Changes for page VFD Application

Last modified by Theodore Xu on 2024/01/19 16:28

From version 17.1
edited by Theodore Xu
on 2024/01/19 16:28
Change comment: There is no comment for this version
To version 5.1
edited by Theodore Xu
on 2024/01/19 16:14
Change comment: Attachment moved to xwiki:Solutions.Inverter.Air Conditioning System.WebHome.

Summary

Details

Page properties
Content
... ... @@ -1,0 +1,53 @@
1 +== ==
2 +
3 +(% style="text-align:center" %)
4 +[[image:图片1.png]]
5 +
6 +VB VFD can achieve various purposes such as energy saving, improving system stability, safety and intelligence by automatically adjusting refrigeration pumps, cooling pumps and other equipment in central air-conditioning systems.
7 +
8 +**Electrical control diagram**
9 +
10 +(% style="text-align:center" %)
11 +[[image:图片2.png]]
12 +
13 +**Parameter Settings**
14 +
15 +|**Parameter**|**Description**|**Set Value**|**Remarks**
16 +|F0.01|Start & Stop Order Source|1|DI Terminal
17 +|F0.03|Main Frequency Source X|3|AI2
18 +|F0.04|Auxiliary Frequency Source Y|0|Keypad
19 +|F0.07|Frequency Calculation Option|02|Switchover between X & Y
20 +|F0.18|Acceleration Time|30.0|30S
21 +|F0.19|Deceleration Time|30.0|30S
22 +|F5.00|DI1 Option|01|FWD Run
23 +|F5.01|DI2 Option|18|Switch Frequency Source
24 +|F5.02|DI3 Option|20|Switch Start & Stop Order Source
25 +|F5.23|AI2 Maximum Input|2.0|AI2-4ma
26 +|F6.15|AO1 Coefficient|20.0|(% rowspan="2" %)AO1 Output 4~~20mA
27 +|F6.18|AO1 Gain|0.8
28 +
29 +== **4. Specific Effect Presentation** ==
30 +
31 +In the case application, VB VFD demonstrated multiple effects.
32 +
33 +First, it has significant economic and energy-saving advantages. Through microcomputer control, the system can automatically adjust the temperature of the end air duct to achieve automated operation. The coils can be turned off even when no one is using them, further saving energy.
34 +
35 +Secondly, the application of VB high-performance VFD makes the equipment start and stop more quickly and stably, and has the advantages of large starting torque and small impact on the power grid. This provides more efficient and reliable guarantee for long-term operation.
36 +
37 +In addition, it has overload, overcurrent, overvoltage, phase loss and other protection functions, which can greatly improve the safety of the system. This enables the system to protect itself promptly and effectively in the face of various possible problems, further ensuring the stability and reliability of the system.
38 +
39 +Finally, VB’s optimized programmable DI terminal allows the VFD to easily cope with the requirements of various occasions. It also provides greater flexibility for practical applications. Users can customize settings and operations according to actual needs to meet various application scenarios.
40 +
41 +== **5. Photos at Site** ==
42 +
43 +(% style="text-align:center" %)
44 +[[image:图片3.png||height="859" width="607"]]
45 +
46 +(% style="text-align:center" %)
47 +[[image:图片4.png||height="450" width="601"]]
48 +
49 +(% style="text-align:center" %)
50 +[[image:图片5.png||height="447" width="597"]]
51 +
52 +(% style="text-align:center" %)
53 +[[image:图片6.png||height="453" width="604"]]
图片1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -102.8 KB
Content
Attachment.Code.RedirectClass[1]
Target Name
... ... @@ -1,1 +1,0 @@
1 -图片3.png
Source Name
... ... @@ -1,1 +1,0 @@
1 -图片3.png
Target Location
... ... @@ -1,1 +1,0 @@
1 -xwiki:Solutions.Inverter.Air Conditioning System.WebHome
Attachment.Code.RedirectClass[2]
Target Name
... ... @@ -1,1 +1,0 @@
1 -图片2.png
Source Name
... ... @@ -1,1 +1,0 @@
1 -图片2.png
Target Location
... ... @@ -1,1 +1,0 @@
1 -xwiki:Solutions.Inverter.Air Conditioning System.WebHome
Attachment.Code.RedirectClass[3]
Target Name
... ... @@ -1,1 +1,0 @@
1 -图片4.png
Source Name
... ... @@ -1,1 +1,0 @@
1 -图片4.png
Target Location
... ... @@ -1,1 +1,0 @@
1 -xwiki:Solutions.Inverter.Air Conditioning System.WebHome
Attachment.Code.RedirectClass[4]
Target Name
... ... @@ -1,1 +1,0 @@
1 -图片5.png
Source Name
... ... @@ -1,1 +1,0 @@
1 -图片5.png
Target Location
... ... @@ -1,1 +1,0 @@
1 -xwiki:Solutions.Inverter.Air Conditioning System.WebHome
Attachment.Code.RedirectClass[5]
Target Name
... ... @@ -1,1 +1,0 @@
1 -图片6.png
Source Name
... ... @@ -1,1 +1,0 @@
1 -图片6.png
Target Location
... ... @@ -1,1 +1,0 @@
1 -xwiki:Solutions.Inverter.Air Conditioning System.WebHome