Wiki source code of 16 PLC Editor2 help

Version 72.1 by Jim on 2023/08/10 15:24

Show last authors
1 (((
2 = **1 Quick start** =
3 )))
4
5 This chapter briefly introduces the use of our PLC programming software (PLC editor2) to write a simple PLC control program and programming operations to help beginners get familiar with and master the operation of our programming software as soon as possible. The following are the development steps of PLC:
6
7 * Step 1: Start our PLC editor2 and enter the programming window.
8 * Step 2: Click "New" to pop up the "New Project" window, and set "PLC Series", "PLC Type" and "Program Language".
9 * Step 3: Click "Program" in the "Project Management" area to start writing the ladder diagram program.
10 * Step 4: Add instructions.
11 * Step 5: Save the program project (when the program has a specified save path, the software will save the current program regularly).
12 * Step 6: Compile the program.
13 * Step 7: Establish a communication connection with PLC.
14 * Step 8: Download the program to the PLC.
15 * Step 9: Start the PLC (RUN state).
16
17 == Start the software ==
18
19 After PLC editor 2 is correctly installed, click on PLC Editor2 in the Windows start menu to start the PLC programming software and enter the main programming screen, which is shown in the following figure:
20
21 (% style="text-align:center" %)
22 [[image:image-20220623161849-29.jpeg||height="861" width="1440"]]
23
24 == Create a project ==
25
26 After starting the programming environment, you first need to create a new project. Click "New" to pop up the "New Program" window, you can select or create a new project:
27
28 * PLC series
29 * PLC model
30 * PLC language
31
32 **To create a new project, please operate as shown in the figure below:**
33
34 1. Move the mouse to the upper left corner of the program, and click the "File" menu.
35 1. After clicking the "File"  menu, a new dialog box will pop up.
36
37 (% style="text-align:center" %)
38 [[image:image-20220623134722-3.jpeg||height="348" width="429"]]
39
40 (% start="3" %)
41 1. Select "PLC Series", "PLC Model" and "Program Language" through the drop-down box.
42 1. Click the "OK" button to create a new project.
43
44 (% style="text-align:center" %)
45 [[image:image-20220623134805-4.jpeg]]
46
47 In this example, we select a 5V type PLC, using ladder diagram as the programming language, after completing the steps of creating a new project, as shown in the following figure:
48
49 [[image:image-20220623135152-5.jpeg]]
50
51 (% class="box infomessage" %)
52 (((
53 **✎Note:** For the operation of specific project management function, please refer to the relevant chapters.
54 )))
55
56 == Add instructions ==
57
58 1. When a project is created, expand the directory tree of "Project Manager".
59
60 (% style="text-align:center" %)
61 [[image:image-20220629110655-2.jpeg]]
62
63 (% start="2" %)
64 1. After expanding "Project Manager", click "Instructions" ->"Basic instructions", select the specific instruction,such as "LD".
65
66 (% style="text-align:center" %)
67 [[image:image-20220623140414-8.jpeg||height="598" width="268"]]
68
69 (% start="3" %)
70 1. Press and hold the mouse, select "LD" and drag it to the right "Ladder Diagram (Write)"" input box, place it in the specified position, and release the left mouse button. Then you can input the parameters and click "OK".
71
72 (% style="text-align:center" %)
73 [[image:image-20220625113552-26.jpeg]]
74
75 (% style="text-align:center" %)
76 [[image:image-20220625113604-27.jpeg||height="184" width="916"]]
77
78 (% class="box infomessage" %)
79 (((
80 **✎Note: **
81
82 * In addition to the system default parameters, the input and output of some added commands are empty, and the user needs to input parameters or component addresses.
83 * If you want to add multiple instructions, repeat the above operation until all the instructions are added.
84 )))
85
86 == Compile program ==
87
88 After the program is written, it needs to be compiled and saved, which can be achieved by pressing F4 on the keyboard or the Compile button in the program panel, as shown in the figure below.
89
90 (% style="text-align:center" %)
91 [[image:image-20220623144306-12.jpeg]]
92
93 If compiled successfully, it is shown as below.
94
95 (% style="text-align:center" %)
96 [[image:image-20220623144157-11.jpeg]]
97
98 If compilation fails, it is shown as below.
99
100 (% style="text-align:center" %)
101 [[image:image-20220623153633-19.jpeg]]
102
103 All errors will be displayed in the list box. You could select the specified error information, double-click the specified information with the left mouse button, and the system will automatically locate the error or warning position, which is convenient for you to debug the program.
104
105 (% class="box infomessage" %)
106 (((
107 **✎Note:** The program could be downloaded to the PLC only when the compilation is successful or there are no errors.
108 )))
109
110 == Communication test ==
111
112 The communication test is to improve the connection stability of the PLC and PC, and avoid the loss of force majeure during the transmission process.
113
114 **Preparation steps:**
115
116 1. Open and run PLC Editor.
117 1. Click "Transfer Settings] of "Online" module above the program panel. As shown below:
118
119 (% style="text-align:center" %)
120 [[image:image-20220623145502-14.jpeg]]
121
122 (% start="3" %)
123 1. The "Transfersettings" dialog box pops up, when the "Detailed settings" is not checked, select the specified port, it is as shown in the figure below.
124
125 (% style="text-align:center" %)
126 [[image:image-20220623154113-20.jpeg]]
127
128 * **USB connection:** This download interface is only supported when using the PLC's USB port to download programs or monitor devices. If a USB device is currently connected, the software system defaults to the "PLC USB interface" button.
129 * **Ethernet configuration": **You could select the corresponding NIC and configure the IP address to connect the PLC with Ethernet function, or search the devices in the LAN by the device search function!
130 ** (% class="box infomessage" %)
131 (((
132 **✎Note:** Currently Ethernet is only supported by 5V-N series and 6V series.
133 )))
134 * **Serial port (COM) connection**: Used when downloading programs or monitoring device using the PLC's round head (8-pin head).
135
136 (% start="4" %)
137 1. When the "Detailed Settings" option box is checked, the detailed settings window will pop up as below. You could set data according to their needs.
138
139 (% style="text-align:center" %)
140 [[image:image-20220623154122-21.jpeg]]
141
142 (% class="box infomessage" %)
143 (((
144 **✎Note:** The range of communication time check is 0 to 9999, and the number of repetitions is 0 to 5. Please do not exceed the limited range.
145 )))
146
147 (% start="5" %)
148 1. After completing the settings, you could click the "Communication Test" or "OK" to perform a connection test.
149 1. If the test fails, the system will prompt as below.
150
151 (% style="text-align:center" %)
152 [[image:image-20220623153332-17.jpeg]]
153
154 (% start="7" %)
155 1. The connection is successful as shown in the figure below:
156
157 (% style="text-align:center" %)
158 [[image:image-20220623153337-18.jpeg]]
159
160 (% start="8" %)
161 1. After successful communication, you could click “Device Info“ to view the device information.
162
163 (% style="text-align:center" %)
164 [[image:image-20220623154456-22.jpeg]]
165
166 == Download program ==
167
168 **Work to be done before downloading:**
169
170 1. Open the compiler;
171 1. Create a new project and make the project compile successfully;
172 1. Install the corresponding PLC driver on the PC and connect the PLC and PC;
173 1. Complete the communication setting through the compiler.
174
175 **Start downloading**
176
177 * After completing the preparations, move the mouse to the Online module, and click the "Write to PLC" button to open the download setting window, as shown in the figure below:
178
179 (% style="text-align:center" %)
180 [[image:image-20220623155646-23.jpeg]]
181
182 * The online operation window is shown in the figure below:
183
184 (% style="text-align:center" %)
185 [[image:image-20220623160440-24.jpeg]]
186
187 * Click "Param+Prog (P)" button, and the system will automatically select the preset option in the message box. After the configuration is completed, click "Execute" . As shown below:
188
189 (% style="text-align:center" %)
190 [[image:image-20220623160446-25.jpeg]]
191
192 * After clicking "Execute", the system will automatically pop up a prompt window. Clicking "Yes" means stop the PLC operation and start downloading the PLC program. Clicking "No" means that the PLC will not be stopped, and the program will not be downloaded to the PLC. As shown below:
193
194 (% style="text-align:center" %)
195 [[image:image-20220623160453-26.jpeg]]
196
197 * After clicking "Yes", the download and compile window will start to run. As shown below:
198
199 (% style="text-align:center" %)
200 [[image:image-20220623160458-27.jpeg||height="619" width="742"]]
201
202 * When the progress bar in the download window completes the progress, the system will promt "Write to PLC(Complete)". As shown below:
203
204 (% style="text-align:center" %)
205 [[image:image-20220623160503-28.jpeg]]
206
207 = **2 Overall introduction** =
208
209 After the software is started, enter the main interface, as shown in the figure below:
210
211 [[image:image-20220623161945-30.jpeg]]
212
213 == Toolbar ==
214
215 Most of the functions of the software can be found here, which are divided into PLC, view and help.
216
217 [[image:image-20220625155137-1.jpeg]]
218
219 1. There are functions such as ladder diagram symbol, comment statement editing mode, compilation, communication function and encryption tool in the PLC classification, which will be explained in detail in the following chapters.
220 1. Functions such as each floating window and ladder diagram display scale can be enabled in the view classification.
221 1. The help of the software can be viewed in the help category, and the software version number information can be viewed through the about button of the category.
222
223 == Project management ==
224
225 It is used to create new programs, operate program pages or program blocks, and configure PLC parameters.
226
227 (% style="text-align:center" %)
228 [[image:image-20220623162814-32.jpeg]]
229
230 == Ladder editing ==
231
232 In short, it is the module for development. In this module, you could write programs, configure PLC and other development. At the same time, you could add, delete, modify and check PLC through this module.
233
234 (% style="text-align:center" %)
235 [[image:image-20220625113828-28.jpeg||height="197" width="983"]]
236
237 == Floating windows ==
238
239 It is used to display or realize a specific function, which will be explained in detail in the following chapters.
240
241 (% style="text-align:center" %)
242 [[image:image-20220629110748-3.jpeg]]
243
244 **Status bar:** used to display the status of the PLC or program page.
245
246 (% style="text-align:center" %)
247 [[image:image-20220623163359-35.jpeg]]
248
249 = **3 PLC function menu** =
250
251 == Clipboard ==
252
253 Clipboard is a basic function of PLC Editor2 and has a very important function. This chapter will explain the basic description of the clipboard.
254
255 The clipboard has five functions: "Cut", "Copy", "Paste", "Undo" and "Redo".
256
257 (% style="text-align:center" %)
258 [[image:image-20220623170127-36.jpeg]]
259
260 * **Cut: **After selecting the ladder diagram, you could use the "Ctrl+X" command or the right mouse button to cut the selected data to the memory and switch to other places for use.
261 * **Copy:** After selecting the ladder diagram, you could use the "Ctrl+C" command or the right mouse button to copy the specified data.
262 * **Paste: **After selecting the ladder diagram, you can use the "Ctrl+V" command or the right mouse button to paste the specified data.
263 * **Undo:** Through "Ctrl+Z" or the right mouse button, the event operated by the user can be rolled back. Only when the software is running continuously, and the cancellation cache will be cleared if you exit.
264 * **Redo: **Through the "Ctrl+Y" or the right mouse button, you could return to the previous action after canceling the event.
265
266 == Ladder symbol ==
267
268 PLC Eidtor provides powerful and complete functions in the menu bar, which can greatly improve programming efficiency, as shown in the following figure:
269
270 (% style="text-align:center" %)
271 [[image:image-20220623171113-37.jpeg||height="120" width="247"]]
272
273 **The following table is a detailed description of the ladder diagram.**
274
275 |=(% scope="row" style="width: 107px;" %)**Image**|=(% style="width: 378px;" %)**Instruction**|=(% style="width: 371px;" %)**Command function description**|=(% style="width: 220px;" %)**Hot key**
276 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_17467c64c59b7dcc.jpg||height="35" width="35"]]|(% style="width:378px" %)LD AND|(% style="width:371px" %)Input series normally open |(% style="width:220px" %)F5
277 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_78ee1c120297f15c.jpg||height="35" width="35"]]|(% style="width:378px" %)OR|(% style="width:371px" %)Input parallel normally open|(% style="width:220px" %)SHIFT+F5
278 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_6d69b74c12b3d4ac.jpg||height="35" width="35"]]|(% style="width:378px" %)LDI ANI|(% style="width:371px" %)Input series normally close|(% style="width:220px" %)F6
279 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_16ca0a4e28932a25.jpg||height="35" width="35"]]|(% style="width:378px" %)ORI|(% style="width:371px" %)Input parallel normally open|(% style="width:220px" %)SHIFT+F6
280 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_91ad97fbb1766cde.jpg||height="35" width="35"]]|(% style="width:378px" %)OUT|(% style="width:371px" %)Ladder diagram output coil|(% style="width:220px" %)F7
281 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_bb11bf59792412cb.jpg||height="35" width="35"]]|(% style="width:378px" %)CJ/CALL and other application instructions|(% style="width:371px" %)Inpuyt application instructions|(% style="width:220px" %)F8
282 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_e11c169668fbc3d7.jpg||height="35" width="35"]]|(% style="width:378px" %) |(% style="width:371px" %)Ladder diagram input horizontal line|(% style="width:220px" %)F9
283 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_25d3575219c37c40.jpg||height="35" width="35"]]|(% style="width:378px" %) |(% style="width:371px" %)Ladder diagram input vertical line|(% style="width:220px" %)F11
284 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_e1fd81d831e4cc1e.jpg||height="35" width="35"]]|(% style="width:378px" %) |(% style="width:371px" %)Delete horizontal line in ladder diagram|(% style="width:220px" %)CTRL+F9
285 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_50a964bc9aa2388f.jpg||height="35" width="35"]]|(% style="width:378px" %) |(% style="width:371px" %)Delete vertical line in ladder diagram|(% style="width:220px" %)CTRL+F11
286 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_4c194d2b4c3e9166.jpg||height="35" width="35"]]|(% style="width:378px" %)LDP ANP|(% style="width:371px" %)Input series rising edge pulse|(% style="width:220px" %)SHIFT+F7
287 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_4e945174029d8824.jpg||height="35" width="35"]]|(% style="width:378px" %)LDF ANF|(% style="width:371px" %)Input series falling edge pulse|(% style="width:220px" %)SHIFT+F8
288 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_94c5f7c4566eeb6e.jpg||height="35" width="35"]]|(% style="width:378px" %)ORP|(% style="width:371px" %)Input parallel rising edge pulse|(% style="width:220px" %)CTRL+ALT+F7
289 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_fe027a1353a855e2.jpg||height="35" width="35"]]|(% style="width:378px" %)ORF|(% style="width:371px" %)Input parallel falling edge pulse|(% style="width:220px" %)CTRL+ALT+F8
290 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_8213f80a4dec5ecc.jpg||height="35" width="35"]]|(% style="width:378px" %)INV|(% style="width:371px" %)Invert the result of the operation|(% style="width:220px" %)CTRL+ALT+F11
291 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_bd63cbbc541dc1c9.png||height="35" width="35"]]|(% style="width:378px" %) |(% style="width:371px" %)Line segment input|(% style="width:220px" %)SHIFT+F9
292 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_fb82ee5fc2b94c23.png||height="42" width="35"]]|(% style="width:378px" %) |(% style="width:371px" %)Line segment deletion|(% style="width:220px" %)SHIFT+F11
293 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_236aac83ad0c365e.png||height="37" width="35"]]|(% style="width:378px" %)MEP|(% style="width:371px" %)Rising edge pulsing of operation results|(% style="width:220px" %)ALT+F5
294 |=(% style="width: 107px;" %)[[image:5V帮助文档_中性_html_fc7bf55c55a8fc75.png||height="35" width="35"]]|(% style="width:378px" %)MEF|(% style="width:371px" %)Falling edge pulsing of operation results|(% style="width:220px" %)CTRL+ALT+F5
295
296 == Comment&statement ==
297
298 Editing comments or statement is mainly to comment the code in the project to better interpret the project.
299
300 As shown in the figure below, it enters the editing state.
301
302 (% style="text-align:center" %)
303 [[image:image-20220623172114-38.jpeg||height="129" width="125"]]
304
305 === Edit comment ===
306
307 Function: Comment on the device.
308
309 Prerequisite: devices are required on the ladder diagram.
310
311 Step:
312
313 1. Click the "Comment" button, when the button color becomes darker, it will enter the editing state.
314 1. After successfully entering the edit comment state, move the mouse to the code segment specified by you, and double-click the target area with the left button, and the "Comment Edit” window will pop up.
315 1. At this time, you could enter the specified comment in the column input box.
316 1. After editing the comment, click “Execute" to save it.
317
318 (% class="box infomessage" %)
319 (((
320 **✎Note:** The comment can be edited up to 128 characters, and the alias can be edited up to 8 characters.
321 )))
322
323 (% style="text-align:center" %)
324 [[image:image-20220623172401-39.jpeg]]
325
326 **Result:**
327
328 (% style="text-align:center" %)
329 [[image:image-20220623172710-40.jpeg]]
330
331 === Edit statement ===
332
333 Function: Annotate the ladder diagram block.
334
335 **Step:**
336
337 1. Click the "Statement" button, when the button color becomes darker, it will enter the editing state.
338 1. After successfully entering the edit statement state, move the mouse to the code segment specified by you, and double-click the target area with the left button, and the "Statement Edit" window will pop up.
339 1. At this time, you could enter the specified statement in the previous input box.
340 1. After editing the statement, click "Execute" to save it.
341
342 (% class="box infomessage" %)
343 (((
344 **✎Note:** The statement line can edit up to 64 characters, and the statement can be downloaded to the PLC when downloading the ladder diagram.
345 )))
346
347 (% style="text-align:center" %)
348 [[image:image-20220623172907-41.jpeg]]
349
350 **Result:**
351
352 (% style="text-align:center" %)
353 [[image:image-20220623172913-42.jpeg]]
354
355 == Program compilation ==
356
357 This chapter mainly introduces the program compilation function.
358
359 The program compilation menu has three functions, including compile, switch, and compile all, as shown in the figure below:
360
361 (% style="text-align:center" %)
362 [[image:image-20220624090820-2.jpeg]]
363
364 === Compile ===
365
366 Function: Refers to the form of converting the ladder diagram (program) of the current program page into the instruction list (IL).
367
368 Steps: After compiling the ladder diagram, click compile or use the hot key F4.
369
370 Results:
371
372 * Compiling correctly will prompt that the compilation is successful.
373
374 (% style="text-align:center" %)
375 [[image:image-20220624091026-3.jpeg]]
376
377 * Failure will prompt compilation failure. Locate the error and go to the information output window. You could modify the ladder diagram according to the prompts.
378
379 (% style="text-align:center" %)
380 [[image:image-20220629110819-4.jpeg]]
381
382 (% style="text-align:center" %)
383 [[image:image-20220629110833-5.jpeg]]
384
385 * Double coil inspection, manifested in the form of warning.
386
387 (% style="text-align:center" %)
388 [[image:image-20220624092222-6.png||height="244" width="618"]]
389
390 === Switch ===
391
392 Function: refers to switching the current program page between the ladder diagram interface and the instruction list (IL) interface.
393
394 Steps: Click the switch button on the program page interface.
395
396 Results:
397
398 * In the compiled program page, click to switch to the instruction list interface.
399
400 (% style="text-align:center" %)
401 [[image:image-20220624093016-7.jpeg||class="img-thumbnail"]]
402
403 * In the uncompiled program page, the prompt "The current ladder diagram is not compiled. Do you want to abandon the current ladder diagram?" Click "Yes" to abandon the editing ladder diagram and convert it to the instruction list, click "No" not to switch.
404
405 (% style="text-align:center" %)
406 [[image:image-20220624094410-9.jpeg||height="380" width="946"]]
407
408 === Compile all ===
409
410 Function: Refers to converting the ladder diagram of all programs under the current project into the form of instruction list (IL).
411
412 Steps: Click the compile all button or use the shortcut key Ctrl+F4.
413
414 Expected: As long as there is a compilation error, it will prompt compilation failure, and only when all compilation succeeds will it prompt compilation success.
415
416 (% style="text-align:center" %)
417 [[image:image-20220624095005-10.jpeg]]
418
419 == Program mode ==
420
421 === Monitor mode ===
422
423 Function: monitor the value of the devices on the ladder diagram, modify and debug the program.
424
425 **Step:**
426
427 * Connect to the PLC and switch to monitoring mode.
428
429 (% style="text-align:center" %)
430 [[image:image-20220624095815-11.jpeg||height="860" width="1440"]]
431
432 * Right-click the menu, click "Debug" to modify the value of the device.
433
434 (% style="text-align:center" %)
435 [[image:image-20220624095855-12.jpeg||class="img-thumbnail"]]
436
437 * Click the ON, OFF, or ON/OFF inversion to set the device.
438
439 (% style="text-align:center" %)
440 [[image:image-20220624100037-13.jpeg]]
441
442 === Monitor edit ===
443
444 PLC Editor2 provides the "Monitor edit" function. You could edit ladder program in the state of monitoring it.
445
446 Steps:
447
448 * Connect to PLC and switch to "Monitor edit" mode.
449
450 (% style="text-align:center" %)
451 [[image:image-20220624101413-14.jpeg]]
452
453 * Modify ladder diagram
454
455 (% style="text-align:center" %)
456 [[image:image-20220624101446-15.jpeg]]
457
458 * Compile the ladder diagram
459
460 (% style="text-align:center" %)
461 [[image:image-20220624101510-16.jpeg||height="861" width="1440"]]
462
463 * After the compilation, download it to PLC.
464
465 (% style="text-align:center" %)
466 [[image:image-20220624101609-17.jpeg]]
467
468 (% class="box infomessage" %)
469 (((
470 **✎Note:** The firmware version requires above v2.000 version.
471 )))
472
473 == Online ==
474
475 The online menu provides rich functions. It is mainly divided into 10 parts: Transfer settings, Read from PLC,Write to PLC, Checksum PLC, PLC Diagnosis, Remote operation, Device monitor, Module monitoring, Clear PLC memory, and PLC clock set.
476
477 (% style="text-align:center" %)
478 [[image:image-20220624103113-18.jpeg]]
479
480 === Transfer settings ===
481
482 Function: The main purpose is to improve the stability of the PLC and PC, and to avoid force majeure problems during transmission that could lead to losses.
483
484 **Steps:**
485
486 Open PLC Editor2, and click "Online" ->"Transfer Settings". As shown below:
487
488 (% style="text-align:center" %)
489 [[image:image-20220624103242-19.jpeg]]
490
491 "Transfer setting" dialog box will pop up. When using USB connection, select the specified port, it is as shown in the figure below.
492
493 (% style="text-align:center" %)
494 [[image:image-20220624103637-20.jpeg]]
495
496 When using Ethernet configuration, you could click "Devices research" to select the corresponding NIC and configure the IP address to connect the PLC with Ethernet function,
497
498 **✎Note:** Currently Ethernet configuration is only supported by 5V-N series and 6V series.
499
500 (% style="text-align:center" %)
501 [[image:image-20220624105239-21.jpeg]]
502
503 Click "Devices research" to pop up a search page, as shown below.
504
505 (% style="text-align:center" %)
506 [[image:image-20220624105429-22.jpeg||height="367" width="627"]]
507
508 **Description: **Clicking "Device search", it will automatically search for all PLC devices supporting Ethernet in the network segment matching subnet mask, i.e., the host computor and PLC must be in the same subnet to be recognized.
509 **The subnet mask matches the network segment:**
510
511 * If the IP of this machine is 192.168.56.237 and the subnet mask is 255.255.255.0, the PLC within the 192.168.56 network segment will be searched.
512 * If the IP of this machine is 172.16.56.1 and the subnet mask is 255.255.0.0, the PLC in the 172.16 network segment will be searched.
513 * If the IP of this machine is 10.244.56.9 and the subnet mask is 255.0.0.0, then the PLC in the 10 network segment will be searched.
514
515 **✎Note:** The NIC used for the IP search function is the NIC selected by the user of the NIC selection interface.
516 **Use:** Click "Device search" to search for devices in the LAN, and the searched devices are displayed on the interface. Selecting the corresponding line and clicking the "OK", the corresponding IP information will be displayed in the IP address input box of the Ethernet configuration. Please refer to the PLC programming manual for the specific PC network address configuration.
517
518 When using the serial port to connect, select the specified port and check the "Detailed setting", the detailed settings window will pop up as below.
519
520 (% style="text-align:center" %)
521 [[image:image-20220625114042-29.jpeg]]
522
523 You could set the data according to their needs.
524
525 **✎Note: **The range of communication time check is 0 to 9999, and the number of repetitions is 0 to 5. Please do not exceed the limited range.
526
527 After completing the settings, you could click the "Communication Test" or "OK" to perform a connection test.
528
529 If the test fails, the system will prompt as below.
530
531 (% style="text-align:center" %)
532 [[image:image-20220624111448-24.jpeg]]
533
534 Successful connection is shown as below.
535
536 (% style="text-align:center" %)
537 [[image:image-20220624111451-25.jpeg||height="186" width="285"]]
538
539 After successful communication, you can click "Device Info" to view the device information.
540
541 (% style="text-align:center" %)
542 [[image:image-20220624111617-26.jpeg]]
543
544 === Read from PLC ===
545
546 **Function: **Upload the data in the series PLC to the software through the communication line.
547
548 (% style="text-align:center" %)
549 [[image:image-20220624114311-27.jpeg]]
550
551 **Interface introduction:**
552
553 * **Para + program: **Upload parameters and programs from the PLC to the software.
554 * **Select all:** Upload parameters, programs, comments, devices memory area settings and electronic cam tables from the PLC to the software.
555 * **Cancel all select:** Cancel all selections.
556 * **Execute: **Start the upload operation.
557 * **Stop: **Stop the upload operation.
558 * **Close:** Exit the current window.
559 * **Execute (upload):** Upload the data of the lower computer to the software.
560 * **Display/Hide: **Display/hide the upload progress and other information, as shown in the figure below:
561
562 (% style="text-align:center" %)
563 [[image:image-20220624114427-28.jpeg]]
564
565 **Steps:**
566
567 Check the data items that need to be uploaded.
568
569 * If the selected data item is device memory, you could click "set" to set the title of the uploaded device memory and the range of the device to be uploaded.
570
571 [[image:image-20220624114632-29.jpeg]]
572
573 * If the selected data item is electronic cam table, you could click "set" to set the title of the uploaded electronic cam table and the uploaded cam table.
574
575 (% style="text-align:center" %)
576 [[image:image-20220624114647-30.jpeg]]
577
578 Click "Execute" to start uploading. At this time, the PLC needs to be in the stop state.
579
580 (% style="text-align:center" %)
581 [[image:image-20220624114918-31.jpeg]]
582
583 Keep communication and wait for the upload to complete.
584
585 (% style="text-align:center" %)
586 [[image:image-20220624114941-32.jpeg]]
587
588 === Write to PLC ===
589
590 **Function: **Download the ladder diagram program or other configuration to the PLC.
591
592 (% style="text-align:center" %)
593 [[image:image-20220624115206-33.jpeg]]
594
595 **Interface introduction:**
596
597 * **Para + program:** Download parameters and programs to the PLC.
598 * **Select all: **Download parameters, programs, comments, and devices memory area settings to the PLC.
599 * **Cancel all selections:** Cancel all selections.
600 * **Execute: **start the download operation.
601 * **Stop: **stop the download operation.
602 * **Close:** Exit the current window.
603 * **Calculated size:** To calculate the number of steps of the ladder diagram, the size of the downloaded file and the size of the comment, it needs to be connected to the PLC.
604 * **Display/Hide:** Display/hide the download progress and other information, as shown in the figure below.
605
606 (% style="text-align:center" %)
607 [[image:image-20220624115419-34.jpeg]]
608
609 **Step:**
610
611 Check the data items that need to be downloaded.
612
613 * If the selected data item is device memory, you could click "set" to set the title of the uploaded device memory and the range of the device to be downloaded.
614
615 (% style="text-align:center" %)
616 [[image:image-20220624115440-35.jpeg]]
617
618 The PLC needs to be in the stop state when downloading.
619
620 (% style="text-align:center" %)
621 [[image:image-20220624115451-36.jpeg]]
622
623 Keep communication and wait for the download to complete.
624
625 (% style="text-align:center" %)
626 [[image:image-20220624115455-37.jpeg]]
627
628 === Device monitor ===
629
630 **Function: **You can view and modify PLC register values and expansion module values online. Click this item to pop up the interface as shown in the figure below.
631
632 [[image:image-20220624134515-1.jpeg]]
633
634 **Interface description:**
635
636 * Monitoring start: start the current monitoring, the value of the register can be viewed or modified.
637 * End of monitoring: End the current monitoring, the value of the register cannot be viewed or modified.
638 * Edit current value: After clicking, a dialog box named "Modify device value" will pop up, and you could modify it.
639 * Close: Close the "Device Monitor” interface.
640
641 **Step:**
642
643 * Click "device monitor" to open the interface.
644
645 (% style="text-align:center" %)
646 [[image:image-20220624135018-2.jpeg]]
647
648 * Click "monitoring start" button under the premise of communicating with the PLC.
649
650 (% style="text-align:center" %)
651 [[image:image-20220624135057-3.jpeg]]
652
653 * The devices can be monitored by modifying the monitoring form, display, numerial and bit order .
654
655 (% style="text-align:center" %)
656 [[image:image-20220624135102-4.jpeg]]
657
658 * Switch device, search device and switch to monitor buffer memory.
659
660 [[image:image-20220624135106-5.jpeg]]
661
662 === Clear PLC memory ===
663
664 **Function**: Clear the data of the PLC
665
666 (% style="text-align:center" %)
667 [[image:image-20220624135402-6.jpeg]]
668
669 **Step:**
670
671 1. Before clearing the PLC memory, the PLC needs to be in the stop state.
672 1. Check the data object. If the PLC memory is checked, it includes but is not limited to data devicess, bit devicess and special devicess.
673 1. Click "Execution" and wait for the PLC to clear the data.
674
675 === PLC clock set ===
676
677 **Function:** Set the PLC clock. You could customize the internal time of the PLC to achieve the purpose of accurate calculation.
678
679 Click “ PLC clock set" to open the clock setting interface.
680
681 (% style="text-align:center" %)
682 [[image:image-20220624143649-1.jpeg]]
683
684 **Explanation:**
685
686 * Connection: Display the information of the currently PLC, read the parameters of this PLC, and cannot be changed.
687 * Time and calendar area: you can easily select time information and match freely.
688 * Read PC time: The software will automatically read the current PC time without manual calibration.
689 * Set time: After finishing the setting, click this button to save the current operation setting to the PLC.
690 * Close: Do not save the current operating data, and exit to close this window.
691
692 **Set time:**
693
694 1. Please ensure that the PLC and PC communicate normally. If it fails to communicate normally, please click "Transfer Settings" and put the PLC in the STOP state.
695 1. Click "PLC clock set" to open the time setting window.
696 1. Select the time required by the user in the time control panel or in the calendar panel.
697 1. The time interval of the year is 2000 to 2099; The interval of the month is January to December;
698 The time interval is from 0 o'clock to 23 o'clock; The partitions are from 0 minutes to 59 minutes; the second interval is from 0 seconds to 59 seconds.
699 1. You can also click [Get PC Time] to quickly match the current time (provided that the PC time is accurate).
700 1. After completing the configuration, please click "Set time" to save, otherwise it will not be saved. Successful setting is shown below.
701
702 (% style="text-align:center" %)
703 [[image:image-20220624143711-2.jpeg]]
704
705 === Remote operation ===
706
707 **Function: **Remote operation can quickly change the state of the PLC online and control the switch of the PLC.
708
709 (% style="text-align:center" %)
710 [[image:image-20220624144217-3.jpeg]]
711
712 === PLC diagnostics ===
713
714 **Function: **PLC diagnostics will monitor the errors generated by PLC in real time and reflect them in the table. You could view the summary of the error, the cause and the treatment method through this interface. If it is a problem with the ladder diagram, click Error Jump to jump to the location where the error occurred.
715
716 (% style="text-align:center" %)
717 [[image:image-20220624144649-4.jpeg||height="465" width="819"]]
718
719 === PLC checksum ===
720
721 **Function:** You could select the items that need to be verified by the PLC, as shown in the figure below:
722
723 (% style="text-align:center" %)
724 [[image:image-20220624145100-5.jpeg]]
725
726 Compare the difference between the program in the current PC software and the program in the PLC, as shown in the figure below:
727
728 (% style="text-align:center" %)
729 [[image:image-20220624145157-6.jpeg]]
730
731 Double-click the list, and you could view the specific differences of the program, as shown in the following figure:
732
733 (% style="text-align:center" %)
734 [[image:image-20220624145325-7.jpeg]]
735
736 === Module monitor ===
737
738 **Function:** This function is used to monitor the BFM value of the module and modify the BFM data. According to the description information corresponding to the BFM, the user can understand the function of the BFM.
739
740 **Interface description:**
741
742 * **Customization: **Create a new module plan, and use the default data as the initial value of the module BFM,. You could edit the plan content on this basis.
743 * **Save:** Create a new module plan, and use the current module monitoring data as the initial value of the module's BFM, You could  edit the plan content on this basis.
744 * **Help: **Open the instruction manual of the module where you could find the detailed instructions for the module.
745 * **Refresh: **You can update the module information of the current PLC connection and refresh the module information list.
746 * **Working mode:**
747 ** Offline: Display all module models that can be connected to the current PLC model. You could view the module BFM information when the module is not connected, or open the module instruction file through the "Help" button;
748 ** Online: Display the module information of the current PLC connection in the module information list, and monitor/modify the BFM value of the module.
749
750 **Step:**
751
752 * Click "Module Monitor".
753
754 (% style="text-align:center" %)
755 [[image:image-20220624151636-8.jpeg]]
756
757 * Select the module you want to monitor to o view and modify the value.
758
759 (% style="text-align:center" %)
760 [[image:5V帮助文档_中性_html_70be57a90d675c22.png||height="453" width="1200" class="img-thumbnail"]]
761
762 == Tool ==
763
764 === PLC encryption tool ===
765
766 In the PLC Editor2, you could set a password for the PLC to maintain security. The PLC encryption tool can be set to "upload password", "download password", and "clock password" respectively.
767
768 **Explanation:** The three types of passwords are independent (you must use separate decryption when performing operations), and the set passwords can be the same or different which ensure the safety and independence of PLC. As shown below:
769
770 (% style="text-align:center" %)
771 [[image:image-20220624152122-9.jpeg]]
772
773 **Precautions for setting a password:**
774
775 * The setting steps of "upload password", "download password", and "clock password" are exactly the same (only the type needs to be customized by the user).
776 * The length of the password can only be 8 characters, no more or less than.
777 * When setting a new password, the first time password and the second confirmation password must be the same.
778 * When performing password operations, please ensure that the PLC and PC are in a normal connection state, and the PLC must be in the NOT RUN state (close the switch of the PLC panel).
779 * When the password is entered incorrectly for 5 times, the password is locked, and the password can be entered again only when the PLC is restarted after power off.
780
781 **Steps to set password:**
782
783 * Connect the PLC and PC normally, and run the compiler at the same time;
784 * Turn off the RUN of the PLC;
785 * Click "PLC Encryption Tool" in the "Tool" panel;
786 * After opening a new window, if the "old password" input box cannot be entered, it means that the PLC is not currently encrypted;
787 * Select the type of password that needs to be set, and click "Set". (The following PLC takes uploading password as an example)
788
789 (% style="text-align:center" %)
790 [[image:image-20220624153523-10.jpeg]]
791
792 * Please follow the instructions to fill in the correct password.
793 * If the password length is not enough, there will be a prompt as follows:
794
795 (% style="text-align:center" %)
796 [[image:image-20220624153725-11.jpeg]]
797
798 * If the secondary password is inconsistent, there will be a prompt as shown below:
799
800 (% style="text-align:center" %)
801 [[image:image-20220624153816-12.jpeg]]
802
803 * If the password is successfully set, there will be a prompt as shown below:
804
805 (% style="text-align:center" %)
806 [[image:image-20220624153830-13.jpeg]]
807
808 **Clear password**
809
810 If the PLC does not have a password, ignore this description. If the PLC has a password, please enter the existing password if you need to clear the password. Please refer to the precautions for input errors more than 5 times.
811
812 (% style="text-align:center" %)
813 [[image:image-20220624154242-16.jpeg]]
814
815 **Steps to clear the password:**
816
817 * Connect the PLC and PC normally, and run the compiler at the same time;
818 * Turn off the RUN of the PLC;
819 * Click "PLC Encryption Tool" in the "Tool" panel;
820 * Select the PLC password to be cleared in "Type", and click "Clear".
821 * After opening a new window, please enter the specified password in the "Please enter password" area, and then click "Execute".
822 * If you input the wrong upload password, there will be a prompt as shown below:
823
824 (% style="text-align:center" %)
825 [[image:image-20220624154309-17.jpeg]]
826
827 * If the password is correct, there will be a prompt as shown below:
828
829 (% style="text-align:center" %)
830 [[image:image-20220624154314-18.jpeg]]
831
832 === **Project encryption tool** ===
833
834 In the PLC Editor2, you could set a password for the project file to maintain security. As shown below:
835
836 (% style="text-align:center" %)
837 [[image:image-20220624154810-19.jpeg||class="img-thumbnail"]]
838
839 **Precautions for setting a password:**
840
841 * The length of the password can only be 8 characters, no more or less than.
842 * When setting a new password, the first time password and the second confirmation password must be the same.
843 * When the password is entered incorrectly for 5 times, the password is locked, and the password can be entered again only when the project file is reopened.
844
845 **Steps to set password:**
846
847 * Click "Project encryption tool" in the "Tool" panel;
848 * After opening a new window, if the "old password" input box cannot be entered, it means that the PLC is not currently encrypted;
849 * Select the password that needs to be entered, and click "Set".
850
851 (% style="text-align:center" %)
852 [[image:image-20220624155700-20.jpeg]]
853
854 * Please follow the instructions to fill in the correct password.
855 * If the password is not long enough, there will be a prompt as shown below:
856
857 (% style="text-align:center" %)
858 [[image:image-20220624155810-21.jpeg]]
859
860 * If the secondary password is inconsistent, there will be a prompt as shown below:
861
862 (% style="text-align:center" %)
863 [[image:image-20220624155815-22.jpeg]]
864
865 * If the password is successfully set, there will be a prompt as shown below:
866
867 (% style="text-align:center" %)
868 [[image:image-20220624155841-23.jpeg]]
869
870 **Clear password**
871
872 If the project does not have a password, ignore this description. If the project has a password, please enter the existing password if you need to clear the password. Please refer to the precautions for input errors more than 5 times.
873
874 (% style="text-align:center" %)
875 [[image:image-20220624155909-24.jpeg]]
876
877 **Steps to clear the password:**
878
879 * Click "PLC Encryption Tool" in the "Tool" panel, and click "Clear".
880 * After opening a new window, please enter the specified password in the "Please enter password" area, and then click "Execute".
881 * If you input the wrong upload password, there will be a prompt as shown below:
882
883 (% style="text-align:center" %)
884 [[image:image-20220624155915-25.jpeg]]
885
886 * If the password is correct, there will be a prompt as shown below:
887
888 (% style="text-align:center" %)
889 [[image:image-20220624155920-26.jpeg]]
890
891 === USB download ===
892
893 **Function:** Generate a bin file. You could use the file to download programs and other configurations through the HMI screen.
894
895 **Step:**
896
897 * Click on the U disk to download and open the interface.
898
899 (% style="text-align:center" %)
900 [[image:image-20220624161054-27.jpeg]]
901
902 * Check the items that need to be downloaded, set the communication port parameters, and select the location of the U disk.
903
904 (% style="text-align:center" %)
905 [[image:image-20220624161153-28.jpeg]]
906
907 * Click "Excute" to generate the bin file.
908 * Insert the U disk into the HMI screen to download.
909
910 === Automatic backup ===
911
912 **Function**: Back up project files. You could view and retrieve historical versions through this function.
913
914 **Step:**
915
916 * Open the saved file, click compile, compile all, close the project, switch historical version or switch program type after editing. You could see the historical version number increase by clicking on the automatic backup window.
917
918 (% style="text-align:center" %)
919 [[image:image-20220624162512-29.jpeg]]
920
921 * Click the remark information to add remarks to the historical version, and click "OK" save it.
922 * Check the version number, and click "switch to this version", it will close the current version and load the historical version, as shown in the figure below:
923
924 (% style="text-align:center" %)
925 [[image:image-20220624162515-30.jpeg]]
926
927 === Generate download file ===
928
929 **Function:** Generate a file for download only, and the file cannot be viewed and uploaded.
930
931 **Step:**
932
933 1. Compile all the program pages, click to generate the download file.
934 1. Select the path and file name.
935 1. Open the generated **.swcp2** file and click download.
936
937 (% style="text-align:center" %)
938 [[image:image-20220624163706-1.jpeg]]
939
940 === Reset window layout ===
941
942 **Function:** Restore all floating windows in the program to the default position.
943
944 **Steps: **Click the reset window layout button in the view.
945
946 Before reset:
947
948 (% style="text-align:center" %)
949 [[image:image-20220624163720-2.jpeg]]
950
951 After reset:
952
953 (% style="text-align:center" %)
954 [[image:image-20220624163725-3.jpeg]]
955
956 = **4 Program editing area** =
957
958 In the program editing area, the user can freely switch between the ladder diagram and the instruction list. The ladder diagram interface provides editing operations. The instruction list interface is only allowed to be viewed and cannot be modified.
959
960 == Ladder work area ==
961
962 **Insert a new row**
963
964 * Select the position where you want to insert the row +1.
965 * Click on the keyboard "Shift] + Insert" to insert a new row, or move the mouse to any position of the specified insertion row, right-click, select "Edit"->"Insert row above (shift+insert)".
966
967 (% style="text-align:center" %)
968 [[image:image-20220625091617-1.jpeg]]
969
970 **Insert the statement**
971
972 Select the position where you want to insert the row.
973
974 * Method 1: Use the keyboard shortcut: Shift+Ctrl+Insert.
975
976 (% style="text-align:center" %)
977 [[image:image-20220625092707-2.jpeg]]
978
979 * Method 2: Keyboard shortcut "Ctrl+F7".
980
981 (% style="text-align:center" %)
982 [[image:image-20220625092847-3.jpeg]]
983
984 * Method 3: Right-click, select "Edit"->"Insert Statement".
985
986 (% style="text-align:center" %)
987 [[image:image-20220625092929-4.jpeg]]
988
989 **Delete row**
990
991 (% style="text-align:center" %)
992 [[image:image-20220625093015-5.jpeg]]
993
994 Move the mouse to the row to be deleted; press and hold the left mouse button to select and move the row to be deleted (multiple rows are possible), the selected area will change color, and then click "Delete" on the keyboard.
995
996 (% style="text-align:center" %)
997 [[image:image-20220625093149-6.jpeg]]
998
999 You could also select the row to be deleted, right-click to select "edit"->"delete row".
1000
1001 (% style="text-align:center" %)
1002 [[image:image-20220625093415-7.jpeg]]
1003
1004 **Delete the statement**
1005
1006 Same as row deletion.
1007
1008 **Insert column**
1009
1010 * Select the position where you want to insert the column.
1011 * Click the keyboard "Ctrl+ Insert" to insert, or move the mouse to any position of the specified insertion row, and right-click, to select "Edit" -> "Insert column to the left".
1012
1013 (% style="text-align:center" %)
1014 [[image:image-20220625094524-8.jpeg]]
1015
1016 (% style="text-align:center" %)
1017 [[image:image-20220625094809-10.jpeg]]
1018
1019 **Delete column**
1020
1021 1. Select the position of the column to be deleted.
1022 1. Press "Ctrl+Delete" on the keyboard to delete the column, or move the mouse to any position of the specified inserted row, right-click, and directly select "Delete", or select "Edit"->"Delete row".
1023
1024 Before deleting:
1025
1026 (% style="text-align:center" %)
1027 [[image:image-20220625094823-11.jpeg]]
1028
1029 After deleting:
1030
1031 (% style="text-align:center" %)
1032 [[image:image-20220625094828-12.jpeg]]
1033
1034 **Copy and paste**
1035
1036 The copy and paste function could save time and reduce the time on repeated operations.
1037
1038 **Steps**
1039
1040 * Move the mouse to the ladder editing area.
1041 * Select the specified cell or drag the mouse to select an area.
1042
1043 (% style="text-align:center" %)
1044 [[image:5V帮助文档_中性_html_d5aa6c70c096349a.png||height="155" width="700" class="img-thumbnail"]]
1045
1046 * Use the "Copy" button of "Clipboard" in the "PLC Menu", or use the right mouse button to "Copy", or use the keyboard "Ctrl+C".
1047
1048 (% style="text-align:center" %)
1049 [[image:image-20220625095651-14.jpeg]]
1050
1051 * After completing the third operation, copy the specified area to the clipboard.
1052 * Move the mouse to the designated position to be pasted, click the "Paste" button on the "Clipboard", or use the "Paste" move the mouse to the designated position to be pasted, click the "Paste" button on the "Clipboard", or use the "Paste" function of the right mouse button, or use the keyboard "Ctrl+V" to copy the specified data Copy to the specified location.
1053
1054 (% style="text-align:center" %)
1055 [[image:image-20220625095656-15.jpeg]]
1056
1057 **Delete and modify ladder diagram devices**
1058
1059 Steps:
1060
1061 1. The ladder diagram can be modified only in the "Edit mode" state.
1062
1063 (% style="text-align:center" %)
1064 [[image:image-20220625100200-16.jpeg]]
1065
1066 (% start="2" %)
1067 1. Use the mouse to select the components that needs to be modified, and double-click the left button or press the "Enter" key on the keyboard.
1068 1. After performing step 2, the output instruction dialog box will pop up.
1069 1. Enter the instruction corresponding to the selected component into the dialog box.
1070 1. Click "Execute" to save the modification.
1071
1072 **✎Note: **
1073
1074 1. The modified instruction must be able to pass the correct instruction verification before it can be saved.
1075 1. The contact element that occupies a cell (normally open, normally closed, rising edge, falling edge, reverse, stepping) cannot modify each other with the comparison contact.
1076 1. All contact components cannot be modified mutually with coils or application instructions.
1077
1078 **Delete ladder diagram components**
1079
1080 Steps:
1081
1082 1. The ladder diagram can be deleted only in the "Edit mode" state.
1083 1. Use the mouse to select the component grid that needs to be deleted, left-click, and the selected part will be locked with a blue frame, and then you could press "Delete" on the keyboard to delete it.
1084 1. Batch delete: Move the mouse to the specified delete area, hold down the left mouse button and drag the mouse, and select cells in batches (cells will turn blue). After completing the selection, you could press "Delete" on the keyboard to delete it.
1085 1. Delete horizontal and vertical lines: In this special ladder diagram, you could perform step 2 or 3 to select the target first, and then click the "CF9" icon or "CF11" in the "Ladder symbol" function of the menu bar to execute the corresponding deletion.
1086
1087 **Enter ladder diagram instructions**
1088
1089 There are 5 ways to input ladder diagram instructions:
1090
1091 1. Direct input
1092 1. Input through instruction set
1093 1. Double-click cell
1094 1. Instruction help
1095 1. Ladder symbol/Shortcut
1096
1097 Direct input method
1098
1099 * Move the mouse and left-click the specified cell.
1100 * Directly use the keyboard to input the specified instruction, the system will automatically pop up the ladder diagram input box.
1101
1102 (% style="text-align:center" %)
1103 [[image:image-20220625102401-17.jpeg]]
1104
1105 * Enter the complete instructions and parameters in the dialog box.
1106 * Click "Execute" or the "Enter" button on the keyboard.
1107 * The system verifies the correctness of the input, and generates the graphic element represented by the instruction after the verification is correct.
1108 * If the instruction is wrong, the instruction help interface will pop up.
1109
1110 (% style="text-align:center" %)
1111 [[image:image-20220625102414-18.jpeg]]
1112
1113 Input through instruction set
1114
1115 1. Move the mouse to the [Project Management] interface on the left side of the window.
1116 1. Expand "Instruction Set" and open the instruction tree you need
1117 1. Select the instruction you need, and left-click and hold, drag it to the "ladder diagram writing area", and place it in the specified area.
1118 1. After completing step above, a "ladder input " will pop up, then input the correct operand.
1119 1. Click "Execute" or "Enter" on the keyboard.
1120
1121 (% style="text-align:center" %)
1122 [[image:image-20220625103448-19.jpeg]]
1123
1124 Double-click the cell
1125
1126 1. Move the mouse to the specified area and double-click the left button.
1127 1. "Ladder input" pops up, enter the correct command in the input box.
1128 1. Click "Execute" or the keyboard "Enter".
1129 1. If the instruction is wrong, the instruction help interface will pop up.
1130
1131 (% style="text-align:center" %)
1132 [[image:image-20220625104404-20.jpeg||class="img-thumbnail"]]
1133
1134 Instruction help
1135
1136 1. Move the mouse to the designated area and double-click the left button to pop up “Ladder input”.
1137 1. Click “Help” to pop up “Instruction Help”。
1138 1. After selecting the instruction that needs to be entered, click the "Detail" button to pop up the "Instruction Wizard".
1139 1. The instruction guide interface selects the correct operand according to different instructions.
1140 1. After selecting the specified instruction, click "Execute" to save the data and complete the instruction input.
1141
1142 [[image:image-20220625105747-21.jpeg]]
1143
1144
1145 (% style="text-align:center" %)
1146 [[image:image-20220625105752-22.jpeg||class="img-thumbnail"]]
1147
1148 Ladder symbol/shortcut
1149
1150 The ladder diagram symbol is located in the PLC menu, as shown in the figure below:
1151
1152 (% style="text-align:center" %)
1153 [[image:image-20220625105848-23.jpeg||height="161" width="336"]]
1154
1155 After selecting the cell, click "Ladder Symbol" in the menu, and enter the operand in the pop-up ladder diagram input box to complete the instruction input. If it is an application instruction, after clicking [[image:5V帮助文档_中性_html_1c8d975fb5bd8c.png]] on the panel, you must input the complete application instruction and its operands in the ladder diagram input box to complete the input instruction. You can also use the shortcut corresponding to the command (see the shortcut key list) to input, and the operation method is the same as the "ladder symbol".
1156
1157 After the instruction input is completed, click the "Execute" button in the ladder diagram input box and it will be displayed in the ladder diagram editing area.
1158
1159 **✎Note: **
1160
1161 1. Some instructions can only be input in the instruction list (IL) editor, but not in the ladder diagram, such as MPS, MPP, etc. When these instructions are directly input in the ladder diagram, no components will be generated.
1162 1. Since coils and application instructions represent the end of one line of the ladder diagram program, no other components can be input after these components.
1163 1. Since the vertical line occupies the space of two lines, when inputting the vertical line, if the corresponding position in the next line is just the middle part of other components, the vertical line cannot be input.
1164 1. The maximum number of input columns in the ladder diagram is 13 columns.
1165
1166 == Instruction list work area ==
1167
1168 Instruction list editor
1169
1170 In the PLC Editor, the program not only provides a ladder diagram editor, but also provides an instruction list interface. The instruction list interface is not editable and only allowed to be viewed. As shown below:
1171
1172 (% style="text-align:center" %)
1173 [[image:5V帮助文档_中性_html_550c5cb7f37a8b23.png||height="190" width="300" class="img-thumbnail"]]
1174
1175 * **Step number: **The step number indicates the position of the instruction in the program, which can be used to quickly locate the program and improve the readability of the program.
1176 * **Ladder diagram-instruction list switching:** If there is an error in the program logic, it cannot be switched.
1177
1178 == **Shortcut menu** ==
1179
1180 In the program editing area, click the right mouse button to pop up frequently used function buttons, which can greatly improve the developer's development efficiency.
1181
1182 (% style="text-align:center" %)
1183 [[image:image-20220625111835-24.jpeg]]
1184
1185 **Undo:** Undo the current operation and roll back the previous step.
1186
1187 **Redo: **Roll back the undo operation.
1188
1189 **Cut:** Cut the selected content in the ladder diagram and put it on the clipboard.
1190
1191 **Copy: **Copy the selected content in the ladder diagram and put it on the clipboard.
1192
1193 **Paste:** Paste the data in the clipboard at the selected position in the ladder diagram. When there is no data in the clipboard, paste is not available.
1194
1195 **Delete:** Delete the selected content in ladder diagram.
1196
1197 **Compile:** Compile the current program page.
1198
1199 **Editing options:**
1200
1201 * Insert row: Insert an blank row in the current selected row in the ladder diagram.
1202 * Insert statement: Insert a blank staement row in the current selected row in the ladder diagram.
1203 * Delete row: Delete the currently selected row in the ladder diagram.
1204 * Insert column to the left: In the ladder diagram, a blank node is added to the selected instruction, and other instructions move one space to the right.
1205 * Delete column: In the ladder diagram, delete the currently selected instruction, and other instructions move one space to the left.
1206
1207 **Search:**
1208
1209 * Device search: open the search/replace window, the default is the device search page, if the selected instruction in the ladder diagram contains a device, the "search device" defaults to the selected instruction's device, and it will be empty if there is none.
1210 * Instruction search: Open the search/replace window, the default is the command search page, if the command is selected in the ladder diagram, the "search command" defaults to the selected command, and it is empty if there is no command.
1211 * String search: Open the search/replace window, the default is the string search page, if a string is selected in the ladder diagram, the "search string" defaults to the selected string, and it is empty if there is no string.
1212
1213 **View:**
1214
1215 * Comment display: In the ladder diagram, the comment of the device is displayed.
1216 * Alias display: In the ladder diagram, display the alias of the device.
1217
1218 **Debugging:**
1219
1220 * Modify the current value: In the monitor mode (write mode is not available), open the device write dialog box. Modify the value of the device of the currently selected instruction.
1221
1222 = **5 Project management** =
1223
1224 == Program ==
1225
1226 MIAN is the default program page name for a new project. There can be multiple program pages in a project. Double-click the program page to open the ladder diagram editing area in the user area, and you could edit the program.
1227
1228 (% style="text-align:center" %)
1229 [[image:image-20220625134223-1.jpeg]]
1230
1231 **New program page:** select scan/event/subroutine/interrupt, right click"scan"->"new", you could open the new program window, as shown in the figure below:
1232
1233 (% style="text-align:center" %)
1234 [[image:5V帮助文档_中性_html_a8e9017d31a283f4.png||height="253" width="300" class="img-thumbnail"]]
1235
1236 (% style="text-align:center" %)
1237 [[image:image-20220625134350-3.jpeg]]
1238
1239 **Program page operations**: Right-click the program page with the mouse to perform corresponding operations.
1240
1241 (% style="text-align:center" %)
1242 [[image:image-20220625134542-5.jpeg]]
1243
1244 **Delete: **Delete the program page.
1245
1246 **Rename: **Rename the program page.
1247
1248 **Program encryption: **Encrypt and decrypt the program page.
1249
1250 * Encryption: select the program page to be encrypted and set the encryption password, After the encryption is executed, the program page is in the "encrypted" state, and the content of the program page is not displayed.
1251
1252 (% style="text-align:center" %)
1253 [[image:5-4.jpg||class="img-thumbnail"]]
1254
1255 (% style="text-align:center" %)
1256 [[image:5-5.jpg]]
1257
1258 (% style="text-align:center" %)
1259 [[image:5-6.jpg]]
1260
1261 * Cancel encryption: After entering the correct password, cancel the encryption of the program page.
1262
1263 (% style="text-align:center" %)
1264 [[image:image-20220625140048-6.jpeg||class="img-thumbnail"]]
1265
1266 (% style="text-align:center" %)
1267 [[image:image-20220625140150-7.jpeg]]
1268
1269 * Modify password: After entering the original program page password, set a new program page password.
1270
1271 (% style="text-align:center" %)
1272 [[image:image-20220625140231-9.jpeg||class="img-thumbnail"]]
1273
1274 (% style="text-align:center" %)
1275 [[image:image-20220625140328-10.jpeg]]
1276
1277 * Display encrypted content: Display the encrypted program page content. This function is only used to temporarily display the content of the program page without canceling the encryption status of the program page, which is convenient for editing the encrypted program page.
1278
1279 (% style="text-align:center" %)
1280 [[image:5-11.jpg||class="img-thumbnail"]]
1281
1282 (% style="text-align:center" %)
1283 [[image:image-20220625140706-11.jpeg||class="img-thumbnail"]]
1284
1285 Set: Right-click it, and you could view the author, date of creation, and remarks on the program page.
1286
1287 (% style="text-align:center" %)
1288 [[image:image-20220625141015-13.jpeg]]
1289
1290 * Configuration: The time and interrupt program page can click the configuration button to set the trigger condition.
1291
1292 (% style="text-align:center" %)
1293 [[image:image-20220625142325-15.jpeg||class="img-thumbnail"]]
1294
1295 Move up: Move the program page up, used to adjust the execution order of the program page.
1296
1297 [[image:5-15.jpg||class="img-thumbnail"]] [[image:5-16.jpg||class="img-thumbnail"]]
1298
1299 Move down: Move the program page down to adjust the execution order of the program page.
1300
1301 [[image:5-17.jpg||class="img-thumbnail"]] [[image:5-18.jpg||class="img-thumbnail"]]
1302
1303 == Device comment ==
1304
1305 Device comment module: A **.wcp2** file has one and only one module named "COMMENT" in "device comment".
1306
1307 Double-click "COMMENT" and shown as below.
1308
1309 [[image:image-20220625143125-16.jpeg||class="img-thumbnail"]]
1310
1311 **Interface label description:**
1312
1313 * **Enter device name:** Input the correct device name and press "Enter" to confirm, the comment list will locate the input device and select it.
1314 * **The comment list is divided into 3 columns: **device name, device comment, and device alias. Click the comment list, and select the device row, and double-click the device comment or alias to pop up an edit box for editing. The device comment value allows 128 characters, and the device alias only allows input of 8 characters.
1315 * **Device interval selection: **Click to select the device interval and change the device displayed in the comment list. The blue device section indicates that the section is selected. The devices interval is as shown in the figure below:
1316
1317 (% style="text-align:center" %)
1318 [[image:image-20220625143652-17.jpeg]]
1319
1320 **Interface button description:**
1321
1322 * **Display commented devices:** The comment list displays all devices with comments or aliases.
1323 * **Import EXCEL:** select the ***.xls **file to be imported, and import all the correct device comments and aliases in the *.xls file into the software (supports *.csv file import).
1324 * **Export EXCEL: **Export and save all the devices information of edit devices comments or aliases as ***.xls** files to local disk.
1325
1326 == Parameter ==
1327
1328 You could set the latch range of the PLC devices and the COM port communications according to your needs. Click the "×" symbol in the upper right corner to close the dialog box and change without saving.
1329
1330 Double-click the "PLC Parameters" node and the interface is shown as below.
1331
1332 (% style="text-align:center" %)
1333 [[image:image-20220625144326-19.jpeg||class="img-thumbnail"]]
1334
1335 **Interface button description:**
1336
1337 * Check: Check the configuration of the current settings, respectively check the "device latch", "COM1 " and "COM2". If the check fails, click the "OK" button to report an error.
1338 * Reset: Click this button to restore the default settings.
1339 * OK: Complete the correct PLC parameter change and set it.
1340 * Cancel: Cancel the PLC parameter setting and keep the parameter setting before the change.
1341
1342 **Device latch**
1343
1344 The address range of various types of registers including PLC is set in the devices. You could set parameters in the white squares in the picture table, but not the gray ones (cannot be modified). By modifying the data at the beginning and end of the latch, the latch range of the register can be modified, and the modified data range must be within the latch range.
1345
1346 (% style="text-align:center" %)
1347 [[image:image-20220625145833-20.jpeg||class="img-thumbnail"]]
1348
1349 **COM1 settings**
1350
1351 (% style="text-align:center" %)
1352 [[image:image-20220625145902-21.jpeg]]
1353
1354 * Whether to set: Whether to enable the COM1 port configuration.
1355 * Baud rate: Select the data transmission rate.
1356 * Data bit: Select the data length.
1357 * Stop bit: Select the number of stop bits.
1358 * Parity: Select the number of parity.
1359 * Station No.: Set the station number, ranging from 1 to 47.
1360
1361 **COM2 settings**
1362
1363 (% style="text-align:center" %)
1364 [[image:image-20220625150016-22.jpeg]]
1365
1366 Whether to set: whether to enable the COM1 port configuration.
1367
1368 * **Communication settings**
1369 ** Baud rate: Select the data transmission rate.
1370 ** Data bit: Select the data length.
1371 ** Stop bit: Select the number of stop bits.
1372 ** Parity: Select the check digit.
1373 ** Timeout: Set the timeout time, ranging from 0 to 32767.
1374 ** Sending interval: Set the sending interval, ranging from 0 to 32767.
1375 ** Protocol: Select the communication protocol.
1376 * **Protocol related**
1377 ** Station No.: Set the station number. According to different protocols, the station number setting range is different.
1378 ** Whether to enable the start character: used to customize the protocol.
1379 ** Starter: set the end character for custom protocol.
1380 ** Whether to enable terminator: used to customize the protocol.
1381 ** Terminator: Set the terminator to customize the agreement.
1382 ** Timeout between characters: used to customize the protocol.
1383
1384 **Ethernet settings**
1385
1386 (% style="text-align:center" %)
1387 [[image:image-20220625150721-23.jpeg]]
1388
1389 **✎Note:** Currently Ethernet configuration is only supported by 5V-N series and 6V series.
1390
1391 * **Communication settings**
1392 ** Whether to set: Whether to enable communication configuration of Ethernet setttings.
1393 ** Whether to enable PLC automatic configuration IP (DHCP) function: automatic configuration IP (DHCP) function. **(only supported by 6V series currently)**
1394 ** IP address: Configure the IP address of PLC
1395 ** Subnet mask: Configure the subnet mask of PLC
1396 ** Default gateway: Configure the default gateway of PLC
1397 * **Protocol related**
1398 ** Whether to set: Whether to enable the protocol configuration of Ethernet settings.
1399 ** Maximum number of connections supported by modbusTCP server: Number of simultaneous connections available for other modbusTCP clients. **(only supported by 5V-N series currently)**
1400
1401 **Basic information settings**
1402
1403 (% style="text-align:center" %)
1404 [[image:image-20220625152250-24.jpeg]]
1405
1406 It is used to configure some basic information.
1407
1408 * Whether to set: Whether to enable the basic information settings.
1409 * PLC name: Used to set the name of PLC. The maximum number of characters allowed to be entered is 32; the range of illegal characters not allowed to be entered: /%$@&=~~`^<>? :{}[],;! *. \'"|
1410
1411 **✎Note:**
1412
1413 * The first one is a space, and a space is also an illegal character.
1414 * Currently, only PLCs with Ethernet function (5V-N series and 6V series) are supported.
1415
1416 == Device memory ==
1417
1418 It is used to set the data of PLC data block when PLC is downloaded, and the data of the read PLC data block is displayed when PLC is uploaded.
1419
1420 New devices memory: Right-click and select the "device memory" → "New" to create a new device memory file (any character in the file name, up to 64 characters in length, and only one can be downloaded at a time). The interface is as follows:
1421
1422 [[image:image-20220625170448-1.jpeg]]
1423
1424 **Interface label description:**
1425
1426 * **Please enter:** Enter the device to be searched, and press "Enter" to locate the device to be searched.
1427 * **Device list:** Divided into 10 intervals: C, D, HSC, LC, M, R, S, T, V, Z.
1428
1429 (% style="text-align:center" %)
1430 [[image:image-20220625171055-2.jpeg]]
1431
1432 * **Device value display area**: Currently editing operations are prohibited.
1433
1434 (% style="text-align:center" %)
1435 [[image:image-20220625171109-3.jpeg]]
1436
1437 * **Cell format:** 7 data formats: binary, decimal, hexadecimal, octal, real number, character string, ASCII code. One format and one color:
1438 ** Binary: red
1439 ** Octal : pink
1440 ** Decimal: blue
1441 ** Hexadecimal: brown
1442 ** Real number: orange
1443 ** Character string: cyan
1444 ** ASCII code: green
1445
1446 (% style="text-align:center" %)
1447 [[image:image-20220627105818-1.jpeg]]
1448
1449 * **The data can be expressed in size:** 16 bits and 32 bits.
1450 * **The data size that each format can represent when the length is 16 bits:**
1451 ** Binary: 0000000000000000 to 1111111111111111;
1452 ** Octal: 0 to 1777777;
1453 ** Decimal: -32768 to 32767;
1454 ** Hexadecimal: 0 to FFFF;
1455 ** String: the size of 2 characters in length;
1456 ** ASCII: 2 ASCII code values.
1457 * **The data size that each format can represent when the length is 32 bits:**
1458 ** Binary: 00000000 00000000 00000000 00000000 to 11111111 11111111 11111111 11111111;
1459 ** Octal: 0 to 37777777777;
1460 ** Decimal: -2147483648 to 2147483647;
1461 ** Hexadecimal: 0 to FFFF FFFF FFFF FFFF;
1462 ** String: the size of the length of 4 strings;
1463 ** ASCII: 4 ASCII code values;
1464 ** Real number: ±1.175495E-38 to ±3.402823E+38.
1465
1466 == Electronic cam ==
1467
1468 In the project management window, right-click “electronic cam table” to create a new electronic cam table (ECAM table).
1469
1470 [[image:5-31.jpg]] [[image:5-32.jpg]]
1471
1472 Open the ECAM interface and set the data.
1473
1474 (% style="text-align:center" %)
1475 [[image:image-20220627110623-2.jpeg||height="723" width="1226"]]
1476
1477 Click the parameter setting to set the parameters, such as the starting device, which indicates the starting position of the download time.
1478
1479 (% style="text-align:center" %)
1480 [[image:image-20220627110657-3.jpeg]]
1481
1482 The ECAM table information written by other programs can be imported into the ECAM table through import and export.
1483
1484 You could download the ECAM to the PLC.
1485
1486 == Instructions ==
1487
1488 Available instructions are as follows: all instructions; basic instructions; step ladder instruction; program flow; transfer and compare; Arithmetic; cycle and shift; data processing; high-speed processing; common instruction; peripheral device IO; peripheral device SER; floating; contact compare; high-speed pulse output; clock calculation; floating contact comparison; data table; data block; communication instruction; electrionic CAM; other instructions; string control; Ethernet.
1489
1490 (% style="text-align:center" %)
1491 [[image:image-20220627112121-4.jpeg]]
1492
1493 == PLCLINK table ==
1494
1495 **New table: **After create a new table, you could view "PLCLINK" in project manager window. Right-click it to create a PLCLINK table.
1496
1497 [[image:image-20220627113003-5.jpeg]]
1498
1499 (% class="wikigeneratedid" %)
1500 **Starting address settings:** You can select D or R device as the area for storing PLCLINK table contents, and edit the starting device address, which will occupy 22+5*n devices starting from this device. This occupancy information reflects the tabular operation in the list of device used.
1501 **New command**: Click "New command" to generate a PLCLINK command.
1502
1503 (% style="text-align:center" %)
1504 [[image:image-20220627115343-6.jpeg]]
1505
1506 (% class="wikigeneratedid" %)
1507 **Delete: **Select the PLCLINK command to be deleted to delete the command.
1508 **Modify station NO.:** You select the station number in the drop-list. The station numbers of station No.1 and station number No.2 cannot be the same. Range: 1 to 31.
1509
1510 (% style="text-align:center" %)
1511 [[image:image-20220627115946-7.jpeg||height="638" width="399" class="img-thumbnail"]]
1512
1513 (% class="wikigeneratedid" %)
1514 **Modify device name:** Select device name in the drop-list, note that the soft component type of station No.1 and station No.2 need to be the same.
1515 **Modify device address:** Edit the start address edit box and enter the value within the range of the device.
1516 **Modify the number of device:** Edit the number of device edit box, and enter the number of device.The number of double-word device ranges from 1 to 64. Device ranges from 1 to 128, and bit device ranges from 1 to 1024.
1517 **Modify instruction enable status:** Click "Station No. Enable" to edit the parameters of the two stations of this instruction. The master station is always enabled and cannot be modified.
1518
1519 * For example:
1520 ** Click "New Command" to create a PLCLINK command.
1521 ** Station NO.1 is selected as 2, station number NO.2 is selected as 3.
1522 ** Click 'Station NO. Enable". If station number NO.1 is checked to enable, but station NO.2 is not checked to enable, the command enable is invalid. Only when both station numbers are checked to enable, the command enable is valid.
1523
1524 (% style="text-align:center" %)
1525 [[image:image-20220627134639-8.jpeg]]
1526
1527 (% class="wikigeneratedid" %)
1528 **PLCLINK operation**
1529
1530 * **Check: **Check whether the data of PLCLINK is legal.
1531 * **Save:** Enabled under the condition that the program is consistent in monitoring mode, and it will compare once automatically when entering.
1532 * **Check Slave:** Send command to PLC to check slave information.
1533 * **Monitor Read:** Get PLCLINK table information from PLC.
1534 * **Monitor Write:** Write PLCLINK table to PLC
1535
1536 == Ethernet ==
1537
1538 Interface: Click "Project manager" -> "Extended function", and right-click "Ethernet" to open the "New-Ethernet configuration" window.
1539
1540 (% style="text-align:center" %)
1541 [[image:image-20220627141744-9.jpeg]]
1542
1543 (% class="wikigeneratedid" %)
1544 The introduction of parameters:
1545
1546 * **Whether to enable: **Whether to enable the Ethernet configuration
1547 * **Socket ID: **The number of socket supports a total of 6 ranging from K0 to K5. The socket ID is used to specify the link. Each ID is used for one link and cannot be defined repeatedly.
1548 * **Communication protocol: **TCP protocol and UDP protocol are supported.
1549 * **Operating mode: **For TCP, you could select client and server. For UDP, this does not work.
1550 * **Local port:**
1551 ** For TCP client mode, the local port will be automatically allocated by PLC without setting.
1552 ** For TCP server mode, the local port could be set within the range of 1 to 65,535. Port 502 is used by internal modbusTCP and cannot be set.
1553 ** For UDP mode, the local port could be set within the range of 1 to 65,535. Port 1092 is used by scanning protocol and cannot be set.
1554 * **Target ID: **Valid in TCP client mode or UDP mode, specifying the peer device IP to be linked.
1555 * **Target port: **Valid in TCP client mode or UDP mode, specifying the peer device port number to be linked.
1556 * **Receive timeout: **After PLC sending data, if the response of the peer device exceeds this timeout, the network is considered abnormal and the error flag bit is set.
1557 * **TCP keep-alive mechanism: **When TCP protocol is used for communication, If the communication line is idle in most cases and only a small amount of data is sent and received, but the link needs to be kept open, or disconnected in time in case of a drop, crash or forced termination of the process at the communication end, you can use the keep-alive mechanism for communication.
1558
1559 **Description: **Ethernet socket configuration, with Ethernet SOC series instructions, can achieve ModbusTCP client, TCP free protocol, UDP free protocol.
1560
1561 (% style="text-align:center" %)
1562 [[image:image-20220627153819-1.jpeg]]
1563
1564 **Use: **Configuring the corresponding properties to achieve the corresponding functions, and download to the PLC through the download interface and the program to. For specific use rules and configuration methods, please refer to the PLC programming manual.
1565
1566 == BD board configuration ==
1567
1568
1569 Function entry: In "Project Management" interface, expand "Extended Function", and double-click "BD Board Configuration".
1570
1571 (% style="text-align:center" %)
1572 [[image:image-20220915161952-1.jpeg]]
1573
1574 **Introduction of function interface**
1575
1576 The main interface is divided into two parts. One is the current configuration information list, and the other is device list for users to choose configuration.
1577
1578 (% style="text-align:center" %)
1579 [[image:image-20220915161952-2.jpeg]]
1580
1581 * **Device list: **It includes "PLC Host" and "BD Board". You can add device to the configuration list on the left by double-clicking the contents under the two nodes.
1582
1583 (% style="text-align:center" %)
1584 [[image:image-20220915161952-3.jpeg]]
1585
1586 "PLC Host" contains all the points existing in the actual device of PLC model set in the current project. Try to ensure that host points in the configuration list are consistent with the points actually connected to PLC, otherwise it may occur that the host computer is configured with two BD boards, but the actually connected PLC has only one BD board slot, resulting in the situation that the configuration of BD2 will not take effect.
1587
1588 (% style="text-align:center" %)
1589 [[image:image-20220915161952-4.jpeg]]
1590
1591 (% style="text-align:center" %)
1592 [[image:image-20220915161952-5.jpeg||class="img-thumbnail"]]
1593
1594 "BD Board" contains all BD board models that can be supported by 5V series PLC at present.
1595
1596 * **Configuration list:** Display the information of PLC host and BD board currently configured.
1597
1598 (% style="text-align:center" %)
1599 [[image:image-20220915161952-6.jpeg||class="img-thumbnail"]]
1600
1601 * Slot number: 0 is the host by default, 1 is BD1, and 2 is BD2.
1602 * Configure device name: Displays the device name.
1603 * Device description: Displays a brief description of the device.
1604 * Device occupancy: Displays the device occupancy of the configuration device.
1605 * Actual installation type: In monitoring mode, display the BD board model actually connected by PLC.
1606 * Device version number: In monitoring mode, display the BD board version number actually connected by PLC.
1607
1608 **Introduction to configuration operations**
1609
1610 (% style="text-align:center" %)
1611 [[image:image-20220915161952-7.jpeg||class="img-thumbnail"]]
1612
1613 * **Add BD board Configuration: **Add by double-clicking BD board in the device list on the right.
1614 * **Modify BD board configuration:** Open the BD board configuration window by right-clicking on the menu or double-clicking on the BD Board in the configuration list.
1615 * **Move up/down:** The positions of the BD boards configuration on slot 1 and slot 2 can be swapped.
1616 * **Delete BD board configuration:** Delete BD board configuration.
1617
1618 **Introduction of BD board configuration interface**
1619
1620 Module configuration: Used to configure the general configuration of BD board, applicable to all channels.
1621
1622 (% style="text-align:center" %)
1623 [[image:image-20220915161952-8.jpeg]]
1624
1625 BD board channel configuration: The enable status and parameter settings of each channel of BD board can be configured.
1626
1627 (% style="text-align:center" %)
1628 [[image:image-20220915161952-9.jpeg]]
1629
1630 I/O mapping: The channel value of the BD board is displayed by the device through mapping.
1631
1632 (% style="text-align:center" %)
1633 [[image:image-20220915161952-10.jpeg]]
1634
1635 Device information: Display device information of BD board.
1636
1637 (% style="text-align:center" %)
1638 [[image:image-20220915161952-11.jpeg]]
1639
1640 Reset: Initialize the configuration data of BD board, and the parameters are the same as when the BD board is added.
1641
1642 (% style="text-align:center" %)
1643 [[image:image-20220915161952-12.jpeg]]
1644
1645 **Other functions**
1646
1647 Device information: You can view the BD board model and corresponding version number currently connected by PLC.
1648
1649 (% style="text-align:center" %)
1650 [[image:image-20220915161952-13.jpeg]]
1651
1652 PLC calibration: Check the configuration of BD board and PLC.
1653
1654 [[image:image-20220915161952-14.jpeg]]
1655
1656 BD board monitoring
1657
1658 (% style="text-align:center" %)
1659 [[image:image-20220915161952-15.jpeg]]
1660
1661 U disk download: BD board configuration function supports U disk download, and the data will be packaged together with the program node.
1662
1663 (% style="text-align:center" %)
1664 [[image:image-20220915161952-16.jpeg]]
1665
1666 **✎Note:**
1667
1668 * The minimum software version number of the slave computer that supports the BD board configuration function: V2.051.
1669
1670 [[image:image-20220915161952-17.jpeg]]
1671
1672 * The BD board model and slot position of PLC currently connected to the host computer should be consistent with the configuration list of BD board of the host computer.
1673 * Ensure that host points in the configuration list is consistent with the number of points actually connected to PLC, otherwise it may occur that the host computer is configured with two BD boards, but the actually connected PLC has only one BD board slot.
1674
1675 = **6 Output window** =
1676
1677 == Information output ==
1678
1679 **Information output window: **Provide users with the results after the software performs operations including the execution result information of the three operations of compiling, communication, and switch.
1680
1681 (% style="text-align:center" %)
1682 [[image:image-20220628142118-1.jpeg]]
1683
1684 If there is an error in the program, the error will be listed in the "Information output" module at the bottom of the ladder diagram. Select the specified error item, and double-click to locate the error position of the ladder diagram.
1685
1686 == Search&Replace ==
1687
1688 **Search and replace function: **Similar to the search and replace function of OFFICE, it can locate the data block specified by the user in a large amount of data, or perform batch addition, deletion, modification, and check, which can greatly improve efficiency.
1689
1690 **How to use: **Open the main program, after creating a new project, click “Ctrl+F” on the keyboard to pop up the search and replace interface, as shown in the following figure:
1691
1692 (% style="text-align:center" %)
1693 [[image:image-20220628142601-2.jpeg]]
1694
1695 Buttons are divided into 4 categories: devices, instruction, string, and result, as shown in the figure above; clicking any one will switch to the corresponding operation interface.
1696
1697 = **7 Modify device value** =
1698
1699 **Modify device value**: modify the PLC internal register and coil value; modify the expansion device register value. As shown below:
1700
1701 (% style="text-align:center" %)
1702 [[image:image-20220628143453-3.jpeg]]
1703
1704 (% style="text-align:center" %)
1705 [[image:image-20220628143458-4.jpeg]]
1706
1707 **PLC internal devices:**
1708
1709 * **Devices:**
1710 ** "Devices" are registers and coils (such as C0, M1, etc.) whose values need to be modified within the range of PLC.
1711 ** "Data type" includes Word (single word) , Bit (binary 0 or 1), double Word, float (single precision floating point number).
1712 ** "Value" is the specific value to be modified (corresponding to the number in the range of "Data Type"), such as -120.
1713 ** The data format can be decimal (single word: -32768 to 32767; double word:  -2147483648 to 2147483647) or hexadecimal (single word: 0 to FFFF; double word:  0 to FFFFFFFF).
1714 ** Click "Set" to write the set value within the correct range to the selected device.
1715 * **Execution result: **Record the successfully modified "device", "data type" and "set value" in the form of a list.
1716 * **Record list:**
1717 ** Click any one in the list, and click "Delete" to delete it.
1718 ** Click "Clear List" to clear the record list.
1719 ** Select any one in the record list and click "**Response to Input Field**" to reflect the items in "device" .
1720
1721 **PLC external expansion module:**
1722
1723 * "Module start" is the extension module number (such as module 0).
1724 * "Address" is the internal writable address of the expansion module, and the address type can be decimal or hexadecimal.
1725 * "Data type" includes Word (single word), Double Word, Float (single precision floating point number) .
1726 * "Value" is the specific value to be modified (corresponding to the number in the "data type" range), such as -120. The type can be decimal or hexadecimal.
1727 * The data can be decimal (single word: -32768 to 32767; double word: -2147483648 to 2147483647) or hexadecimal (single word: 0 to FFFF; double word: 0 to FFFFFFFF).
1728 * Click "Set" to write the set value within the correct range to the selected device.
1729
1730 **✎Note: **
1731
1732 1. Modification of the device value must be executed in the case of communication with the PLC.
1733 1. The device must be within the available range of the corresponding PLC model.
1734 1. The input value must be within the allowable range.
1735 1*. Decimal: single word (-32768 to 32767), double word (-2147483648 to 2147483647)
1736 1*. Hexadecimal: single word (0 to FFFF); double word (0to FFFFFFFF)
1737 1*. Floating: ±1.175495E-38 to 3.402823E+38
1738
1739 = **8 Print ladder diagram** =
1740
1741 The print function is divided into: print, print preview, and print settings.
1742
1743 **Preconditions for printing**
1744
1745 1. Open the project file (not the project file generated by the "Generate Download File" function).
1746 1. The program has all been compiled.
1747 1. The program is in edit mode.
1748
1749 Only when the above three conditions are met, the print button can be clicked.
1750
1751 (% style="text-align:center" %)
1752 [[image:image-20220628145819-5.jpeg]]
1753
1754 == Printing preview ==
1755
1756 Before printing, you could preview the print on the screen. Click the "File" → "Print" → "Print Preview" to open the print preview window as shown in the figure below:
1757
1758 (% style="text-align:center" %)
1759 [[image:image-20220628145842-6.jpeg]]
1760
1761 **Print preview interface**
1762
1763 (% style="text-align:center" %)
1764 [[image:image-20220628145927-7.jpeg]]
1765
1766 == Print ==
1767
1768 When you need to print, please click the print button, and a standard print dialog box will pop up. You could set the print options here. After setting, you could click "OK" to output the current program to the printer.
1769
1770 (% style="text-align:center" %)
1771 [[image:image-20220628150306-8.jpeg]]
1772
1773 == Printer settings ==
1774
1775 Set print information. As shown below:
1776
1777 (% style="text-align:center" %)
1778 [[image:image-20220628150319-9.jpeg]]
1779
1780 = **9 Status bar** =
1781
1782 Indication: language, uppercase and lowercase status, digital keyboard lock status, rewrite/insert status, communication port, project model, current program steps/total program steps and other status information.
1783
1784 (% style="text-align:center" %)
1785 [[image:image-20220628150551-10.jpeg]]
1786
1787 * **Language: **The language type displayed by the software. Highlighted means enabled.
1788 * **Case state:** English input state.
1789 * **Numeric keypad lock:** Whether the numeric keypad is available.
1790 * **Rewrite/insert state:** ladder diagram editing mode.
1791 * **Communication port:** communication COM port. Click it to pop up the communication setting window.
1792 * **Project type:** Display the PLC model of the current project.
1793 * **Current program steps/total program steps:** Program editing page, program steps of the currently selected instruction/total program steps.
1794
1795 = **10 Device usage list** =
1796
1797 The device usage list mainly displays the specified type of device. You could check the usage, and the corresponding comment and alias of the device.
1798
1799 (% style="text-align:center" %)
1800 [[image:image-20220628152232-11.jpeg]]
1801
1802 **Instructions for using the list of devices:**
1803
1804 * Device selection drop-down box: select the drop-down box option, search for and display the usage of the corresponding type of Device (starting from serial number 0).
1805
1806 (% style="text-align:center" %)
1807 [[image:image-20220628152301-12.jpeg||class="img-thumbnail"]]
1808
1809 * Start devices drop-down box: You could enter the full name or serial number of the start devices, press the Enter key or press the "search" button to search and display the usage of this type of devices (starting from the initial serial number). Record the search record in the drop-down box. After selecting the record, you could perform the search again.
1810
1811 (% style="text-align:center" %)
1812 [[image:image-20220628152611-13.jpeg]]
1813
1814 * Search button: Perform a search operation. When the starting device is empty, it will prompt to input a device.
1815
1816 (% style="text-align:center" %)
1817 [[image:image-20220628152633-14.jpeg]]
1818
1819 * Search range: Specify the search range of the device.
1820 ** Current program page: Search only for the currently active program page.
1821 ** Current program type: Only for all program pages of the same type in the currently activated program page.
1822 ** Whole project: for all program pages of the current project. (The program page types are divided into: scan, event, subroutine, interrupt)
1823
1824 (% style="text-align:center" %)
1825 [[image:image-20220628152800-15.jpeg]]
1826
1827 * Expand and close the sub-items of the device usage list.
1828
1829 (% style="text-align:center" %)
1830 [[image:image-20220628153639-16.jpeg||class="img-thumbnail"]]
1831
1832 * The sub-items of the devices usage list includes instruction, step number, type and other information of the devices in the program. Double-click the content of the sub-item to locate the corresponding position in the program.
1833
1834 (% style="text-align:center" %)
1835 [[image:image-20220628153730-17.jpeg||class="img-thumbnail"]]
1836
1837 * Device comment and alias column: (the background color is white) displays the comment or alias of the device.
1838
1839 (% style="text-align:center" %)
1840 [[image:image-20220628153741-18.jpeg||class="img-thumbnail"]]
1841
1842 **Display options:**
1843
1844 * All devices: After selecting, search all devices of this type.
1845
1846 (% style="text-align:center" %)
1847 [[image:image-20220628154043-19.jpeg]]
1848
1849 * Used devices: After selecting, search for the used devices of this type according to the contact and coil options.
1850 ** Neither the contact nor the coil is selected, and all the devicess of this type that have been used in the program are displayed.
1851 ** Select the contact (coil) to display the type of devices as the contact (coil) in the program.
1852 ** Select both contacts and coils, and display the type of devices that are used as contacts and coils in the program.
1853
1854 (% style="text-align:center" %)
1855 [[image:image-20220628154051-20.jpeg]]
1856
1857 * Unused devices: After selecting, display all the devicess of this type that are not used in the program.
1858
1859 (% style="text-align:center" %)
1860 [[image:image-20220628154101-21.jpeg]]
1861
1862 = **11 Shortcut keys list** =
1863
1864 == Universal shortcut keys ==
1865
1866 The universal shortcut keys are as follows:
1867
1868 (% class="table-bordered" %)
1869 |=(% scope="row" style="width: 149px;" %)**Hot key**|=(% style="width: 361px;" %)**Corresponding menu (function name)**|=(% style="width: 566px;" %)**Summary**
1870 |=(% style="width: 149px;" %)Ctrl + N|(% style="width:361px" %)New Project|(% style="width:566px" %)New Project
1871 |=(% style="width: 149px;" %)Ctrl + O|(% style="width:361px" %)Open the project|(% style="width:566px" %)Open an existing project
1872 |=(% style="width: 149px;" %)Ctrl + S|(% style="width:361px" %)Save the project|(% style="width:566px" %)Save the project
1873 |=(% style="width: 149px;" %)Ctrl + X|(% style="width:361px" %)Cut|(% style="width:566px" %)Cut selected data and range
1874 |=(% style="width: 149px;" %)Ctrl + C|(% style="width:361px" %)Copy|(% style="width:566px" %)Copy selected data and range
1875 |=(% style="width: 149px;" %)Ctrl + V|(% style="width:361px" %)Paste|(% style="width:566px" %)Cut/paste the copied data at the cursor position
1876 |=(% style="width: 149px;" %)Ctrl + Z|(% style="width:361px" %)Revoke|(% style="width:566px" %)Revoke the previous operation
1877 |=(% style="width: 149px;" %)Ctrl + Y|(% style="width:361px" %)Restore|(% style="width:566px" %)Resume the operation canceled by "Undo"
1878 |=(% style="width: 149px;" %)Ctrl + F|(% style="width:361px" %)Search device|(% style="width:566px" %)Search device
1879 |=(% style="width: 149px;" %)Ctrl + F1|(% style="width:361px" %)Display/hide menu toolbar|(% style="width:566px" %)Display/hide menu toolbar
1880 |=(% style="width: 149px;" %)F3|(% style="width:361px" %)Start Monitoring|(% style="width:566px" %)Currently, start to monitor the window that is the target of the operation
1881 |=(% style="width: 149px;" %)Ctrl + F3|(% style="width:361px" %)Monitoring stop|(% style="width:566px" %)Currently, stop monitoring the window that is the target of operation
1882 |=(% style="width: 149px;" %)F4|(% style="width:361px" %)Compile|(% style="width:566px" %)Compile (switch) the program page currently being edited
1883 |=(% style="width: 149px;" %)Ctrl+F4|(% style="width:361px" %)Compile all|(% style="width:566px" %)Compile (switch) all program pages in the current project
1884 |=(% style="width: 149px;" %)Alt+F4|(% style="width:361px" %)Exit the software|(% style="width:566px" %)Exit the software
1885
1886 == Shortcut keys for ladder editor ==
1887
1888 The shortcut keys that can be used in the ladder diagram editor are as follows:
1889
1890 (% class="table-bordered" %)
1891 |=(% scope="row" style="width: 150px;" %)**Shortcut key**|=(% style="width: 363px;" %)**Corresponding menu (function name)**|=(% style="width: 563px;" %)**Summary**
1892 |=(% style="width: 150px;" %)F5|(% style="width:363px" %)Normally open contact|(% style="width:563px" %)Write normally open contact to the cursor position
1893 |=(% style="width: 150px;" %)Shift + F5|(% style="width:363px" %)Normally open contact OR|(% style="width:563px" %)Write normally open contact OR to the cursor position
1894 |=(% style="width: 150px;" %)F6|(% style="width:363px" %)Normally closed contact|(% style="width:563px" %)Write normally closed contact to the cursor position
1895 |=(% style="width: 150px;" %)Shift + F6|(% style="width:363px" %)Normally closed contact OR|(% style="width:563px" %)Write normally closed contact OR to the cursor position
1896 |=(% style="width: 150px;" %)F7|(% style="width:363px" %)Coil|(% style="width:563px" %)Write coil to the cursor position
1897 |=(% style="width: 150px;" %)F8|(% style="width:363px" %)Application instructions|(% style="width:563px" %)Write application instructions to the cursor position
1898 |=(% style="width: 150px;" %)F9|(% style="width:363px" %)Horizontal line input|(% style="width:563px" %)Write horizontal line to cursor position
1899 |=(% style="width: 150px;" %)F11|(% style="width:363px" %)Vertical line input|(% style="width:563px" %)Write the vertical line to the cursor position
1900 |=(% style="width: 150px;" %)Ctrl + F9|(% style="width:363px" %)Delete horizontal line|(% style="width:563px" %)Delete the horizontal line at the cursor position
1901 |=(% style="width: 150px;" %)Ctrl + F11|(% style="width:363px" %)Delete vertical line|(% style="width:563px" %)Delete the vertical line at the cursor position
1902 |=(% style="width: 150px;" %)Shift + F7|(% style="width:363px" %)Rising edge pulse|(% style="width:563px" %)Write the rising edge pulse to the cursor position
1903 |=(% style="width: 150px;" %)Shift + F8|(% style="width:363px" %)Falling edge pulse|(% style="width:563px" %)Write the falling edge pulse to the cursor position
1904 |=(% style="width: 150px;" %)Ctrl + Alt + F7|(% style="width:363px" %)Parallel rising edge pulse|(% style="width:563px" %)Write the parallel rising edge pulse to the cursor position
1905 |=(% style="width: 150px;" %)Ctrl + Alt + F8|(% style="width:363px" %)Parallel falling edge pulse|(% style="width:563px" %)Write the parallel falling edge pulse to the cursor position
1906 |=(% style="width: 150px;" %)Ctrl + Alt + F11|(% style="width:363px" %)Invert the result of the operation|(% style="width:563px" %)Write the result of the calculation to the cursor position
1907 |=(% style="width: 150px;" %)Ctrl + Shift + Insert|(% style="width:363px" %)Insert statement between lines|(% style="width:563px" %)Insert the declaration line at the cursor position
1908 |=(% style="width: 150px;" %)Shift + Insert|(% style="width:363px" %)Insert program row|(% style="width:563px" %)Insert the  row at the cursor position
1909 |=(% style="width: 150px;" %)Shift + Delete|(% style="width:363px" %)Delete row|(% style="width:563px" %)Delete the row at the cursor position
1910 |=(% style="width: 150px;" %)Ctrl + Insert|(% style="width:363px" %)Insert column|(% style="width:563px" %)Insert the column at cursor position
1911 |=(% style="width: 150px;" %)Ctrl + Delete|(% style="width:363px" %)Delete column|(% style="width:563px" %)Delete the column at the cursor position
1912 |=(% style="width: 150px;" %)Ctrl + →|(% style="width:363px" %)Enter/delete horizontal line in the right direction|(% style="width:563px" %)Enter/delete horizontal line from the cursor position to the right
1913 |=(% style="width: 150px;" %)Ctrl + ←|(% style="width:363px" %)Horizontal line input/delete in the left direction|(% style="width:563px" %)Enter/delete horizontal line from the cursor position to the left
1914 |=(% style="width: 150px;" %)Ctrl + ↓|(% style="width:363px" %)Enter/delete the vertical line in the downward direction|(% style="width:563px" %)Enter/delete the vertical line from the cursor position down
1915 |=(% style="width: 150px;" %)Ctrl + ↑|(% style="width:363px" %)Upward vertical line input/delete|(% style="width:563px" %)Enter/delete the vertical line up from the cursor position
1916 |=(% style="width: 150px;" %)Ctrl + /|(% style="width:363px" %)Normally open/normally closed contact switching|(% style="width:563px" %)Switch between normally open contact and normally closed contact
1917 |=(% style="width: 150px;" %)Ctrl + G|(% style="width:363px" %)Jump|(% style="width:563px" %)Display jump to the instruction position corresponding to the specified number of steps
1918 |=(% style="width: 150px;" %)Ctrl + F5|(% style="width:363px" %)Comment display|(% style="width:563px" %)Display device comments and label comments
1919 |=(% style="width: 150px;" %)Ctrl + F7|(% style="width:363px" %)Statement display|(% style="width:563px" %)Display statement
1920 |=(% style="width: 150px;" %)F1|(% style="width:363px" %)Open instruction help|(% style="width:563px" %)Display instruction help