Wiki source code of 12

Version 1.2 by Joey on 2022/06/09 15:22

Show last authors
1 = **Contact comparison instruction** =
2
3 == **Signed 16-bit contact comparison instruction** ==
4
5 **LD £, AND £, OR £**
6
7 The BIN 16-bit data of the device specified in (s1) and the BIN 16-bit data of the device specified in (s2) are compared by normal open contact processing.
8
9 LD£: Normally open contact comparison instruction
10
11 AND£: Normally open contact series connection comparison instruction
12
13 OR£: Normally open contact parallel connection comparison instruction
14
15 **Ladder diagram**
16
17 (% style="text-align:center" %)
18 [[image:07-5 Basic instructions_html_63210db6b7e1512f.png]]
19
20 (You can enter "=", "<>", ">", "<", ">=", "<=" in "£")
21
22 **Content, range and data type**
23
24 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
25 |(s1)|Comparison data or device storing comparison data|-32768 to 32767|Signed BIN 16 bit|ANY16_S
26 |(s2)|Comparison data or device storing comparison data|-32768 to 32767|Signed BIN 16 bit|ANY16_S
27
28 **Device used**
29
30 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="11" %)**Devices**|(((
31 **Offset modification**
32 )))|(((
33 **Pulse extension**
34 )))
35 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**[D]**|**XXP**
36 |LD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
37 |LD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
38 |LD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
39 |LD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
40 |LD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
41 |LD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
42 |AND=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
43 |AND>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
44 |AND<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
45 |AND>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
46 |AND<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
47 |AND<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
48 |OR=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
49 |OR>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
50 |OR<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
51 |OR>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
52 |OR<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
53 |OR<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|
54
55 **Features**
56
57 The BIN 16-bit data of the device specified in (s1) and the BIN 16-bit data of the device specified in (s2) are compared by normal open contact processing.
58
59 The comparison operation result of each instruction is shown below.
60
61 |**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result**
62 |==|(s1)=(s2)|(% rowspan="6" %)On state|==|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state
63 |<>|(s1)≠(s2)|<>|(s1)=(s2)
64 |>|(s1)>(s2)|>|(s1)≤(s2)
65 |<|(s1)<(s2)|<|(s1)≥(s2)
66 |>=|(s1)≥(s2)|>=|(s1)<(s2)
67 |<=|(s1)≤(s2)|<=|(s1)>(s2)
68
69 **Error code**
70
71 |**Error code**|**Content**
72 |4085H|(s) read address exceeds the device range
73
74 **Example**
75
76 (((
77 (1) When the current value of counter C10 is 200, Y10 is set
78
79 When the content of D200 is above -29, and X1 is ON, Y11 is set
80
81 LD£ instruction:
82
83 (% style="text-align:center" %)
84 [[image:07-5 Basic instructions_html_1309199eccc7134.png]]
85 )))
86
87 (2) AND£ instruction
88
89 (((
90 When X0 is ON, or when the current value of counter C10 is 200, Y10 is set
91
92 When X1 is OFF, and the content of data counter D0 is not -10, Y11 is set
93
94 (% style="text-align:center" %)
95 [[image:07-5 Basic instructions_html_1c966f74b0bd808e.png]]
96
97
98 )))
99
100 (3) OR£ instruction:
101
102 (((
103 When X1 is ON, or when the current value of counter C10 is 200, Y0 is set
104
105 When X2 and M30 are ON, or the content of register D100 is K10000 and above, M60 is set
106
107 (% style="text-align:center" %)
108 [[image:07-5 Basic instructions_html_8b000809015ea436.png]]
109 )))
110
111 == **Signed 32-bit contact comparison instruction** ==
112
113 **LDD £, ANDD £, ORD £**
114
115 The BIN 32-bit data of the device specified in (s1) and the BIN 32-bit data of the device specified in (s2) are compared by normal open contact processing.
116
117 LDD£: Normally open contact comparison command
118
119 ANDD£: Normally open contact series link comparison instruction
120
121 ORD£: Normally open contact parallel link comparison instruction
122
123 **Ladder diagram**
124
125 (% style="text-align:center" %)
126 [[image:07-5 Basic instructions_html_63210db6b7e1512f.png]]
127
128 “=”, “<>”, “>”, “<”, “>=”, “<=” can be input in “£”
129
130 **Content, range and data type**
131
132 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
133 |(s1)|Comparison data or device storing comparison data|-2147483648 to 2147483647|Signed BIN 32 bit|ANY32_S
134 |(s2)|Comparison data or device storing comparison data|-2147483648 to 2147483647|Signed BIN 32 bit|ANY32_S
135
136 **Device used**
137
138 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="14" %)**Devices**|(((
139 **Offset modification**
140 )))|(((
141 **Pulse extension**
142 )))
143 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
144 |LDD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
145 |LDD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
146 |LDD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
147 |LDD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
148 |LDD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
149 |LDD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
150 |ANDD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
151 |ANDD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
152 |ANDD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
153 |ANDD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
154 |ANDD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
155 |ANDD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
156 |ORD=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
157 |ORD>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
158 |ORD<|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
159 |ORD>=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
160 |ORD<=|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
161 |ORD<>|s1, s2|●|●|●|●|●|●|●|●|●|●|●|●|●| |●|
162
163 **Features**
164
165 The BIN 32-bit data of the device specified in (s1) and the BIN 32-bit data of the device specified in (s2) are compared by normal open contact processing.
166
167 The comparison operation result of each instruction is shown below.
168
169 |**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result**
170 |==|(s1)=(s2)|(% rowspan="6" %)On state|==|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state
171 |<>|(s1)≠(s2)|<>|(s1)=(s2)
172 |>|(s1)>(s2)|>|(s1)≤(s2)
173 |<|(s1)<(s2)|<|(s1)≥(s2)
174 |>=|(s1)≥(s2)|>=|(s1)<(s2)
175 |<=|(s1)≤(s2)|<=|(s1)>(s2)
176
177 **Error code**
178
179 |**Error code**|**Content**
180 |4085H|(S) read address exceeds the device range
181
182 **Example**
183
184 (1) LDD£ instruction:
185
186 When the data of LC10 is 200000, Y10 is set, otherwise Y10 is reset.
187
188 When the 32-bit data composed of D201 and D200 exceeds -5000, and X1 is ON, Y11 is turned ON.
189
190 1. ANDD£ instruction:
191
192 [[image:07-5 Basic instructions_html_38be93eec0ced6c.png]]
193
194 When X0 is ON and the value of LC10 is 200000, Y10 is set, otherwise it is reset.
195
196 When X1 is OFF and the 32-bit data composed of D1 and D0 is not equal to K-50000, Y11 is set.
197
198 1. ORD£ instruction:
199
200 [[image:07-5 Basic instructions_html_8ebfc7b0562cf370.png]]
201
202 When X1 is ON, or the data of LC10 is equal to the data of LC10 is equal to 200000, Y0 is set.
203
204 When X2 and M30 are set, or the double word data composed of D101 and D100 is greater than or equal to 100000, M60 is set.
205
206 {{id name="_Toc28789"/}}{{id name="_Toc29577"/}}**Single precision real number contact comparison instruction**
207
208 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **LDE £, ANDE £, ORE £**
209
210 The single precision real number of the device specified in (s1) and the single precision real number of the device specified in (s2) are compared by normal open contact processing.
211
212 LDE□: Normally open contact comparison command
213
214 ANDE□: Normally open contact series link comparison instruction
215
216 ORE□: Normally open contact parallel link comparison instruction
217
218 **Ladder diagram**
219
220 [[image:07-5 Basic instructions_html_6ac28f30e24ad296.png]]
221
222 “=”, “<>”, “>”, “<”, “>=”, “<=” can be input in “£”
223
224 **Content, range and data type**
225
226 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
227 |(s1)|{{id name="OLE_LINK28"/}}Comparison data or the device start number storing the comparison data|{{id name="OLE_LINK339"/}}0, 2^^-126^^ ≤~|(s)~|< 2^^128^^|Single precision real number|ANYREAL_32
228 |(s2)|Comparison data or the device start number storing the comparison data|0, 2^^-126^^ ≤~|(s)~|< 2^^128^^|Single precision real number|ANYREAL_32
229
230 **Device used**
231
232 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
233 **Offset**
234
235 **modification**
236 )))|(((
237 **Pulse**
238
239 **extension**
240 )))
241 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
242 |LDE=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
243 |LDE>|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
244 |LDE<|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
245 |LDE>=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
246 |LDE<=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
247 |LDE<>|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
248 |ANDE=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
249 |ANDE>|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
250 |ANDE<|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
251 |ANDE>=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
252 |ANDE<=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
253 |ANDE<>|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
254 |ORE=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
255 |ORD>|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
256 |ORE<|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
257 |ORE>=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
258 |ORE<=|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
259 |ORE<>|s1, s2| | | | | | | | | | | | | | |●|●|●|●|●|●|●| | |●|●|
260
261 **Features**
262
263 The single precision real number of the device specified in (s1) and the single precision real number of the device specified in (s2) are compared by normal open contact processing.
264
265 The comparison operation result of each instruction is shown below.
266
267 |**Instruction Sign**|**Condition**|**Comparison operation result**|**Instruction Sign**|**Condition**|**Comparison operation result**
268 |E=|(s1)=(s2)|(% rowspan="6" %)On state|E=|(s1)≠(s2)|(% rowspan="6" %)Non-conduction state
269 |E<>|(s1)≠(s2)|E<>|(s1)=(s2)
270 |E>|(s1)>(s2)|E>|(s1)≤(s2)
271 |E<|(s1)<(s2)|E<|(s1)≥(s2)
272 |E>=|(s1)≥(s2)|E>=|(s1)<(s2)
273 |E<=|(s1)≤(s2)|E<=|(s1)>(s2)
274
275 **Error code**
276
277 |**Error code**|**Content**
278 |4084H|{{id name="OLE_LINK340"/}}When the content of the specified device by (s1) and (s2) is an irregular number, a non-number, or ±∞
279 |4085H|{{id name="OLE_LINK343"/}}The read address of (s1) and (s2exceeds the device range
280
281 **Example**
282
283 1. LDE£ instruction:
284
285 [[image:07-5 Basic instructions_html_c4c820cf59601493.png]]
286
287 When the real number input in D0 is equal to E1.23, Y10 is ON, otherwise Y10 is OFF.
288
289 When the real number in R0 is greater than or equal to the real number in LC0, Y11 is ON, otherwise it is OFF.
290
291 If the input in D0, R0, LC0 is not a real number, it will report H4084 error.
292
293 1. ANDE£ instruction:
294
295 [[image:07-5 Basic instructions_html_7cdd2117360e179b.png]]
296
297 Only when M0 is ON and D2 real number is not equal to E1.23 and R2 real number is less than real number LC2 , Y12 is ON, otherwise all are OFF.
298
299 1. ORE£ instruction:
300
301 [[image:07-5 Basic instructions_html_3eba0bd56176441d.png]]
302
303 When the real number of R4 is less than or equal to the real number of R15, or the real number R6 is equal to the real number R20, Y13 is ON, otherwise Y13 is OFF.
304
305 {{id name="_Toc16295"/}}{{id name="_Toc20251"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **String comparison**
306
307 **LDS£、ANDS£、 ORS£**
308
309 {{id name="OLE_LINK27"/}}Compare the string stored after the device number specified in (s1) with the string stored after the device number specified in (s2).
310
311 LDS£: String comparison instruction
312
313 ANDS£: String serial connection comparison instruction
314
315 {{id name="OLE_LINK341"/}}ORS£: String parallel connection comparison instruction
316
317 **Ladder diagram**
318
319 [[image:07-5 Basic instructions_html_5fb3b3b70645fef5.png]]
320
321 “=” and “<>” could be entered in “£”
322
323 **Content, range and data type**
324
325 |**Parameter**|**Content**|**Range**|**Date type**|**Date type(label)**
326 |(S1)|{{id name="OLE_LINK342"/}}Connection data or the device start number storing the data or the string specified directly|-|String|ANYSTRING_SINGLE
327 |(S1)|Connection data or the device start number storing the data or the string specified directly|-|{{id name="OLE_LINK29"/}}String|ANYSTRING_SINGLE
328
329 **Device used**
330
331 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
332 **Offset**
333
334 **modification**
335 )))|(((
336 **Pulse**
337
338 **extension**
339 )))
340 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
341 |LDS=|s1、s2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|
342 |LDS<>|s1、s2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|
343 |ANDS=|s1、s2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|
344 |ANDS<>|s1、s2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|
345 |ORS=|s1、s2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|
346 |ORS<>|s1、s2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|
347
348 **Features**
349
350 • Compare the string stored after the device number specified in (s1) with the string stored after the device number specified in (s2).
351
352 • The comparison operation result of each instruction is shown below.
353
354 |**Instruction sign**|**Condition**|**Comparison operation result**|**Instruction sign**|**Condition**|**Comparison operation result**
355 |= |(s1)=(s2)|(% rowspan="2" %)On stat|= |(s1)≠(s2)|(% rowspan="2" %)Non-conduction state
356 |<>|(s1)≠(s2)|<>|(s1)=(s2)
357
358 **Error code**
359
360 |**Error code**|**Content**
361 |4085H|The read address of (s1) or (s2) exceeds the device range
362 |408AH|The length of the read string of (s1) or (s2) exceeds, and the continuous length of the string exceeds 400 characters.
363 |408BH|When (s1) or (s2) reading the string, the maximum range of the device is read but 00H is not found as the end.
364
365 **Example**
366
367 1. 1、LDS£ instruction
368
369 [[image:07-5 Basic instructions_html_449a071f61ff5b58.png]]
370
371 1. ANDS£ instruction
372
373 [[image:07-5 Basic instructions_html_dd6aa995d193bdd2.png]]
374
375 1. ORS£ instruction
376
377 [[image:07-5 Basic instructions_html_4f8fb7c94f87c58d.png]]
378
379 {{id name="_Toc11737"/}}[[image:07-5 Basic instructions_html_a2e3294e01b2f206.gif]] **7.12 Clock operation instruction**
380
381 {{id name="_Toc9100"/}}{{id name="_Toc26958"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TADD/The addition of clock data**
382
383 **TADD(P)**
384
385 Add the time data stored after the device number specified in (s1) and the time data stored after the device number specified in (s2), and store the result of the addition operation after the device number specified in (d) .
386
387 -[TADD (s1) (s2) (d)]
388
389 **Content, range and data type**
390
391 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
392 |(s1)|{{id name="OLE_LINK345"/}}The device start number that stores the added time data|-|Signed BIN 16 bit|(((
393 ANY16_ARRAY
394
395 (number of elements: 3)
396 )))
397 |(s2)|The device start number that stores the addition operation time (time) data|-|Signed BIN 16 bit|(((
398 ANY16_ARRAY
399
400 (number of elements: 3)
401 )))
402 |(d)|The device start number that stores the time (time) data of the addition operation result|-|Signed BIN 16 bit|(((
403 ANY16_ARRAY
404
405 (number of elements: 3)
406 )))
407
408 **Device used**
409
410 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
411 **Offset**
412
413 **modification**
414 )))|(((
415 **Pulse**
416
417 **extension**
418 )))
419 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
420 |(% rowspan="3" %)TADD|Parameter 1| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
421 |Parameter 2| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
422 |Parameter 3| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
423
424 **Features**
425
426 Add the time data specified in (s1) and the time data specified in (s2), and store the result of the addition in the device number specified in (d) or later.
427
428 [[image:07-5 Basic instructions_html_37222a6e282347f9.png]]
429
430 **Example**
431
432 When 6:32:40 and 7:48:10 are added together
433
434 [[image:07-5 Basic instructions_html_90138670198ab422.png]]
435
436 When the calculation result time exceeds 24 o'clock, the carry flag turns ON, and the value after 24 hours is subtracted becomes the calculation result. For example, when 14:20:30 and 20:20:20 are added, the result is not 34:40:50, but 10:40:50.
437
438 [[image:07-5 Basic instructions_html_bac419ce2dc0dc2.png]]
439
440 When the calculation result is 0 (0 hour, 0 minute, 0 second), the zero flag turns on.
441
442 When 23:59:59 and 1 second are added, the result of the calculation is 0:00:00, and the carry flag and zero flag are turned on.
443
444 Related device are as follows:
445
446 |**Devices**|**Name**|**Content**
447 |SM151|Carry|It is ON when the result of the TADD(P) instruction exceeds the maximum clock data value of 23:59:59
448 |SM153|Zero|It is ON when the result of the TADD(P) instruction is 0:00:00
449
450 ✎**Note**
451
452 The devices specified in (s1), (s2), (d) occupy 3 points respectively. Be careful not to overlap with the device used for machine control.
453
454 When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
455
456 **Error code**
457
458 |**Error code**|**Content**
459 |4085H|{{id name="OLE_LINK344"/}}When reading the specified device range exceeds the corresponding device range
460 |4086H|When writing the specified device range exceeds the corresponding device range
461 |4084H|(((
462 When the values specified in (s1) and (s2) are other than 0 to 23
463
464 When the values specified in (s1)+1, (s2)+1, (s1)+2 and (s2)+2 are other than 0 to 59
465 )))
466
467 **Example**
468
469 [[image:07-5 Basic instructions_html_4f75eedee7172bbb.png]]
470
471 Set D0 time to 16:30:00 and D10 time to 4:30:0
472
473 [[image:07-5 Basic instructions_html_c64e0faf2af172f8.png]]
474
475 [[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png]]
476
477 After the coil is turned on, the D20 time is 21:0:0
478
479 [[image:07-5 Basic instructions_html_a9b235835aa41200.png]]
480
481
482
483 {{id name="_Toc6604"/}}{{id name="_Toc16422"/}}**TSUB/The subtraction of clock data**
484
485 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TSUB(P)**
486
487 Subtract the time data stored after the device number specified in (s1) and the time data stored after the device number specified in (s2), and store the subtraction result in the device number specified in (d) or later .
488
489 -[TSUB (s1) (s2) (d)]
490
491 **Content, range and data type**
492
493 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
494 |(s1)|The device start number that stores the subtracted time data|-|Signed BIN 16 bit|(((
495 ANY16_ARRAY
496
497 (number of elements: 3)
498 )))
499 |(s2)|The device start number that stores the subtraction operation time (time) data|-|Signed BIN 16 bit|(((
500 ANY16_ARRAY
501
502 (number of elements: 3)
503 )))
504 |(d)|The device start number that stores the time (time) data of the subtraction result|-|Signed BIN 16 bit|(((
505 ANY16_ARRAY
506
507 (number of elements: 3)
508 )))
509
510 **Device used**
511
512 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
513 **Offset**
514
515 **modification**
516 )))|(((
517 **Pulse**
518
519 **extension**
520 )))
521 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
522 |(% rowspan="3" %)TSUB|Parameter 1| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
523 |Parameter 2| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
524 |Parameter 3| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
525
526 **Features**
527
528 Subtract the time data specified in (s1) and the time data specified in (s2), and store the subtraction result in the device number specified in (d) or later.
529
530 [[image:07-5 Basic instructions_html_5a93455e4cd8a27.png]]
531
532 **Example**
533
534 When subtracting 10:40:20 and 3:50:10
535
536 [[image:07-5 Basic instructions_html_2473f03fc493780c.png]]
537
538 When the calculation result time is a negative number, the borrow flag turns on and the data +24 is the calculation result. For example, in the case of subtracting 4:50:32 and 10:42:12, the result is not -6:8:20, but 18:8:20.
539
540 [[image:07-5 Basic instructions_html_24b998b4c3c4ec73.png]]
541
542 When the calculation result is 0 (0 hour, 0 minute, 0 second), the zero flag turns on.
543
544 Related device are as follows:
545
546 |**Devices**|**Name**|**Content**
547 |SM152|Borrow|It is ON when the result of the TSUB(P) instruction is less than 0:00:00
548 |SM153|Zero|It is ON when the result of the TSUB(P) instruction is at the time of 0:00:00:00
549
550 ✎**Note**
551
552 • The devices specified in (s1), (s2), and (d) occupy 3 points respectively. Be careful not to overlap with the device used for machine control.
553
554 • When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
555
556 **Error code**
557
558 |**Error code**|**Content**
559 |4085H|When reading the specified device range exceeds the corresponding device range
560 |4086H|When writing the specified device range exceeds the corresponding device range
561 |4084H|(((
562 When the values specified in (s1) and (s2) are other than 0 to 23
563
564 When the values specified in (s1)+1, (s2)+1, (s1)+2 and (s2)+2 are other than 0 to 59
565 )))
566
567 **Example**
568
569 [[image:07-5 Basic instructions_html_e3a5d4793d3ccd2d.png]]
570
571 Set D0 time to 16:30:00 and D10 time to 4:30:0
572
573 [[image:07-5 Basic instructions_html_c64e0faf2af172f8.png]]
574
575 [[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png]]
576
577 After the coil is turned on, the D20 time is 12:00:00
578
579 [[image:07-5 Basic instructions_html_8f93ea19ba10652b.png]]
580
581 {{id name="_Toc10358"/}}{{id name="_Toc12073"/}}[[image:07-5 Basic instructions_html_501fb256fd034ca6.gif]] **TRD/Clock data reading**
582
583 **TRD(P)**
584
585 Read the clock data of the built-in real-time clock of the CPU module.
586
587 -[TRD (d)]
588
589 **Content, range and data type**
590
591 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
592 |(d)|Read destination and start device number of clock data|-|Signed BIN 16 bit|(((
593 ANY16_ARRAY
594
595 (number of elements: 7)
596 )))
597
598 **Device used**
599
600 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
601 **Offset**
602
603 **modification**
604 )))|(((
605 **Pulse**
606
607 **extension**
608 )))
609 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
610 |TRD|Parameter 1| | | | | | | | | | | | | | |●|●|●|●| | | | | | |●|●
611
612 **Features**
613
614 Read the clock data (SD100 to SD106) of the real-time clock built into the CPU module into (d) to (d)+6 in the following format.
615
616 |**Parameter**|**Element**|**Project**|**Clock data**| |**Element**|**Project**
617 |(% rowspan="7" %)Special register|SD105|Year (Gregorian)|2000 to 2099|→|(d)|Year (Gregorian)
618 |SD104|Month|1 to 12|→|(d)+1|Month
619 |SD103|Day|1 to 31|→|(d)+2|Day
620 |SD102|Hour|0 to 23|→|(d)+3|Hour
621 |SD101|Minute|0 to 59|→|(d)+4|Minute
622 |SD100|Seconds|0 to 59|→|(d)+5|Seconds
623 |SD106|Week|0 (Sun) to 6 (Sat)|→|(d)+6|Week
624
625 • The related devices are shown below. The clock data of these special registers are updated through END processing.
626
627 |**Devices**|**Content**
628 |SD100|The second data of the clock data is stored in BIN code.
629 |SD101|The sub-data of the clock data is stored in BIN code.
630 |SD102|Time data of clock data is stored in BIN code.
631 |SD103|The daily data of the clock data is stored in BIN code.
632 |SD104|The monthly data of the clock data is stored in BIN code.
633 |SD105|The year data of the clock data is stored in a 4-digit BIN code of the Gregorian calendar.
634 |SD106|The week data of the clock data is stored in BIN code. (0: day, 1: one, ..., 6: six) are stored in BIN code.
635
636 ✎**Note**
637
638 • The device specified in (d) occupies 7 points. Be careful not to overlap with the device used for machine control.
639
640 **Error code**
641
642 |**Error code**|**Content**
643 |4086H|When reading the specified device range exceeds the corresponding device range
644
645 **Example**
646
647 [[image:07-5 Basic instructions_html_b81c1991fec5b4b1.png]]
648
649 After the M0 coil is turned on, the current date and time are read as 2020-2-19 13:10:38 Wednesday
650
651 [[image:07-5 Basic instructions_html_fe82ecd18ebfd787.png]]
652
653 {{id name="_Toc24237"/}}{{id name="_Toc487"/}}**TWR/Clock data writing**
654
655 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TWR(P)**
656
657 Write the clock data of the built-in real-time clock of the CPU module.
658
659 -[TWR (s)]
660
661 **Content, range and data type**
662
663 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
664 |(s)|Clock data write source, start device number|-|Signed BIN 16 bit|ANY16_ARRAY (number of elements: 7)
665
666 **Device used**
667
668 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
669 **Offset**
670
671 **modification**
672 )))|(((
673 **Pulse**
674
675 **extension**
676 )))
677 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
678 |TWR|Parameter 1| | | | | | | | | | | | | | |●|●|●|●| | | | | | |●|●
679
680 **Features**
681
682 Write the set clock data (s) to (s)+6 to the clock data (SD100 to SD106) of the real-time clock built into the CPU module.
683
684 |(% colspan="3" %)**Set data at all times**|(% rowspan="2" %) |(% colspan="2" %)**Special register**
685 |**Element**|**Project**|**Clock data**|**Element**|**Project**
686 |(s)|Year (Gregorian)|2000 to 2099 or 0 to 99|→|SD105|Year (Gregorian)
687 |(s)+1|Month|1 to 12|→|SD104|Month
688 |(s)+2|Day|1 to 31|→|SD103|Day
689 |(s)+3|Hour|0 to 23|→|SD102|Hour
690 |(s)+4|Minute|0 to 59|→|SD101|Minute
691 |(s)+5|Seconds|0 to 59|→|SD100|Seconds
692 |(s)+6|Week|0 (Sun) to 6 (Sat)|→|SD106|Week
693
694 • If the TWR(P) instruction is executed, the clock data of the real-time clock is changed immediately. Therefore, the clock data after a few minutes should be transferred to the set clock data (s) to (s)+6 in advance, and the instruction will be executed when the correct time is reached.
695
696 • If the year in (s) is in the range of 0 to 99, it will be automatically treated as 2000 to 2099.
697
698 • When a value indicating an impossible time is set, the clock data will not be updated. Set the correct clock data and write again.
699
700 • The day of the week (SD100) is automatically corrected.
701
702 • The related devices are shown below.
703
704 |**Devices**|**Content**
705 |SD100|The second data of the clock data is stored in BIN code.
706 |SD101|The sub-data of the clock data is stored in BIN code.
707 |SD102|Time data of clock data is stored in BIN code.
708 |SD103|The daily data of the clock data is stored in BIN code.
709 |SD104|The monthly data of the clock data is stored in BIN code.
710 |SD105|The year data of the clock data is stored in a 4-digit BIN code of the Gregorian calendar.
711 |SD106|The week data of the clock data is stored in BIN code. (0: day, 1: one, ..., 6: six) are stored in BIN code.
712
713 ✎**Note**
714
715 The device specified in (s) occupies 7 points. Be careful not to overlap with the device used for machine control.
716
717 **Error code**
718
719 |**Error code**|**Content**
720 |4085H|When reading the specified device range exceeds the corresponding device range
721
722 **Example**
723
724 Set D0 date and time to 2020-2-19 12:36:00 in advance
725
726 [[image:07-5 Basic instructions_html_994c66d1a4cbd45f.png]]
727
728 At the moment when the time 12:36:00 arrives, turn on the M0 coil and write the time.
729
730 [[image:07-5 Basic instructions_html_bf3e906ee5265598.png]]
731
732 {{id name="_Toc5357"/}}{{id name="_Toc6196"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **HTOS/16-bit data conversion of time data (hour, minute, second → second)**
733
734 **HTOS(P)**
735
736 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result as BIN 16-bit data in the device specified in (d).
737
738 -[HTOS (s) (d)]
739
740 **Content, range and data type**
741
742 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
743 |(s)|The device start number that stores the data of the subtracted time|-|Signed BIN 16 bit|ANY16_ARRAY (number of elements: 3)
744 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|ANY16
745
746 **Device used**
747
748 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
749 **Pulse**
750
751 **extension**
752 )))
753 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
754 |(% rowspan="2" %)HTOS|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
755 |Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
756
757 **Features**
758
759 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d).
760
761 [[image:07-5 Basic instructions_html_a84b7741fd5bef2f.png]]
762
763 **Example**
764
765 When 4 hours, 29 minutes and 31 seconds are specified in (s)
766
767 [[image:07-5 Basic instructions_html_5effb7bc9b8e5cf7.png]]
768
769 **Error code**
770
771 |**Error code**|**Content**
772 |4085H|When reading the specified device range exceeds the corresponding device range
773 |4086H|When writing the specified device range exceeds the corresponding device range
774 |4084H|(((
775 {{id name="OLE_LINK348"/}}When the calculation result is not in the range of 0 to 32767
776
777 When the value specified in (s) is not in the range of 0 to 9
778
779 When the value specified in (s)+1 and (s)+2 is not in the range of 0 to 59
780 )))
781
782 **Example**
783
784 [[image:07-5 Basic instructions_html_e23e38c4ba4c34bb.png]]
785
786 D0 time is set to 5:36:53
787
788 [[image:07-5 Basic instructions_html_2866a121e5ca5713.png]]
789
790 The time of D10 after the M0 coil is turned on is as below.
791
792 [[image:07-5 Basic instructions_html_1dd6c5de05890797.png]]
793
794 {{id name="_Toc13431"/}}{{id name="_Toc5278"/}}**DHTOS/32-bit data conversion of time data (hour, minute, second → second)**
795
796 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DHTOS(P)**
797
798 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result as BIN 32-bit data in the device specified in (d).
799
800 -[DHTOS (s) (d)]
801
802 **Content, range and data type**
803
804 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
805 |(s)|The device start number that stores the data of the subtracted time|-|Signed BIN 16 bit|ANY16_ARRAY (number of elements: 3)
806 |(d)|The device start number that stores the converted clock data|-|Signed BIN 32 bit|ANY32
807
808 **Device used**
809
810 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
811 **Offset**
812
813 **modification**
814 )))|(((
815 **Pulse**
816
817 **extension**
818 )))
819 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
820 |(% rowspan="2" %)DHTOS|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
821 |Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
822
823 **Features**
824
825 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d).
826
827 [[image:07-5 Basic instructions_html_f4be08508575ea01.png]]
828
829 **Example**
830
831 When 35 hours, 10 minutes and 58 seconds are specified in (s)
832
833 [[image:07-5 Basic instructions_html_5b9ad230ed5e1fd0.png]]
834
835 **Error code**
836
837 |**Error code**|**Content**
838 |4085H|When reading the specified device range exceeds the corresponding device range
839 |4086H|When writing the specified device range exceeds the corresponding device range
840 |4084H|(((
841 When the calculation result is not in the range of 0 to 32767
842
843 When the value specified in (s)+1 and (s)+2 is not in the range of 0 to 59
844 )))
845
846 **Example**
847
848 [[image:07-5 Basic instructions_html_ae8ab4379e8bdb91.png]]
849
850 D0 time is set to 15:33:24
851
852 [[image:07-5 Basic instructions_html_57a15d9e1045e93e.png]]
853
854 The second of D10 after the M0 coil is turned on is
855
856 [[image:07-5 Basic instructions_html_194e906b1dc12078.png]]
857
858 {{id name="_Ref22686"/}}{{id name="_Toc11231"/}}{{id name="_Toc7401"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **HOUR/Hour measuring 16-bit**
859
860 **HOUR(P)**
861
862 The time for the input contact to be ON is measured in units of one hour.C
863
864 -[HOUR (s) (d1) (d2)]
865
866 **Content, range and data type**
867
868 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
869 |(s)|(((
870 The time when the alarm (d2) is turned ON
871
872 (set by one hour)
873 )))|K0 to K32767|Signed BIN 16 bit|ANY16
874 |(d1)|Device that stores the current value of measurement (specified data register for power failure retention)|-|Unsigned BIN 16 bit|(((
875 ANY16_ARRAY
876
877 (Number of elements: 2)
878 )))
879 |(d2)|Device that turns ON when the time limit expires (alarm output)|-|Bit|ANY_BOOL
880
881 **Device used**
882
883 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
884 **Offset**
885
886 **modification**
887 )))|(((
888 **Pulse**
889
890 **extension**
891 )))
892 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
893 |(% rowspan="3" %)HOUR|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
894 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
895 |Parameter 3| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
896
897 **Features**
898
899 The input contact ON time is measured in units of 1 hour. When the cumulative ON time exceeds the time (BIN 16-bit data) specified in (s), the device specified in (d2) is turned on .
900
901 • In (s), set the time until the alarm (d2) turns ON in units of 1 hour.
902
903 • (d1) stores the current measured value in units of 1 hour.
904
905 • If the median value of (d1) exceeds 32767, it will be modified to 32767.
906
907 • (d1)+1 stores the current measured value (in units of 1 second) that is less than 1 hour.
908
909 • (d2) turns on when the current value (d1) exceeds the time specified in (s).
910
911 • In order to continue to use the current value data even after the power of the CPU module is turned off, specify the data register for power failure retention to (d1). If you use general-purpose data registers, the current value data will be cleared by powering off the CPU module and STOP→RUN operations.
912
913 • After the alarm output specified in (d2) turns ON, measurement will continue.
914
915 • The measurement stops when the current value reaches the 16-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+1.
916
917 ✎**Note**
918
919 • The device specified in (d1) occupies 2 points. Be careful not to overlap with the device used for machine control.
920
921 • After the instruction stops running, the measurement stops and the output continues to be maintained.
922
923 **Error code**
924
925 |**Error code**|**Content**
926 |4085H|When reading the specified device range exceeds the corresponding device range
927 |4086H|When writing the specified device range exceeds the corresponding device range
928 |4084H|When the value of (s) is negative
929
930
931
932 **Example**
933
934 [[image:07-5 Basic instructions_html_7570f8c392470a9f.png]]
935
936 When M0 = ON, the duration of the state is accumulated, the time is recorded in D0, and the seconds less than 1 hour are recorded in D1. When the accumulated time of D0 reaches 98 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K98), the accumulated timing will continue and the reading will continue to increase; the current time value D0 reaches the maximum value of 32767 hours and D1 reaches 3599 seconds, the timing measurement will stop. The current time values D0 and D1 are cleared to 0.
937
938 {{id name="_Toc8523"/}}{{id name="_Toc9364"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DHOUR/Hour measuring 32 bits**
939
940 **DHOUR(P)**
941
942 The time for the input contact to be ON is measured in units of one hour.
943
944 -[DHOUR (s) (d1) (d2)]
945
946 **Content, range and data type**
947
948 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
949 |(s)|(((
950 The time when the alarm (d2) is turned ON
951
952 (set by one hour)
953 )))|0 to 2147483647|Signed BIN 32 bit|ANY32
954 |(d1)|Device that stores the current value of measurement (specified data register for power failure retention)|-|Unsigned BIN 32 bit|(((
955 ANY32_ARRAY
956
957 (Number of elements: 2)
958 )))
959 |(d2)|Device that turns ON when the time limit expires (alarm output)|-|Bit|ANY_BOOL
960
961 **Device used**
962
963 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
964 **Offset**
965
966 **modification**
967 )))|(((
968 **Pulse**
969
970 **extension**
971 )))
972 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
973 |(% rowspan="3" %)DHOUR|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
974 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
975 |Parameter 3| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
976
977 **Features**
978
979 • The input contact ON time is measured in units of 1 hour. When the cumulative ON time exceeds the time (BIN 32-bit data) specified in (s), the device specified in (d2) is set to ON.
980
981 • In (s)+1, (s), set the time until the alarm (d2) turns ON in units of 1 hour.
982
983 • (D1)+1 and (d1) store the current value measured in units of 1 hour. ((d1)+1: high bit, (d1): low bit)
984
985 • If the median of (d1)+1 and (d1) exceeds 2147483647, it will be modified to 2147483647.
986
987 • (D1)+2 stores the current value (in units of 1 second) of the measurement that is less than 1 hour.
988
989 • (D2) turns on when the current value (d1)+1, (d1) exceeds the time specified in (s).
990
991 • In order to continue to use the current value data even after the power of the CPU module is turned off, specify the data register for power failure retention to (d1). If you use general-purpose data registers, the current value data will be cleared by powering off the CPU module and STOP→RUN operations.
992
993 • After the alarm output specified in (d2) turns on, the measurement will continue.
994
995 • The measurement stops when the current value reaches the 32-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+2.
996
997 ✎**Note**
998
999 • The device specified in (d1) occupies 3 points. Be careful not to overlap with the device used for machine control.
1000
1001 • After the instruction stops running, the measurement stops and the output continues to be maintained.
1002
1003 **Error code**
1004
1005 |**Error code**|**Content**
1006 |4085H|When reading the specified device range exceeds the corresponding device range
1007 |4086H|When writing the specified device range exceeds the corresponding device range
1008 |4084H|When the value of (s) is negative
1009
1010
1011
1012 **Example**
1013
1014 [[image:07-5 Basic instructions_html_3f1ef5ecc835de30.png]]
1015
1016 When M0=ON, the duration of this state is accumulated, the time is recorded in D1, D0, and the seconds less than 1 hour are recorded in D2. When the accumulated time of D1, D0 reaches 1000 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K1000), the accumulated timing will continue, and the reading will continue to increase; the current time values D1 and D0 reach the maximum value of 2147483647 hours, and when D2 reaches 3599 seconds, the timing measurement will stop and the timing should be restarted. The current time values D0, D1, and D2 must be cleared to 0.
1017
1018 **{{id name="_Toc11629"/}}STOH/16-bit data conversion of time data (second → hour, minute, second)**
1019
1020 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **STOH(P)**
1021
1022 Convert the second 16-bit data stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
1023
1024 -[STOH (s) (d)]
1025
1026 **Content, range and data type**
1027
1028 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1029 |(s)|{{id name="OLE_LINK353"/}}The device start number that stores the clock data before conversion|0 to 32767|Signed BIN 16 bit|ANY16
1030 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|(((
1031 ANY16_ARRAY
1032
1033 (number of elements: 3)
1034 )))
1035
1036 **Device used**
1037
1038 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1039 **Offset**
1040
1041 **modification**
1042 )))|(((
1043 **Pulse**
1044
1045 **extension**
1046 )))
1047 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1048 |(% rowspan="2" %)STOH|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1049 |Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1050
1051 **Features**
1052
1053 Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
1054
1055 [[image:07-5 Basic instructions_html_1f5f3f1d80af2a34.png]]
1056
1057 **Example**
1058
1059 When 29,011 seconds are specified in (s)
1060
1061 [[image:07-5 Basic instructions_html_682516cbf773f515.png]]
1062
1063 **Error code**
1064
1065 |**Error code**|**Content**
1066 |4085H|When reading the specified device range exceeds the corresponding device range
1067 |4086H|When writing the specified device range exceeds the corresponding device range
1068 |4084H|When the value of (s) exceeds the range
1069
1070 **Example**
1071
1072 [[image:07-5 Basic instructions_html_e783349d57adf7d2.png]]
1073
1074 Set D0 seconds to 12537
1075
1076 The hour, minute and second of D10 after the M0 coil is turned on are
1077
1078 [[image:07-5 Basic instructions_html_d3c33949e8684891.png]]
1079
1080 {{id name="_Toc10764"/}}{{id name="_Toc30243"/}}**DSTOH/32-bit data conversion of time data (second → hour, minute, second)**
1081
1082 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSTOH(P)**
1083
1084 Convert the second 32-bit data of second stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
1085
1086 -[DSTOH (s) (d)]
1087
1088 **Content, range and data type**
1089
1090 |**Parameter**|**Content**|**Range**|**Data type**|**Data &nbsp;&nbsp;&nbsp;&nbsp;type (label)**
1091 |(s)|The device start number that stores the clock data before conversion|0 to 117964799|Signed BIN 32 bit|ANY32
1092 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|(((
1093 ANY16_ARRAY
1094
1095 (number of elements: 3)
1096 )))
1097
1098 **Device used**
1099
1100 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1101 **Offset**
1102
1103 **modification**
1104 )))|(((
1105 **Pulse**
1106
1107 **extension**
1108 )))
1109 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1110 |(% rowspan="2" %)DSTOH|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1111 |Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1112
1113 **Features**
1114
1115 Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
1116
1117 [[image:07-5 Basic instructions_html_cbf13fc3d10fbe61.png]]
1118
1119 **Example**
1120
1121 When 45,325 seconds is specified in (s)
1122
1123 [[image:07-5 Basic instructions_html_d6045506b13275a0.png]]
1124
1125 **Error code**
1126
1127 |**Error code**|**Content**
1128 |4085H|When reading the specified device range exceeds the corresponding device range
1129 |4086H|When writing the specified device range exceeds the corresponding device range
1130 |4084H|When the value of (s) exceeds the range
1131
1132 **Example**
1133
1134 [[image:07-5 Basic instructions_html_e7dd49d953db6da4.png]]
1135
1136 Set D0 seconds to 2152537
1137
1138 The hour, minute and second of D10 after the M0 coil is turned on are
1139
1140 [[image:07-5 Basic instructions_html_10d57bde1ac0a218.png]]
1141
1142 {{id name="_Toc2937"/}}{{id name="_Toc24209"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TCMP/Clock data comparison**
1143
1144 **TCMP(P)**
1145
1146 Compare the comparison time specified in (s1), (s2), (s3) with the time data specified in (s4), and turn the bit device specified in (d) ON/OFF according to their size match.
1147
1148 -[TCMP (s1) (s2) (s3) (s4) (d)]
1149
1150 **Content, range and data type**
1151
1152 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1153 |(s1)|Specify the "hour" of the comparison base time.|0 to 23|Signed BIN 16 bit|ANY16
1154 |(s2)|Specify the "minute" of the comparison base time.|0 to 59|Signed BIN 16 bit|ANY16
1155 |(s3)|Specify the "second" of the comparison base time.|0 to 59|Signed BIN 16 bit|ANY16
1156 |(s4)|Specify the "hour" of the time data (hour, minute, second).|-|Signed BIN 16 bit|ANY16_ARRAY
1157 |(d)|The bit device is turned ON/OFF according to the comparison result.|-|Bit|ANYBIT_ARRAY
1158
1159 **Device used**
1160
1161 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1162 **Offset**
1163
1164 **modification**
1165 )))|(((
1166 **Pulse**
1167
1168 **extension**
1169 )))
1170 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1171 |(% rowspan="5" %)TCMP|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1172 |Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1173 |Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1174 |Parameter 4| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1175 |Parameter 5| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
1176
1177 **Features**
1178
1179 Compare the time of the reference time (hour, minute, second) [(s1), (s2), (s3)] with the time data (hour, minute, second) [(s4), (s4)+1, (s4) +2] Compare the size and turn on/off the 3 points from (d) according to the result of the same size.
1180
1181 [[image:07-5 Basic instructions_html_5df7ad3057fada12.png]]
1182
1183 ✎**Note**
1184
1185 The device specified in (s4) and (d) occupies 3 points. Be careful not to overlap with the device used for machine control.
1186
1187 When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
1188
1189 **Error code**
1190
1191 |**Error code**|**Content**
1192 |4085H|When reading the specified device range exceeds the corresponding device range
1193 |4086H|When writing the specified device range exceeds the corresponding device range
1194 |4084H|(((
1195 When the value specified in (s) and (s4) is not in the range of 0 to 23
1196
1197 {{id name="OLE_LINK355"/}}When the value specified in (s2),(s3) (s4)+1 and (s4)+2 is not in the range of 0 to 59
1198 )))
1199
1200 **Example**
1201
1202 [[image:07-5 Basic instructions_html_fcc16317cf7c0700.png]]
1203
1204 Set D10 to 1, D11 to 30, D12 to 0
1205
1206 When M0 is turned on, the time that D23 will come is 0:31:27
1207
1208 [[image:07-5 Basic instructions_html_de97dd7a612b2323.png]]
1209
1210 M10 is turned ON
1211
1212 [[image:07-5 Basic instructions_html_56e2d606adc09fd.png]]
1213
1214 {{id name="_Toc29031"/}}{{id name="_Toc22923"/}}**TZCP/Clock data bandwidth comparison**
1215
1216 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **TZCP(P)**
1217
1218 Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth.
1219
1220 -[TZCP (s1) (s2) (s3) (d)]
1221
1222 **Content, range and data type**
1223
1224 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1225 |(s1)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|(((
1226 ANY16_ARRAY
1227
1228 (number of elements: 3)
1229 )))
1230 |(s2)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|(((
1231 ANY16_ARRAY
1232
1233 (number of elements: 3)
1234 )))
1235 |(s3)|Specify "hour" of time data (hour, minute, second)|-|Signed BIN 16 bit|(((
1236 ANY16_ARRAY
1237
1238 (number of elements: 3)
1239 )))
1240 |(d)|The bit device is turned ON/OFF according to the comparison result.|-|Bit|(((
1241 ANY16_ARRAY
1242
1243 (number of elements: 3)
1244 )))
1245
1246 **Device used**
1247
1248 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1249 **Pulse**
1250
1251 **extension**
1252 )))
1253 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1254 |(% rowspan="4" %)TZCP|Parameter 1| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1255 |Parameter 2| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1256 |Parameter 3| | | | | | | | | | | | | | |●|●|●|●|●| | | | | |●|●
1257 |Parameter 4| |●|●|●|●| | | | |●| | | | | | | | | | | | | | |●|●
1258
1259 **Features**
1260
1261 Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth.
1262
1263 [[image:07-5 Basic instructions_html_844291270080313d.png]]
1264
1265 ✎**Note**
1266
1267 • The devices specified in (s1), (s2), (s3), (d) occupy 3 points. Be careful not to overlap with the device used for machine control.
1268
1269 • When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
1270
1271 • When (s1)> (s2), two of (d), (d)+1, (d)+2 are ON/OFF.
1272
1273 **Error code**
1274
1275 |**Error code**|**Content**
1276 |4085H|When reading the specified device range exceeds the corresponding device range
1277 |4086H|When writing the specified device range exceeds the corresponding device range
1278 |4084H|(((
1279 When the value specified in (s1), (s2) and (s3) is not in the range of 0 to 23
1280
1281 When the value specified in (s1)+1, (s2)+1, (s3)+1, (s1)+2, (s2)+2 and (s3)+2 is not in the range of 0 to 59
1282 )))
1283
1284 **Example**
1285
1286 [[image:07-5 Basic instructions_html_30027a2387c26c2e.png]]
1287
1288 Set D0 time to 16:30:00 and D10 time to 4:30:0
1289
1290 [[image:07-5 Basic instructions_html_c64e0faf2af172f8.png]]
1291
1292 [[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png]]
1293
1294 After the coil is turned on, the reading time to D20 time is 8:30:00
1295
1296 [[image:07-5 Basic instructions_html_75c44dad07eaf80a.png]]
1297
1298 M0/M12 is ON
1299
1300 [[image:07-5 Basic instructions_html_f512f36261705953.png]]
1301
1302 {{id name="_Toc6129"/}}[[image:07-5 Basic instructions_html_a2e3294e01b2f206.gif]] **7.13 Data control instructions**
1303
1304 {{id name="_Toc3339"/}}{{id name="_Toc27829"/}}{{id name="_Toc9204"/}}**BAND/BIN 16-bit data dead zone control**
1305
1306 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **BAND(P)**
1307
1308 The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2).
1309
1310 -[BAND (s1) (s2) (S3) (d)]
1311
1312 **Content, range and data type**
1313
1314 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1315 |(s1)|Lower limit of dead zone (no output zone)|-32,768 to +32,767|Signed BIN 16 bit|ANY16_S
1316 |(s2)|Upper limit of dead zone (no output zone)|-32,768 to +32,767|Signed BIN 16 bit|ANY16_S
1317 |(S3)|Input value controlled by dead zone control|-32768 to +32,767|Signed BIN 16 bit|ANY16_S
1318 |(D)|The start number of the device that stores the output value controlled by the dead zone control|-|Signed BIN 16 bit|ANY16_S
1319
1320 **Device used**
1321
1322 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1323 **Offset**
1324
1325 **modification**
1326 )))|(((
1327 **Pulse**
1328
1329 **extension**
1330 )))
1331 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1332 |(% rowspan="4" %)BAND|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1333 |Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1334 |Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1335 |Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1336
1337 **Features**
1338
1339 The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). The output value is controlled as follows.
1340
1341 |**Condition**|**The value stored in the output value**
1342 |When dead zone low limit (s1)> input value (s3)|Input value (s3)-Dead zone low limit (s1)
1343 |When dead zone high limit (s1) <input value (s3)|Input value (s3)- Dead zone high limit (s2)
1344 |When dead zone low limit (s1) ≤ input value (s3) ≤ dead zone low limit (s2)|0
1345
1346
1347 (((
1348 •When the output value stored in (d) is a signed BIN 16-bit value, and the operation result exceeds the range of -32768 to 32767, the situation is shown in the following example.
1349
1350 For example, when (s1) is 10 and (s3) is -32768,
1351
1352 the output value = -32768-10=8000H-000AH=7FFFH=32758.
1353
1354 [[image:07-5 Basic instructions_html_6850e21a76b813c0.png]]
1355 )))
1356
1357 **Error code**
1358
1359 |**Error code**|**Content**
1360 |4085H|When the specified device range for reading exceeds the range of the corresponding device.
1361 |4086H|When the specified device range for writing exceeds the range of the corresponding device.
1362 |4084H|When the low limit specified in (s1) is greater than the high limit specified in (s2).
1363
1364 **Example &nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;**
1365
1366 [[image:07-5 Basic instructions_html_c0e65cfeed403ecf.png]]
1367
1368 When X000 is ON, when D0<(-1,000), the value of ( D0)-(-1,000) is stored in (D1).
1369
1370 • When -1,000≦ D0≦1,000, 0 is stored in D1.
1371
1372 • When D0<1,000, the value of (D0)-1,000 is stored in D1.
1373
1374 {{id name="_Toc1180"/}}{{id name="_Toc21657"/}}{{id name="_Toc27323"/}}[[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DBAND/BIN 32-bit data dead zone control**
1375
1376 **DBAND(P)**
1377
1378 The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2).
1379
1380 -[DBAND (s1) (s2) (S3) (d)]
1381
1382 **Content, range and data type**
1383
1384 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1385 |(s1)|Dead zone low limit (no output zone)|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
1386 |(s2)|Dead zone high limit (no output zone)|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
1387 |(S3)|Input value controlled by dead zone control|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
1388 |(d)|The start number of the device that stores the output value controlled by the dead zone control|-|Signed BIN 32 bit|ANY32_S
1389
1390 **Device used**
1391
1392 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1393 **Pulse**
1394
1395 **extension**
1396 )))
1397 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1398 |(% rowspan="4" %)DBAND|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1399 |Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1400 |Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|●
1401 |Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
1402
1403 **Features**
1404
1405 The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limits of the dead zone specified in (s1) and (s2). The output value is controlled as follows.
1406
1407 |**Condition**|**The value stored in the output value**
1408 |When dead zone low limit ((s1), (s1)+1)> input value ((s3), (s3)+1)|{{id name="OLE_LINK42"/}}Input value ((s3), (s3)+1)-dead zone low limit ((s1), (s1)+1)
1409 |When dead zone high limit ((s1), (s1)+1) <input value ((s3), (s3)+1)|{{id name="OLE_LINK357"/}}Input value ((s3), (s3)+1)-dead zone high limit ((s2), (s2)+1)
1410 |When dead zone low limit ((s1), (s1)+1) ≤ input value ((s3), (s3)+1) ≤ dead zone high limit ((s2), (s2)+1)|0
1411
1412
1413 (((
1414 • When the output value stored in (d) is a signed BIN 32-bit value, and the operation result exceeds the range of -2,147,483,648 to 2,147,483,647, the situation is as the following example. For example,** &nbsp;**When (s1) and (s1)+1 are 1000, (s3) and (s3)+1 are -2,147,483,648, then the output value=
1415
1416 -2,147,483,648-1000=80000000H-000003E8H=7FFFFC18H=2,147,482,648.
1417
1418 [[image:07-5 Basic instructions_html_e0144674dad3e8fd.png]]
1419
1420
1421
1422 )))
1423
1424 **Error code**
1425
1426 |**Error code**|**Content**
1427 |4085H|When the specified device range for reading exceeds the range of the corresponding device.
1428 |4086H|When the specified device range for writing exceeds the range of the corresponding device.
1429 |4084H|When the low limit specified in (s1) is greater than the high limit specified in (s2).
1430
1431 **Example**
1432
1433 [[image:07-5 Basic instructions_html_88f3fe0fb4841bab.png]]
1434
1435 • When (D1, D0)<(-10,000), the value of (D1, D0)-(-10,000) is stored in (D11, D10).
1436
1437 • When -10,000≦(D1, D0)≦10,000, 0 is stored in (D11, D10).
1438
1439 • When 10,000< (D1, D0), the value of (D1, D0)-10,000 is stored in D1.
1440
1441 {{id name="_Toc21668"/}}{{id name="_Toc25056"/}}{{id name="_Toc17582"/}}{{id name="OLE_LINK165"/}}**BINDA/BIN 16-bit data → Decimal ASCII conversion**
1442
1443 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **BINDA(P)**
1444
1445 Convert the BIN 16-bit data specified in (s) and the value of each digit in decimal numbers into ASCII codes and store them after the device number specified in (d).
1446
1447 -[BINDA(s)(d)]
1448
1449 **Content, range and data type**
1450
1451 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1452 |(s)|BIN data for ASCII conversion|-32768 to +32767|Signed BIN 16 bit|ANY16_S
1453 |(d)|The start number of the device storing the conversion result|-|String|ANYSTRING_SINGLE
1454
1455 **Device used**
1456
1457 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1458 **Pulse**
1459
1460 **extension**
1461 )))
1462 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1463 |(% rowspan="2" %)BINDA|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1464 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1465
1466 **Features**
1467
1468 Convert the BIN 16-bit data specified in (s) and the value of each digit in decimal numbers into ASCII codes and store them after the device number specified in (d).
1469
1470
1471
1472 (((
1473 ←Only store 0 when SM191 is OFF
1474
1475 [[image:07-5 Basic instructions_html_57bda5f08026449d.png]]
1476 )))
1477
1478 For example, when -12,345 is specified in (s) (in the case of specifying signed)
1479
1480 [[image:07-5 Basic instructions_html_f346102467b9bef9.png]]
1481
1482 The calculation result stored in (d) will be as below.
1483
1484 • In "Sign", 20H is stored when the BIN data is positive, and 2DH is stored when it is negative.
1485
1486 • In the 0 to the left of the effective digit, 20H is stored. (Suppress 0.) For example, in the case of "00325", "00" becomes 20H, and "325" becomes the effective digit.
1487
1488 • When storing data to the device specified in (d)+3, when SM191 (output character number switching signal) is OFF, 0 is stored, and it does not change when it is ON.
1489
1490 ✎**Note: **The number of occupied points of (d) is 3 when SM191 is ON, and it is 4 when SM191 is OFF.
1491
1492 **Error code**
1493
1494 |**Error code**|**Content**
1495 |4085H|The read address of (s) exceeds the device range.
1496 |4086H|The write address of (d) exceeds the device range.
1497
1498 **Example**
1499
1500
1501
1502 (((
1503 When X000 is ON, convert the value of 16-bit data (BIN) D1000 into decimal ASCII code, and then use PR instruction to output the
1504
1505 converted ASCII code character by character to the program of Y040 to Y057.
1506
1507 [[image:07-5 Basic instructions_html_c598806a42484ed.png]]
1508 )))
1509
1510 {{id name="_Toc12255"/}}{{id name="_Toc8216"/}}{{id name="_Toc470"/}}**DBINDA/BIN 32-bit data → Decimal ASCII conversion**
1511
1512 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DBINDA(P)**
1513
1514 Convert the BIN 32-bit data specified in (s) and the value of each bit in decimal numbers into ASCII codes and store them after the device number specified in (d).
1515
1516 -[DBINDA(s)(d)]
1517
1518 **Content, range and data type**
1519
1520 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1521 |(s)|BIN data for ASCII conversion|-2,147483648 to 2147483647|Signed BIN 32 bit|ANY32_S
1522 |(d)|{{id name="OLE_LINK2"/}}The start number of the device storing the conversion result|-|String|ANYSTRING_SINGLE
1523
1524 **Device used**
1525
1526 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|(((
1527 **Offset**
1528
1529 **modification**
1530 )))|(((
1531 **Pulse**
1532
1533 **extension**
1534 )))
1535 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1536 |(% rowspan="2" %)DBINDA|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1537 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1538
1539 **Features**
1540
1541 Convert the BIN 32-bit data specified in (s) and the value of each bit when expressed in decimal numbers into ASCII codes, and store them after the device number specified in (d).
1542
1543 For example, when -12345678 is specified in (s). (in the case of specifying signed)
1544
1545 [[image:07-5 Basic instructions_html_4d939462838cf09b.gif]] The calculation result stored in (d) will be as below.
1546
1547 • In "Sign", 20H is stored when the BIN data is positive, and 2DH is stored when it is negative.
1548
1549 • 20H is stored at 0 to the left of the effective number of digits. (Suppress 0.) For example, in the case of "0012034560", "00" becomes 20H, and "12034560" becomes effective digits.
1550
1551 • For the data stored in the upper 8 bits of the device specified in (d)+5, 0 will be stored when SM191 (output character switching signal) is OFF, and 20H will be stored when it is ON.
1552
1553 ✎**Note: **(d) Occupies 6 points.
1554
1555 **Error code**
1556
1557 |**Error code**|**Content**
1558 |4085H|(s) read address exceeds the device range
1559 |4086H|(d) write address exceeds the device range
1560
1561 **Example**
1562
1563 [[image:07-5 Basic instructions_html_ec8ac32d748a991c.png]]
1564
1565 When X000 is ON, convert the value of 32-bit data (BIN) D1000 into decimal ASCII code, and then use PR (FNC 77) instruction to output the converted ASCII code character by character to the program in Y040 to Y051 in time and time division.
1566
1567 {{id name="_Toc19693"/}}{{id name="_Toc18078"/}}{{id name="_Toc5726"/}}**DABIN/Decimal ASCII → BIN conversion**
1568
1569 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DABIN(P)**
1570
1571 Digital ASCII code (30H to 39H) is a instruction to convert real data into BIN data.
1572
1573 -[DABIN (s) (d)]
1574
1575 **Content, range and data type**
1576
1577 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1578 |(s)|The start number of the device that stores the data (ASCII code) to be converted into a BIN value|-|String|ANYSTRING_SINGLE
1579 |(d)|The device number for storing conversion result|-|BIN16 bit|ANY16_S
1580
1581 **Device used**
1582
1583 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1584 **Pulse**
1585
1586 **extension**
1587 )))
1588 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1589 |(% rowspan="2" %)DABIN|Parameter 1| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1590 |Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1591
1592 **Features**
1593
1594 The decimal ASCII data stored after the device number specified in (s) is converted into BIN 16-bit data and stored in the device specified in (d).
1595
1596 [[image:07-5 Basic instructions_html_22c5cb32a0a32214.png]]
1597
1598 |**ASCII S**|**ASCII 10^^0^^**|**ASCII 10^^1^^**|**ASCII 10^^2^^**|**ASCII 10^^3^^**|**ASCII 10^^4^^**
1599 |**ASCII code**|(((
1600 {{id name="OLE_LINK36"/}}Units of
1601
1602 ASCII code
1603 )))|(((
1604 Tens of
1605
1606 ASCII code
1607 )))|(((
1608 Hundreds of
1609
1610 ASCII code
1611 )))|(((
1612 Thousands of
1613
1614 ASCII code
1615 )))|(((
1616 Ten thousands
1617
1618 of ASCII code
1619 )))
1620
1621 For example, When -25,108 is specified in (s)
1622
1623 [[image:07-5 Basic instructions_html_10fb2792e37dbf23.png]]
1624
1625 • The ASCII data specified in (s) to (s)+2 is within the range of -32,768 to +32,767.
1626
1627 • In “Sign”, set 20H when the converted data is positive, and set 2DH when it is negative. (When other than 20H or 2DH is set, it will be treated as positive data. (DABIN(P))
1628
1629 • The range of the ASCII code set in each digit is 30H to 39H.
1630
1631 • When the ASCII code set in each bit is 20H or 00H, it will be treated as 30H.
1632
1633 **Error code**
1634
1635 |**Error code**|**Content**
1636 |4084H|(((
1637 When the Sign data exceeds the range of 30H to 39H, 20H, 00H, 2DH;
1638
1639 When the ASCII code of each bit specified in (s) to (s)+2 exceeds the range of 30H to 39H, 20H, 00H;
1640
1641 When the ASCII data specified in (s) to (s)+2 is other than -32,768 to +32,767.
1642 )))
1643 |4085H|The read address of (s) exceeds the device range.
1644 |4086H|The write address of (d) exceeds the device range.
1645
1646
1647 (((
1648 When X000 is ON, the Signs set in D20 to D22 and the ASCII code data of 5-digit decimal numbers are converted into BIN values, and then stored in the program of D0.
1649
1650 **Example**
1651 )))
1652
1653 [[image:07-5 Basic instructions_html_bec2bea131b58c03.png]]
1654
1655 {{id name="_Toc3351"/}}{{id name="_Toc26383"/}}{{id name="_Toc26233"/}}**DDABIN/Decimal ASCII → BIN32-bit data conversion**
1656
1657 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DDABIN(P)**
1658
1659 The decimal ASCII data stored after the device number specified in (s) is converted into BIN 32-bit data and stored in the device number specified in (d).
1660
1661 -[DDABIN (s) (d) ]
1662
1663 **Content, range and data type**
1664
1665 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1666 |(s)|The start number of the device that stores data (ASCII code) to be converted into a BIN value|-|String|ANYSTRING_SINGLE
1667 |(d)|The device number for storing conversion result|-|Signed BIN 32 bit|ANY32_S
1668
1669 **Device used**
1670
1671 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1672 **Pulse**
1673
1674 **extension**
1675 )))
1676 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1677 |(% rowspan="2" %)DDABIN|Parameter 1| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1678 |Parameter 2| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
1679
1680 **Features**
1681
1682 The decimal ASCII data stored after the device number specified in (s) is converted into BIN 32-bit data and stored in the device specified in (d).
1683
1684 [[image:07-5 Basic instructions_html_c444110b273f33b7.gif]]
1685
1686 |**ASCII S**|**ASCII code**|**ASCII S**|**ASCII code**
1687 |ASCII 10^^0^^|Units of ASCII code|ASCII 10^^5^^|{{id name="OLE_LINK38"/}}Hundred thousands of ASCII code
1688 |ASCII 10^^1^^|Tens of ASCII code|ASCII 10^^6^^|Millions of ASCII code
1689 |ASCII 10^^2^^|Hundreds of ASCII code|ASCII 10^^7^^|Ten millions of ASCII code
1690 |ASCII 10^^3^^|{{id name="OLE_LINK37"/}}Thousands of ASCII code|ASCII 10^^8^^|Hundred millions of ASCII code
1691 |ASCII 10^^4^^|Tens thousands of ASCII code|ASCII 10^^9^^|billions of ASCII code
1692
1693 When -1234543210 is specified in (s) (When signed is specified)
1694
1695 [[image:07-5 Basic instructions_html_1b4c7e1c663a4399.png]]
1696
1697 • The ASCII data specified in (s) to (s)+5 is within the range of -2,147,483,648 to +2,147,483,647. In addition, the data stored in the high byte of (s)+5 will be ignored.
1698
1699 • In the Sign data, set 20H when the converted data is positive, and set 2DH when it is negative. (When other than 20H or 2DH is set, it will be treated as positive data. (DABIN(P))
1700
1701 • The range of ASCII code set in each digit is 30H to 39H.
1702
1703 • When the ASCII code set in each bit is 20H or 00H, it will be treated as 30H.
1704
1705 **Error code**
1706
1707 |**Error code**|**Content**
1708 |4084H|(((
1709 When the Sign data exceeds the range of 30H to 39H, 20H, 00H and 2DH;
1710
1711 {{id name="OLE_LINK39"/}}When the ASCII code of each bit specified in (s) to (s)+5 exceeds the range of 30H to 39H, 20H and 00H;
1712
1713 When the ASCII data specified in (s) to (s)+5 exceeds the range of -2,147,483,648 to +2,147,483,647
1714 )))
1715 |4085H|The read address of (s) exceeds the device range.
1716 |4086H|The write address of (d) exceeds the device range.
1717
1718 **Example**
1719
1720 [[image:07-5 Basic instructions_html_feea438c943ea9dd.png]]
1721
1722 When X000 is ON, the Signs set in to D20 to D25 and the ASCII code data of 10-digit decimal numbers are converted into BIN values and then saved to the program in D0 to D1.
1723
1724 {{id name="_Toc26556"/}}{{id name="_Toc12799"/}}{{id name="_Toc23863"/}}**LIMIT/ BIN 16-bit data high and low limit control**
1725
1726 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **LIMIT(P)**
1727
1728 The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the upper and lower limit value ranges specified in (s1) and (s2).
1729
1730 -[LIMIT (s1) (s2) (s3) (d)]
1731
1732 **Content, range and data type**
1733
1734 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1735 |s1|Low limit value (minimum output limit value)|-32,768 to 32,767|BIN16 bit|ANY16_S
1736 |s2|High limit value (maximum output limit value)|-32,768 to 32,767|BIN16 bit|ANY16_S
1737 |s3|Input value controlled by high and low limit control|-32,768 to 32,767|BIN16 bit|ANY16_S
1738 |d|The start number of device that stores the output value controlled by high and low limit control|-|BIN16 bit|ANY16_S
1739
1740 **Device used**
1741
1742 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1743 **Pulse**
1744
1745 **extension**
1746 )))
1747 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1748 |(% rowspan="4" %)LIMIT|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1749 |Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1750 |Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
1751 |Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1752
1753 **Features**
1754
1755 The input value (BIN 16-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the high and low limit value ranges specified in (s1) and (s2). The output value is controlled as follows.
1756
1757 |**Condition**|**The value stored in the output value**
1758 |Low limit value (s1)>input value (s3)|Low limit value (s1)
1759 |High limit value (s1) <input value (s3)|High limit value (s2)
1760 |Low limit value (s1) ≤ input value (s3) ≤ high limit value (s2)|Input value (s3)
1761
1762
1763 (((
1764 •Only in the case of controlling high limit value, set the minimum value of data range in the low limit value specified in (s1).
1765
1766 • Only in the case of controlling low limit value, set the maximum value of data range in the high limit value specified in (s2).
1767
1768 [[image:07-5 Basic instructions_html_50eb5229b027aa14.png]]
1769 )))
1770
1771 **Error code**
1772
1773 |**Error code**|**Content**
1774 |4085H|The read address exceeds the device range
1775 |4086H|The write address exceeds the device range
1776 |4084H|High limit <low limit
1777
1778 **Example**
1779
1780 [[image:07-5 Basic instructions_html_d67a2e740d4fc738.png]]
1781
1782 When X000 is ON
1783
1784 • When D0 <500, D1 is 500.
1785
1786 • When 500 ≤ D0 ≤ 5,000, D1 is the value of D0.
1787
1788 • When 5,000 <D0, D1 is 5,000.
1789
1790 {{id name="_Toc32553"/}}{{id name="_Toc9981"/}}{{id name="_Toc9158"/}}**DLIMIT/BIN 32-bit data high and low limit control**
1791
1792 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DLIMIT(P)**
1793
1794 The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the range of high and low limit values specified in (s1) and (s2).
1795
1796 -[DLIMIT (s1) (s2) (s3) (d)]
1797
1798 **Content, range and data type**
1799
1800 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1801 |s1|Low limit value (minimum output limit value)|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S
1802 |s2|High limit value (maximum output limit value)|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S
1803 |s3|Input value controlled by high and low limit control|-2,147,483,648 to 2,147,483,647|BIN32 bit|ANY32_S
1804 |d|The start number of the device that stores the output value controlled by high and low limit control|-|BIN32 bit|ANY32_S
1805
1806 **Device used**
1807
1808 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1809 **Pulse**
1810
1811 **extension**
1812 )))
1813 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1814 |(% rowspan="4" %)DLIMIT|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1815 |Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1816 |Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|●
1817 |Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
1818
1819 **Features**
1820
1821 The input value (BIN 32-bit value) specified in (s3) controls the output value stored in the device specified in (d) according to the range of high and low limit values specified in (s1) and (s2). The output value is controlled as follows.
1822
1823 |**Condition**|**The value stored in the output value**
1824 |Low limit value ((s1), (s1)+1)> input value ((s3), (s3)+1)|Low limit value ((s1), (s1)+1)
1825 |High limit value ((s2), (s2)+1) <input value ((s3), (s3)+1)|High limit value ((s2), (s2)+1)
1826 |Low limit value ((s1), (s1)+1) ≤ input value ((s3), (s3)+1) ≤ high limit value ((s2), (s2)+1)|Input value ((s3), (s3)+1)
1827
1828 {{id name="OLE_LINK43"/}}{{id name="OLE_LINK40"/}}•Only in the case of controlling high limit value, set the minimum value of data range in the low limit value specified in (s1).
1829
1830 • Only in the case of controlling low limit value, set the maximum value of data range in the high limit value specified in (s2).
1831
1832 **Error code**
1833
1834 |**Error code**|**Content**
1835 |4085H|The read address exceeds the device range
1836 |4086H|The write address exceeds the device range
1837 |4084H|High limit <low limit
1838
1839 **Example**
1840
1841 [[image:07-5 Basic instructions_html_217355b90f4b4e16.png]]
1842
1843 Operation:
1844
1845 • When (D1, D0) <10,000, (D11, D10) is 10,000.
1846
1847 • When 10,000 ≤ (D1, D0) ≤ 1,000,000, (D11, D10) is the value of (D1, D0).
1848
1849 • When 1,000,000 <(D1, D0), (D11, D10) is 1,000,000.
1850
1851 {{id name="_Toc12534"/}}{{id name="_Toc28213"/}}{{id name="_Toc24591"/}}**SCL/BIN 16-bit unit scale (coordinate data of each point)**
1852
1853 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **SCL(P)**
1854
1855 The scaling conversion data (16-bit data unit) specified in (s2) is scaled from the input value specified in (s1), and the calculation result is stored in the device specified in (d).
1856
1857 -[SCL (s1) (s2) (d)]
1858
1859 **Content, range and data type**
1860
1861 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1862 |(s1)|The input value for scaling or the start number of device storing the input value|-32,768 to 32,767|Signed BIN 16 bit|ANY16_S
1863 |(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 16 bit|ANY16_S
1864 |(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 16 bit|ANY16_S
1865
1866 **Device used**
1867
1868 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
1869 **Pulse**
1870
1871 **extension**
1872 )))
1873 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1874 |(% rowspan="3" %)SCL|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
1875 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1876 |Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
1877
1878 **Features**
1879
1880 For the scale conversion data (16-bit data unit) specified in (s2), scale by the input value specified in (s1), and store the operation result in the device specified in (d). Scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
1881
1882 |(% colspan="2" %)**Setting items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
1883 |(% colspan="2" %)Coordinate points|(s2)
1884 |(% rowspan="2" %)Point 1|X coordinate|(s2)+1
1885 |Y coordinate|(s2)+2
1886 |(% rowspan="2" %)Point 2|X coordinate|(s2)+3
1887 |Y coordinate|(s2)+4
1888 |(% colspan="3" %)........
1889 |(% rowspan="2" %)Point n|X coordinate|(s2)+2n-1
1890 |Y coordinate|(s2)+2n
1891
1892 [[image:07-5 Basic instructions_html_80185ccddb878234.png]]
1893
1894 • If the operation result is not an integer value, round the first digit below the decimal point.
1895
1896 • The X coordinate data of the conversion data for scaling should be set in ascending order.
1897
1898 • (s1) should be set within the range of conversion data for scaling (device value of (s2)).
1899
1900 • If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
1901
1902 • Set the number of coordinate points of the conversion data for scaling within the range of 1 to 32,767.
1903
1904 • Setting example of conversion table for scaling.
1905
1906 In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
1907
1908 [[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
1909
1910 |(% colspan="2" rowspan="2" %)**Set &nbsp;&nbsp;&nbsp;&nbsp;items**|(% colspan="3" %)**Sett &nbsp;&nbsp;&nbsp;&nbsp;device and content**|(% rowspan="2" %)**Remarks**
1911 |(% colspan="2" %)**When R0 is specified in (s2)**|**Set &nbsp;&nbsp;&nbsp;&nbsp;content**
1912 |(% colspan="2" %)Coordinate points|(s2)|R0|K10|
1913 |(% rowspan="2" %)Point 1|X coordinate|(s2)+1|R1|K5|
1914 |Y coordinate|(s2)+2|R2|K20|
1915 |(% rowspan="2" %)Point 2|X coordinate|(s2)+3|R3|K30|
1916 |Y coordinate|(s2)+4|R4|K50|
1917 |(% rowspan="2" %)Point 3|X coordinate|(s2)+5|R5|K100|
1918 |Y coordinate|(s2)+6|R6|K200|
1919 |(% rowspan="2" %)Point 4|X coordinate|(s2)+7|R7|K25|(% rowspan="6" %)(((
1920 If the coordinates are specified by 3 points, the intermediate value could be the output value.
1921
1922 In this example, the output value (median value) is specified by the Y coordinate of point 5.
1923
1924 When the X coordinate is the same at 3 points or more, the value of the 2nd point is also output.
1925 )))
1926 |Y coordinate|(s2)+8|R8|K200
1927 |(% rowspan="2" %)Point 5|X coordinate|(s2)+9|R9|K70
1928 |Y coordinate|(s2)+10|R10|K200
1929 |(% rowspan="2" %)Point 6|X coordinate|(s2)+11|R11|K250
1930 |Y coordinate|(s2)+12|R12|K250
1931 |(% rowspan="2" %)Point 7|X coordinate|(s2)+13|R13|K250|
1932 |Y coordinate|(s2)+14|R14|K90|
1933 |(% rowspan="2" %)Point 8|X coordinate|(s2)+15|R15|K350|(% rowspan="4" %)(((
1934 If the coordinates are specified by two points, the output value is the value of the Y coordinate of the next point.
1935
1936 In this example, the output value is specified by the Y coordinate of point 9.
1937 )))
1938 |Y coordinate|(s2)+16|R16|K90
1939 |(% rowspan="2" %)Point 9|X coordinate|(s2)+17|R17|K350
1940 |Y coordinate|(s2)+18|R18|K30
1941 |(% rowspan="2" %)Point 10|X coordinate|(s2)+19|R19|K400|
1942 |Y coordinate|(s2)+20|R20|K7|
1943
1944 **Error code**
1945
1946 |**Error code**|**Content**
1947 |4085H|When the specified device range for reading exceeds the range of the corresponding device.
1948 |4086H|When the specified device range for writing exceeds the range of the corresponding device.
1949 |4084H|(((
1950 When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
1951
1952 When the input value specified in (s1) exceeds the range of the set scale conversion data;
1953
1954 When the number of start coordinate points of device (s2) is less than 0.
1955 )))
1956
1957 **Example**
1958
1959 [[image:07-5 Basic instructions_html_5519d7b41f15b6d6.png]]
1960
1961 [[image:07-5 Basic instructions_html_ace075fb7675de8e.gif]] When -100 ≤ D0(X) < 0, D100(Y)=
1962
1963 [[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] when D0(X)=0, D100(Y)=0;
1964
1965 when 0< D0(X) ≤ 100, D100(Y)=
1966
1967 [[image:07-5 Basic instructions_html_e35e13160c08a133.png]]
1968
1969
1970
1971 {{id name="_Toc4862"/}}{{id name="_Toc11340"/}}{{id name="_Toc25383"/}}**DSCL/32-bit unit scale (coordinate data of each point)**
1972
1973 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSCL(P)**
1974
1975 The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d).
1976
1977 -[DSCL (s1) (s2) (d)]
1978
1979 **Content, range and data type**
1980
1981 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
1982 |(s1)|The input value for scaling or the start number of the device storing the input value|-2,147,483,648 to 2,147,483,647|Signed BIN 32 bit|ANY32_S
1983 |(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 32 bit|ANY32_S
1984 |(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 32 bit|ANY32_S
1985
1986 **Device used**
1987
1988 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Device**|**Offset modification**|(((
1989 **Pulse**
1990
1991 **extension**
1992 )))
1993 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1994 |(% rowspan="3" %)DSCL|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
1995 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
1996 |Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
1997
1998 **Features**
1999
2000 {{id name="OLE_LINK41"/}}The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
2001
2002 |(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
2003 |(% colspan="2" %)Coordinate points|(s2)+1, (s2)
2004 |(% rowspan="2" %)Point 1|X coordinate|(s2)+3, (s2)+2
2005 |Y coordinate|(s2)+5, (s2)+4
2006 |(% rowspan="2" %)Point 2|X coordinate|(s2)+7, (s2)+6
2007 |Y coordinate|(s2)+9, (s2)+8
2008 |(% colspan="3" %)........
2009 |(% rowspan="2" %)Point n|X coordinate|(s2)+4n-1, (s2)+4n-2
2010 |Y coordinate|(s2)+4n+1, (s2)+4n
2011
2012 [[image:07-5 Basic instructions_html_6633ca18cee1218c.png]]
2013
2014 • If the calculation result is not an integer value, round the first digit below the decimal point.
2015
2016 • The X coordinate data of the conversion data for scaling should be set in ascending order.
2017
2018 • For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value).
2019
2020 • If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
2021
2022 • Set the number of coordinate points of conversion data for scaling within the range of 1 to 2,147,483,647.
2023
2024 • Setting example of conversion table for scaling.
2025
2026 In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
2027
2028 [[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
2029
2030 |(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Set &nbsp;&nbsp;&nbsp;&nbsp;device and content**|(% rowspan="2" %)**Remarks**
2031 |(% colspan="2" %)**When R0 is specified in (s2)**|**Set &nbsp;&nbsp;&nbsp;&nbsp;content**
2032 |(% colspan="2" %)Coordinate points|(s2)+1, (s2)|R1, R0|K10|
2033 |(% rowspan="2" %)Point 1|X coordinate|(s2)+3, (s2)+2|R3, R2|K5|
2034 |Y coordinate|(s2)+5, (s2)+4|R5, R4|K7|
2035 |(% rowspan="2" %)Point 2|X coordinate|(s2)+7, (s2)+6|R7, R6|K20|
2036 |Y coordinate|(s2)+9, (s2)+8|R9, R8|K30|
2037 |(% rowspan="2" %)Point 3|X coordinate|(s2)+11, (s2)+10|R10, R11|K50|
2038 |Y coordinate|(s2)+13, (s2)+12|R13, R12|K100|
2039 |(% rowspan="2" %)Point 4|X coordinate|(s2)+15, (s2)+14|R15, R14|K200|(% rowspan="6" %)(((
2040 if the coordinates are specified by 3 points, the intermediate value could be the output value.
2041
2042 In this example, the output value (median value) is specified by the Y coordinate of point 5.
2043
2044 When the X coordinate is the same at 3 points or more, the value of the 2nd point is also output.
2045 )))
2046 |Y coordinate|(s2)+17, (s2)+16|R17, R16|K25
2047 |(% rowspan="2" %)Point 5|X coordinate|(s2)+19, (s2)+18|R19, R18|K200
2048 |Y coordinate|(s2)+21, (s2)+20|R21, R20|K70
2049 |(% rowspan="2" %)Point 6|X coordinate|(s2)+23, (s2)+22|R23, R22|K200
2050 |Y coordinate|(s2)+25, (s2)+24|R25, R24|K250
2051 |(% rowspan="2" %)Point 7|X coordinate|(s2)+27, (s2)+26|R27, R26|K250|
2052 |Y coordinate|(s2)+29, (s2)+28|R29, R28|K90|
2053 |(% rowspan="2" %)Point 8|X coordinate|(s2)+31, (s2)+30|R31, R30|K350|(% rowspan="4" %)(((
2054 If the coordinates are specified by two points, the output value is the value of the Y coordinate of the next point.
2055
2056 In this example, the output value is specified by the Y coordinate of point 9.
2057 )))
2058 |Y coordinate|(s2)+33, (s2)+32|R33, R32|K90
2059 |(% rowspan="2" %)Point 9|X coordinate|(s2)+35, (s2)+34|R35, R34|K350
2060 |Y coordinate|(s2)+37, (s2)+36|R37, R36|K30
2061 |(% rowspan="2" %)Point 10|X coordinate|(s2)+39, (s2)+38|R39, R38|K400|
2062 |Y coordinate|(s2)+41, (s2)+40|R41, R40|K7|
2063
2064 **Error code**
2065
2066 |**Error code**|**Content**
2067 |4085H|When the specified device range for reading exceeds the range of the corresponding device.
2068 |4086H|When the specified device range for writing exceeds the range of the corresponding device.
2069 |4084H|(((
2070 When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
2071
2072 When the input value specified in (s1) exceeds the range of the set scale conversion data;
2073
2074 When the number of start coordinate points of device (s2) is less than 0.
2075 )))
2076
2077 **Example**
2078
2079 [[image:07-5 Basic instructions_html_ba95b2d50d8d1d3e.png]]
2080
2081 [[image:07-5 Basic instructions_html_1de79c7d87d51f78.gif]] When -100 ≤ D0(X) < 0, D100(Y)=
2082
2083 [[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] When D0(X)=0, D100(Y)=0;
2084
2085 When 0 < D0(X) ≤ 100, D100(Y)=
2086
2087 [[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]]
2088
2089 {{id name="_Toc3776"/}}{{id name="_Toc11170"/}}{{id name="_Toc2957"/}}**SCL2/BIN 16-bit unit scale (X/Y coordinate data)**
2090
2091 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **SCL2(P)**
2092
2093 The conversion data (16-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d).
2094
2095 -[SCL2 (s1) (s2) (d)]
2096
2097 **Content, range and data type**
2098
2099 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2100 |(s1)|The input value for scaling or the start number of the device storing the input value|-32,768 to 32,767|Signed BIN 16 bit|ANY16_S
2101 |(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 16 bit|ANY16_S
2102 |(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 16 bit|ANY16_S
2103
2104 **Device used**
2105
2106 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2107 **Pulse**
2108
2109 **extension**
2110 )))
2111 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2112 |(% rowspan="3" %)SCL2|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
2113 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
2114 |Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
2115
2116 **Features**
2117
2118 The conversion data (16-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
2119
2120 |(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
2121 |(% colspan="2" %)Coordinate points|(s2)
2122 |(% rowspan="4" %)X coordinate|Point 1|(s2)+1
2123 |Point 2|(s2)+2
2124 |.....|......
2125 |Point n|(s2)+n
2126 |(% rowspan="4" %)Y coordinate|Point 1|(s2)+n+1
2127 |Point 2|(s2)+n+2
2128 |.....|.....
2129 |Point n|(s2)+2n
2130
2131 [[image:07-5 Basic instructions_html_80185ccddb878234.png]]
2132
2133 • If the operation result is not an integer value, round the first digit below the decimal point.
2134
2135 • The X coordinate data of the conversion data for scaling should be set in ascending order.
2136
2137 • For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value).
2138
2139 • If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
2140
2141 • Set the number of coordinate points of conversion data for scaling within the range of 1 to 32,767.
2142
2143 • Setting example of conversion table for scaling.
2144
2145 In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
2146
2147 [[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
2148
2149 |(% colspan="2" rowspan="2" %)**Set items**|(% colspan="3" %)**Set device and content**|(% rowspan="2" %)**Remarks**
2150 |(% colspan="2" %)**When R0 is specified in (s2)**|**Set content**
2151 |(% colspan="2" %)Coordinate points|(s2)|R0|K10|
2152 |(% rowspan="10" %)X coordinate|Point 1|(s2)+1|R1|K5|
2153 |Point 2|(s2)+2|R2|K20|
2154 |Point 3|(s2)+3|R3|K50|
2155 |Point 4|(s2)+4|R4|K200|(% rowspan="3" %)Refer to** ✎1**
2156 |Point 5|(s2)+5|R5|K200
2157 |Point 6|(s2)+6|R6|K200
2158 |Point 7|(s2)+7|R7|K250|
2159 |Point 8|(s2)+8|R8|K350|(% rowspan="2" %)Refer to** ✎2**
2160 |Point 9|(s2)+9|R9|K350
2161 |Point 10|(s2)+10|R10|K400|
2162 |(% rowspan="10" %)Y coordinate|Point 1|(s2)+11|R11|K7|
2163 |Point 2|(s2)+12|R12|K30|
2164 |Point 3|(s2)+13|R13|K100|
2165 |Point 4|(s2)+14|R14|K25|(% rowspan="3" %)Refer to**✎1**
2166 |Point 5|(s2)+15|R15|K70
2167 |Point 6|(s2)+16|R16|K250
2168 |Point 7|(s2)+17|R17|K90|
2169 |Point 8|(s2)+18|R18|K90|(% rowspan="2" %)Refer to** ✎2**
2170 |Point 9|(s2)+19|R19|K30
2171 |Point 10|(s2)+20|R20|K7|
2172
2173 ✎**1** Like points 4, 5, and 6, if the coordinates are specified by 3 points, the intermediate value could be the output value.
2174
2175 In this example, the output value (median value) is specified by the Y coordinate of point 5.
2176
2177 When the X coordinate is the same at 3 or more points, the value of the second point is also output.
2178
2179 ✎**2** Like points 8 and 9, if the coordinates are specified by 2 points, the output value is the value of the Y coordinate of next point.
2180
2181 In this example, the output value is specified by the Y coordinate of point 9.
2182
2183 **Error code**
2184
2185 |**Error code**|**Content**
2186 |4085H|When the specified device range for reading exceeds the range of the corresponding device.
2187 |4086H|When the specified device range for writing exceeds the range of the corresponding device.
2188 |4084H|(((
2189 When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
2190
2191 When the input value specified in (s1) exceeds the range of the set scale conversion data;
2192
2193 When the number of start coordinate points of device (s2) is less than 0.
2194 )))
2195
2196 **Example**
2197
2198 [[image:07-5 Basic instructions_html_ace075fb7675de8e.gif]] [[image:07-5 Basic instructions_html_de529c9a16a62ef0.png]]
2199
2200 When -100 ≤D0 (X) < 0, D100(Y)=
2201
2202 [[image:07-5 Basic instructions_html_9acd6306c6d91847.gif]] when D0(X)=0, D100(Y)=0;
2203
2204 when 0 < D0(X) ≤ 100, D100(Y)=
2205
2206 [[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]]
2207
2208 {{id name="_Toc5608"/}}{{id name="_Toc1756"/}}{{id name="_Toc21402"/}}**DSCL2/BIN 32-bit unit scale (X/Y coordinate data)**
2209
2210 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **DSCL2(P)**
2211
2212 The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device specified in (d).
2213
2214 -[DSCL2 (s1) (s2) (d)]
2215
2216 **Content, range and data type**
2217
2218 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2219 |(s1)|The input value for scaling or the start number of the device storing the input value|-2,147,483,648 to +2,147,483,647|Signed BIN 32 bit|ANY32_S
2220 |(s2)|The start number of the device storing conversion data for scaling|-|Signed BIN 32 bit|ANY32_S
2221 |(d)|The start number of the device that stores the output value controlled by scaling|-|Signed BIN 32 bit|ANY32_S
2222
2223 **Device used**
2224
2225 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2226 **Pulse**
2227
2228 **extension**
2229 )))
2230 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2231 |(% rowspan="3" %)DSCL2|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
2232 |Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | |●|●
2233 |Parameter 3| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
2234
2235 **Features**
2236
2237 The conversion data (32-bit data unit) for scaling specified in (s2) is scaled by the input value specified in (s1), and the operation result is stored in the device number specified in (d). The scale conversion is performed based on the scale conversion data stored after the device specified in (s2).
2238
2239 |(% colspan="2" %)**Set items (n represents the number of coordinate points specified in (s2))**|**Device allocation**
2240 |(% colspan="2" %)Coordinate points|(s2)+1, (s2)
2241 |(% rowspan="4" %)X coordinate|Point 1|(s2)+3, (s2)+2
2242 |Point 2|(s2)+5, (s2)+4
2243 |.....|......
2244 |Point n|(s2)+2n+1, (s2)+2n
2245 |(% rowspan="4" %)Y coordinate|Point 1|(s2)+2n+3, (s2)+2n+2
2246 |Point 2|(s2)+2n+5, (s2)+2n+4
2247 |.....|.....
2248 |Point n|(s2)+4n+1, (s2)+4n
2249
2250 [[image:07-5 Basic instructions_html_6633ca18cee1218c.png]]
2251
2252 • If the operation result is not an integer value, round the first digit below the decimal point.
2253
2254 • The X coordinate data of the conversion data for scaling should be set in ascending order.
2255
2256 • For (s1), set within the range of the conversion data for scaling ((s2), (s2) + 1 device value).
2257
2258 • If the same X coordinate is specified for multiple points, the Y coordinate value of the second point will be output.
2259
2260 • Set the number of coordinate points of conversion data for scaling within the range of 1 to 2,147,483,647.
2261
2262 • Setting example of conversion table for scaling.
2263
2264 In the case of scaling conversion characteristics as shown in the figure below, set it as the following data sheet.
2265
2266 [[image:07-5 Basic instructions_html_74fd22d845ad450e.png]]
2267
2268 |(% colspan="2" rowspan="2" %)**Set &nbsp;&nbsp;&nbsp;&nbsp;items**|(% colspan="3" %)**Set device and content**|(% rowspan="2" %)**Remarks**
2269 |(% colspan="2" %)**When R0 is specified in (s2)**|**Set content**
2270 |(% colspan="2" %)Coordinate points|(s2)+1, (s2)|R1, R0|K10|
2271 |(% rowspan="10" %)X|Point 1|(s2)+3, (s2)+2|R3, R2|K5|
2272 |Point 2|(s2)+5, (s2)+4|R5, R4|K20|
2273 |Point 3|(s2)+7, (s2)+6|R7, R6|K50|
2274 |Point 4|(s2)+9, (s2)+8|R9, R8|K200|(% rowspan="3" %)Refer to** ✎1**
2275 |Point 5|(s2)+11, (s2)+10|R10, R11|K200
2276 |Point 6|(s2)+13, (s2)+12|R13, R12|K200
2277 |Point 7|(s2)+15, (s2)+14|R15, R14|K250|
2278 |Point 8|(s2)+17, (s2)+16|R17, R16|K350|(% rowspan="2" %)Refer to** ✎2**
2279 |Point 9|(s2)+19, (s2)+18|R19, R18|K350
2280 |Point 10|(s2)+21, (s2)+20|R21, R20|K400|
2281 |(% rowspan="10" %)Y coordinate|Point 1|(s2)+23, (s2)+22|R23, R22|K7|
2282 |Point 2|(s2)+25, (s2)+24|R25, R24|K30|
2283 |Point 3|(s2)+27, (s2)+26|R27, R26|K100|
2284 |Point 4|(s2)+29, (s2)+28|R29, R28|K25|(% rowspan="3" %)Refer to** ✎1**
2285 |Point 5|(s2)+31, (s2)+30|R31, R30|K70
2286 |Point 6|(s2)+33, (s2)+32|R33, R32|K250
2287 |Point 7|(s2)+35, (s2)+34|R35, R34|K90|
2288 |Point 8|(s2)+37, (s2)+36|R37, R36|K90|(% rowspan="2" %)Refer to** ✎2**
2289 |Point 9|(s2)+39, (s2)+38|R39, R38|K30
2290 |Point 10|(s2)+41, (s2)+40|R41, R40|K7|
2291
2292 ✎**1** Like points 4, 5, and 6, if the coordinates are specified by 3 points, the intermediate value could be the output value.
2293
2294 In this example, the output value (median value) is specified by the Y coordinate of point 5.
2295
2296 When the X coordinate is the same at 3 or more points, the value of the second point is also output.
2297
2298 ✎**2** Like points 8 and 9, if the coordinates are specified by 2 points, the output value is the value of the Y coordinate of the next point.
2299
2300 In this example, the output value is specified by the Y coordinate of point 9.
2301
2302 **Error code**
2303
2304 |**Error code**|**Content**
2305 |4085H|When the specified device range for reading exceeds the range of the corresponding device.
2306 |4086H|When the specified device range for writing exceeds the range of the corresponding device.
2307 |4084H|(((
2308 When the Xn data of data table is not sorted in ascending order. However, the instruction will be executed until the position where the error occurs;
2309
2310 When the input value specified in (s1) exceeds the range of the set scale conversion data;
2311
2312 When the number of start coordinate points of device (s2) is less than 0.
2313 )))
2314
2315 **Example**
2316
2317 [[image:07-5 Basic instructions_html_91dbc16faa9d2ec3.png]]
2318
2319 When -100 ≤D0(X) < 0, D100(Y)=[[image:/xwiki/bin/download/PLC%20Editor2/1%20User%20manual/2.1%20LX5V%20user%20manual/07-5%20Basic%20instruction/WebHome/07-5%20Basic%20instructions_html_2c96d630f666e72c.gif?rev=1.1||alt="07-5 Basic instructions_html_2c96d630f666e72c.gif"]],,[[image:07-5 Basic instructions_html_2c96d630f666e72c.gif]] ,,;
2320
2321 when D0(X)=0, D100(Y)=0;
2322
2323 when 0< D0(X) ≤ 100, D100(Y)=[[image:/xwiki/bin/download/PLC%20Editor2/1%20User%20manual/2.1%20LX5V%20user%20manual/07-5%20Basic%20instruction/WebHome/07-5%20Basic%20instructions_html_47ebf5cc7733fccc.gif?rev=1.1||alt="07-5 Basic instructions_html_47ebf5cc7733fccc.gif"]],,[[image:07-5 Basic instructions_html_47ebf5cc7733fccc.gif]] ,,.
2324
2325 [[image:07-5 Basic instructions_html_a5b19d1af74a9620.png]]
2326
2327 {{id name="_Toc32057"/}}{{id name="_Toc9941"/}}{{id name="_Toc6492"/}}**ZONE/BIN 16-bit data zone control**
2328
2329 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] **ZONE(P)**
2330
2331 After adding the offset value specified in (s1) or (s2) to the input value specified in (s3), it is stored in the device number specified in (d).
2332
2333 -[ZONE (s1) (s2) (s3) (d)]
2334
2335 **Content, range and data type**
2336
2337 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2338 |s1|The negative offset value for addition in the input value|-32,768 to 32,767|BIN16 bit|ANY16_S
2339 |s2|The positive offset value for addition in the input value|-32,768 to 32,767|BIN16 bit|ANY16_S
2340 |s3|Input value for zone control`|-32,768 to 32,767|BIN16 bit|ANY16_S
2341 |d|The start number of the device storing the output value controlled by zone control|-|BIN16 bit|ANY16_S
2342
2343 **Device used**
2344
2345 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2346 **Pulse**
2347
2348 **extension**
2349 )))
2350 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2351 |(% rowspan="4" %)ZONE|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
2352 |Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | |●|●| |●|●
2353 |Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●| | | | | |●|●
2354 |Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●| | | | | |●|●
2355
2356 **Features**
2357
2358 After adding the offset value specified in (s1) or (s2) to the input value (BIN 16-bit value) specified in (s3), it is stored in the device number specified in (d). The offset value is controlled as follows.
2359
2360 |**Condition**|**The value stored in the output value**
2361 |When input value (s3)<0|Input value (s3) + negative offset value (s1)
2362 |When input value (s3)=0|0
2363 |When input value (s3)>0|Input value (s3) + positive offset value (s2)
2364
2365
2366 (((
2367 • When the output value stored in (d) is a signed BIN 16-bit value, and the operation result exceeds the range of -32,768 to 32,767, the situation is shown in the following example.
2368
2369 For example, when (s1) is -100 and (s3) is -32,768,
2370
2371 the output value = -32768+(-100)=8000H-FF9CH=7F9CH=32668.
2372
2373 [[image:07-5 Basic instructions_html_a2adbf9ccf8f839.png]]
2374
2375
2376
2377 )))
2378
2379 **Error code**
2380
2381 |**Error code**|**Content**
2382 |4085H|When the specified device range for reading exceeds the range of the corresponding device
2383 |4086H|When the specified device range for writing exceeds the range of the corresponding device
2384
2385 **Example**
2386
2387 [[image:07-5 Basic instructions_html_5da523c7765bf5be.png]]
2388
2389 When X000 is ON
2390
2391 • When D0<0, the value of (D0)+(-1,000) is stored in D1.
2392
2393 • When D0=0, 0 is stored in D1.
2394
2395 • When 0<D0, the value of (D0)+(1,000) is stored in D1.
2396
2397 {{id name="_Toc28351"/}}{{id name="_Toc11023"/}}{{id name="_Toc30269"/}}**DZONE/BIN 32-bit data zone control**
2398
2399 [[image:07-5 Basic instructions_html_11b3991e89e21efc.gif]] DZONE(P)
2400
2401 After adding the offset value specified in (s1) or (s2) to the input value specified in (s3), it is stored in the device number specified in (d).
2402
2403 -[DZONE (s1) (s2) (s3) (d)]
2404
2405 **Content, range and data type**
2406
2407 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
2408 |(s1)|The negative offset value for addition in the input value|-2147483648 to 2147483647|BIN32 bit|ANY32_S
2409 |(s2)|The positive offset value for addition in the input value|-2147483648 to 2147483647|BIN32 bit|ANY32_S
2410 |(s3)|Input value for zone control|-2147483648 to 2147483647|BIN32 bit|ANY32_S
2411 |(d)|The start number of the device storing the output value controlled by zone control|-|BIN32 bit|ANY32_S
2412
2413 **Device used**
2414
2415 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="24" %)**Devices**|**Offset modification**|(((
2416 **Pulse**
2417
2418 **extension**
2419 )))
2420 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
2421 |(% rowspan="4" %)DZONE|Parameter 1| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
2422 |Parameter 2| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●| |●|●
2423 |Parameter 3| | | | | | | | | | |●|●|●|●|●|●|●|●|●|●|●| | | |●|●
2424 |Parameter 4| | | | | | | | | | | |●|●|●|●|●|●|●|●|●|●| | | |●|●
2425
2426 **Features**
2427
2428 After adding the offset value specified in (s1) or (s2) to the input value (BIN 32-bit value) specified in (s3), it is stored in the device number specified in (d). The offset value is controlled as follows.
2429
2430 |**Condition**|**The value stored in the output value**
2431 |When input value ((s3), (s3)+1)<0|Input value ((s3), (s3)+1) + negative offset value (s1), (s1)+1
2432 |When input value ((s3), (s3)+1)=0|0
2433 |When input value ((s3), (s3)+1)>0|Input value ((s3), (s3)+1) + positive offset value (s2), (s2)+1
2434
2435
2436 (((
2437 • When the output value stored in (d) and (d)+1 is a signed BIN 32-bit value, and the operation result exceeds the range of -2,147,483,648 to 2,147,483,647, the situation is shown in the following example.
2438
2439 For example, (s1), (s1)+1 is -1,000, (s3), (s3)+1 is -2,147,483,648, then the output value=-2,147,483,648+(-1000)=80000000H+FFFFFC18H=2,147,482,648.
2440
2441 [[image:07-5 Basic instructions_html_2f3a96a2565c75c7.png]]
2442 )))
2443
2444 **Error code**
2445
2446 |**Error code**|**Content**
2447 |4085H|When the specified device range for reading exceeds the range of the corresponding device
2448 |4086H|When the specified device range for writing exceeds the range of the corresponding device
2449
2450 **Example**
2451
2452 [[image:07-5 Basic instructions_html_b831b14748df07ab.png]]
2453
2454 • When (D1, D0)<0, the value of (D1, D0)+(-10,000) is stored in (D11, D10).
2455