 10^^3^^|{{id name="OLE_LINK37"/}}Thousands of ASCII code|ASCII 10^^8^^|Hundred millions of ASCII code 1698 +|ASCII 10^^4^^|Tens thousands of ASCII code|ASCII 10^^9^^|billions of ASCII code 1699 + 1700 +When -1234543210 is specified in (s) (When signed is specified) 1701 + 1702 +[[image:07-5 Basic instructions_html_1b4c7e1c663a4399.png]] 1703 + 1704 +• The ASCII data specified in (s) to (s)+5 is within the range of -2,147,483,648 to +2,147,483,647. In addition, the data stored in the high byte of (s)+5 will be ignored. 1705 + 1706 +• In the Sign data, set 20H when the converted data is positive, and set 2DH when it is negative. (When other than 20H or 2DH is set, it will be treated as positive data. (DABIN(P)) 1707 + 1708 +• The range of ASCII code set in each digit is 30H to 39H. 1709 + 1710 +• When the ASCII code set in each bit is 20H or 00H, it will be treated as 30H. 1711 + 1712 +**Error code** 1713 + 1714 +|**Error code**|**Content** 1715 +|4084H|((( 1716 +When the Sign data exceeds the range of 30H to 39H, 20H, 00H and 2DH; 1717 + 1718 +{{id name="OLE_LINK39"/}}When the ASCII code of each bit specified in (s) to (s)+5 exceeds the range of 30H to 39H, 20H and 00H; 1719 + 1720 +When the ASCII data specified in (s) to (s)+5 exceeds the range of -2,147,483,648 to +2,147,483,647 1721 +))) 1722 +|4085H|The read address of (s) exceeds the device range. 1723 +|4086H|The write address of (d) exceeds the device range. 1724 + 1725 +**Example** 1726 + 1727 +[[image:07-5 Basic instructions_html_feea438c943ea9dd.png]] 1728 + 1729 +When X000 is ON, the Signs set in to D20 to D25 and the ASCII code data of 10-digit decimal numbers are converted into BIN values and then saved to the program in D0 to D1. 1730 + 1731 +{{id name="_Toc26556"/}}{{id name="_Toc12799"/}}{{id name="_Toc23863"/}}**LIMIT/ BIN 16-bit data high and low limit control** 1732 + 1733 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **LIMIT(P)** 1734 + 1735 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limit value ranges specified in (s1) and (s2). 1736 + 1737 +-[LIMIT (s1) (s2) (s3) (d)] 1738 + 1739 +**Content, range and data type** 1740 + 1741 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1742 +|s1|Low limit value (minimum output limit value)|-32,768 to 32,767|BIN16 bit|ANY16_S 1743 +|s2|High limit value (maximum output limit value)|-32,768 to 32,767|BIN16 bit|ANY16_S 1744 +|s3|Input value controlled by high and low limit control|-32,768 to 32,767|BIN16 bit|ANY16_S 1745 +|d|The start number of device that stores the output value controlled by high and low limit control|-|BIN16 bit|ANY16_S 1746 + 1747 +**Device used** 1748 + 1749 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1750 +**Pulse** 1751 + 1752 +**extension** 1753 +))) 1754 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1755 +|(% rowspan="4" %)LIMIT|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1756 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1757 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|● 1758 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 1759 + 1760 +**Features** 1761 + 1762 +The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the high and low limit value ranges specified in (s1) and (s2). The output value is controlled as follows. 1763 + 1764 +|**Condition**|**The value stored in the output value** 1765 +|Low limit value (s1)>input value (s3)|Low limit value (s1) 1766 +|High limit value (s1) <input value (s3)|High limit value (s2) 1767 +|Low limit value (s1) ≤ input value (s3) ≤ high limit value (s2)|Input value (s3) 1768 + 1769 + 1770 +((( 1771 +•Only in the case of controlling high limit value, set the minimum value of data range in the low limit value specified in (s1). 1772 + 1773 +• Only in the case of controlling low limit value, set the maximum value of data range in the high limit value specified in (s2). 1774 + 1775 +[[image:07-5 Basic instructions_html_50eb5229b027aa14.png]] 1776 +))) 1777 + 1778 +**Error code** 1779 + 1780 +|**Error code**|**Content** 1781 +|4085H|The read address exceeds the device range 1782 +|4086H|The write address exceeds the device range 1783 +|4084H|High limit <low limit 1784 + 1785 +**Example** 1786 + 1787 +[[image:07-5 Basic instructions_html_d67a2e740d4fc738.png]] 1788 + 1789 +When X000 is ON 1790 + 1791 +• When D0 <500, D1 is 500. 1792 + 1793 +• When 500 ≤ D0 ≤ 5,000, D1 is the value of D0. 1794 + 1795 +• When 5,000 <D0, D1 is 5,000. 1796 + 1797 +{{id name="_Toc32553"/}}{{id name="_Toc9981"/}}{{id name="_Toc9158"/}}**DLIMIT/BIN 32-bit data high and low limit control** 1798 + 1799 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DLIMIT(P)** 1800 + 1801 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the range of high and low limit values specified in (s1) and (s2). 1802 + 1803 +-[DLIMIT (s1) (s2) (s3) (d)] 1804 + 1805 +**Content, range and data type** 1806 + 1807 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1808 +|s1|Low limit value (minimum output limit value)|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S 1809 +|s2|High limit value (maximum output limit value)|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S 1810 +|s3|Input value controlled by high and low limit control|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S 1811 +|d|The start number of the device that stores the output value controlled by high and low limit control|-|BIN32 bit|ANY32_S 1812 + 1813 +**Device used** 1814 + 1815 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1816 +**Pulse** 1817 + 1818 +**extension** 1819 +))) 1820 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1821 +|(% rowspan="4" %)DLIMIT|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 1822 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 1823 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|● 1824 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|● 1825 + 1826 +**Features** 1827 + 1828 +The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the range of high and low limit values specified in (s1) and (s2). The output value is controlled as follows. 1829 + 1830 +|**Condition**|**The value stored in the output value** 1831 +|Low limit value ((s1), (s1)+1)> input value ((s3), (s3)+1)|Low limit value ((s1), (s1)+1) 1832 +|High limit value ((s2), (s2)+1) <input value ((s3), (s3)+1)|High limit value ((s2), (s2)+1) 1833 +|Low limit value ((s1), (s1)+1) ≤ input value ((s3), (s3)+1) ≤ high limit value ((s2), (s2)+1)|Input value ((s3), (s3)+1) 1834 + 1835 +{{id name="OLE_LINK43"/}}{{id name="OLE_LINK40"/}}•Only in the case of controlling high limit value, set the minimum value of data range in the low limit value specified in (s1). 1836 + 1837 +• Only in the case of controlling low limit value, set the maximum value of data range in the high limit value specified in (s2). 1838 + 1839 +**Error code** 1840 + 1841 +|**Error code**|**Content** 1842 +|4085H|The read address exceeds the device range 1843 +|4086H|The write address exceeds the device range 1844 +|4084H|High limit <low limit 1845 + 1846 +**Example** 1847 + 1848 +[[image:07-5 Basic instructions_html_217355b90f4b4e16.png]] 1849 + 1850 +Operation: 1851 + 1852 +• When (D1, D0) <10,000, (D11, D10) is 10,000. 1853 + 1854 +• When 10,000 ≤ (D1, D0) ≤ 1,000,000, (D11, D10) is the value of (D1, D0). 1855 + 1856 +• When 1,000,000 <(D1, D0), (D11, D10) is 1,000,000. 1857 + 1858 +{{id name="_Toc12534"/}}{{id name="_Toc28213"/}}{{id name="_Toc24591"/}}**SCL/BIN 16-bit unit scale (coordinate data of each point)** 1859 + 1860 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **SCL(P)** 1861 + 1862 +The scaling conversion data (16-bit data unit) specified in (s2) is scaled from the input value specified in (s1), and the calculation result is stored in the device specified in (d). 1863 + 1864 +-[SCL (s1) (s2) (d)] 1865 + 1866 +**Content, range and data type** 1867 + 1868 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1869 +|(s1)|The input value for scaling or the start number of device storing the input value|-32,768 to 32,767|Signed BIN 16 bit|ANY16_S 1870 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 16 bit|ANY16_S 1871 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 16 bit|ANY16_S 1872 + 1873 +**Device used** 1874 + 1875 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 1876 +**Pulse** 1877 + 1878 +**extension** 1879 +))) 1880 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 1881 +|(% rowspan="3" %)SCL|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 1882 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 1883 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 1884 + 1885 +**Features** 1886 + 1887 +For the scale conversion data (16-bit data unit) specified in (s2), scale by the input value specified in (s1), and store the operation result in the device specified in (d). Scale conversion is performed based on the scale conversion data stored after the device specified in (s2). 1888 + 1889 +|(% colspan="2" %)**Setting items (n represents the number of coordinate points specified in (s2))**|**Device allocation** 1890 +|(% colspan="2" %)Coordinate points|(s2) 1891 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+1 1892 +|Y coordinate|(s2)+2 1893 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+3 1894 +|Y coordinate|(s2)+4 1895 +|(% colspan="3" %)........ 1896 +|(% rowspan="2" %)Point n|X coordinate|(s2)+2n-1 1897 +|Y coordinate|(s2)+2n 1898 + 1899 +[[image:07-5 Basic instructions_html_80185ccddb878234.png]] 1900 + 1901 +• If the operation result is not an integer value, round the first digit below the decimal point. 1902 + 1903 +• The X coordinate data of the conversion data for scaling should be set in ascending order. 1904 + 1905 +• (s1) should be set within the range of conversion data for scaling (device value of (s2)). 1906 + 1907 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output. 1908 + 1909 +• Set the number of coordinate points of the conversion data for scaling within the range of 1 to 32,767. 1910 + 1911 +• Setting example of conversion table for scaling. 1912 + 1913 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet. 1914 + 1915 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]] 1916 + 1917 +|(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Sett device and content**|(% rowspan="2" %)**Remarks** 1918 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set content** 1919 +|(% colspan="2" %)Coordinate points|(s2)|R0|K10| 1920 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+1|R1|K5| 1921 +|Y coordinate|(s2)+2|R2|K20| 1922 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+3|R3|K30| 1923 +|Y coordinate|(s2)+4|R4|K50| 1924 +|(% rowspan="2" %)Point 3|X coordinate|(s2)+5|R5|K100| 1925 +|Y coordinate|(s2)+6|R6|K200| 1926 +|(% rowspan="2" %)Point 4|X coordinate|(s2)+7|R7|K25|(% rowspan="6" %)((( 1927 +If the coordinates are specified by 3 points, the intermediate value could be the output value. 1928 + 1929 +In this example, the output value (median value) is specified by the Y coordinate of point 5. 1930 + 1931 +When the X coordinate is the same at 3 points or more, the value of the 2nd point is also output. 1932 +))) 1933 +|Y coordinate|(s2)+8|R8|K200 1934 +|(% rowspan="2" %)Point 5|X coordinate|(s2)+9|R9|K70 1935 +|Y coordinate|(s2)+10|R10|K200 1936 +|(% rowspan="2" %)Point 6|X coordinate|(s2)+11|R11|K250 1937 +|Y coordinate|(s2)+12|R12|K250 1938 +|(% rowspan="2" %)Point 7|X coordinate|(s2)+13|R13|K250| 1939 +|Y coordinate|(s2)+14|R14|K90| 1940 +|(% rowspan="2" %)Point 8|X coordinate|(s2)+15|R15|K350|(% rowspan="4" %)((( 1941 +If the coordinates are specified by two points, the output value is the value of the Y coordinate of the next point. 1942 + 1943 +In this example, the output value is specified by the Y coordinate of point 9. 1944 +))) 1945 +|Y coordinate|(s2)+16|R16|K90 1946 +|(% rowspan="2" %)Point 9|X coordinate|(s2)+17|R17|K350 1947 +|Y coordinate|(s2)+18|R18|K30 1948 +|(% rowspan="2" %)Point 10|X coordinate|(s2)+19|R19|K400| 1949 +|Y coordinate|(s2)+20|R20|K7| 1950 + 1951 +**Error code** 1952 + 1953 +|**Error code**|**Content** 1954 +|4085H|When the specified device range for reading exceeds the range of the corresponding device. 1955 +|4086H|When the specified device range for writing exceeds the range of the corresponding device. 1956 +|4084H|((( 1957 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs; 1958 + 1959 +When the input value specified in (s1) exceeds the range of the set scale conversion data; 1960 + 1961 +When the number of start coordinate points of device (s2) is less than 0. 1962 +))) 1963 + 1964 +**Example** 1965 + 1966 +[[image:07-5 Basic instructions_html_5519d7b41f15b6d6.png]] 1967 + 1968 +[[image:07-5 Basic instructions_html_ace075fb7675de8e.gif]] When -100 ≤ D0(X) < 0, D100(Y)= 1969 + 1970 +[[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] when D0(X)=0, D100(Y)=0; 1971 + 1972 +when 0< D0(X) ≤ 100, D100(Y)= 1973 + 1974 +[[image:07-5 Basic instructions_html_e35e13160c08a133.png]] 1975 + 1976 + 1977 + 1978 +{{id name="_Toc4862"/}}{{id name="_Toc11340"/}}{{id name="_Toc25383"/}}**DSCL/32-bit unit scale (coordinate data of each point)** 1979 + 1980 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSCL(P)** 1981 + 1982 +The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d). 1983 + 1984 +-[DSCL (s1) (s2) (d)] 1985 + 1986 +**Content, range and data type** 1987 + 1988 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 1989 +|(s1)|The input value for scaling or the start number of the device storing the input value|-2,147,483,648 to 2,147,483,647|Signed BIN 32 bit|ANY32_S 1990 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 32 bit|ANY32_S 1991 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 32 bit|ANY32_S 1992 + 1993 +**Device used** 1994 + 1995 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Device**|**Offset modification**|((( 1996 +**Pulse** 1997 + 1998 +**extension** 1999 +))) 2000 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 2001 +|(% rowspan="3" %)DSCL|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 2002 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 2003 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|● 2004 + 2005 +**Features** 2006 + 2007 +{{id name="OLE_LINK41"/}}The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2). 2008 + 2009 +|(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation** 2010 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2) 2011 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+3, (s2)+2 2012 +|Y coordinate|(s2)+5, (s2)+4 2013 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+7, (s2)+6 2014 +|Y coordinate|(s2)+9, (s2)+8 2015 +|(% colspan="3" %)........ 2016 +|(% rowspan="2" %)Point n|X coordinate|(s2)+4n-1, (s2)+4n-2 2017 +|Y coordinate|(s2)+4n+1, (s2)+4n 2018 + 2019 +[[image:07-5 Basic instructions_html_6633ca18cee1218c.png]] 2020 + 2021 +• If the calculation result is not an integer value, round the first digit below the decimal point. 2022 + 2023 +• The X coordinate data of the conversion data for scaling should be set in ascending order. 2024 + 2025 +• For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value). 2026 + 2027 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output. 2028 + 2029 +• Set the number of coordinate points of conversion data for scaling within the range of 1 to 2,147,483,647. 2030 + 2031 +• Setting example of conversion table for scaling. 2032 + 2033 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet. 2034 + 2035 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]] 2036 + 2037 +|(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Set device and content**|(% rowspan="2" %)**Remarks** 2038 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set content** 2039 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2)|R1, R0|K10| 2040 +|(% rowspan="2" %)Point 1|X coordinate|(s2)+3, (s2)+2|R3, R2|K5| 2041 +|Y coordinate|(s2)+5, (s2)+4|R5, R4|K7| 2042 +|(% rowspan="2" %)Point 2|X coordinate|(s2)+7, (s2)+6|R7, R6|K20| 2043 +|Y coordinate|(s2)+9, (s2)+8|R9, R8|K30| 2044 +|(% rowspan="2" %)Point 3|X coordinate|(s2)+11, (s2)+10|R10, R11|K50| 2045 +|Y coordinate|(s2)+13, (s2)+12|R13, R12|K100| 2046 +|(% rowspan="2" %)Point 4|X coordinate|(s2)+15, (s2)+14|R15, R14|K200|(% rowspan="6" %)((( 2047 +if the coordinates are specified by 3 points, the intermediate value could be the output value. 2048 + 2049 +In this example, the output value (median value) is specified by the Y coordinate of point 5. 2050 + 2051 +When the X coordinate is the same at 3 points or more, the value of the 2nd point is also output. 2052 +))) 2053 +|Y coordinate|(s2)+17, (s2)+16|R17, R16|K25 2054 +|(% rowspan="2" %)Point 5|X coordinate|(s2)+19, (s2)+18|R19, R18|K200 2055 +|Y coordinate|(s2)+21, (s2)+20|R21, R20|K70 2056 +|(% rowspan="2" %)Point 6|X coordinate|(s2)+23, (s2)+22|R23, R22|K200 2057 +|Y coordinate|(s2)+25, (s2)+24|R25, R24|K250 2058 +|(% rowspan="2" %)Point 7|X coordinate|(s2)+27, (s2)+26|R27, R26|K250| 2059 +|Y coordinate|(s2)+29, (s2)+28|R29, R28|K90| 2060 +|(% rowspan="2" %)Point 8|X coordinate|(s2)+31, (s2)+30|R31, R30|K350|(% rowspan="4" %)((( 2061 +If the coordinates are specified by two points, the output value is the value of the Y coordinate of the next point. 2062 + 2063 +In this example, the output value is specified by the Y coordinate of point 9. 2064 +))) 2065 +|Y coordinate|(s2)+33, (s2)+32|R33, R32|K90 2066 +|(% rowspan="2" %)Point 9|X coordinate|(s2)+35, (s2)+34|R35, R34|K350 2067 +|Y coordinate|(s2)+37, (s2)+36|R37, R36|K30 2068 +|(% rowspan="2" %)Point 10|X coordinate|(s2)+39, (s2)+38|R39, R38|K400| 2069 +|Y coordinate|(s2)+41, (s2)+40|R41, R40|K7| 2070 + 2071 +**Error code** 2072 + 2073 +|**Error code**|**Content** 2074 +|4085H|When the specified device range for reading exceeds the range of the corresponding device. 2075 +|4086H|When the specified device range for writing exceeds the range of the corresponding device. 2076 +|4084H|((( 2077 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs; 2078 + 2079 +When the input value specified in (s1) exceeds the range of the set scale conversion data; 2080 + 2081 +When the number of start coordinate points of device (s2) is less than 0. 2082 +))) 2083 + 2084 +**Example** 2085 + 2086 +[[image:07-5 Basic instructions_html_ba95b2d50d8d1d3e.png]] 2087 + 2088 +[[image:07-5 Basic instructions_html_1de79c7d87d51f78.gif]] When -100 ≤ D0(X) < 0, D100(Y)= 2089 + 2090 +[[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] When D0(X)=0, D100(Y)=0; 2091 + 2092 +When 0 < D0(X) ≤ 100, D100(Y)= 2093 + 2094 +[[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]] 2095 + 2096 +{{id name="_Toc3776"/}}{{id name="_Toc11170"/}}{{id name="_Toc2957"/}}**SCL2/BIN 16-bit unit scale (X/Y coordinate data)** 2097 + 2098 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **SCL2(P)** 2099 + 2100 +The conversion data (16-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d). 2101 + 2102 +-[SCL2 (s1) (s2) (d)] 2103 + 2104 +**Content, range and data type** 2105 + 2106 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 2107 +|(s1)|The input value for scaling or the start number of the device storing the input value|-32,768 to 32,767|Signed BIN 16 bit|ANY16_S 2108 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 16 bit|ANY16_S 2109 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 16 bit|ANY16_S 2110 + 2111 +**Device used** 2112 + 2113 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 2114 +**Pulse** 2115 + 2116 +**extension** 2117 +))) 2118 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 2119 +|(% rowspan="3" %)SCL2|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 2120 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 2121 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 2122 + 2123 +**Features** 2124 + 2125 +The conversion data (16-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2). 2126 + 2127 +|(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation** 2128 +|(% colspan="2" %)Coordinate points|(s2) 2129 +|(% rowspan="4" %)X coordinate|Point 1|(s2)+1 2130 +|Point 2|(s2)+2 2131 +|.....|...... 2132 +|Point n|(s2)+n 2133 +|(% rowspan="4" %)Y coordinate|Point 1|(s2)+n+1 2134 +|Point 2|(s2)+n+2 2135 +|.....|..... 2136 +|Point n|(s2)+2n 2137 + 2138 +[[image:07-5 Basic instructions_html_80185ccddb878234.png]] 2139 + 2140 +• If the operation result is not an integer value, round the first digit below the decimal point. 2141 + 2142 +• The X coordinate data of the conversion data for scaling should be set in ascending order. 2143 + 2144 +• For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value). 2145 + 2146 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output. 2147 + 2148 +• Set the number of coordinate points of conversion data for scaling within the range of 1 to 32,767. 2149 + 2150 +• Setting example of conversion table for scaling. 2151 + 2152 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet. 2153 + 2154 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]] 2155 + 2156 +|(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Set device and content**|(% rowspan="2" %)**Remarks** 2157 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set content** 2158 +|(% colspan="2" %)Coordinate points|(s2)|R0|K10| 2159 +|(% rowspan="10" %)X coordinate|Point 1|(s2)+1|R1|K5| 2160 +|Point 2|(s2)+2|R2|K20| 2161 +|Point 3|(s2)+3|R3|K50| 2162 +|Point 4|(s2)+4|R4|K200|(% rowspan="3" %)Refer to** ✎1** 2163 +|Point 5|(s2)+5|R5|K200 2164 +|Point 6|(s2)+6|R6|K200 2165 +|Point 7|(s2)+7|R7|K250| 2166 +|Point 8|(s2)+8|R8|K350|(% rowspan="2" %)Refer to** ✎2** 2167 +|Point 9|(s2)+9|R9|K350 2168 +|Point 10|(s2)+10|R10|K400| 2169 +|(% rowspan="10" %)Y coordinate|Point 1|(s2)+11|R11|K7| 2170 +|Point 2|(s2)+12|R12|K30| 2171 +|Point 3|(s2)+13|R13|K100| 2172 +|Point 4|(s2)+14|R14|K25|(% rowspan="3" %)Refer to**✎1** 2173 +|Point 5|(s2)+15|R15|K70 2174 +|Point 6|(s2)+16|R16|K250 2175 +|Point 7|(s2)+17|R17|K90| 2176 +|Point 8|(s2)+18|R18|K90|(% rowspan="2" %)Refer to** ✎2** 2177 +|Point 9|(s2)+19|R19|K30 2178 +|Point 10|(s2)+20|R20|K7| 2179 + 2180 +✎**1** Like points 4, 5, and 6, if the coordinates are specified by 3 points, the intermediate value could be the output value. 2181 + 2182 +In this example, the output value (median value) is specified by the Y coordinate of point 5. 2183 + 2184 +When the X coordinate is the same at 3 or more points, the value of the second point is also output. 2185 + 2186 +✎**2** Like points 8 and 9, if the coordinates are specified by 2 points, the output value is the value of the Y coordinate of next point. 2187 + 2188 +In this example, the output value is specified by the Y coordinate of point 9. 2189 + 2190 +**Error code** 2191 + 2192 +|**Error code**|**Content** 2193 +|4085H|When the specified device range for reading exceeds the range of the corresponding device. 2194 +|4086H|When the specified device range for writing exceeds the range of the corresponding device. 2195 +|4084H|((( 2196 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs; 2197 + 2198 +When the input value specified in (s1) exceeds the range of the set scale conversion data; 2199 + 2200 +When the number of start coordinate points of device (s2) is less than 0. 2201 +))) 2202 + 2203 +**Example** 2204 + 2205 +[[image:07-5 Basic instructions_html_ace075fb7675de8e.gif]] [[image:07-5 Basic instructions_html_de529c9a16a62ef0.png]] 2206 + 2207 +When -100 ≤D0 (X) < 0, D100(Y)= 2208 + 2209 +[[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] when D0(X)=0, D100(Y)=0; 2210 + 2211 +when 0 < D0(X) ≤ 100, D100(Y)= 2212 + 2213 +[[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]] 2214 + 2215 +{{id name="_Toc5608"/}}{{id name="_Toc1756"/}}{{id name="_Toc21402"/}}**DSCL2/BIN 32-bit unit scale (X/Y coordinate data)** 2216 + 2217 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSCL2(P)** 2218 + 2219 +The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d). 2220 + 2221 +-[DSCL2 (s1) (s2) (d)] 2222 + 2223 +**Content, range and data type** 2224 + 2225 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 2226 +|(s1)|The input value for scaling or the start number of the device storing the input value|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S 2227 +|(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 32 bit|ANY32_S 2228 +|(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 32 bit|ANY32_S 2229 + 2230 +**Device used** 2231 + 2232 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 2233 +**Pulse** 2234 + 2235 +**extension** 2236 +))) 2237 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 2238 +|(% rowspan="3" %)DSCL2|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 2239 +|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|● 2240 +|Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|● 2241 + 2242 +**Features** 2243 + 2244 +The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2). 2245 + 2246 +|(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation** 2247 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2) 2248 +|(% rowspan="4" %)X coordinate|Point 1|(s2)+3, (s2)+2 2249 +|Point 2|(s2)+5, (s2)+4 2250 +|.....|...... 2251 +|Point n|(s2)+2n+1, (s2)+2n 2252 +|(% rowspan="4" %)Y coordinate|Point 1|(s2)+2n+3, (s2)+2n+2 2253 +|Point 2|(s2)+2n+5, (s2)+2n+4 2254 +|.....|..... 2255 +|Point n|(s2)+4n+1, (s2)+4n 2256 + 2257 +[[image:07-5 Basic instructions_html_6633ca18cee1218c.png]] 2258 + 2259 +• If the operation result is not an integer value, round the first digit below the decimal point. 2260 + 2261 +• The X coordinate data of the conversion data for scaling should be set in ascending order. 2262 + 2263 +• For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value). 2264 + 2265 +• If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output. 2266 + 2267 +• Set the number of coordinate points of conversion data for scaling within the range of 1 to 2,147,483,647. 2268 + 2269 +• Setting example of conversion table for scaling. 2270 + 2271 +In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet. 2272 + 2273 +[[image:07-5 Basic instructions_html_74fd22d845ad450e.png]] 2274 + 2275 +|(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Set device and content**|(% rowspan="2" %)**Remarks** 2276 +|(% colspan="2" %)**When R0 is specified in (s2)**|**Set content** 2277 +|(% colspan="2" %)Coordinate points|(s2)+1, (s2)|R1, R0|K10| 2278 +|(% rowspan="10" %)X|Point 1|(s2)+3, (s2)+2|R3, R2|K5| 2279 +|Point 2|(s2)+5, (s2)+4|R5, R4|K20| 2280 +|Point 3|(s2)+7, (s2)+6|R7, R6|K50| 2281 +|Point 4|(s2)+9, (s2)+8|R9, R8|K200|(% rowspan="3" %)Refer to** ✎1** 2282 +|Point 5|(s2)+11, (s2)+10|R10, R11|K200 2283 +|Point 6|(s2)+13, (s2)+12|R13, R12|K200 2284 +|Point 7|(s2)+15, (s2)+14|R15, R14|K250| 2285 +|Point 8|(s2)+17, (s2)+16|R17, R16|K350|(% rowspan="2" %)Refer to** ✎2** 2286 +|Point 9|(s2)+19, (s2)+18|R19, R18|K350 2287 +|Point 10|(s2)+21, (s2)+20|R21, R20|K400| 2288 +|(% rowspan="10" %)Y coordinate|Point 1|(s2)+23, (s2)+22|R23, R22|K7| 2289 +|Point 2|(s2)+25, (s2)+24|R25, R24|K30| 2290 +|Point 3|(s2)+27, (s2)+26|R27, R26|K100| 2291 +|Point 4|(s2)+29, (s2)+28|R29, R28|K25|(% rowspan="3" %)Refer to** ✎1** 2292 +|Point 5|(s2)+31, (s2)+30|R31, R30|K70 2293 +|Point 6|(s2)+33, (s2)+32|R33, R32|K250 2294 +|Point 7|(s2)+35, (s2)+34|R35, R34|K90| 2295 +|Point 8|(s2)+37, (s2)+36|R37, R36|K90|(% rowspan="2" %)Refer to** ✎2** 2296 +|Point 9|(s2)+39, (s2)+38|R39, R38|K30 2297 +|Point 10|(s2)+41, (s2)+40|R41, R40|K7| 2298 + 2299 +✎**1** Like points 4, 5, and 6, if the coordinates are specified by 3 points, the intermediate value could be the output value. 2300 + 2301 +In this example, the output value (median value) is specified by the Y coordinate of point 5. 2302 + 2303 +When the X coordinate is the same at 3 or more points, the value of the second point is also output. 2304 + 2305 +✎**2** Like points 8 and 9, if the coordinates are specified by 2 points, the output value is the value of the Y coordinate of the next point. 2306 + 2307 +In this example, the output value is specified by the Y coordinate of point 9. 2308 + 2309 +**Error code** 2310 + 2311 +|**Error code**|**Content** 2312 +|4085H|When the specified device range for reading exceeds the range of the corresponding device. 2313 +|4086H|When the specified device range for writing exceeds the range of the corresponding device. 2314 +|4084H|((( 2315 +When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs; 2316 + 2317 +When the input value specified in (s1) exceeds the range of the set scale conversion data; 2318 + 2319 +When the number of start coordinate points of device (s2) is less than 0. 2320 +))) 2321 + 2322 +**Example** 2323 + 2324 +[[image:07-5 Basic instructions_html_91dbc16faa9d2ec3.png]] 2325 + 2326 +When -100 ≤D0(X) < 0, D100(Y)=[[image:/xwiki/bin/download/PLC%20Editor2/1%20User%20manual/2.1%20LX5V%20user%20manual/07-5%20Basic%20instruction/WebHome/07-5%20Basic%20instructions_html_2c96d630f666e72c.gif?rev=1.1||alt="07-5 Basic instructions_html_2c96d630f666e72c.gif"]],,[[image:07-5 Basic instructions_html_2c96d630f666e72c.gif]] ,,; 2327 + 2328 +when D0(X)=0, D100(Y)=0; 2329 + 2330 +when 0< D0(X) ≤ 100, D100(Y)=[[image:/xwiki/bin/download/PLC%20Editor2/1%20User%20manual/2.1%20LX5V%20user%20manual/07-5%20Basic%20instruction/WebHome/07-5%20Basic%20instructions_html_47ebf5cc7733fccc.gif?rev=1.1||alt="07-5 Basic instructions_html_47ebf5cc7733fccc.gif"]],,[[image:07-5 Basic instructions_html_47ebf5cc7733fccc.gif]] ,,. 2331 + 2332 +[[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]] 2333 + 2334 +{{id name="_Toc32057"/}}{{id name="_Toc9941"/}}{{id name="_Toc6492"/}}**ZONE/BIN 16-bit data zone control** 2335 + 2336 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **ZONE(P)** 2337 + 2338 +After adding the offset value specified in (s1) or (s2) to the input value specified in (s3), it is stored in the device number specified in (d). 2339 + 2340 +-[ZONE (s1) (s2) (s3) (d)] 2341 + 2342 +**Content, range and data type** 2343 + 2344 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 2345 +|s1|The negative offset value for addition in the input value|-32,768 to 32,767|BIN16 bit|ANY16_S 2346 +|s2|The positive offset value for addition in the input value|-32,768 to 32,767|BIN16 bit|ANY16_S 2347 +|s3|Input value for zone control`|-32,768 to 32,767|BIN16 bit|ANY16_S 2348 +|d|The start number of the device storing the output value controlled by zone control|-|BIN16 bit|ANY16_S 2349 + 2350 +**Device used** 2351 + 2352 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 2353 +**Pulse** 2354 + 2355 +**extension** 2356 +))) 2357 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 2358 +|(% rowspan="4" %)ZONE|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 2359 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|● 2360 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|● 2361 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|● 2362 + 2363 +**Features** 2364 + 2365 +After adding the offset value specified in (s1) or (s2) to the input value (BIN 16-bit value) specified in (s3), it is stored in the device number specified in (d). The offset value is controlled as follows. 2366 + 2367 +|**Condition**|**The value stored in the output value** 2368 +|When input value (s3)<0|Input value (s3) + negative offset value (s1) 2369 +|When input value (s3)=0|0 2370 +|When input value (s3)>0|Input value (s3) + positive offset value (s2) 2371 + 2372 + 2373 +((( 2374 +• When the output value stored in (d) is a signed BIN 16-bit value, and the operation result exceeds the range of -32,768 to 32,767, the situation is shown in the following example. 2375 + 2376 +For example, when (s1) is -100 and (s3) is -32,768, 2377 + 2378 +the output value = -32768+(-100)=8000H-FF9CH=7F9CH=32668. 2379 + 2380 +[[image:07-5 Basic instructions_html_a2adbf9ccf8f839.png]] 2381 + 2382 + 2383 + 2384 +))) 2385 + 2386 +**Error code** 2387 + 2388 +|**Error code**|**Content** 2389 +|4085H|When the specified device range for reading exceeds the range of the corresponding device 2390 +|4086H|When the specified device range for writing exceeds the range of the corresponding device 2391 + 2392 +**Example** 2393 + 2394 +[[image:07-5 Basic instructions_html_5da523c7765bf5be.png]] 2395 + 2396 +When X000 is ON 2397 + 2398 +• When D0<0, the value of (D0)+(-1,000) is stored in D1. 2399 + 2400 +• When D0=0, 0 is stored in D1. 2401 + 2402 +• When 0<D0, the value of (D0)+(1,000) is stored in D1. 2403 + 2404 +{{id name="_Toc28351"/}}{{id name="_Toc11023"/}}{{id name="_Toc30269"/}}**DZONE/BIN 32-bit data zone control** 2405 + 2406 +[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] DZONE(P) 2407 + 2408 +After adding the offset value specified in (s1) or (s2) to the input value specified in (s3), it is stored in the device number specified in (d). 2409 + 2410 +-[DZONE (s1) (s2) (s3) (d)] 2411 + 2412 +**Content, range and data type** 2413 + 2414 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 2415 +|(s1)|The negative offset value for addition in the input value|-2147483648 to 2147483647|BIN32 bit|ANY32_S 2416 +|(s2)|The positive offset value for addition in the input value|-2147483648 to 2147483647|BIN32 bit|ANY32_S 2417 +|(s3)|Input value for zone control|-2147483648 to 2147483647|BIN32 bit|ANY32_S 2418 +|(d)|The start number of the device storing the output value controlled by zone control|-|BIN32 bit|ANY32_S 2419 + 2420 +**Device used** 2421 + 2422 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|((( 2423 +**Pulse** 2424 + 2425 +**extension** 2426 +))) 2427 +|**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 2428 +|(% rowspan="4" %)DZONE|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 2429 +|Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|● 2430 +|Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|● 2431 +|Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|● 2432 + 2433 +**Features** 2434 + 2435 +After adding the offset value specified in (s1) or (s2) to the input value (BIN 32-bit value) specified in (s3), it is stored in the device number specified in (d). The offset value is controlled as follows. 2436 + 2437 +|**Condition**|**The value stored in the output value** 2438 +|When input value ((s3), (s3)+1)<0|Input value ((s3), (s3)+1) + negative offset value (s1), (s1)+1 2439 +|When input value ((s3), (s3)+1)=0|0 2440 +|When input value ((s3), (s3)+1)>0|Input value ((s3), (s3)+1) + positive offset value (s2), (s2)+1 2441 + 2442 + 2443 +((( 2444 +• When the output value stored in (d) and (d)+1 is a signed BIN 32-bit value, and the operation result exceeds the range of -2,147,483,648 to 2,147,483,647, the situation is shown in the following example. 2445 + 2446 +For example, (s1), (s1)+1 is -1,000, (s3), (s3)+1 is -2,147,483,648, then the output value=-2,147,483,648+(-1000)=80000000H+FFFFFC18H=2,147,482,648. 2447 + 2448 +[[image:07-5 Basic instructions_html_2f3a96a2565c75c7.png]] 2449 +))) 2450 + 2451 +**Error code** 2452 + 2453 +|**Error code**|**Content** 2454 +|4085H|When the specified device range for reading exceeds the range of the corresponding device 2455 +|4086H|When the specified device range for writing exceeds the range of the corresponding device 2456 + 2457 +**Example** 2458 + 2459 +[[image:07-5 Basic instructions_html_b831b14748df07ab.png]] 2460 + 2461 +• When (D1, D0)<0, the value of (D1, D0)+(-10,000) is stored in (D11, D10). 2462 + 2463 +• When (D1, D0)=0, 0 is stored in (D11, D10). 2464 + 2465 +• When 0<(D1, D0), the value of (D1, D0)+10,000 is stored in (D11, D10).