1 -= {{id name="HAllen-Bradley28Rockwell29"/}}Allen-Bradley(**Rockwell**) =
2 -
3 -== {{id name="HDF1AdvancedA0A0Serial"/}}**DF1 Advanced  Serial** ==
4 -
5 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
6 -
7 -**1) V-Box Settings**
8 -
9 -|=Item|=Recommended |=Note
10 -|=Protocol|Allen Bradley DF1 Advanced|
11 -|=Connection|RS232|
12 -|=Baud rate|19200|
13 -|=Stop bits|1|
14 -|=Data bits|8|
15 -|=Parity|None|
16 -|=PLC Station No.|1|
17 -|=HMI Station No.|0|
18 -
19 -**2) Address List**
20 -
21 -|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
22 -|(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
23 -|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
24 -|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
25 -|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
26 -|BN|BNddddd.dd|0.0~~99255.15|(((
27 -Bit data file B0~~B99
28 -
29 -First two digits is for file number
30 -
31 -For example, BN13001.00 represents file number B13, address 001, the 0th bit.
32 -)))
33 -|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
34 -|NN|NNddddd.dd|0.0~~99255.15|(((
35 -Integer data file bit format N0~~N99
36 -
37 -First two digits is for file number
38 -
39 -For example, NN13001.00 represents file number N13, address 001, the 0th bit.
40 -)))
41 -|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
42 -|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
43 -|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
44 -|TNS|TNSddddd|0~~99255|(((
45 -Timer Preset Value
46 -
47 -First two digits is for file number
48 -
49 -For example, TNS99255 represents file number T99, address 255.
50 -)))
51 -|TNP|TNPddddd|0~~99255|(((
52 -Timer Accumulator Value
53 -
54 -First two digits is for file number
55 -
56 -For example, TNP99255 represents file number T99, address 255.
57 -)))
58 -|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
59 -|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
60 -|CNS|CNSddddd|0~~99255|(((
61 -Counter Preset Value
62 -
63 -First two digits is for file number
64 -
65 -For example, CNS99255 represents file number C99, address 255.
66 -)))
67 -|CNP|CNPddddd|0~~99255|(((
68 -Counter Accumulator Value
69 -
70 -First two digits is for file number
71 -
72 -For example, CNP99255 represents file number C99, address 255.
73 -)))
74 -|N7|N7ddd|0~~255|Only able to communicate with file number N7
75 -|NN|NNddd|0~~99255|(((
76 -Integer data file
77 -
78 -First two digits is for file number
79 -
80 -For example, NN99255 represents file number N99, address 255.
81 -)))
82 -|(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number N7
83 -|FN|FNddddd|0~~99255|(((
84 -Floating point data file
85 -
86 -First two digits is for file number
87 -
88 -For example, FN99255 represents file number F99, address 255.
89 -)))
90 -|LN|LNddddd|0~~99255|Long
91 -
92 -**3) Cable Wiring**
93 -
94 -{{id name="IABRS232.gif"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_25f468ac2575918b.gif||alt="ABRS232.gif" height="247" width="400"]]
95 -
96 -{{id name="cke_bm_5621S"/}}{{id name="HMicroLogixA0Protocol"/}}** **
97 -
98 -== {{id name="HMicroLogixA0Serial"/}}**MicroLogix Serial** ==
99 -
100 -MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
101 -
102 -**1)V-BOX setting**
103 -
104 -|**Item**|**Settings**|**Note**
105 -|Protocol|Allen-Bradley DF1 Advanced|
106 -|Connection|RS232|
107 -|Baud rate|19200|
108 -|Data bit|8|
109 -|Parity|None|
110 -|Stop bit|1|
111 -|PLC station No.|1|
112 -
113 -**2)Address List**
114 -
115 -|**Type**|**Device registers**|**Format**|**Range**|**Note**
116 -|(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
117 -|O|O d.d|0.0~~255.15|
118 -|B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
119 -|S|S d.d|0.0~~255.15|
120 -|N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
121 -|(% rowspan="9" %)Word|S|S d|0~~255|
122 -|TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
123 -|TP|TP nnhh|0~~ffff
124 -|CS|CS nnhh|0~~ffff
125 -|CP|CP nnhh|0~~ffff
126 -|N|N nnhh|0~~ffff
127 -|C|C nnhh|0~~ffff
128 -|T|T nnhh|0~~ffff
129 -|R|R nnhh|0~~ffff
130 -
131 -{{id name="Iimage-20220824152928-1.png"/}}**3)Configure the communication protocol**[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_3e790cb11779d822.png||alt="image-20220824152928-1.png" height="1010" width="1920"]]
132 -
133 -**4)Configure the communication protocol**
134 -
135 -{{id name="Iimage-20220824110724-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_faf98d75129f59e9.png||alt="image-20220824110724-1.png" height="326" width="548"]]
136 -
137 -== {{id name="HMicro850_FreeTagEthernet"/}}**Micro850_FreeTag Ethernet** ==
138 -
139 -This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
140 -
141 -**Software configuration of PLC**
142 -
143 -**1)PLC programming software**
144 -
145 -{{id name="Iimage-20220714162600-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dba9ec452ee41c5.png||alt="image-20220714162600-1.png" height="527" width="437"]]
146 -
147 -**2)New PLC project**
148 -
149 -Click New Project and select the PLC model.
150 -
151 -{{id name="Iimage-20220714162617-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_54a31bd52186c53c.png||alt="image-20220714162617-2.png" height="434" width="803"]]
152 -
153 -
154 -
155 -{{id name="Iimage-20220714162652-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_5d52824614585e13.png||alt="image-20220714162652-4.png" height="591" width="732"]]
156 -
157 -**3)Set Ethernet parameters**
158 -
159 -Follow the steps below to configure Ethernet parameters
160 -
161 -PLC IP address:192.168.40.101
162 -
163 -default gateway:192.168.40.1
164 -
165 -subnet mask:255.255.255.0
166 -
167 -{{id name="Iimage-20220714162713-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_cea23d115ccaaa63.png||alt="image-20220714162713-5.png" height="868" width="1919"]]
168 -
169 -
170 -
171 -**V-box software configuration**
172 -
173 -**1)V-box programming software**
174 -
175 -{{id name="Iimage-20220714162725-6.png"/}} [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_65a3ecdb93694966.png||alt="image-20220714162725-6.png" height="441" width="731"]]
176 -
177 -**2)Configure device network**
178 -
179 -{{id name="Iimage-20220714115308-8.png"/}}Click the Configuration Download button[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ad012010777dc078.png||alt="image-20220714115308-8.png" height="22" width="15"]] , It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
180 -
181 -In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
182 -
183 -{{id name="Iimage-20220714162737-7.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a2b83bb70af39146.png||alt="image-20220714162737-7.png" height="736" width="1370"]]
184 -
185 -
186 -
187 -**3)V-net add device**
188 -
189 -{{id name="Iimage-20220714162752-8.png"/}}Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_bff671605e8a8f53.png||alt="image-20220714162752-8.png" height="793" width="1470"]]
190 -
191 -
192 -
193 -**4)Set communication port parameters**
194 -
195 -In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
196 -
197 -{{id name="Iimage-20220714162805-9.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_acc2b9d2e75a2791.png||alt="image-20220714162805-9.png" height="792" width="1471"]]
198 -
199 -The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
200 -
201 -{{id name="Iimage-20220824164346-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_68274e3dec90a425.png||alt="image-20220824164346-1.png" height="553" width="991"]]
202 -
203 -{{id name="Iimage-20220714143838-2.png"/}}{{id name="Iimage-20220714162827-11.png"/}}After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_bff5c072d145b8c.png||alt="image-20220714143838-2.png" height="27" width="30"]] icon add label.[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c8c6550cf2a1e96b.png||alt="image-20220714162827-11.png" height="574" width="1054"]]
204 -
205 -**5)Engineering production**
206 -
207 -According to your own needs, use the V-NET client software to edit the required data monitoring points.
208 -
209 -{{id name="Iimage-20220714162841-12.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ce5d38d21d89c3e3.png||alt="image-20220714162841-12.png" height="478" width="1614"]]
210 -
211 -**hardware connection**
212 -
213 -**1)Hardware wiring diagram**
214 -
215 -This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
216 -
217 -{{id name="Iimage-20220714162856-13.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_43bb560ec0411230.png||alt="image-20220714162856-13.png" height="322" width="693"]]
218 -
219 -The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
220 -
221 -== {{id name="HMicro850_FreeTagEthernetFF08newFF09"/}}**Micro850_FreeTag Ethernet(new)** ==
222 -
223 -This example introduces the establishment of Ethernet communication between Wecon V-box and 2080-LC50-48QWB,Micro850. It is introduced through three parts: PLC software configuration, V-box software configuration.
224 -
225 -**Software configuration of PLC**
226 -
227 -**1)PLC programming software:Connected Components Workbench™**
228 -
229 -{{id name="Isoftware.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_3711a5e1c2a7f00f.png||alt="software.png" height="485" width="378"]]
230 -
231 -**2)New PLC project**
232 -
233 -Click New Project and select the PLC model.
234 -
235 -{{id name="Iprojectcreate.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_6c0da8fb6efff6c5.png||alt="project create.png" height="806" width="901"]]
236 -
237 -**3)Set Ethernet parameters**
238 -
239 -Follow the steps below to configure Ethernet parameters
240 -
241 -PLC IP address:192.168.39.56
242 -
243 -default gateway:192.168.39.1
244 -
245 -subnet mask:255.255.255.0
246 -
247 -{{id name="IEthernet.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c79ec9884ea8fe28.png||alt="Ethernet.png" height="656" width="935"]]
248 -
249 -**4)connect PLC**
250 -
251 -**When downloading the setting, need to change the status of the PLC to PRG**
252 -
253 -{{id name="Iconneabplc.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_85b0c5a416b2a77d.png||alt="conne ab plc.png" height="765" width="696"]]
254 -
255 -**V-box software configuration**
256 -
257 -**1)V-box programming software**
258 -
259 -{{id name="Iv-netclientvers.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac791772fd34e1a0.png||alt="v-net client vers.png" height="277" width="281"]]
260 -
261 -**2)Set communication port parameters**
262 -
263 -In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
264 -
265 -{{id name="IV-NET_Client_t2Rg2wpSoY.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_6af9507fa57e3f6e.png||alt="V-NET_Client_t2Rg2wpSoY.png" height="791" width="1086"]]
266 -
267 -The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
268 -
269 -{{id name="IV-NET_Client_communication.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ecdfe646ccfb5f9f.png||alt="V-NET_Client_communication.png" height="601" width="894"]]
270 -
271 -{{id name="cke_bm_1950S"/}}Export variables from PLC, select CSV file, comma delimited.
272 -
273 -{{id name="Iexport1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_306bf46ce1a5a0d3.png||alt="export1.png" height="613" width="604"]]
274 -
275 -{{id name="ICCW.Shell_E5Cwj4tUL3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9e367a57c3e9201.png||alt="CCW.Shell_E5Cwj4tUL3.png" height="278" width="915"]]
276 -
277 -{{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FV-BOX2FV-Net2FTraining2F12520Communication2FWebHome2Fimage-20220714143838-2.png3Frev3D1.1"/}}After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220714143838-2.png?rev=1.1||alt="image-20220714143838-2.png" height="38" width="76"]] icon add label.
278 -
279 -{{id name="IV-NET_Client_TNBuqy7T5r.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_820dbb012d8d584d.png||alt="V-NET_Client_TNBuqy7T5r.png" height="449" width="952"]]
280 -
281 -**3)Engineering production**
282 -
283 -According to your own needs, use the V-NET client software to edit the required data monitoring points.
284 -
285 -{{id name="IV-NET_Client_KOR0AHEA4M.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_32fe301a04258d72.png||alt="V-NET_Client_KOR0AHEA4M.png" height="182" width="825"]]
286 -
287 -
288 -
289 -== {{id name="HEthernetDF1"/}}**Ethernet DF1** ==
290 -
291 -[[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]