Joey 1.4 3 == **TADD/The addition of clock data** ==
Leo Wei 1.1 4
5 **TADD(P)**
6
7 Add the time data stored after the device number specified in (s1) and the time data stored after the device number specified in (s2), and store the result of the addition operation after the device number specified in (d) .
8
9 -[TADD (s1) (s2) (d)]
10
11 **Content, range and data type**
12
13 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
Joey 1.4 14 |(s1)|The device start number that stores the added time data|-|Signed BIN 16 bit|(((
Leo Wei 1.1 15 ANY16_ARRAY
16
17 (number of elements: 3)
18 )))
19 |(s2)|The device start number that stores the addition operation time (time) data|-|Signed BIN 16 bit|(((
20 ANY16_ARRAY
21
22 (number of elements: 3)
23 )))
24 |(d)|The device start number that stores the time (time) data of the addition operation result|-|Signed BIN 16 bit|(((
25 ANY16_ARRAY
26
27 (number of elements: 3)
28 )))
29
30 **Device used**
31
Joey 1.5 32 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="5" %)**Devices**|(((
33 **Offset modification**
Leo Wei 1.1 34 )))|(((
Joey 1.5 35 **Pulse extension**
Leo Wei 1.1 36 )))
Joey 1.5 37 |**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
38 |(% rowspan="3" %)TADD|Parameter 1|●|●|●|●|●|●|●
39 |Parameter 2|●|●|●|●|●|●|●
40 |Parameter 3|●|●|●|●|●|●|●
Leo Wei 1.1 41
42 **Features**
43
44 Add the time data specified in (s1) and the time data specified in (s2), and store the result of the addition in the device number specified in (d) or later.
45
Joey 1.5 46 (% style="text-align:center" %)
47 [[image:07-5 Basic instructions_html_37222a6e282347f9.png||height="79" width="750"]]
Leo Wei 1.1 48
49 **Example**
50
51 When 6:32:40 and 7:48:10 are added together
52
Joey 1.5 53 (% style="text-align:center" %)
54 [[image:07-5 Basic instructions_html_90138670198ab422.png||height="94" width="750"]]
Leo Wei 1.1 55
56 When the calculation result time exceeds 24 o'clock, the carry flag turns ON, and the value after 24 hours is subtracted becomes the calculation result. For example, when 14:20:30 and 20:20:20 are added, the result is not 34:40:50, but 10:40:50.
57
Joey 1.5 58 (% style="text-align:center" %)
59 [[image:07-5 Basic instructions_html_bac419ce2dc0dc2.png||height="91" width="750"]]
Leo Wei 1.1 60
61 When the calculation result is 0 (0 hour, 0 minute, 0 second), the zero flag turns on.
62
63 When 23:59:59 and 1 second are added, the result of the calculation is 0:00:00, and the carry flag and zero flag are turned on.
64
65 Related device are as follows:
66
67 |**Devices**|**Name**|**Content**
68 |SM151|Carry|It is ON when the result of the TADD(P) instruction exceeds the maximum clock data value of 23:59:59
69 |SM153|Zero|It is ON when the result of the TADD(P) instruction is 0:00:00
70
Mora Zhou 29.1 71 (% class="box infomessage" %)
72 (((
73 ✎**Note:** The devices specified in (s1), (s2), (d) occupy 3 points respectively. Be careful not to overlap with the device used for machine control.
Leo Wei 1.1 74
75 When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
Mora Zhou 29.1 76 )))
Leo Wei 1.1 77
78 **Error code**
79
80 |**Error code**|**Content**
Joey 1.5 81 |4085H|When reading the specified device range exceeds the corresponding device range
Leo Wei 1.1 82 |4086H|When writing the specified device range exceeds the corresponding device range
83 |4084H|(((
84 When the values specified in (s1) and (s2) are other than 0 to 23
85
86 When the values specified in (s1)+1, (s2)+1, (s1)+2 and (s2)+2 are other than 0 to 59
87 )))
88
89 **Example**
90
Joey 1.5 91 (% style="text-align:center" %)
92 [[image:07-5 Basic instructions_html_4f75eedee7172bbb.png||height="35" width="349"]]
Leo Wei 1.1 93
94 Set D0 time to 16:30:00 and D10 time to 4:30:0
95
Joey 1.5 96 (% style="text-align:center" %)
Leo Wei 1.1 97 [[image:07-5 Basic instructions_html_c64e0faf2af172f8.png]]
98
Joey 1.5 99 (% style="text-align:center" %)
Leo Wei 1.1 100 [[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png]]
101
102 After the coil is turned on, the D20 time is 21:0:0
103
Joey 1.5 104 (% style="text-align:center" %)
Leo Wei 1.1 105 [[image:07-5 Basic instructions_html_a9b235835aa41200.png]]
106
Joey 1.5 107 == **TSUB/The subtraction of clock data** ==
Leo Wei 1.1 108
Joey 1.5 109 **TSUB(P)**
Leo Wei 1.1 110
111 Subtract the time data stored after the device number specified in (s1) and the time data stored after the device number specified in (s2), and store the subtraction result in the device number specified in (d) or later .
112
113 -[TSUB (s1) (s2) (d)]
114
115 **Content, range and data type**
116
117 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
118 |(s1)|The device start number that stores the subtracted time data|-|Signed BIN 16 bit|(((
119 ANY16_ARRAY
120
121 (number of elements: 3)
122 )))
123 |(s2)|The device start number that stores the subtraction operation time (time) data|-|Signed BIN 16 bit|(((
124 ANY16_ARRAY
125
126 (number of elements: 3)
127 )))
128 |(d)|The device start number that stores the time (time) data of the subtraction result|-|Signed BIN 16 bit|(((
129 ANY16_ARRAY
130
131 (number of elements: 3)
132 )))
133
134 **Device used**
135
Joey 1.5 136 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="5" %)**Devices**|(((
137 **Offset modification**
Leo Wei 1.1 138 )))|(((
Joey 1.5 139 **Pulse extension**
Leo Wei 1.1 140 )))
Joey 1.5 141 |**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
142 |(% rowspan="3" %)TSUB|Parameter 1|●|●|●|●|●|●|●
143 |Parameter 2|●|●|●|●|●|●|●
144 |Parameter 3|●|●|●|●|●|●|●
Leo Wei 1.1 145
146 **Features**
147
148 Subtract the time data specified in (s1) and the time data specified in (s2), and store the subtraction result in the device number specified in (d) or later.
149
Joey 1.5 150 (% style="text-align:center" %)
Leo Wei 1.1 151 [[image:07-5 Basic instructions_html_5a93455e4cd8a27.png]]
152
153 **Example**
154
155 When subtracting 10:40:20 and 3:50:10
156
Joey 1.5 157 (% style="text-align:center" %)
Leo Wei 1.1 158 [[image:07-5 Basic instructions_html_2473f03fc493780c.png]]
159
160 When the calculation result time is a negative number, the borrow flag turns on and the data +24 is the calculation result. For example, in the case of subtracting 4:50:32 and 10:42:12, the result is not -6:8:20, but 18:8:20.
161
Joey 1.5 162 (% style="text-align:center" %)
Leo Wei 1.1 163 [[image:07-5 Basic instructions_html_24b998b4c3c4ec73.png]]
164
165 When the calculation result is 0 (0 hour, 0 minute, 0 second), the zero flag turns on.
166
167 Related device are as follows:
168
169 |**Devices**|**Name**|**Content**
170 |SM152|Borrow|It is ON when the result of the TSUB(P) instruction is less than 0:00:00
171 |SM153|Zero|It is ON when the result of the TSUB(P) instruction is at the time of 0:00:00:00
172
Joey 1.5 173 ✎**Note:**
Leo Wei 1.1 174
175 • The devices specified in (s1), (s2), and (d) occupy 3 points respectively. Be careful not to overlap with the device used for machine control.
176
177 • When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
178
179 **Error code**
180
181 |**Error code**|**Content**
182 |4085H|When reading the specified device range exceeds the corresponding device range
183 |4086H|When writing the specified device range exceeds the corresponding device range
184 |4084H|(((
185 When the values specified in (s1) and (s2) are other than 0 to 23
186
187 When the values specified in (s1)+1, (s2)+1, (s1)+2 and (s2)+2 are other than 0 to 59
188 )))
189
190 **Example**
191
Joey 1.5 192 (% style="text-align:center" %)
193 [[image:07-5 Basic instructions_html_e3a5d4793d3ccd2d.png||height="36" width="372"]]
Leo Wei 1.1 194
195 Set D0 time to 16:30:00 and D10 time to 4:30:0
196
Joey 1.5 197 (% style="text-align:center" %)
Leo Wei 1.1 198 [[image:07-5 Basic instructions_html_c64e0faf2af172f8.png]]
199
Joey 1.5 200 (% style="text-align:center" %)
Leo Wei 1.1 201 [[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png]]
202
203 After the coil is turned on, the D20 time is 12:00:00
204
Joey 1.5 205 (% style="text-align:center" %)
Leo Wei 1.1 206 [[image:07-5 Basic instructions_html_8f93ea19ba10652b.png]]
207
Jim 8.1 208 == **TRD/Clock data reading** ==
Leo Wei 1.1 209
210 **TRD(P)**
211
212 Read the clock data of the built-in real-time clock of the CPU module.
213
214 -[TRD (d)]
215
216 **Content, range and data type**
217
218 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
219 |(d)|Read destination and start device number of clock data|-|Signed BIN 16 bit|(((
220 ANY16_ARRAY
221
222 (number of elements: 7)
223 )))
224
225 **Device used**
226
Joey 1.5 227 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="4" %)**Devices**|(((
228 **Offset modification**
Leo Wei 1.1 229 )))|(((
Joey 1.5 230 **Pulse extension**
Leo Wei 1.1 231 )))
Joey 1.5 232 |**T**|**C**|**D**|**R**|**[D]**|**XXP**
233 |TRD|Parameter 1|●|●|●|●|●|●
Leo Wei 1.1 234
235 **Features**
236
237 Read the clock data (SD100 to SD106) of the real-time clock built into the CPU module into (d) to (d)+6 in the following format.
238
Joey 1.2 239 |**Parameter**|**Element**|**Project**|**Clock data**| |**Element**|**Project**
Leo Wei 1.1 240 |(% rowspan="7" %)Special register|SD105|Year (Gregorian)|2000 to 2099|→|(d)|Year (Gregorian)
241 |SD104|Month|1 to 12|→|(d)+1|Month
242 |SD103|Day|1 to 31|→|(d)+2|Day
243 |SD102|Hour|0 to 23|→|(d)+3|Hour
244 |SD101|Minute|0 to 59|→|(d)+4|Minute
245 |SD100|Seconds|0 to 59|→|(d)+5|Seconds
246 |SD106|Week|0 (Sun) to 6 (Sat)|→|(d)+6|Week
247
248 • The related devices are shown below. The clock data of these special registers are updated through END processing.
249
250 |**Devices**|**Content**
251 |SD100|The second data of the clock data is stored in BIN code.
252 |SD101|The sub-data of the clock data is stored in BIN code.
253 |SD102|Time data of clock data is stored in BIN code.
254 |SD103|The daily data of the clock data is stored in BIN code.
255 |SD104|The monthly data of the clock data is stored in BIN code.
256 |SD105|The year data of the clock data is stored in a 4-digit BIN code of the Gregorian calendar.
257 |SD106|The week data of the clock data is stored in BIN code. (0: day, 1: one, ..., 6: six) are stored in BIN code.
258
Joey 1.5 259 ✎**Note:**
Leo Wei 1.1 260
261 • The device specified in (d) occupies 7 points. Be careful not to overlap with the device used for machine control.
262
263 **Error code**
264
265 |**Error code**|**Content**
266 |4086H|When reading the specified device range exceeds the corresponding device range
267
268 **Example**
269
Joey 1.5 270 (% style="text-align:center" %)
271 [[image:07-5 Basic instructions_html_b81c1991fec5b4b1.png||height="68" width="250"]]
Leo Wei 1.1 272
273 After the M0 coil is turned on, the current date and time are read as 2020-2-19 13:10:38 Wednesday
274
Joey 1.5 275 (% style="text-align:center" %)
276 [[image:07-5 Basic instructions_html_fe82ecd18ebfd787.png||height="48" width="602"]]
Leo Wei 1.1 277
Joey 1.5 278 == **TWR/Clock data writing** ==
Leo Wei 1.1 279
Joey 1.6 280 **TWR(P)**
Leo Wei 1.1 281
282 Write the clock data of the built-in real-time clock of the CPU module.
283
284 -[TWR (s)]
285
286 **Content, range and data type**
287
288 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
289 |(s)|Clock data write source, start device number|-|Signed BIN 16 bit|ANY16_ARRAY (number of elements: 7)
290
291 **Device used**
292
Joey 1.6 293 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="4" %)**Devices**|(((
294 **Offset modification**
Leo Wei 1.1 295 )))|(((
Joey 1.6 296 **Pulse extension**
Leo Wei 1.1 297 )))
Joey 1.6 298 |**T**|**C**|**D**|**R**|**[D]**|**XXP**
299 |TWR|Parameter 1|●|●|●|●|●|●
Leo Wei 1.1 300
301 **Features**
302
303 Write the set clock data (s) to (s)+6 to the clock data (SD100 to SD106) of the real-time clock built into the CPU module.
304
Joey 1.2 305 |(% colspan="3" %)**Set data at all times**|(% rowspan="2" %) |(% colspan="2" %)**Special register**
Leo Wei 1.1 306 |**Element**|**Project**|**Clock data**|**Element**|**Project**
307 |(s)|Year (Gregorian)|2000 to 2099 or 0 to 99|→|SD105|Year (Gregorian)
308 |(s)+1|Month|1 to 12|→|SD104|Month
309 |(s)+2|Day|1 to 31|→|SD103|Day
310 |(s)+3|Hour|0 to 23|→|SD102|Hour
311 |(s)+4|Minute|0 to 59|→|SD101|Minute
312 |(s)+5|Seconds|0 to 59|→|SD100|Seconds
313 |(s)+6|Week|0 (Sun) to 6 (Sat)|→|SD106|Week
314
315 • If the TWR(P) instruction is executed, the clock data of the real-time clock is changed immediately. Therefore, the clock data after a few minutes should be transferred to the set clock data (s) to (s)+6 in advance, and the instruction will be executed when the correct time is reached.
316
317 • If the year in (s) is in the range of 0 to 99, it will be automatically treated as 2000 to 2099.
318
319 • When a value indicating an impossible time is set, the clock data will not be updated. Set the correct clock data and write again.
320
321 • The day of the week (SD100) is automatically corrected.
322
323 • The related devices are shown below.
324
325 |**Devices**|**Content**
326 |SD100|The second data of the clock data is stored in BIN code.
327 |SD101|The sub-data of the clock data is stored in BIN code.
328 |SD102|Time data of clock data is stored in BIN code.
329 |SD103|The daily data of the clock data is stored in BIN code.
330 |SD104|The monthly data of the clock data is stored in BIN code.
331 |SD105|The year data of the clock data is stored in a 4-digit BIN code of the Gregorian calendar.
332 |SD106|The week data of the clock data is stored in BIN code. (0: day, 1: one, ..., 6: six) are stored in BIN code.
333
Joey 1.6 334 ✎**Note:**
Leo Wei 1.1 335
336 The device specified in (s) occupies 7 points. Be careful not to overlap with the device used for machine control.
337
338 **Error code**
339
340 |**Error code**|**Content**
341 |4085H|When reading the specified device range exceeds the corresponding device range
342
343 **Example**
344
345 Set D0 date and time to 2020-2-19 12:36:00 in advance
346
Joey 1.6 347 (% style="text-align:center" %)
348 [[image:07-5 Basic instructions_html_994c66d1a4cbd45f.png||height="57" width="305"]]
Leo Wei 1.1 349
350 At the moment when the time 12:36:00 arrives, turn on the M0 coil and write the time.
351
Joey 1.6 352 (% style="text-align:center" %)
353 [[image:07-5 Basic instructions_html_bf3e906ee5265598.png||height="42" width="586"]]
Leo Wei 1.1 354
Joey 1.6 355 == **HTOS/16-bit data conversion of time data (hour, minute, second → second)** ==
Leo Wei 1.1 356
357 **HTOS(P)**
358
359 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result as BIN 16-bit data in the device specified in (d).
360
361 -[HTOS (s) (d)]
362
363 **Content, range and data type**
364
365 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
366 |(s)|The device start number that stores the data of the subtracted time|-|Signed BIN 16 bit|ANY16_ARRAY (number of elements: 3)
367 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|ANY16
368
369 **Device used**
370
Joey 1.6 371 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|**Offset modification**|(((
372 **Pulse extension**
Leo Wei 1.1 373 )))
Joey 1.6 374 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
375 |(% rowspan="2" %)HTOS|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
376 |Parameter 2| |●|●|●|●|●|●|●|●|●|●
Leo Wei 1.1 377
378 **Features**
379
380 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d).
381
Joey 1.6 382 (% style="text-align:center" %)
383 [[image:07-5 Basic instructions_html_a84b7741fd5bef2f.png||height="130" width="550"]]
Leo Wei 1.1 384
385 **Example**
386
387 When 4 hours, 29 minutes and 31 seconds are specified in (s)
388
Joey 1.6 389 (% style="text-align:center" %)
390 [[image:07-5 Basic instructions_html_5effb7bc9b8e5cf7.png||height="162" width="550"]]
Leo Wei 1.1 391
392 **Error code**
393
394 |**Error code**|**Content**
395 |4085H|When reading the specified device range exceeds the corresponding device range
396 |4086H|When writing the specified device range exceeds the corresponding device range
397 |4084H|(((
Joey 1.6 398 When the calculation result is not in the range of 0 to 32767
Leo Wei 1.1 399
400 When the value specified in (s) is not in the range of 0 to 9
401
402 When the value specified in (s)+1 and (s)+2 is not in the range of 0 to 59
403 )))
404
405 **Example**
406
Joey 1.6 407 (% style="text-align:center" %)
408 [[image:07-5 Basic instructions_html_e23e38c4ba4c34bb.png||height="43" width="338"]]
Leo Wei 1.1 409
410 D0 time is set to 5:36:53
411
Joey 1.6 412 (% style="text-align:center" %)
Leo Wei 1.1 413 [[image:07-5 Basic instructions_html_2866a121e5ca5713.png]]
414
415 The time of D10 after the M0 coil is turned on is as below.
416
Joey 1.6 417 (% style="text-align:center" %)
Leo Wei 1.1 418 [[image:07-5 Basic instructions_html_1dd6c5de05890797.png]]
419
Joey 1.6 420 == **DHTOS/32-bit data conversion of time data (hour, minute, second → second)** ==
Leo Wei 1.1 421
Joey 1.6 422 **DHTOS(P)**
Leo Wei 1.1 423
424 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result as BIN 32-bit data in the device specified in (d).
425
426 -[DHTOS (s) (d)]
427
428 **Content, range and data type**
429
430 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
431 |(s)|The device start number that stores the data of the subtracted time|-|Signed BIN 16 bit|ANY16_ARRAY (number of elements: 3)
432 |(d)|The device start number that stores the converted clock data|-|Signed BIN 32 bit|ANY32
433
434 **Device used**
435
Joey 1.6 436 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|(((
437 **Offset modification**
Leo Wei 1.1 438 )))|(((
Joey 1.6 439 **Pulse extension**
Leo Wei 1.1 440 )))
Joey 1.6 441 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
442 |(% rowspan="2" %)DHTOS|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
443 |Parameter 2| |●|●|●|●|●|●|●|●|●|●
Leo Wei 1.1 444
445 **Features**
446
447 Convert the time data stored after the device number specified in (s) into seconds and store the conversion result in the device specified in (d).
448
Joey 1.6 449 (% style="text-align:center" %)
450 [[image:07-5 Basic instructions_html_f4be08508575ea01.png||height="99" width="550"]]
Leo Wei 1.1 451
452 **Example**
453
454 When 35 hours, 10 minutes and 58 seconds are specified in (s)
455
Joey 1.6 456 (% style="text-align:center" %)
457 [[image:07-5 Basic instructions_html_5b9ad230ed5e1fd0.png||height="125" width="550"]]
Leo Wei 1.1 458
459 **Error code**
460
461 |**Error code**|**Content**
462 |4085H|When reading the specified device range exceeds the corresponding device range
463 |4086H|When writing the specified device range exceeds the corresponding device range
464 |4084H|(((
465 When the calculation result is not in the range of 0 to 32767
466
467 When the value specified in (s)+1 and (s)+2 is not in the range of 0 to 59
468 )))
469
470 **Example**
471
Joey 1.6 472 (% style="text-align:center" %)
473 [[image:07-5 Basic instructions_html_ae8ab4379e8bdb91.png||height="45" width="263"]]
Leo Wei 1.1 474
475 D0 time is set to 15:33:24
476
Joey 1.6 477 (% style="text-align:center" %)
478 [[image:07-5 Basic instructions_html_57a15d9e1045e93e.png||height="41" width="313"]]
Leo Wei 1.1 479
480 The second of D10 after the M0 coil is turned on is
481
Joey 1.6 482 (% style="text-align:center" %)
483 [[image:07-5 Basic instructions_html_194e906b1dc12078.png||height="64" width="365"]]
Leo Wei 1.1 484
Joey 1.6 485 **HOUR/Hour measuring 16-bit**
Leo Wei 1.1 486
487 **HOUR(P)**
488
489 The time for the input contact to be ON is measured in units of one hour.C
490
491 -[HOUR (s) (d1) (d2)]
492
493 **Content, range and data type**
494
495 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
496 |(s)|(((
497 The time when the alarm (d2) is turned ON
498
499 (set by one hour)
500 )))|K0 to K32767|Signed BIN 16 bit|ANY16
501 |(d1)|Device that stores the current value of measurement (specified data register for power failure retention)|-|Unsigned BIN 16 bit|(((
502 ANY16_ARRAY
503
504 (Number of elements: 2)
505 )))
506 |(d2)|Device that turns ON when the time limit expires (alarm output)|-|Bit|ANY_BOOL
507
508 **Device used**
509
Joey 1.6 510 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="17" %)**Devices**|(((
511 **Offset modification**
Leo Wei 1.1 512 )))|(((
Joey 1.6 513 **Pulse extension**
Leo Wei 1.1 514 )))
Joey 1.6 515 |**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP**
516 |(% rowspan="3" %)HOUR|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
517 |Parameter 2| | | | | | | | | | | |●|●|●| | | |●|●
518 |Parameter 3|●|●|●|●|●| | | | | | | | | | | | |●|●
Leo Wei 1.1 519
520 **Features**
521
522 The input contact ON time is measured in units of 1 hour. When the cumulative ON time exceeds the time (BIN 16-bit data) specified in (s), the device specified in (d2) is turned on .
523
524 • In (s), set the time until the alarm (d2) turns ON in units of 1 hour.
525
526 • (d1) stores the current measured value in units of 1 hour.
527
528 • If the median value of (d1) exceeds 32767, it will be modified to 32767.
529
530 • (d1)+1 stores the current measured value (in units of 1 second) that is less than 1 hour.
531
532 • (d2) turns on when the current value (d1) exceeds the time specified in (s).
533
534 • In order to continue to use the current value data even after the power of the CPU module is turned off, specify the data register for power failure retention to (d1). If you use general-purpose data registers, the current value data will be cleared by powering off the CPU module and STOP→RUN operations.
535
536 • After the alarm output specified in (d2) turns ON, measurement will continue.
537
538 • The measurement stops when the current value reaches the 16-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+1.
539
Joey 1.7 540 ✎**Note:**
Leo Wei 1.1 541
542 • The device specified in (d1) occupies 2 points. Be careful not to overlap with the device used for machine control.
543
544 • After the instruction stops running, the measurement stops and the output continues to be maintained.
545
546 **Error code**
547
548 |**Error code**|**Content**
549 |4085H|When reading the specified device range exceeds the corresponding device range
550 |4086H|When writing the specified device range exceeds the corresponding device range
551 |4084H|When the value of (s) is negative
552
553 **Example**
554
Joey 1.7 555 (% style="text-align:center" %)
556 [[image:07-5 Basic instructions_html_7570f8c392470a9f.png||height="45" width="320"]]
Leo Wei 1.1 557
558 When M0 = ON, the duration of the state is accumulated, the time is recorded in D0, and the seconds less than 1 hour are recorded in D1. When the accumulated time of D0 reaches 98 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K98), the accumulated timing will continue and the reading will continue to increase; the current time value D0 reaches the maximum value of 32767 hours and D1 reaches 3599 seconds, the timing measurement will stop. The current time values D0 and D1 are cleared to 0.
559
Joey 1.7 560 == **DHOUR/Hour measuring 32 bits** ==
Leo Wei 1.1 561
562 **DHOUR(P)**
563
564 The time for the input contact to be ON is measured in units of one hour.
565
566 -[DHOUR (s) (d1) (d2)]
567
568 **Content, range and data type**
569
570 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
571 |(s)|(((
Joey 1.7 572 The time when the alarm (d2) is turned ON (set by one hour)
Leo Wei 1.1 573 )))|0 to 2147483647|Signed BIN 32 bit|ANY32
574 |(d1)|Device that stores the current value of measurement (specified data register for power failure retention)|-|Unsigned BIN 32 bit|(((
575 ANY32_ARRAY
576
577 (Number of elements: 2)
578 )))
579 |(d2)|Device that turns ON when the time limit expires (alarm output)|-|Bit|ANY_BOOL
580
581 **Device used**
582
Joey 1.7 583 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="18" %)**Devices**|(((
584 **Offset modification**
Leo Wei 1.1 585 )))|(((
Joey 1.7 586 **Pulse extension**
Leo Wei 1.1 587 )))
Joey 1.7 588 |**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**[D]**|**XXP**
589 |(% rowspan="3" %)DHOUR|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●|●|●|●|●
590 |Parameter 2| | | | | | | | | | | |●|●|●| | | | |●|●
591 |Parameter 3|●|●|●|●|●| | | | | | | | | | | | | |●|●
Leo Wei 1.1 592
593 **Features**
594
595 • The input contact ON time is measured in units of 1 hour. When the cumulative ON time exceeds the time (BIN 32-bit data) specified in (s), the device specified in (d2) is set to ON.
596
597 • In (s)+1, (s), set the time until the alarm (d2) turns ON in units of 1 hour.
598
599 • (D1)+1 and (d1) store the current value measured in units of 1 hour. ((d1)+1: high bit, (d1): low bit)
600
601 • If the median of (d1)+1 and (d1) exceeds 2147483647, it will be modified to 2147483647.
602
603 • (D1)+2 stores the current value (in units of 1 second) of the measurement that is less than 1 hour.
604
605 • (D2) turns on when the current value (d1)+1, (d1) exceeds the time specified in (s).
606
607 • In order to continue to use the current value data even after the power of the CPU module is turned off, specify the data register for power failure retention to (d1). If you use general-purpose data registers, the current value data will be cleared by powering off the CPU module and STOP→RUN operations.
608
609 • After the alarm output specified in (d2) turns on, the measurement will continue.
610
611 • The measurement stops when the current value reaches the 32-bit maximum. To continue the measurement, clear the current value of (d1) to (d1)+2.
612
Joey 1.7 613 ✎**Note:**
Leo Wei 1.1 614
615 • The device specified in (d1) occupies 3 points. Be careful not to overlap with the device used for machine control.
616
617 • After the instruction stops running, the measurement stops and the output continues to be maintained.
618
619 **Error code**
620
621 |**Error code**|**Content**
622 |4085H|When reading the specified device range exceeds the corresponding device range
623 |4086H|When writing the specified device range exceeds the corresponding device range
624 |4084H|When the value of (s) is negative
625
626 **Example**
627
Joey 1.7 628 (% style="text-align:center" %)
629 [[image:07-5 Basic instructions_html_3f1ef5ecc835de30.png||height="43" width="448"]]
Leo Wei 1.1 630
631 When M0=ON, the duration of this state is accumulated, the time is recorded in D1, D0, and the seconds less than 1 hour are recorded in D2. When the accumulated time of D1, D0 reaches 1000 hours, the Y0 output state is ON. When the timing conditions are met, after reaching the specified value (K1000), the accumulated timing will continue, and the reading will continue to increase; the current time values D1 and D0 reach the maximum value of 2147483647 hours, and when D2 reaches 3599 seconds, the timing measurement will stop and the timing should be restarted. The current time values D0, D1, and D2 must be cleared to 0.
632
Joey 1.7 633 == **STOH/16-bit data conversion of time data (second → hour, minute, second)** ==
Leo Wei 1.1 634
Joey 1.7 635 **STOH(P)**
Leo Wei 1.1 636
637 Convert the second 16-bit data stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
638
639 -[STOH (s) (d)]
640
641 **Content, range and data type**
642
643 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
Joey 1.7 644 |(s)|The device start number that stores the clock data before conversion|0 to 32767|Signed BIN 16 bit|ANY16
Leo Wei 1.1 645 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|(((
Joey 1.7 646 ANY16_ARRAY (number of elements: 3)
Leo Wei 1.1 647 )))
648
649 **Device used**
650
Joey 1.7 651 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|(((
652 **Offset modification**
Leo Wei 1.1 653 )))|(((
Joey 1.7 654 **Pulse extension**
Leo Wei 1.1 655 )))
Joey 1.7 656 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
657 |(% rowspan="2" %)STOH|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
658 |Parameter 2| |●|●|●|●|●|●|●|●|●|●
Leo Wei 1.1 659
660 **Features**
661
662 Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
663
Joey 1.7 664 (% style="text-align:center" %)
665 [[image:07-5 Basic instructions_html_1f5f3f1d80af2a34.png||height="110" width="550"]]
Leo Wei 1.1 666
667 **Example**
668
669 When 29,011 seconds are specified in (s)
670
Joey 1.7 671 (% style="text-align:center" %)
672 [[image:07-5 Basic instructions_html_682516cbf773f515.png||height="163" width="550"]]
Leo Wei 1.1 673
674 **Error code**
675
676 |**Error code**|**Content**
677 |4085H|When reading the specified device range exceeds the corresponding device range
678 |4086H|When writing the specified device range exceeds the corresponding device range
679 |4084H|When the value of (s) exceeds the range
680
681 **Example**
682
Joey 1.7 683 (% style="text-align:center" %)
684 [[image:07-5 Basic instructions_html_e783349d57adf7d2.png||height="47" width="350"]]
Leo Wei 1.1 685
686 Set D0 seconds to 12537
687
688 The hour, minute and second of D10 after the M0 coil is turned on are
689
Joey 1.7 690 (% style="text-align:center" %)
691 [[image:07-5 Basic instructions_html_d3c33949e8684891.png||height="52" width="645"]]
Leo Wei 1.1 692
Joey 1.7 693 == **DSTOH/32-bit data conversion of time data (second → hour, minute, second)** ==
Leo Wei 1.1 694
Joey 1.7 695 **DSTOH(P)**
Leo Wei 1.1 696
697 Convert the second 32-bit data of second stored in the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
698
699 -[DSTOH (s) (d)]
700
701 **Content, range and data type**
702
703 |**Parameter**|**Content**|**Range**|**Data type**|**Data     type (label)**
704 |(s)|The device start number that stores the clock data before conversion|0 to 117964799|Signed BIN 32 bit|ANY32
705 |(d)|The device start number that stores the converted clock data|-|Signed BIN 16 bit|(((
Joey 1.7 706 ANY16_ARRAY (number of elements: 3)
Leo Wei 1.1 707 )))
708
709 **Device used**
710
Joey 1.7 711 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="9" %)**Devices**|(((
712 **Offset modification**
Leo Wei 1.1 713 )))|(((
Joey 1.7 714 **Pulse extension**
Leo Wei 1.1 715 )))
Joey 1.7 716 |**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
717 |(% rowspan="2" %)DSTOH|Parameter 1|●|●|●|●|●|●|●|●|●|●|●
718 |Parameter 2| |●|●|●|●|●|●|●|●|●|●
Leo Wei 1.1 719
720 **Features**
721
722 Convert the second data stored after the device number specified in (s) into hour, minute, and second, and store the conversion result in the device specified in (d) and later.
723
Joey 1.7 724 (% style="text-align:center" %)
725 [[image:07-5 Basic instructions_html_cbf13fc3d10fbe61.png||height="99" width="600"]]
Leo Wei 1.1 726
727 **Example**
728
729 When 45,325 seconds is specified in (s)
730
Joey 1.7 731 (% style="text-align:center" %)
732 [[image:07-5 Basic instructions_html_d6045506b13275a0.png||height="135" width="600"]]
Leo Wei 1.1 733
734 **Error code**
735
736 |**Error code**|**Content**
737 |4085H|When reading the specified device range exceeds the corresponding device range
738 |4086H|When writing the specified device range exceeds the corresponding device range
739 |4084H|When the value of (s) exceeds the range
740
741 **Example**
742
Joey 1.7 743 (% style="text-align:center" %)
744 [[image:07-5 Basic instructions_html_e7dd49d953db6da4.png||height="39" width="316"]]
Leo Wei 1.1 745
746 Set D0 seconds to 2152537
747
748 The hour, minute and second of D10 after the M0 coil is turned on are
749
Joey 1.7 750 (% style="text-align:center" %)
751 [[image:07-5 Basic instructions_html_10d57bde1ac0a218.png||height="52" width="661"]]
Leo Wei 1.1 752
Joey 1.7 753 == **TCMP/Clock data comparison** ==
Leo Wei 1.1 754
755 **TCMP(P)**
756
757 Compare the comparison time specified in (s1), (s2), (s3) with the time data specified in (s4), and turn the bit device specified in (d) ON/OFF according to their size match.
758
759 -[TCMP (s1) (s2) (s3) (s4) (d)]
760
761 **Content, range and data type**
762
763 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
764 |(s1)|Specify the "hour" of the comparison base time.|0 to 23|Signed BIN 16 bit|ANY16
765 |(s2)|Specify the "minute" of the comparison base time.|0 to 59|Signed BIN 16 bit|ANY16
766 |(s3)|Specify the "second" of the comparison base time.|0 to 59|Signed BIN 16 bit|ANY16
767 |(s4)|Specify the "hour" of the time data (hour, minute, second).|-|Signed BIN 16 bit|ANY16_ARRAY
768 |(d)|The bit device is turned ON/OFF according to the comparison result.|-|Bit|ANYBIT_ARRAY
769
770 **Device used**
771
Joey 1.7 772 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="17" %)**Devices**|(((
773 **Offset modification**
Leo Wei 1.1 774 )))|(((
Joey 1.7 775 **Pulse extension**
Leo Wei 1.1 776 )))
Joey 1.7 777 |**Y**|**M**|**S**|**SM**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**K**|**H**|**E**|**[D]**|**XXP**
778 |(% rowspan="5" %)TCMP|Parameter 1| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
779 |Parameter 2| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
780 |Parameter 3| | | | | |●|●|●|●|●|●|●|●|●|●|●| |●|●
781 |Parameter 4| | | | | | | | | |●|●|●|●|●| | | |●|●
782 |Parameter 5|●|●|●|●|●| | | | | | | | | | | | |●|●
Leo Wei 1.1 783
784 **Features**
785
786 Compare the time of the reference time (hour, minute, second) [(s1), (s2), (s3)] with the time data (hour, minute, second) [(s4), (s4)+1, (s4) +2] Compare the size and turn on/off the 3 points from (d) according to the result of the same size.
787
Joey 1.8 788 (% style="text-align:center" %)
789 [[image:07-5 Basic instructions_html_5df7ad3057fada12.png||height="385" width="750"]]
Leo Wei 1.1 790
Joey 1.8 791 ✎**Note:**
Leo Wei 1.1 792
793 The device specified in (s4) and (d) occupies 3 points. Be careful not to overlap with the device used for machine control.
794
795 When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
796
797 **Error code**
798
799 |**Error code**|**Content**
800 |4085H|When reading the specified device range exceeds the corresponding device range
801 |4086H|When writing the specified device range exceeds the corresponding device range
802 |4084H|(((
803 When the value specified in (s) and (s4) is not in the range of 0 to 23
804
Joey 1.8 805 When the value specified in (s2),(s3) (s4)+1 and (s4)+2 is not in the range of 0 to 59
Leo Wei 1.1 806 )))
807
808 **Example**
809
Joey 1.8 810 (% style="text-align:center" %)
811 [[image:07-5 Basic instructions_html_fcc16317cf7c0700.png||height="68" width="359"]]
Leo Wei 1.1 812
813 Set D10 to 1, D11 to 30, D12 to 0
814
815 When M0 is turned on, the time that D23 will come is 0:31:27
816
Joey 1.8 817 (% style="text-align:center" %)
818 [[image:07-5 Basic instructions_html_de97dd7a612b2323.png||height="50" width="653"]]
Leo Wei 1.1 819
820 M10 is turned ON
821
Joey 1.8 822 (% style="text-align:center" %)
823 [[image:07-5 Basic instructions_html_56e2d606adc09fd.png||height="52" width="239"]]
Leo Wei 1.1 824
Joey 1.8 825 == **TZCP/Clock data bandwidth comparison** ==
Leo Wei 1.1 826
Joey 1.8 827 **TZCP(P)**
Leo Wei 1.1 828
829 Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth.
830
831 -[TZCP (s1) (s2) (s3) (d)]
832
833 **Content, range and data type**
834
835 |**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)**
836 |(s1)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|(((
Joey 1.8 837 ANY16_ARRAY (number of elements: 3)
Leo Wei 1.1 838 )))
839 |(s2)|Specify the "hour" of the lower limit time (hour, minute, second)|-|Signed BIN 16 bit|(((
Joey 1.8 840 ANY16_ARRAY (number of elements: 3)
Leo Wei 1.1 841 )))
842 |(s3)|Specify "hour" of time data (hour, minute, second)|-|Signed BIN 16 bit|(((
Joey 1.8 843 ANY16_ARRAY (number of elements: 3)
Leo Wei 1.1 844 )))
845 |(d)|The bit device is turned ON/OFF according to the comparison result.|-|Bit|(((
Joey 1.8 846 ANY16_ARRAY (number of elements: 3)
Leo Wei 1.1 847 )))
848
849 **Device used**
850
Joey 1.8 851 |(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="10" %)**Devices**|**Offset modification**|(((
852 **Pulse extension**
Leo Wei 1.1 853 )))
Joey 1.8 854 |**Y**|**M**|**S**|**SM**|**D.b**|**T**|**C**|**D**|**R**|**SD**|**[D]**|**XXP**
855 |(% rowspan="4" %)TZCP|Parameter 1| | | | | |●|●|●|●|●|●|●
856 |Parameter 2| | | | | |●|●|●|●|●|●|●
857 |Parameter 3| | | | | |●|●|●|●|●|●|●
858 |Parameter 4|●|●|●|●|●| | | | | |●|●
Leo Wei 1.1 859
860 **Features**
861
862 Compare the comparison time of the high and low points specified in (s1) and (s2) with the time data specified in (s3), and turn the bit device specified in (d) ON/OFF according to its size and bandwidth.
863
Joey 1.8 864 (% style="text-align:center" %)
865 [[image:07-5 Basic instructions_html_844291270080313d.png||height="339" width="750"]]
Leo Wei 1.1 866
Joey 1.8 867 ✎**Note:**
Leo Wei 1.1 868
869 • The devices specified in (s1), (s2), (s3), (d) occupy 3 points. Be careful not to overlap with the device used for machine control.
870
871 • When using the clock data time (hour, minute, second) of the built-in real-time clock of the CPU module, use the TRD(P) instruction to read the value of the special register and assign the word device to each operand.
872
873 • When (s1)> (s2), two of (d), (d)+1, (d)+2 are ON/OFF.
874
875 **Error code**
876
877 |**Error code**|**Content**
878 |4085H|When reading the specified device range exceeds the corresponding device range
879 |4086H|When writing the specified device range exceeds the corresponding device range
880 |4084H|(((
881 When the value specified in (s1), (s2) and (s3) is not in the range of 0 to 23
882
883 When the value specified in (s1)+1, (s2)+1, (s3)+1, (s1)+2, (s2)+2 and (s3)+2 is not in the range of 0 to 59
884 )))
885
886 **Example**
887
Joey 1.8 888 (% style="text-align:center" %)
889 [[image:07-5 Basic instructions_html_30027a2387c26c2e.png||height="46" width="439"]]
Leo Wei 1.1 890
891 Set D0 time to 16:30:00 and D10 time to 4:30:0
892
Joey 1.8 893 (% style="text-align:center" %)
894 [[image:07-5 Basic instructions_html_c64e0faf2af172f8.png||height="49" width="626"]]
Leo Wei 1.1 895
Joey 1.8 896 (% style="text-align:center" %)
897 [[image:07-5 Basic instructions_html_66e3a2eadeb2ecbb.png||height="50" width="625"]]
Leo Wei 1.1 898
899 After the coil is turned on, the reading time to D20 time is 8:30:00
900
Joey 1.8 901 (% style="text-align:center" %)
902 [[image:07-5 Basic instructions_html_75c44dad07eaf80a.png||height="49" width="625"]]
Leo Wei 1.1 903
904 M0/M12 is ON
905
Joey 1.8 906 (% style="text-align:center" %)
907 [[image:07-5 Basic instructions_html_f512f36261705953.png||height="48" width="218"]]
Bob 11.1 908
909
Bob 12.1 910 == **TON/BIN 16-bit Turn-on delay timer** ==
Bob 11.1 911
Bob 12.1 912 **TON(P)**
Bob 11.1 913
914 Specify the T timer device in (s1), the expected time in (s2), and the time base (resolution) in (s3). And the result of the measured individual time interval operation is stored in the device specified in (s1).
915
916 PLC Editor2 version that supports this instruction: 2.3.1 and above.
917
918 -[TON (s1) (s2) (s3)]
919
920 **Content, scope, data type**
921
922 |**parameter**|**Content**|**range**|**type of data**|**Data type (label)**
923 |(s1)|T device|0~~511|Signed BIN 16 bit|ANY16_S
924 |(s2)|Expected time|0~~32767|Signed BIN 16 bit|ANY16_S
925 |(s3)|Time base(resolution)|1/10/100/1000/10000|Signed BIN 16 bit|ANY16_S
926
927 **Device used**
928
929 |(% rowspan="2" %)**instruction**|(% rowspan="2" %)**parameter**|(% colspan="24" %)**Devices**|**Offset modification**|**Pulse extension**
930 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
931 |(% rowspan="3" %)TON|Parameter 1| | | | | | | | | | | | | | |●| | | | | | | | | | |
932 |Parameter 2| | | | | | | | | | |●|●|●|●| |●|●|●|●| | |●|●| | |
933 |Parameter 3| | | | | | | | | | | | | | | | | | | | | |●|●| | |
934
935 **Timing Chart**
936
Bob 21.1 937 (% style="text-align:center" %)
Bob 26.1 938 [[image:图片3.png]]
Bob 11.1 939
Jim 13.1 940 **Features**
941
Bob 11.1 942 1) When the timer starts timing, the instruction after the timer starts to run when the timing time is greater than the time value of "the product of S2 and S3".
943
944 2) When the timer value is greater than 0 and less than the time value of "the product of S2 and S3", the timer will stop whenever the contact is disconnected, and when the contact is connected, the timer will start timing again.
945
946
947 |**S3 time base**|**Actual value**
948 |1|100us
949 |10|1ms
950 |100|10ms
951 |1000|100ms
952 |10000|1s
953
954 **Precautions**
955
956 • Avoid timer number conflict: the same timer number cannot be used for TON, TONR, TOF, TP, OUT_T timers at the same time. For example, TON T32 and TOF T32 cannot be used at the same time (it may cause data confusion and not achieve the effect of the corresponding instruction function).
957
958 **Error code**
959
960 |**Error code**|**Content**
961 |4084H|Input data in (s2) (s3) is outside the specified range.
962 |4085H|Device tpye in (s1) (s2) (s3) is outside the specified range.
963 |4086H|Device tpye in (s1) is outside the specified range.
964
Bob 12.1 965 **Example**
Bob 11.1 966
Bob 21.1 967 (% style="text-align:center" %)
Bob 26.1 968 [[image:图片4.png]]
Bob 11.1 969
970 T1 is used for storing time, setting the expected time as K10 and the time base as K10000.
971
972 After set on (M8) contact and waiting for the value in the turn-on delay timer (T1) to reach the estimated time of 10s, the contact of (T1) on and output Y0.
973
974 If the (M8) contact is off in the process of turn-on delay timer (T1) timing, the turn-on delay timer (T1) value is cleared to 0 and the timing ends.
Bob 16.1 975
976 == **TONR/BIN 16-bit Hold-type turn-on delay timer** ==
977
Bob 20.1 978 **TONR(P)**
Bob 16.1 979
980 Specify the T timer device in (s1), the expected time in (s2), and the time base (resolution) in (s3). And store the time values of the accumulated multiple timing intervals into the device specified in (s1).
981
982 PLC Editor2 version that supports this instruction: 2.3.1 and above.
983
984 -[TONR (s1) (s2) (s3)]
985
986 **Content, scope, data type**
987
988 |**parameter**|**Content**|**range**|**type of data**|**Data type (label)**
989 |(s1)|T device|0~~511|Signed BIN 16 bit|ANY16_S
990 |(s2)|Expected time|0~~32767|Signed BIN 16 bit|ANY16_S
991 |(s3)|Time base(resolution)|1/10/100/1000/10000|Signed BIN 16 bit|ANY16_S
992
993 **Device used**
994
995 |(% rowspan="2" %)**instruction**|(% rowspan="2" %)**parameter**|(% colspan="24" %)**Devices**|**Offset modification**|**Pulse extension**
996 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
997 |(% rowspan="3" %)TON|Parameter 1| | | | | | | | | | | | | | |●| | | | | | | | | | |
998 |Parameter 2| | | | | | | | | | |●|●|●|●| |●|●|●|●| | |●|●| | |
999 |Parameter 3| | | | | | | | | | | | | | | | | | | | | |●|●| | |
1000
1001 **Timing Chart**
1002
Bob 20.1 1003 (% style="text-align:center" %)
Bob 25.1 1004 [[image:图片2.png]]
Bob 16.1 1005
1006 **Features**
1007
1008 1) When the timer starts timing, the instruction after the timer starts to run when the timing time is greater than the time value of "the product of S2 and S3".
1009
1010 2) When the coil in front of the timer is off, the TONR timer saves the current value. When the coil is on, the TONR timer continues to timing.
1011
1012 3) The current value of TONR can be cleared using the reset command. After the preset time is reached, TONR maintains the current value of the timer.
1013
1014
1015 |**S3 time base**|**Actual value**
1016 |1|100us
1017 |10|1ms
1018 |100|10ms
1019 |1000|100ms
1020 |10000|1s
1021
1022 **Precautions**
1023
1024 • Avoid timer number conflict: the same timer number cannot be used for TON, TONR, TOF, TP, OUT_T timers at the same time. For example, TON T32 and TOF T32 cannot be used at the same time (it may cause data confusion and not achieve the effect of the corresponding instruction function).
1025
1026 **Error code**
1027
1028 |**Error code**|**Content**
1029 |4084H|Input data in (s2) (s3) is outside the specified range.
1030 |4085H|Device tpye in (s1) (s2) (s3) is outside the specified range.
1031 |4086H|Device tpye in (s1) is outside the specified range.
1032
1033 **Example**
1034
Bob 20.1 1035 (% style="text-align:center" %)
Bob 25.1 1036 [[image:图片1.png]]
Bob 16.1 1037
1038 T1 is used for storing time, setting the expected time as K10 and the time base as K10000.
1039
1040 When the (M8) contact off and on again during timing. (T1) maintains the value at the last disconnection and continues timing until the estimated time of 10s. After the estimated time is reached, the (T1) contact on and output Y0. If the (M8) contact off in this time, the (T1) contact is still ON but Y0 is off.
1041
1042 When (M0) contact turn ON, the (T1) timer value is cleared to 0 with the RST reset command, the (T1) contact is off, and the Y0 OFF.
1043
1044 == **TOF/BIN 16-bit Turn-off delay timer** ==
1045
Bob 19.1 1046 **TOF(P)**
Bob 16.1 1047
1048 Specify the T timer device in (s1), the expected time in (s2), and the time base (resolution) in (s3). And store the time values of the accumulated multiple timing intervals into the device specified in (s1).
1049
1050 PLC Editor2 version that supports this instruction: 2.3.1 and above.
1051
1052 -[TOF (s1) (s2) (s3)]
1053
1054 **Content, scope, data type**
1055
1056 |**parameter**|**Content**|**range**|**type of data**|**Data type (label)**
1057 |(s1)|T device|0~~511|Signed BIN 16 bit|ANY16_S
1058 |(s2)|Expected time|0~~32767|Signed BIN 16 bit|ANY16_S
1059 |(s3)|Time base(resolution)|1/10/100/1000/10000|Signed BIN 16 bit|ANY16_S
1060
1061 **Device used**
1062
1063 |(% rowspan="2" %)**instruction**|(% rowspan="2" %)**parameter**|(% colspan="24" %)**Devices**|**Offset modification**|**Pulse extension**
1064 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1065 |(% rowspan="3" %)TON|Parameter 1| | | | | | | | | | | | | | |●| | | | | | | | | | |
1066 |Parameter 2| | | | | | | | | | |●|●|●|●| |●|●|●|●| | |●|●| | |
1067 |Parameter 3| | | | | | | | | | | | | | | | | | | | | |●|●| | |
1068
1069 **Timing Chart**
1070
Bob 19.1 1071 (% style="text-align:center" %)
Bob 27.1 1072 [[image:图片5.png]]
Bob 16.1 1073
1074 **Features**
1075
1076 1) After the input is disconnected, the output is delayed for a fixed time before stopping. The timer bit turns on immediately when the input is started and the current value is set to 0. When the input is disconnected, timing starts until the current time is equal to the preset time, then timing stops.
1077
1078 2) When the preset value is reached, the timer bit is disconnected and the current value stops incrementing; If the input is turned on again before the TOF reaches the preset value, the timer bit remains on.
1079
1080 3) For the TOF timer to start timing, the enable input must perform an on-off transition.
1081
1082
1083 |**S3 time base**|**Actual value**
1084 |1|100us
1085 |10|1ms
1086 |100|10ms
1087 |1000|100ms
1088 |10000|1s
1089
1090 **Precautions**
1091
1092 • Avoid timer number conflict: the same timer number cannot be used for TON, TONR, TOF, TP, OUT_T timers at the same time. For example, TON T32 and TOF T32 cannot be used at the same time (it may cause data confusion and not achieve the effect of the corresponding instruction function).
1093
1094 **Error code**
1095
1096 |**Error code**|**Content**
1097 |4084H|Input data in (s2) (s3) is outside the specified range.
1098 |4085H|Device tpye in (s1) (s2) (s3) is outside the specified range.
1099 |4086H|Device tpye in (s1) is outside the specified range.
1100
1101 **Example**
1102
Bob 19.1 1103 (% style="text-align:center" %)
Bob 27.1 1104 [[image:图片6.png]]
Bob 16.1 1105
1106 T1 is used for storing time, setting the expected time as K10 and the time base as K10000.
1107
1108 Make the (M8) contact ON and oFF, When (M8) ON, (T1) contact is ON and Y0 is ON. when (M8) OFF, (Y0) is OFF and (T1) starts timing. When the estimated time of 5s is reached, the (T1) contact is also 0FF.
1109
1110 If the (M8) contact ON again during (T1) timing, the (T1) value clears to 0 and the timing ends
1111
Bob 17.1 1112 == **TP/BIN 16-bit Start pulse timer** ==
1113
Bob 18.1 1114 **TP(P)**
Bob 17.1 1115
1116 Specify the T timer device in (s1), the expected time in (s2), and the time base (resolution) in (s3). And output TRUE in the set time of "(s2)*(s3)" product.
1117
1118 PLC Editor2 version that supports this instruction: 2.3.1 and above.
1119
1120 -[TP (s1) (s2) (s3)]
1121
1122 **Content, scope, data type**
1123
1124 |**parameter**|**Content**|**range**|**type of data**|**Data type (label)**
1125 |(s1)|T device|0~~511|Signed BIN 16 bit|ANY16_S
1126 |(s2)|Expected time|0~~32767|Signed BIN 16 bit|ANY16_S
1127 |(s3)|Time base(resolution)|1/10/100/1000/10000|Signed BIN 16 bit|ANY16_S
1128
1129 **Device used**
1130
1131 |(% rowspan="2" %)**instruction**|(% rowspan="2" %)**parameter**|(% colspan="24" %)**Devices**|**Offset modification**|**Pulse extension**
1132 |**X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**
1133 |(% rowspan="3" %)TON|Parameter 1| | | | | | | | | | | | | | |●| | | | | | | | | | |
1134 |Parameter 2| | | | | | | | | | |●|●|●|●| |●|●|●|●| | |●|●| | |
1135 |Parameter 3| | | | | | | | | | | | | | | | | | | | | |●|●| | |
1136
1137 **Timing Chart**
1138
Bob 18.1 1139 (% style="text-align:center" %)
Bob 28.1 1140 [[image:图片7.png]]
Bob 17.1 1141
1142 **Features**
1143
1144 Timer that outputs TRUE only for the set time after startup
1145
1146 1) When the enable input is turned on, timer (s1) is started and timer (s1) bit is immediately turned on. Timer (s1) stops as time increases and reaches the expected time.
1147
1148 2) After timer (s1) reaches the predetermined time (s2), timer (s1) bit is disconnected. At this time, timer (s1) stops increasing. If the enable input becomes FALSE, timer (s1) will reset. The expected time (s2) becomes 0.
1149
1150 3) After starting, if the enable input becomes FALSE before the timer (s1) reaches the expected time (s2), the timer will be reset after reaching the expected time (s2).
1151
1152
1153 |**S3 time base**|**Actual value**
1154 |1|100us
1155 |10|1ms
1156 |100|10ms
1157 |1000|100ms
1158 |10000|1s
1159
1160 **Precautions**
1161
1162 • Avoid timer number conflict: the same timer number cannot be used for TON, TONR, TOF, TP, OUT_T timers at the same time. For example, TON T32 and TOF T32 cannot be used at the same time (it may cause data confusion and not achieve the effect of the corresponding instruction function).
1163
1164 **Error code**
1165
1166 |**Error code**|**Content**
1167 |4084H|Input data in (s2) (s3) is outside the specified range.
1168 |4085H|Device tpye in (s1) (s2) (s3) is outside the specified range.
1169 |4086H|Device tpye in (s1) is outside the specified range.
1170
1171 **Example**
1172
Bob 18.1 1173 (% style="text-align:center" %)
Bob 28.1 1174 [[image:图片8.png]]
Bob 17.1 1175
1176 T1 is used for storing time, setting the expected time as K5 and the time base as K10000.
1177
1178 When the enable input (M8) is on, the timer (T1) is started and the timer (T1) bit turns on immediately. Timer (T1) stops as time increases and reaches the expected time.
1179