Changes for page 08 Communication
Last modified by Iris on 2025/07/24 15:23
Summary
-
Page properties (2 modified, 0 added, 0 removed)
Details
- Page properties
-
- Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki. Mora1 +XWiki.Stone - Content
-
... ... @@ -2,12 +2,12 @@ 2 2 3 3 = **Modbus communication** = 4 4 5 -== Hardware wiring == 5 +== **Hardware wiring** == 6 6 7 7 The position of RS485 communication port (take VD2B as an example) is as the figure below. 8 8 9 9 (% style="text-align:center" %) 10 -[[image:image-20220608154248-1.png ||class="img-thumbnail"]]10 +[[image:image-20220608154248-1.png]] 11 11 12 12 Figure 8-1 The position of RS485 communication port of VD2B drive 13 13 ... ... @@ -16,7 +16,7 @@ 16 16 The servo drive adopts RS485 half-duplex communication mode. The 485 bus should adopt the hand-in-hand structure instead of the star structure or the bifurcated structure. The star structure or bifurcation structure will produce reflected signals, which will affect the 485 communication. 17 17 18 18 (% class="table-bordered" %) 19 - (% class="warning" %)|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153134-1.png]]19 +|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153134-1.png]] 20 20 |((( 21 21 ✎The wiring must use shielded twisted pair, stay away from strong electricity, do not run in parallel with the power line, let alone bundle it together! 22 22 ... ... @@ -24,7 +24,7 @@ 24 24 ))) 25 25 26 26 (% style="text-align:center" %) 27 -[[image:image-20220608174415-1.png ||class="img-thumbnail"]]27 +[[image:image-20220608174415-1.png]] 28 28 29 29 Figure 8-2 RS485 communication network wiring diagram 30 30 ... ... @@ -33,7 +33,7 @@ 33 33 No point in the RS485 network can be directly grounded. All devices in the network must be well grounded through their own grounding terminals. 34 34 35 35 (% class="table-bordered" %) 36 - (% class="warning" %)|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153144-2.png]]36 +|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153144-2.png]] 37 37 |Under no circumstances can the grounding wire form a closed loop. 38 38 39 39 When wiring, consider the drive capability of the computer/PLC and the distance between the computer/PLC and the servo drive. If the drive capacity is insufficient, a repeater is needed. ... ... @@ -40,20 +40,20 @@ 40 40 41 41 = **Modbus communication protocol analysis** = 42 42 43 -== Modbus data frame format == 43 +== **Modbus data frame format** == 44 44 45 45 The VD2 series servo drives currently support the RTU communication format. The typical data frame format is shown in the table. 46 46 47 47 (% class="table-bordered" %) 48 -| =(% rowspan="2" scope="row" style="text-align:;" %)**There should be a message interval not less than 3.5 characters at the beginning**|=(% style="text-align:;" %)**Address**|=(% style="text-align:;" %)**Function code**|=(% style="text-align:;" %)**Data**|=(% style="text-align:;" %)**CRC check code**48 +|(% rowspan="2" style="text-align:center; vertical-align:middle; width:425px" %)**There should be a message interval not less than 3.5 characters at the beginning**|(% style="text-align:center; vertical-align:middle; width:166px" %)**Address**|(% style="text-align:center; vertical-align:middle; width:189px" %)**Function code**|(% style="text-align:center; vertical-align:middle; width:155px" %)**Data**|(% style="text-align:center; vertical-align:middle; width:158px" %)**CRC check code** 49 49 |(% style="text-align:center; vertical-align:middle; width:166px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:189px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:155px" %)N bytes|(% style="text-align:center; vertical-align:middle; width:158px" %)2 bytes 50 50 51 -== Supported function codes ==51 +== **Description of supported function codes** == 52 52 53 53 The host reads and writes data to the servo through Modbus RTU format (03, 06 function codes). The corresponding Modbus function codes are as follows: 54 54 55 55 (% class="table-bordered" %) 56 -| =(% style="text-align:;" %)**Operate**|=(% style="text-align:;" %)**Command code**56 +|(% style="text-align:center; vertical-align:middle" %)**Operate**|(% style="text-align:center; vertical-align:middle" %)**Command code** 57 57 |(% style="text-align:center; vertical-align:middle" %)Read 16-bit/32-bit function code|(% style="text-align:center; vertical-align:middle" %)0x03 58 58 |(% style="text-align:center; vertical-align:middle" %)Write 16-bit function code|(% style="text-align:center; vertical-align:middle" %)0x06 59 59 |(% style="text-align:center; vertical-align:middle" %)Write 32-bit function code|(% style="text-align:center; vertical-align:middle" %)0x10 ... ... @@ -62,16 +62,15 @@ 62 62 63 63 Request format: 64 64 65 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% colspan="2" %)**Initial address**|=(% colspan="2" %)**Number of reads**|=(% rowspan="2" %)**CRC check code**66 -| =**high byte**|=**low byte**|=**high byte**|=**low byte**65 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Initial address**|(% colspan="2" %)**Number of reads**|(% rowspan="2" %)**CRC check code** 66 +|**high byte**|**low byte**|**high byte**|**low byte** 67 67 |1 byte|03|1 byte|1 byte|1 byte|1 byte|2 bytes 68 68 69 69 Correct response format: 70 70 71 -(% style="width:1055px" %) 72 -|=(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% rowspan="2" style="width: 279px;" %)**Number of bytes of returned data**|=(% colspan="2" style="width: 274px;" %)**Register 1**|=(% rowspan="2" style="width: 98px;" %)**…**|=(% rowspan="2" %)**CRC check code** 73 -|=(% style="width: 160px;" %)**high byte**|=(% style="width: 114px;" %)**low byte** 74 -|1 byte|03|(% style="width:279px" %)1 byte|(% style="width:160px" %)1 byte|(% style="width:114px" %)1 byte|(% style="width:98px" %)…|2 bytes 71 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% rowspan="2" %)**Number of bytes of returned data**|(% colspan="2" %)**Register 1**|(% rowspan="2" %)**…**|(% rowspan="2" %)**CRC check code** 72 +|**high byte**|**low byte** 73 +|1 byte|03|1 byte|1 byte|1 byte|…|2 bytes 75 75 76 76 **Write function code: 0x06** 77 77 ... ... @@ -85,16 +85,16 @@ 85 85 86 86 Response format: 87 87 88 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% colspan="2" %)**Register address**|=(% colspan="2" %)**Data**|=(% rowspan="2" %)**CRC check code**89 -| =**high byte**|=**low byte**|=**high byte**|=**low byte**87 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code** 88 +|**high byte**|**low byte**|**high byte**|**low byte** 90 90 |1 byte|06|1 byte|1 byte|1 byte|1 byte|2 bytes 91 91 92 92 If the setting is successful, the original is returned 93 93 94 -| =(% rowspan="2"style="width: 551px;"%)**There should be a message interval not less than 3.5 characters at the beginning**|=(% style="width: 114px;" %)**Address**|=(% style="width: 127px;" %)**Function code**|=(% style="width: 104px;" %)**Data**|=(% style="width: 180px;" %)**CRC check code**95 -| (% style="width:114px"%)1byte|(% style="width:127px"%)1byte|(% style="width:104px" %)N bytes|(% style="width:180px" %)2 bytes93 +|(% rowspan="2" %)**There should be a message interval not less than 3.5 characters at the beginning**|**Address**|**Function code**|**Data**|**CRC check code** 94 +|1 byte|1 byte|N bytes|2 bytes 96 96 97 - ==(% style="color:inherit; font-family:inherit; font-size:26px" %)CRC check(%%) ==96 +(% style="color:inherit; font-family:inherit; font-size:26px" %)**CRC check** 98 98 99 99 The servo uses a 16-bit CRC check, and the host computer must also use the same check rule, otherwise the CRC check will make mistake. When transmitting, the low bit is in the front and the high bit is at the back. The CRC code are as follows: 100 100 ... ... @@ -151,13 +151,13 @@ 151 151 == **Error response frame** == 152 152 153 153 (% class="table-bordered" %) 154 -| =(% style="text-align:;" %)**Address**|=(% style="text-align:;" %)**Function code**|=(% style="text-align:;" %)**Error code**|=(% style="text-align:;" %)**CRC check code**153 +|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Error code**|(% style="text-align:center; vertical-align:middle" %)**CRC check code** 155 155 |(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)Command code+0x80|(% style="text-align:center; vertical-align:middle" %)Error code|(% style="text-align:center; vertical-align:middle" %)2 bytes 156 156 157 157 When an error occurs, set the function code bit7 issued by the host to 1, and return (for example, 0x03 returns 0x83, 0x06 returns 0x86); the description of the error code are as follows. 158 158 159 159 (% class="table-bordered" %) 160 -| =(% style="text-align:;" %)**Error code**|=(% style="text-align:;" %)**Coding description**159 +|(% style="text-align:center; vertical-align:middle" %)**Error code**|(% style="text-align:center; vertical-align:middle" %)**Coding description** 161 161 |(% style="text-align:center; vertical-align:middle" %)0x0001|(% style="text-align:center; vertical-align:middle" %)Illegal command code 162 162 |(% style="text-align:center; vertical-align:middle" %)0x0002|(% style="text-align:center; vertical-align:middle" %)Illegal data address 163 163 |(% style="text-align:center; vertical-align:middle" %)0x0003|(% style="text-align:center; vertical-align:middle" %)Illegal data ... ... @@ -165,6 +165,8 @@ 165 165 166 166 == **Communication example** == 167 167 167 + 168 + 168 168 **03 Function code read** 169 169 170 170 Read the monitoring volume U0-31 bus voltage, the Modbus register address corresponding to this variable is 7716 (0x1E24) ... ... @@ -171,18 +171,20 @@ 171 171 172 172 Request format: 173 173 174 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% colspan="2" %)**Register address**|=(% colspan="2" %)**Data**|=(% rowspan="2" %)**CRC check code**175 -| =**high byte**|=**low byte**|=**high byte**|=**low byte**175 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code** 176 +|**high byte**|**low byte**|**high byte**|**low byte** 176 176 |01|03|1E|24|00|01|C2 29 177 177 178 178 The slave responds normally: 179 179 180 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% rowspan="2" %)**Number of bytes**|=(% colspan="2" %)**Data**|=(% rowspan="2" %)**CRC high byte**181 -| =**high byte**|=**low byte**181 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% rowspan="2" %)**Number of bytes**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC high byte** 182 +|**high byte**|**low byte** 182 182 |01|03|02|0C|4F|FC B0 183 183 184 184 For example: The value read is 0x0C4F, which means that the voltage is 315.1V. 185 185 187 + 188 + 186 186 **06 Function Code Write** 187 187 188 188 P1-10 the maximum speed threshold is set to 3000rpm. This variable corresponds to the Modbus address: 266 (0x010A) ... ... @@ -189,14 +189,14 @@ 189 189 190 190 Request format: 191 191 192 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% colspan="2" %)**Register address**|=(% colspan="2" %)**Data**|=(% rowspan="2" %)**CRC check code**193 -| =**high byte**|=**low byte**|=**high byte**|=**low byte**195 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code** 196 +|**high byte**|**low byte**|**high byte**|**low byte** 194 194 |01|06|01|0A|0B|B8|AF, 76 195 195 196 196 The slave responds normally: 197 197 198 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% colspan="2" %)**Register address**|=(% colspan="2" %)**Data**|=(% rowspan="2" %)**CRC check code**199 -| =**high byte**|=**low byte**|=**high byte**|=**low byte**201 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code** 202 +|**high byte**|**low byte**|**high byte**|**low byte** 200 200 |01|06|01|0A|0B|B8|AF, 76 201 201 202 202 **10 Function code write** ... ... @@ -205,33 +205,32 @@ 205 205 206 206 Request format: 207 207 208 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% colspan="2" %)**Initial address**|=(% colspan="2" %)**Number of register**|=(% rowspan="2" %)**Number of data**|=(% colspan="2" %)**Data 1**|=(% colspan="2" %)**Data 2**|=(% colspan="2" %)**CRC check code**209 -| =**high byte**|=**low byte**|=**high byte**|=**low byte**|=**high byte**|=**low byte**|=**high byte**|=**low byte**|=**high byte**|=**low byte**211 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Initial address**|(% colspan="2" %)**Number of register**|(% rowspan="2" %)**Number of data**|(% colspan="2" %)**Data 1**|(% colspan="2" %)**Data 2**|(% colspan="2" %)**CRC check code** 212 +|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte** 210 210 |01|10|07|09|00|02|04|00|00|07|D0|16|59 211 211 212 212 The slave responds normally: 213 213 214 -| =(% rowspan="2" %)**Address**|=(% rowspan="2" %)**Function code**|=(% colspan="2" %)**Register address**|=(% colspan="2" %)**Data**|=(% colspan="2" %)**CRC check code**215 -| =**high byte**|=**low byte**|=**high byte**|=**low byte**|=**high byte**|=**low byte**217 +|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% colspan="2" %)**CRC check code** 218 +|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte** 216 216 |01|10|07|09|00|02|90|BE 217 217 218 218 = **Servo communication parameter setting** = 219 219 220 220 (% style="text-align:center" %) 221 -((( 222 -(% class="wikigeneratedid img-thumbnail" style="display:inline-block" %) 223 -[[Figure 8-3 Modbus communication parameter setting process>>image:image-20220608174504-2.png||id="Iimage-20220608174504-2.png"]] 224 -))) 224 +[[image:image-20220608174504-2.png]] 225 225 226 - **Set the servoaddressP12-1**226 +Figure 8-3 Modbus communication parameter setting process 227 227 228 +**(1) Set the servo address P12-1** 229 + 228 228 When multiple servos are in network communication, each servo can only have a unique address, otherwise it will cause abnormal communication and fail to communicate. 229 229 230 -**Set the serial port baud rate P12-2** 232 +**(2) Set the serial port baud rate P12-2** 231 231 232 232 The communication rate of the servo and the communication rate of the host computer must be set consistently, otherwise the communication cannot be carried out. 233 233 234 -**Set the serial port data format P12-3** 236 +**(3) Set the serial port data format P12-3** 235 235 236 236 The data bit check methods of servo communication are: 237 237 ... ... @@ -242,7 +242,7 @@ 242 242 243 243 The data frame format of the servo and the host computer must be consistent, otherwise the communication cannot be carried out. 244 244 245 -**Set that whether the function code changed by Modbus communication is written into EEPROM in real time [P12-4]** 247 +**(4) Set that whether the function code changed by Modbus communication is written into EEPROM in real time [P12-4]** 246 246 247 247 When the host computer modifies the servo function code through communication, it can choose to store it in EEPROM in real time, which has the function of power-off storage. 248 248 ... ... @@ -251,10 +251,10 @@ 251 251 If you need to change the value of the function code frequently, it is recommended to turn off the function of real-time writing to EERPOM of function code, otherwise the EEPROM will be shortened due to frequent erasing and writing of the EEPROM. 252 252 253 253 (% class="table-bordered" %) 254 - (% class="warning" %)|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153214-3.png]]256 +|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153214-3.png]] 255 255 |After the EEPROM is damaged, the servo will have an non resettable fault! 256 256 257 -**Set the high and low order of the 32-bit monitoring data** 259 +**(5) Set the high and low order of the 32-bit monitoring data** 258 258 259 259 Part of the monitoring volume is 32-bit length and occupies 2 consecutive bias numbers. The user needs to set the order of the data high bit and low bit correctly, otherwise it will cause data reading and writing errors! 260 260 ... ... @@ -263,35 +263,33 @@ 263 263 The description of related function codes are as follows. 264 264 265 265 (% class="table-bordered" %) 266 -| =(% style="text-align:;" %)**Function code**|=(% style="text-align:165px;" %)**Name**|=(% style="text-align:48px;" %)(((268 +|(% style="text-align:center; vertical-align:middle; width:121px" %)**Function code**|(% style="text-align:center; vertical-align:middle; width:205px" %)**Name**|(% style="text-align:center; vertical-align:middle; width:187px" %)((( 267 267 **Setting method** 268 -)))| =(% style="text-align:5px;" %)(((270 +)))|(% style="text-align:center; vertical-align:middle; width:186px" %)((( 269 269 **Effective time** 270 -)))| =(% style="text-align:9px;" %)**Default value**|=(% style="text-align:85px;" %)**Range**|=(% style="text-align:4px;" %)**Definition**|=(% style="text-align:69px;" %)**Unit**271 -|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-02|(% style="text-align:center; vertical-align:middle; width: 165px" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:148px" %)(((272 +)))|(% style="text-align:center; vertical-align:middle; width:130px" %)**Default value**|(% style="text-align:center; vertical-align:middle; width:132px" %)**Range**|(% style="text-align:center; vertical-align:middle; width:252px" %)**Definition**|(% style="text-align:center; vertical-align:middle; width:85px" %)**Unit** 273 +|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-02|(% style="text-align:center; vertical-align:middle; width:205px" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:187px" %)((( 272 272 Operation setting 273 -)))|(% style="text-align:center; vertical-align:middle; width:16 5px" %)(((275 +)))|(% style="text-align:center; vertical-align:middle; width:186px" %)((( 274 274 Effective immediately 275 -)))|(% style="text-align:center; vertical-align:middle; width:10 9px" %)2|(% style="text-align:center; vertical-align:middle; width:85px" %)0 to6|(% style="width:224px" %)(((276 -0 :2400bps277 +)))|(% style="text-align:center; vertical-align:middle; width:130px" %)2|(% style="text-align:center; vertical-align:middle; width:132px" %)0 to 5|(% style="width:252px" %)((( 278 +0-2400bps 277 277 278 -1 :4800bps280 +1-4800bps 279 279 280 -2 :9600bps282 +2-9600bps 281 281 282 -3 :19200bps284 +3-19200bps 283 283 284 -4 :38400bps286 +4-38400bps 285 285 286 -5: 57600bp 287 - 288 -6:115200bps 289 -)))|(% style="text-align:center; vertical-align:middle; width:69px" %)- 290 -|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-03|(% style="text-align:center; vertical-align:middle; width:165px" %)Serial data format|(% style="text-align:center; vertical-align:middle; width:148px" %)((( 288 +5-57600bp 289 +)))|(% style="text-align:center; vertical-align:middle; width:85px" %)- 290 +|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-03|(% style="text-align:center; vertical-align:middle; width:205px" %)Serial data format|(% style="text-align:center; vertical-align:middle; width:187px" %)((( 291 291 Operation setting 292 -)))|(% style="text-align:center; vertical-align:middle; width:16 5px" %)(((292 +)))|(% style="text-align:center; vertical-align:middle; width:186px" %)((( 293 293 Effective immediately 294 -)))|(% style="text-align:center; vertical-align:middle; width:10 9px" %)0|(% style="text-align:center; vertical-align:middle; width:85px" %)0 to 3|(% style="width:224px" %)(((294 +)))|(% style="text-align:center; vertical-align:middle; width:130px" %)0|(% style="text-align:center; vertical-align:middle; width:132px" %)0 to 3|(% style="width:252px" %)((( 295 295 0: 1 stop bit, no parity 296 296 297 297 1: 1 stop bit, odd parity ... ... @@ -299,33 +299,20 @@ 299 299 2: 1 stop bit, even parity 300 300 301 301 3: 2 stop bits, no parity 302 -)))|(% style="text-align:center; vertical-align:middle; width: 69px" %)-303 -|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-04|(% style="text-align:center; vertical-align:middle; width: 165px" %)Modbus communication data is written into EEPROM|(% style="text-align:center; vertical-align:middle; width:148px" %)(((302 +)))|(% style="text-align:center; vertical-align:middle; width:85px" %)- 303 +|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-04|(% style="text-align:center; vertical-align:middle; width:205px" %)Modbus communication data is written into EEPROM|(% style="text-align:center; vertical-align:middle; width:187px" %)((( 304 304 Operation setting 305 -)))|(% style="text-align:center; vertical-align:middle; width:16 5px" %)(((305 +)))|(% style="text-align:center; vertical-align:middle; width:186px" %)((( 306 306 Effective immediately 307 -)))|(% style="text-align:center; vertical-align:middle; width:10 9px" %)0|(% style="text-align:center; vertical-align:middle; width:85px" %)0 to 1|(% style="width:224px" %)(((307 +)))|(% style="text-align:center; vertical-align:middle; width:130px" %)0|(% style="text-align:center; vertical-align:middle; width:132px" %)0 to 1|(% style="width:252px" %)((( 308 308 0: Do not write to EEPROM, and do not store after power failure; 309 309 310 310 1: Write to EEPROM, power-down storage. 311 -)))|(% style="text-align:center; vertical-align:middle; width:69px" %)- 312 -|P12-06|Modbus 32-bit variable big endian and little endian|((( 313 -Operation 311 +)))|(% style="text-align:center; vertical-align:middle; width:85px" %)- 314 314 315 -setting 316 -)))|((( 317 -Effective 318 - 319 -immediately 320 -)))|0|0-1|((( 321 -0: Big-endian mode, the lower address stores the higher 16 bits of data, and the higher address stores the lower 16 bits of data 322 - 323 -1: Little-endian mode, the lower address stores the lower 16 bits of data, and the higher address stores the higher 16 bits of data 324 -)))|- 325 - 326 326 = **Modbus communication variable address and value** = 327 327 328 -== **Variable address** == 315 +== **Variable address description** == 329 329 330 330 Modbus registers are divided into two categories: 331 331 ... ... @@ -351,16 +351,20 @@ 351 351 In order to facilitate actual use, this manual provides both decimal and hexadecimal address identification, it is shown in the following table: 352 352 353 353 (% class="table-bordered" %) 354 -|=(% style="text-align: center; vertical-align: middle; width: 162px;" %)**Function code**|=(% style="text-align: center; vertical-align: middle; width: 302px;" %)((( 355 -**Modbus address (Hexadecimal)** 356 -)))|=(% style="text-align: center; vertical-align: middle; width: 278px;" %)((( 357 -**Modbus address (Decimal)** 358 -)))|=(% style="text-align: center; vertical-align: middle; width: 192px;" %)**Category**|=(% style="text-align: center; vertical-align: middle; width: 142px;" %)**Name** 359 -|(% style="text-align:center; vertical-align:middle; width:162px" %)P0-1|(% style="text-align:center; vertical-align:middle; width:302px" %)0x0001|(% style="text-align:center; vertical-align:middle; width:278px" %)1|(% style="text-align:center; vertical-align:middle; width:192px" %)Basic settings|(% style="text-align:center; vertical-align:middle; width:142px" %)Control mode 341 +|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)((( 342 +**Modbus address** 360 360 344 +**(Hexadecimal)** 345 +)))|(% style="text-align:center; vertical-align:middle" %)((( 346 +**Modbus address** 347 + 348 +**(Decimal)** 349 +)))|(% style="text-align:center; vertical-align:middle" %)**Category**|(% style="text-align:center; vertical-align:middle" %)**Name** 350 +|(% style="text-align:center; vertical-align:middle" %)P0-1|(% style="text-align:center; vertical-align:middle" %)0x0001|(% style="text-align:center; vertical-align:middle" %)1|(% style="text-align:center; vertical-align:middle" %)Basic settings|(% style="text-align:center; vertical-align:middle" %)Control mode 351 + 361 361 For detailed parameter addresses, please refer to __[["11.1 Lists of parameters".>>https://docs.we-con.com.cn/bin/view/Servo/Manual/02%20VD2%20SA%20Series/11%20Appendix/#HListsofparameters]]__ 362 362 363 -== **Variable value type** == 354 +== **Variable value type description** == 364 364 365 365 When writing function codes with signed numbers, you need to convert the pre-written data into hexadecimal complements. The conversion rules are as follows: 366 366