Changes for page 08 Communication

Last modified by Iris on 2025/07/24 15:23

From version 4.14
edited by Stone Wu
on 2022/07/07 15:34
Change comment: There is no comment for this version
To version 1.1
edited by Leo Wei
on 2022/06/08 12:57
Change comment: Imported from XAR

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Servo.1 User Manual.02 VD2 SA Series.WebHome
1 +Servo.2\. User Manual.06 VD2 SA Series Servo Drives Manual (Full V1\.1).WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Stone
1 +XWiki.admin
Content
... ... @@ -6,17 +6,16 @@
6 6  
7 7  The position of RS485 communication port (take VD2B as an example) is as the figure below.
8 8  
9 -(% style="text-align:center" %)
10 -[[image:image-20220608154248-1.png]]
9 +[[image:http://docs.we-con.com.cn/wiki/servo/download/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/WebHome/Wecon%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29_html_6583b880b8115df0.gif?rev=1.1||alt="Wecon VD2 SA Series Servo Drives Manual (Full V1.1)_html_6583b880b8115df0.gif"]]
11 11  
12 12  Figure 8-1 The position of RS485 communication port of VD2B drive
13 13  
14 -For the position of the RS485 communication port of other models, see __[[4.5 Communication signal wiring>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/04%20Wiring/#HCommunicationsignalwiring]]__.
13 +For the position of the RS485 communication port of other models, see __[[4.5 Communication signal wiring>>http://13.229.109.52:8080/wiki/servo/view/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/04%20Wiring/#HCommunicationsignalwiring]]__.
15 15  
16 16  The servo drive adopts RS485 half-duplex communication mode. The 485 bus should adopt the hand-in-hand structure instead of the star structure or the bifurcated structure. The star structure or bifurcation structure will produce reflected signals, which will affect the 485 communication.
17 17  
18 18  (% class="table-bordered" %)
19 -|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153134-1.png]]
18 +|(% style="text-align:center; vertical-align:middle" %)[[image:http://docs.we-con.com.cn/wiki/servo/download/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/WebHome/Wecon%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29_html_6db94f5d0421f97a.png?rev=1.1||alt="Wecon VD2 SA Series Servo Drives Manual (Full V1.1)_html_6db94f5d0421f97a.png"]]
20 20  |(((
21 21  ✎The wiring must use shielded twisted pair, stay away from strong electricity, do not run in parallel with the power line, let alone bundle it together!
22 22  
... ... @@ -23,8 +23,7 @@
23 23  ✎In a half-duplex connection, only one servo drive can communicate with the host computer at the same time. If two or more servo drives upload data at the same time, bus competition will occur. Not only will it lead to communication failure, it may also cause some components to generate large currents and damage the components.
24 24  )))
25 25  
26 -(% style="text-align:center" %)
27 -[[image:image-20220608174415-1.png]]
25 +[[image:http://docs.we-con.com.cn/wiki/servo/download/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/WebHome/Wecon%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29_html_ec4180b4b0c8dd01.gif?rev=1.1||alt="Wecon VD2 SA Series Servo Drives Manual (Full V1.1)_html_ec4180b4b0c8dd01.gif"]]
28 28  
29 29  Figure 8-2 RS485 communication network wiring diagram
30 30  
... ... @@ -33,7 +33,7 @@
33 33  No point in the RS485 network can be directly grounded. All devices in the network must be well grounded through their own grounding terminals.
34 34  
35 35  (% class="table-bordered" %)
36 -|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153144-2.png]]
34 +|(% style="text-align:center; vertical-align:middle" %)[[image:http://docs.we-con.com.cn/wiki/servo/download/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/WebHome/Wecon%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29_html_6db94f5d0421f97a.png?rev=1.1||alt="Wecon VD2 SA Series Servo Drives Manual (Full V1.1)_html_6db94f5d0421f97a.png"]]
37 37  |Under no circumstances can the grounding wire form a closed loop.
38 38  
39 39  When wiring, consider the drive capability of the computer/PLC and the distance between the computer/PLC and the servo drive. If the drive capacity is insufficient, a repeater is needed.
... ... @@ -54,46 +54,58 @@
54 54  
55 55  (% class="table-bordered" %)
56 56  |(% style="text-align:center; vertical-align:middle" %)**Operate**|(% style="text-align:center; vertical-align:middle" %)**Command code**
57 -|(% style="text-align:center; vertical-align:middle" %)Read 16-bit/32-bit function code|(% style="text-align:center; vertical-align:middle" %)0x03
55 +|(% style="text-align:center; vertical-align:middle" %)Read 16-bit function code|(% style="text-align:center; vertical-align:middle" %)0x03
58 58  |(% style="text-align:center; vertical-align:middle" %)Write 16-bit function code|(% style="text-align:center; vertical-align:middle" %)0x06
59 -|(% style="text-align:center; vertical-align:middle" %)Write 32-bit function code|(% style="text-align:center; vertical-align:middle" %)0x10
60 60  
61 -**Read function code: 0x03**
58 +**(1) Read function code: 0x03**
62 62  
63 63  Request format:
64 64  
65 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Initial address**|(% colspan="2" %)**Number of reads**|(% rowspan="2" %)**CRC check code**
66 -|**high byte**|**low byte**|**high byte**|**low byte**
67 -|1 byte|03|1 byte|1 byte|1 byte|1 byte|2 bytes
62 +(% class="table-bordered" %)
63 +|(% style="text-align:center; vertical-align:middle; width:84px" %)**Address**|(% style="text-align:center; vertical-align:middle; width:104px" %)**Function code**|(% style="text-align:center; vertical-align:middle; width:179px" %)(((
64 +**Initial address high byte**
65 +)))|(% style="text-align:center; vertical-align:middle; width:162px" %)(((
66 +**Initial address low byte**
67 +)))|(% style="text-align:center; vertical-align:middle; width:194px" %)(((
68 +**Number of reads high byte**
69 +)))|(% style="text-align:center; vertical-align:middle; width:195px" %)(((
70 +**Number of reads low byte**
71 +)))|(% style="text-align:center; vertical-align:middle; width:158px" %)**CRC check code**
72 +|(% style="text-align:center; vertical-align:middle; width:84px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:104px" %)03|(% style="text-align:center; vertical-align:middle; width:179px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:162px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:194px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:195px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:158px" %)2 bytes
68 68  
69 69  Correct response format:
70 70  
71 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% rowspan="2" %)**Number of bytes of returned data**|(% colspan="2" %)**Register 1**|(% rowspan="2" %)**…**|(% rowspan="2" %)**CRC check code**
72 -|**high byte**|**low byte**
73 -|1 byte|03|1 byte|1 byte|1 byte|…|2 bytes
76 +(% class="table-bordered" %)
77 +|(% style="text-align:center; vertical-align:middle; width:85px" %)**Address**|(% style="text-align:center; vertical-align:middle; width:139px" %)**Function code**|(% style="text-align:center; vertical-align:middle; width:244px" %)(((
78 +**Return data number of bytes**
79 +)))|(% style="text-align:center; vertical-align:middle; width:203px" %)(((
80 +**Register 1 high byte**
81 +)))|(% style="text-align:center; vertical-align:middle; width:190px" %)(((
82 +**Register 1 low byte**
83 +)))|(% style="text-align:center; vertical-align:middle; width:72px" %)…|(% style="text-align:center; vertical-align:middle; width:143px" %)**CRC check code**
84 +|(% style="text-align:center; vertical-align:middle; width:85px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:139px" %)03|(% style="text-align:center; vertical-align:middle; width:244px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:203px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:190px" %)1 byte|(% style="text-align:center; vertical-align:middle; width:72px" %)…|(% style="text-align:center; vertical-align:middle; width:143px" %)2 bytes
74 74  
75 -**Write function code: 0x06**
86 +**(2) Write function code: 0x06**
76 76  
77 77  Request format:
78 78  
79 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)(((
80 -**Register address**
81 -)))|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code**
82 -|**high byte**|**low byte**|**high byte**|**low byte**
83 -|1 byte|06|1 byte|1 byte|1 byte|1 byte|2 bytes
90 +(% class="table-bordered" %)
91 +|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Register address high byte**|(% style="text-align:center; vertical-align:middle" %)**Register address low byte**|(% style="text-align:center; vertical-align:middle" %)**Data high byte**|(% style="text-align:center; vertical-align:middle" %)**Data low byte**|(% style="text-align:center; vertical-align:middle" %)**CRC check code**
92 +|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)06|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)2 bytes
84 84  
85 85  Response format:
86 86  
87 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code**
88 -|**high byte**|**low byte**|**high byte**|**low byte**
89 -|1 byte|06|1 byte|1 byte|1 byte|1 byte|2 bytes
96 +(% class="table-bordered" %)
97 +|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Register address high byte**|(% style="text-align:center; vertical-align:middle" %)**Register address low byte**|(% style="text-align:center; vertical-align:middle" %)**Data high byte**|(% style="text-align:center; vertical-align:middle" %)**Data low byte**|(% style="text-align:center; vertical-align:middle" %)**CRC check code**
98 +|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)06|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)2 bytes
90 90  
91 91  If the setting is successful, the original is returned
92 92  
93 -|(% rowspan="2" %)**There should be a message interval not less than 3.5 characters at the beginning**|**Address**|**Function code**|**Data**|**CRC check code**
94 -|1 byte|1 byte|N bytes|2 bytes
102 +(% class="table-bordered" %)
103 +|(% rowspan="2" style="text-align:center; vertical-align:middle" %)**There should be a message interval not less than 3.5 characters at the beginning**|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Data**|(% style="text-align:center; vertical-align:middle" %)**CRC check code**
104 +|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)N bytes|(% style="text-align:center; vertical-align:middle" %)2 bytes
95 95  
96 -(% style="color:inherit; font-family:inherit; font-size:26px" %)**CRC check**
106 +== **CRC check** ==
97 97  
98 98  The servo uses a 16-bit CRC check, and the host computer must also use the same check rule, otherwise the CRC check will make mistake. When transmitting, the low bit is in the front and the high bit is at the back. The CRC code are as follows:
99 99  
... ... @@ -164,66 +164,42 @@
164 164  
165 165  == **Communication example** ==
166 166  
177 +**03 Function Code Read**
167 167  
168 -
169 -**03 Function code read**
170 -
171 171  Read the monitoring volume U0-31 bus voltage, the Modbus register address corresponding to this variable is 7716 (0x1E24)
172 172  
173 173  Request format:
174 174  
175 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code**
176 -|**high byte**|**low byte**|**high byte**|**low byte**
177 -|01|03|1E|24|00|01|C2 29
183 +(% class="table-bordered" %)
184 +|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Register address high byte**|(% style="text-align:center; vertical-align:middle" %)**Register address low byte**|(% style="text-align:center; vertical-align:middle" %)**Data high byte**|(% style="text-align:center; vertical-align:middle" %)**Data low byte**|(% style="text-align:center; vertical-align:middle" %)**CRC check code**
185 +|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)06|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)1 byte|(% style="text-align:center; vertical-align:middle" %)2 bytes
178 178  
179 179  The slave responds normally:
180 180  
181 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% rowspan="2" %)**Number of bytes**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC high byte**
182 -|**high byte**|**low byte**
183 -|01|03|02|0C|4F|FC B0
189 +(% class="table-bordered" %)
190 +|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Number of bytes**|(% style="text-align:center; vertical-align:middle" %)**Data high byte**|(% style="text-align:center; vertical-align:middle" %)**Data low byte**|(% style="text-align:center; vertical-align:middle" %)**CRC low byte**|(% style="text-align:center; vertical-align:middle" %)**CRC high byte**
191 +|(% style="text-align:center; vertical-align:middle" %)01|(% style="text-align:center; vertical-align:middle" %)03|(% style="text-align:center; vertical-align:middle" %)02|(% style="text-align:center; vertical-align:middle" %)0C|(% style="text-align:center; vertical-align:middle" %)26|(% style="text-align:center; vertical-align:middle" %)3C|(% style="text-align:center; vertical-align:middle" %)9E
184 184  
185 -For example: The value read is 0x0C4F, which means that the voltage is 315.1V.
193 +The value read is 0x0C26, which means that the voltage is 311.0V. 
186 186  
187 -
188 -
189 189  **06 Function Code Write**
190 190  
191 -P1-10 the maximum speed threshold is set to 3000rpm. This variable corresponds to the Modbus address: 266 (0x010A)
197 +P1-10 the maximum speed threshold is set to 3000rpm. This variable corresponds to the Modbus address: 266 (0x010A)
192 192  
193 193  Request format:
194 194  
195 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code**
196 -|**high byte**|**low byte**|**high byte**|**low byte**
197 -|01|06|01|0A|0B|B8|AF, 76
201 +(% class="table-bordered" %)
202 +|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Register address high byte**|(% style="text-align:center; vertical-align:middle" %)**Register address low byte**|(% style="text-align:center; vertical-align:middle" %)**Data high byte**|(% style="text-align:center; vertical-align:middle" %)**Data low byte**|(% style="text-align:center; vertical-align:middle" %)**CRC low byte**
203 +|(% style="text-align:center; vertical-align:middle" %)01|(% style="text-align:center; vertical-align:middle" %)06|(% style="text-align:center; vertical-align:middle" %)01|(% style="text-align:center; vertical-align:middle" %)0A|(% style="text-align:center; vertical-align:middle" %)0B|(% style="text-align:center; vertical-align:middle" %)B8|(% style="text-align:center; vertical-align:middle" %)AF
198 198  
199 199  The slave responds normally:
200 200  
201 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% rowspan="2" %)**CRC check code**
202 -|**high byte**|**low byte**|**high byte**|**low byte**
203 -|01|06|01|0A|0B|B8|AF, 76
207 +|(% style="text-align:center; vertical-align:middle" %)**Address**|(% style="text-align:center; vertical-align:middle" %)**Function code**|(% style="text-align:center; vertical-align:middle" %)**Register address high byte**|(% style="text-align:center; vertical-align:middle" %)**Register address low byte**|(% style="text-align:center; vertical-align:middle" %)**Data high byte**|(% style="text-align:center; vertical-align:middle" %)**Data low byte**|(% style="text-align:center; vertical-align:middle" %)**CRC low byte**
208 +|(% style="text-align:center; vertical-align:middle" %)01|(% style="text-align:center; vertical-align:middle" %)06|(% style="text-align:center; vertical-align:middle" %)01|(% style="text-align:center; vertical-align:middle" %)0A|(% style="text-align:center; vertical-align:middle" %)0B|(% style="text-align:center; vertical-align:middle" %)B8|(% style="text-align:center; vertical-align:middle" %)AF
204 204  
205 -
206 -
207 -**10 Function code write**
208 -
209 -P07-09 set the 1st segment position to 2000, and this variable corresponds to the Modbus address: 1801 (0x0709).
210 -
211 -Request format:
212 -
213 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Initial address**|(% colspan="2" %)**Number of register**|(% rowspan="2" %)**Number of data**|(% colspan="2" %)**Data 1**|(% colspan="2" %)**Data 2**|(% colspan="2" %)**CRC check code**
214 -|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte**
215 -|01|10|07|09|00|02|04|00|00|07|D0|16|59
216 -
217 -The slave responds normally:
218 -
219 -|(% rowspan="2" %)**Address**|(% rowspan="2" %)**Function code**|(% colspan="2" %)**Register address**|(% colspan="2" %)**Data**|(% colspan="2" %)**CRC check code**
220 -|**high byte**|**low byte**|**high byte**|**low byte**|**high byte**|**low byte**
221 -|01|10|07|09|00|02|90|BE
222 -
223 223  = **Servo communication parameter setting** =
224 224  
225 -(% style="text-align:center" %)
226 -[[image:image-20220608174504-2.png]]
212 +[[image:http://docs.we-con.com.cn/wiki/servo/download/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/WebHome/Wecon%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29_html_fd76131f4dd0361c.gif?rev=1.1||alt="Wecon VD2 SA Series Servo Drives Manual (Full V1.1)_html_fd76131f4dd0361c.gif"]]
227 227  
228 228  Figure 8-3 Modbus communication parameter setting process
229 229  
... ... @@ -258,7 +258,7 @@
258 258  If you need to change the value of the function code frequently, it is recommended to turn off the function of real-time writing to EERPOM of function code, otherwise the EEPROM will be shortened due to frequent erasing and writing of the EEPROM.
259 259  
260 260  (% class="table-bordered" %)
261 -|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611153214-3.png]]
247 +|(% style="text-align:center; vertical-align:middle" %)[[image:http://docs.we-con.com.cn/wiki/servo/download/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/WebHome/Wecon%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29_html_6db94f5d0421f97a.png?rev=1.1||alt="Wecon VD2 SA Series Servo Drives Manual (Full V1.1)_html_6db94f5d0421f97a.png"]]
262 262  |After the EEPROM is damaged, the servo will have an non resettable fault!
263 263  
264 264  **(5) Set the high and low order of the 32-bit monitoring data**
... ... @@ -270,16 +270,16 @@
270 270  The description of related function codes are as follows.
271 271  
272 272  (% class="table-bordered" %)
273 -|(% style="text-align:center; vertical-align:middle; width:121px" %)**Function code**|(% style="text-align:center; vertical-align:middle; width:205px" %)**Name**|(% style="text-align:center; vertical-align:middle; width:187px" %)(((
259 +|(% style="text-align:center; vertical-align:middle; width:121px" %)**Function code**|(% style="text-align:center; vertical-align:middle; width:205px" %)**Name**|(% style="text-align:center; vertical-align:middle; width:135px" %)(((
274 274  **Setting method**
275 -)))|(% style="text-align:center; vertical-align:middle; width:186px" %)(((
261 +)))|(% style="text-align:center; vertical-align:middle; width:171px" %)(((
276 276  **Effective time**
277 -)))|(% style="text-align:center; vertical-align:middle; width:130px" %)**Default value**|(% style="text-align:center; vertical-align:middle; width:132px" %)**Range**|(% style="text-align:center; vertical-align:middle; width:335px" %)**Definition**|(% style="text-align:center; vertical-align:middle; width:189px" %)**Unit**
278 -|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-02|(% style="text-align:center; vertical-align:middle; width:205px" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:187px" %)(((
263 +)))|(% style="text-align:center; vertical-align:middle; width:115px" %)**Default value**|(% style="text-align:center; vertical-align:middle; width:61px" %)**Range**|(% style="text-align:center; vertical-align:middle; width:347px" %)**Definition**|(% style="text-align:center; vertical-align:middle" %)**Unit**
264 +|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-02|(% style="text-align:center; vertical-align:middle; width:205px" %)Baud rate|(% style="text-align:center; vertical-align:middle; width:135px" %)(((
279 279  Operation setting
280 -)))|(% style="text-align:center; vertical-align:middle; width:186px" %)(((
266 +)))|(% style="text-align:center; vertical-align:middle; width:171px" %)(((
281 281  Effective immediately
282 -)))|(% style="text-align:center; vertical-align:middle; width:130px" %)2|(% style="text-align:center; vertical-align:middle; width:132px" %)0 to 5|(% style="width:335px" %)(((
268 +)))|(% style="text-align:center; vertical-align:middle; width:115px" %)2|(% style="text-align:center; vertical-align:middle; width:61px" %)0 to 5|(% style="width:347px" %)(((
283 283  0-2400bps
284 284  
285 285  1-4800bps
... ... @@ -291,12 +291,12 @@
291 291  4-38400bps
292 292  
293 293  5-57600bp
294 -)))|(% style="text-align:center; vertical-align:middle; width:189px" %)-
295 -|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-03|(% style="text-align:center; vertical-align:middle; width:205px" %)Serial data format|(% style="text-align:center; vertical-align:middle; width:187px" %)(((
280 +)))|(% style="text-align:center; vertical-align:middle" %)-
281 +|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-03|(% style="text-align:center; vertical-align:middle; width:205px" %)Serial data format|(% style="text-align:center; vertical-align:middle; width:135px" %)(((
296 296  Operation setting
297 -)))|(% style="text-align:center; vertical-align:middle; width:186px" %)(((
283 +)))|(% style="text-align:center; vertical-align:middle; width:171px" %)(((
298 298  Effective immediately
299 -)))|(% style="text-align:center; vertical-align:middle; width:130px" %)0|(% style="text-align:center; vertical-align:middle; width:132px" %)0 to 3|(% style="width:335px" %)(((
285 +)))|(% style="text-align:center; vertical-align:middle; width:115px" %)0|(% style="text-align:center; vertical-align:middle; width:61px" %)0 to 3|(% style="width:347px" %)(((
300 300  0: 1 stop bit, no parity
301 301  
302 302  1: 1 stop bit, odd parity
... ... @@ -304,16 +304,16 @@
304 304  2: 1 stop bit, even parity
305 305  
306 306  3: 2 stop bits, no parity
307 -)))|(% style="text-align:center; vertical-align:middle; width:189px" %)-
308 -|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-04|(% style="text-align:center; vertical-align:middle; width:205px" %)Modbus communication data is written into EEPROM|(% style="text-align:center; vertical-align:middle; width:187px" %)(((
293 +)))|(% style="text-align:center; vertical-align:middle" %)-
294 +|(% style="text-align:center; vertical-align:middle; width:121px" %)P12-04|(% style="text-align:center; vertical-align:middle; width:205px" %)Modbus communication data is written into EEPROM|(% style="text-align:center; vertical-align:middle; width:135px" %)(((
309 309  Operation setting
310 -)))|(% style="text-align:center; vertical-align:middle; width:186px" %)(((
296 +)))|(% style="text-align:center; vertical-align:middle; width:171px" %)(((
311 311  Effective immediately
312 -)))|(% style="text-align:center; vertical-align:middle; width:130px" %)0|(% style="text-align:center; vertical-align:middle; width:132px" %)0 to 1|(% style="width:335px" %)(((
298 +)))|(% style="text-align:center; vertical-align:middle; width:115px" %)0|(% style="text-align:center; vertical-align:middle; width:61px" %)0 to 1|(% style="width:347px" %)(((
313 313  0: Do not write to EEPROM, and do not store after power failure;
314 314  
315 315  1: Write to EEPROM, power-down storage.
316 -)))|(% style="text-align:center; vertical-align:middle; width:189px" %)-
302 +)))|(% style="text-align:center; vertical-align:middle" %)-
317 317  
318 318  = **Modbus communication variable address and value** =
319 319  
... ... @@ -357,7 +357,7 @@
357 357  )))|(% style="text-align:center; vertical-align:middle" %)**Category**|(% style="text-align:center; vertical-align:middle" %)**Name**
358 358  |(% style="text-align:center; vertical-align:middle" %)P0-1|(% style="text-align:center; vertical-align:middle" %)0x0001|(% style="text-align:center; vertical-align:middle" %)1|(% style="text-align:center; vertical-align:middle" %)Basic settings|(% style="text-align:center; vertical-align:middle" %)Control mode
359 359  
360 -For detailed parameter addresses, please refer to __[["11.1 Lists of parameters".>>https://docs.we-con.com.cn/bin/view/Servo/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/11%20Appendix/#HListsofparameters]]__
346 +For detailed parameter addresses, please refer to __[["11.1 Lists of parameters".>>http://13.229.109.52:8080/wiki/servo/view/2.%20User%20Manual/06%20VD2%20SA%20Series%20Servo%20Drives%20Manual%20%28Full%20V1.1%29/11%20Appendix/#HListsofparameters]]__
361 361  
362 362  == **Variable value type description** ==
363 363  
image-20220608154248-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -12.3 KB
Content
image-20220608154320-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -10.1 KB
Content
image-20220608154619-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -10.8 KB
Content
image-20220608174415-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -54.9 KB
Content
image-20220608174504-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -87.2 KB
Content
image-20220611153134-1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -3.8 KB
Content
image-20220611153144-2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -3.8 KB
Content
image-20220611153214-3.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.Joey
Size
... ... @@ -1,1 +1,0 @@
1 -3.8 KB
Content