Delta
DVP serial
Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
V-BOX Settings
Items | Settings | Note |
---|---|---|
Protocol | DELTA DVP PROTOCOL | |
Connection | RS232 | |
Baud Rate | 9600 | |
Stop Bit | 1 | |
Data Bit | 7 | |
Parity | EVEN | |
Device No. | 1 |
Address List
Type | Device registers | HMI registers | Format | Range | Note |
---|---|---|---|---|---|
Bit | X | X | X d | 0~303237 | |
Bit | Y | Y | Y d | 0~303237 | |
Bit | M | M | M d | 0~99999 | |
Bit | T | T | T d | 0~99999 | |
Bit | C | C | T d | 0~99999 | |
Bit | S | S | T d | 0~99999 | |
Word | D | D | D d | 0~99999 | |
Word | T | T | T d | 0~99999 | |
Word | C | C | C d | 0~99999 |
Wiring Diagram
DVP Ethernet
Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
V-BOX Settings
Items | Settings | Note |
---|---|---|
Protocol | DELTA DVP Modbus TCP | |
Connection | Ethernet | |
Port No. | 502 | Must be the same as the PLC setting |
PLC station No. | 0 | Must be the same as the PLC setting |
Address List
Type | Device registers | VBox registers | Format | Range | Note |
---|---|---|---|---|---|
Bit | X | X | X OOO | 0~377 | |
Bit | Y | Y | Y OOO | 0~377 | |
Bit | M0 | M0 | M0DDDD | 0~1535 | |
Bit | M1 | M1 | M1DDDD | 1536~4096 | |
Bit | T | T | TDDD | 0~255 | |
Bit | C | C | CDDD | 0~255 | |
Bit | S | S | SDDDD | 0~1023 | |
Word | D0 | D0 | D0DDDD | 0~4095 | |
Word | D1 | D1 | D1DDDD | 4096~11999 | |
Word | T | T | TDDD | 0~255 | |
Word | C | C | CDDD | 0~199 | |
Double Word | HC | HC | HCDDD | 200~255 |
PLC Setting:
1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
2. Set up the communication type and PLC IP:
3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
V-BOX Setting:
Set the same IP address according to the setting from WPL Soft:
AS Series Serial
Supported Series: Delta AS200/AS300
V-BOX Settings
Item | Settings | Note |
Protocol | DELTA AS300 MODBUS RTU | |
Connection | RS485 | |
Baud rate | 9600 | |
Data bit | 8 | |
Parity | NONE | |
Stop bit | 1 | |
PLC station No. | 1 |
Address List
Type | Device registers | Format | Range | Note |
---|---|---|---|---|
Bit | X | Xdd.dd | 0~63.15 | Read only |
Y | Ydd.dd | 0~63.15 | ||
D | Dddddd | 0~29999 | ||
M | Mdddd | 0~8191 | ||
SM | SMdddd | 0~4095 | ||
S | Sdddd | 0~2047 | ||
T | Tddd | 0~511 | ||
C | Cddd | 0~511 | ||
HC | HCddd | 0~255 | Double Word | |
Word | X | Xdd | 0~63 | |
Y | Ydd | 0~63 | ||
SR | SRdddd | 0~2047 | Special register | |
D | Dddddd | 0~29999 | ||
T | Tddd | 0~511 | ||
C | Cddd | 0~511 | ||
E | Ed | 0~9 |
PLC Settings
Create project
Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
Double click the HWCONFIG to open the communication settings window.
Expand the Project Tree, open the hardware configuration, double click the PLC icon.
Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
Cable Wiring
Pin Definition Diagram
AS Series Ethernet
Items | Settings | Note |
---|---|---|
Protocol | DELTA AS300 MODBUS TCP | |
Connection | Ethernet | |
Port No. | 502 | |
Device No. | 1 | |
HMI No. | 0 |
Address List
Type | Device registers | HMI registers | Format | Range | Note |
Bit | X | X | X d | 0~63 | |
Bit | Y | Y | Y d | 0~63 | |
Bit | D | D | D d | 0~29999 | |
Bit | M | M | M d | 0~8191 | |
Bit | SM | SM | SM d | 0~4095 | |
Bit | S | S | S h | 0~2047 | |
Bit | T | T | T d | 0~511 | |
Bit | C | C | C d | 0~511 | |
Bit | HC | HC | HC d | 0~255 | |
Word | X | X | X h | 0~63 | |
Word | Y | Y | Y d | 0~63 | |
Word | SR | SR | SR d | 0~2047 | |
Word | D | D | D d | 0~29999 | |
Word | T | T | T d | 0~511 | |
Word | C | C | C h | 0~511 | |
Word | E | E | E d | 0~9 |
PLC Setting
1.Open COMMGR ,[Add]→[Driver Name] Driver1→[Connection Setup]→[Type] Ethernet→[Ethernet Card] →[Description] Realtek PCIe GBE Family Controller→[Search] PC and PLC are in
the same LAN, click the corresponding PLC IP searched.→[OK]
2. Open ISPSoft,[Project]→Double click[HWCONFIG]
PLC Default Parameters:
[Device]→[Hardware Configuration]→[CPU(AS332T-A)]→[Hardware Configuration]→[General] →[Ethernet Port Basic Setting]: [IP Address]192.168.40.122, [Subnet Mask]255.255.255.0,[Gateway]
192.168.40.1→[Download]
Cable Wiring
Figure