Changes for page 10 Malfunctions

Last modified by Theodore Xu on 2025/02/13 17:16

From version 1.2
edited by Leo Wei
on 2022/06/11 12:58
Change comment: There is no comment for this version
To version 2.2
edited by Leo Wei
on 2022/06/11 12:59
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -161,7 +161,7 @@
161 161  1. The clearing method of category 2 and category 3 clearable faults: first turn off the servo enable signal (set S-ON to OFF), then set P10-03=1 or use DI function 02.
162 162  1. The clearing method of category 4 of clearable warnings: set P10-03=1 or use DI function 02.
163 163  
164 -|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611125801-1.png]]
164 +|(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611125934-1.png]]
165 165  |For some faults and warnings, you must change the settings to eliminate the causes before they can be cleared, but clearing does not mean that the changes take effect. For the changes that need to be re-powered to take effect, the power must be re-powered. For the changes that need to be stopped to take effect, the servo enable must be turned off. After the change takes effect, the servo drive can operate normally.
166 166  
167 167  Associated function codes