Theodore Xu 15.1 5 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
Leo Wei 2.1 6
Theodore Xu 15.1 7 **V-BOX Settings**
Leo Wei 2.1 8
9 |=**Items**|=**Settings**|=**Note**
Theodore Xu 15.1 10 |Protocol|DELTA DVP PROTOCOL|
11 |Connection|RS232|
12 |Baud Rate|9600|
13 |Stop Bit|1|
14 |Data Bit|7|
15 |Parity|EVEN|
Leo Wei 2.1 16 |Device No.|1|
17
Theodore Xu 15.1 18 **Address List**
Leo Wei 2.1 19
Theodore Xu 15.1 20 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
21 |Bit|X|X|X d|0~~303237|
22 |Bit|Y|Y|Y d|0~~303237|
23 |Bit|M|M|M d|0~~99999|
24 |Bit|T|T|T d|0~~99999|
25 |Bit|C|C|T d|0~~99999|
26 |Bit|S|S|T d|0~~99999|
27 |Word|D|D|D d|0~~99999|
28 |Word|T|T|T d|0~~99999|
29 |Word|C|C|C d|0~~99999|
30
31 **Wiring Diagram**
32
33 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_96f8e9b105b4268c.png||alt="Delta DVP PROTOCOLSerial232.png" height="247" width="400"]]
34
35 == **DVP Ethernet** ==
36
37 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
38
39 **V-BOX Settings**
40
41 |=**Items**|=**Settings**|=**Note**
42 |Protocol|DELTA DVP Modbus TCP|
43 |Connection|Ethernet|
44 |Port No.|502|Must be the same as the PLC setting
45 |PLC station No.|0|Must be the same as the PLC setting
46
Theodore Xu 18.1 47 (% style="text-align:center" %)
48 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_514e38138de7059.png||alt="DVPEthernetVNETPortocol.png" height="493" width="729"]]
49
Theodore Xu 15.1 50 **Address List **
51
Leo Wei 2.1 52 |=**Type**|=**Device registers**|=**VBox registers**|=**Format**|=**Range**|=**Note**
53 |Bit|X|X|X OOO|0~~377|
54 |Bit|Y|Y|Y OOO|0~~377|
55 |Bit|M0|M0|M0DDDD|0~~1535|
56 |Bit|M1|M1|M1DDDD|1536~~4096|
57 |Bit|T|T|TDDD|0~~255|
58 |Bit|C|C|CDDD|0~~255|
59 |Bit|S|S|SDDDD|0~~1023|
60 |Word|D0|D0|D0DDDD|0~~4095|
61 |Word|D1|D1|D1DDDD|4096~~11999|
62 |Word|T|T|TDDD|0~~255|
63 |Word|C|C|CDDD|0~~199|
64 |Double Word|HC|HC|HCDDD|200~~255|
65
Theodore Xu 15.1 66 **PLC Setting:**
Leo Wei 2.1 67
68 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
69
Theodore Xu 15.1 70 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c5e594a6b73bdd68.png||alt="DVPEthernetWPLSoft2.png" height="727" width="1366"]]
Leo Wei 2.1 71
72 2. Set up the communication type and PLC IP:
73
Theodore Xu 15.1 74 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_92343d448762200c.png||alt="DVPEthernetSetup.png" height="592" width="346"]]
Leo Wei 2.1 75
76 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
77
78 {{id name="IDVPEthernetTransfer.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a24e318f1e5f0839.png||alt="DVPEthernetTransfer.png" height="726" width="1366"]]
79
80 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
81
Theodore Xu 15.1 82 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ae301f5422be2294.png||alt="DVPEthernetPLCtoPC.png" height="303" width="308"]]
Leo Wei 2.1 83
84 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
85
86 {{id name="IDVPEthernetAutoSearch.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e2c32050bbe425bc.png||alt="DVPEthernetAutoSearch.png" height="723" width="1366"]]
87
88
Theodore Xu 15.1 89 == **AS Series Serial** ==
Leo Wei 2.1 90
Theodore Xu 15.1 91 Supported Series: Delta AS200/AS300
Leo Wei 2.1 92
Theodore Xu 15.1 93 **V-BOX Settings**
Leo Wei 2.1 94
Theodore Xu 15.1 95 |**Item**|**Settings**|**Note**
96 |Protocol|DELTA AS300 MODBUS RTU|
97 |Connection|RS485|
98 |Baud rate|9600|
99 |Data bit|8|
100 |Parity|NONE|
101 |Stop bit|1|
102 |PLC station No.|1|
Leo Wei 2.1 103
Theodore Xu 15.1 104 **Address List**
Leo Wei 2.1 105
Theodore Xu 15.1 106 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
107 |(% colspan="1" rowspan="9" %)Bit|X|Xdd.dd|0~~63.15|Read only
108 |Y|Ydd.dd|0~~63.15|
109 |D|Dddddd|0~~29999|
110 |M|Mdddd|0~~8191|
111 |SM|SMdddd|0~~4095|
112 |S|Sdddd|0~~2047|
113 |T|Tddd|0~~511|
114 |C|Cddd|0~~511|
115 |HC|HCddd|0~~255|Double Word
116 |(% colspan="1" rowspan="7" %)Word|X|Xdd|0~~63|
117 |Y|Ydd|0~~63|
118 |SR|SRdddd|0~~2047|Special register
119 |D|Dddddd|0~~29999|
120 |T|Tddd|0~~511|
121 |C|Cddd|0~~511|
122 |E|Ed|0~~9|
Leo Wei 2.1 123
Theodore Xu 15.1 124 **PLC Settings**
Leo Wei 2.1 125
Theodore Xu 15.1 126 Create project
Leo Wei 2.1 127
Theodore Xu 15.1 128 (% style="text-align:center" %)
129 [[image:台达1.png]]
Leo Wei 2.1 130
Theodore Xu 15.1 131 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
132
133 (% style="text-align:center" %)
134 [[image:1696906027584-350.png]]
135
136 Double click the HWCONFIG to open the communication settings window.
137
138 (% style="text-align:center" %)
139 [[image:台达3.png]]
140
141 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
142
143 (% style="text-align:center" %)
144 [[image:台达4.png]]
145
146 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
147
148 (% style="text-align:center" %)
149 [[image:台达5.png]]
150
151
152 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
153
154 (% style="text-align:center" %)
155 [[image:台达6.png]]
156
157 **Cable Wiring**
158
Theodore Xu 16.1 159 (% id="cke_bm_36592S" style="display:none" %) (%%)Pin Definition Diagram
Theodore Xu 15.1 160
Theodore Xu 16.1 161 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_daa33fcae616e61c.png||alt="image-20220831155157-3.png" height="181" width="320"]]
Theodore Xu 15.1 162
163 == **AS Series Ethernet** ==
164
Leo Wei 2.1 165 |=**Items**|=**Settings**|=**Note**
166 |Protocol|DELTA AS300 MODBUS TCP|
167 |Connection|Ethernet|
168 |Port No.|502|
169 |Device No.|1|
170 |HMI No.|0|
171
Theodore Xu 15.1 172 **Address List**
Leo Wei 2.1 173
174 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
175 |Bit|X|X|X d|0~~63|
176 |Bit|Y|Y|Y d|0~~63|
177 |Bit|D|D|D d|0~~29999|
178 |Bit|M|M|M d|0~~8191|
179 |Bit|SM|SM|SM d|0~~4095|
180 |Bit|S|S|S h|0~~2047|
181 |Bit|T|T|T d|0~~511|
182 |Bit|C|C|C d|0~~511|
183 |Bit|HC|HC|HC d|0~~255|
184 |Word|X|X|X h|0~~63|
185 |Word|Y|Y|Y d|0~~63|
186 |Word|SR|SR|SR d|0~~2047|
187 |Word|D|D|D d|0~~29999|
188 |Word|T|T|T d|0~~511|
189 |Word|C|C|C h|0~~511|
190 |Word|E|E|E d|0~~9|
191
Theodore Xu 16.1 192 **PLC Setting**
Leo Wei 2.1 193
Theodore Xu 16.1 194 1.Open COMMGR ,[Add]→[Driver Name] Driver1→[Connection Setup]→[Type] Ethernet→[Ethernet Card] →[Description] Realtek PCIe GBE Family Controller→[Search] PC and PLC are in
195 the same LAN, click the corresponding PLC IP searched.→[OK]
196
197 (% style="text-align:center" %)
198 [[image:2.1.png]]
199
200 2. Open ISPSoft,[Project]→Double click[HWCONFIG]
201
202 (% style="text-align:center" %)
203 [[image:台达2.2.png]]
204
205 PLC Default Parameters:
206 [Device]→[Hardware Configuration]→[CPU(AS332T-A)]→[Hardware Configuration]→[General] →[Ethernet Port Basic Setting]: [IP Address]192.168.40.122, [Subnet Mask]255.255.255.0,[Gateway]
207 192.168.40.1→[Download]
208
209 (% style="text-align:center" %)
210 [[image:台达2.3-.png]]
211
212 (% style="text-align:center" %)
213 [[image:台达2.4.png]]
214
Theodore Xu 15.1 215 **Cable Wiring**
Leo Wei 2.1 216
217 Figure
218
Theodore Xu 15.1 219 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_f2c92ecd57ebfbd0.png||alt="image-20220831155101-1.png" height="262" width="118"]] [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_32ea98dfbc23a591.png||alt="image-20220831160055-5.png" height="198" width="455"]]