... ... @@ -159,7 +159,7 @@
159 159  
160 160  1. Set the function code P10-03=1 (fault clearing) or use DI function 02 (02-A-CLR, fault and warning clearing) and set it to logic valid, which can stop the fault display on the panel.
161 161  1. The clearing method of category 2 and category 3 clearable faults: first turn off the servo enable signal (set S-ON to OFF), then set P10-03=1 or use DI function 02.
162 -1. The clearing method of category 4 of clearable warnings: set P10-03=1 or use DI function 02.[[image:image-20220611130000-2.png]]
162 +1. The clearing method of category 4 of clearable warnings: set P10-03=1 or use DI function 02.
163 163  
164 164  |(% style="text-align:center; vertical-align:middle" %)[[image:image-20220611125934-1.png]]
165 165  |For some faults and warnings, you must change the settings to eliminate the causes before they can be cleared, but clearing does not mean that the changes take effect. For the changes that need to be re-powered to take effect, the power must be re-powered. For the changes that need to be stopped to take effect, the servo enable must be turned off. After the change takes effect, the servo drive can operate normally.