Hunter 20.1 4 = DVP Serial =
5
Hunter 19.1 6 (% class="wikigeneratedid" %)
Theodore Xu 15.1 7 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
Leo Wei 2.1 8
Theodore Xu 15.1 9 **V-BOX Settings**
Leo Wei 2.1 10
11 |=**Items**|=**Settings**|=**Note**
Theodore Xu 15.1 12 |Protocol|DELTA DVP PROTOCOL|
13 |Connection|RS232|
14 |Baud Rate|9600|
15 |Stop Bit|1|
16 |Data Bit|7|
17 |Parity|EVEN|
Leo Wei 2.1 18 |Device No.|1|
19
Theodore Xu 15.1 20 **Address List**
Leo Wei 2.1 21
Theodore Xu 15.1 22 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
23 |Bit|X|X|X d|0~~303237|
24 |Bit|Y|Y|Y d|0~~303237|
25 |Bit|M|M|M d|0~~99999|
26 |Bit|T|T|T d|0~~99999|
27 |Bit|C|C|T d|0~~99999|
28 |Bit|S|S|T d|0~~99999|
29 |Word|D|D|D d|0~~99999|
30 |Word|T|T|T d|0~~99999|
31 |Word|C|C|C d|0~~99999|
32
33 **Wiring Diagram**
34
35 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_96f8e9b105b4268c.png||alt="Delta DVP PROTOCOLSerial232.png" height="247" width="400"]]
36
37 == **DVP Ethernet** ==
38
39 Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2/SE Controller
40
41 **V-BOX Settings**
42
43 |=**Items**|=**Settings**|=**Note**
44 |Protocol|DELTA DVP Modbus TCP|
45 |Connection|Ethernet|
46 |Port No.|502|Must be the same as the PLC setting
47 |PLC station No.|0|Must be the same as the PLC setting
48
Theodore Xu 18.1 49 (% style="text-align:center" %)
50 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_514e38138de7059.png||alt="DVPEthernetVNETPortocol.png" height="493" width="729"]]
51
Theodore Xu 15.1 52 **Address List **
53
Leo Wei 2.1 54 |=**Type**|=**Device registers**|=**VBox registers**|=**Format**|=**Range**|=**Note**
55 |Bit|X|X|X OOO|0~~377|
56 |Bit|Y|Y|Y OOO|0~~377|
57 |Bit|M0|M0|M0DDDD|0~~1535|
58 |Bit|M1|M1|M1DDDD|1536~~4096|
59 |Bit|T|T|TDDD|0~~255|
60 |Bit|C|C|CDDD|0~~255|
61 |Bit|S|S|SDDDD|0~~1023|
62 |Word|D0|D0|D0DDDD|0~~4095|
63 |Word|D1|D1|D1DDDD|4096~~11999|
64 |Word|T|T|TDDD|0~~255|
65 |Word|C|C|CDDD|0~~199|
66 |Double Word|HC|HC|HCDDD|200~~255|
67
Theodore Xu 15.1 68 **PLC Setting:**
Leo Wei 2.1 69
70 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
71
Theodore Xu 15.1 72 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c5e594a6b73bdd68.png||alt="DVPEthernetWPLSoft2.png" height="727" width="1366"]]
Leo Wei 2.1 73
74 2. Set up the communication type and PLC IP:
75
Theodore Xu 15.1 76 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_92343d448762200c.png||alt="DVPEthernetSetup.png" height="592" width="346"]]
Leo Wei 2.1 77
78 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
79
80 {{id name="IDVPEthernetTransfer.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a24e318f1e5f0839.png||alt="DVPEthernetTransfer.png" height="726" width="1366"]]
81
82 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
83
Theodore Xu 15.1 84 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ae301f5422be2294.png||alt="DVPEthernetPLCtoPC.png" height="303" width="308"]]
Leo Wei 2.1 85
86 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
87
88 {{id name="IDVPEthernetAutoSearch.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e2c32050bbe425bc.png||alt="DVPEthernetAutoSearch.png" height="723" width="1366"]]
89
90
Theodore Xu 15.1 91 == **AS Series Serial** ==
Leo Wei 2.1 92
Theodore Xu 15.1 93 Supported Series: Delta AS200/AS300
Leo Wei 2.1 94
Theodore Xu 15.1 95 **V-BOX Settings**
Leo Wei 2.1 96
Theodore Xu 15.1 97 |**Item**|**Settings**|**Note**
98 |Protocol|DELTA AS300 MODBUS RTU|
99 |Connection|RS485|
100 |Baud rate|9600|
101 |Data bit|8|
102 |Parity|NONE|
103 |Stop bit|1|
104 |PLC station No.|1|
Leo Wei 2.1 105
Theodore Xu 15.1 106 **Address List**
Leo Wei 2.1 107
Theodore Xu 15.1 108 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
109 |(% colspan="1" rowspan="9" %)Bit|X|Xdd.dd|0~~63.15|Read only
110 |Y|Ydd.dd|0~~63.15|
111 |D|Dddddd|0~~29999|
112 |M|Mdddd|0~~8191|
113 |SM|SMdddd|0~~4095|
114 |S|Sdddd|0~~2047|
115 |T|Tddd|0~~511|
116 |C|Cddd|0~~511|
117 |HC|HCddd|0~~255|Double Word
118 |(% colspan="1" rowspan="7" %)Word|X|Xdd|0~~63|
119 |Y|Ydd|0~~63|
120 |SR|SRdddd|0~~2047|Special register
121 |D|Dddddd|0~~29999|
122 |T|Tddd|0~~511|
123 |C|Cddd|0~~511|
124 |E|Ed|0~~9|
Leo Wei 2.1 125
Theodore Xu 15.1 126 **PLC Settings**
Leo Wei 2.1 127
Theodore Xu 15.1 128 Create project
Leo Wei 2.1 129
Theodore Xu 15.1 130 (% style="text-align:center" %)
131 [[image:台达1.png]]
Leo Wei 2.1 132
Theodore Xu 15.1 133 Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.
134
135 (% style="text-align:center" %)
136 [[image:1696906027584-350.png]]
137
138 Double click the HWCONFIG to open the communication settings window.
139
140 (% style="text-align:center" %)
141 [[image:台达3.png]]
142
143 Expand the Project Tree, open the hardware configuration, double click the PLC icon.
144
145 (% style="text-align:center" %)
146 [[image:台达4.png]]
147
148 Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.
149
150 (% style="text-align:center" %)
151 [[image:台达5.png]]
152
153
154 Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.
155
156 (% style="text-align:center" %)
157 [[image:台达6.png]]
158
159 **Cable Wiring**
160
Theodore Xu 16.1 161 (% id="cke_bm_36592S" style="display:none" %) (%%)Pin Definition Diagram
Theodore Xu 15.1 162
Theodore Xu 16.1 163 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_daa33fcae616e61c.png||alt="image-20220831155157-3.png" height="181" width="320"]]
Theodore Xu 15.1 164
165 == **AS Series Ethernet** ==
166
Leo Wei 2.1 167 |=**Items**|=**Settings**|=**Note**
168 |Protocol|DELTA AS300 MODBUS TCP|
169 |Connection|Ethernet|
170 |Port No.|502|
171 |Device No.|1|
172 |HMI No.|0|
173
Theodore Xu 15.1 174 **Address List**
Leo Wei 2.1 175
176 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
177 |Bit|X|X|X d|0~~63|
178 |Bit|Y|Y|Y d|0~~63|
179 |Bit|D|D|D d|0~~29999|
180 |Bit|M|M|M d|0~~8191|
181 |Bit|SM|SM|SM d|0~~4095|
182 |Bit|S|S|S h|0~~2047|
183 |Bit|T|T|T d|0~~511|
184 |Bit|C|C|C d|0~~511|
185 |Bit|HC|HC|HC d|0~~255|
186 |Word|X|X|X h|0~~63|
187 |Word|Y|Y|Y d|0~~63|
188 |Word|SR|SR|SR d|0~~2047|
189 |Word|D|D|D d|0~~29999|
190 |Word|T|T|T d|0~~511|
191 |Word|C|C|C h|0~~511|
192 |Word|E|E|E d|0~~9|
193
Theodore Xu 16.1 194 **PLC Setting**
Leo Wei 2.1 195
Theodore Xu 16.1 196 1.Open COMMGR ,[Add]→[Driver Name] Driver1→[Connection Setup]→[Type] Ethernet→[Ethernet Card] →[Description] Realtek PCIe GBE Family Controller→[Search] PC and PLC are in
197 the same LAN, click the corresponding PLC IP searched.→[OK]
198
199 (% style="text-align:center" %)
200 [[image:2.1.png]]
201
202 2. Open ISPSoft,[Project]→Double click[HWCONFIG]
203
204 (% style="text-align:center" %)
205 [[image:台达2.2.png]]
206
207 PLC Default Parameters:
208 [Device]→[Hardware Configuration]→[CPU(AS332T-A)]→[Hardware Configuration]→[General] →[Ethernet Port Basic Setting]: [IP Address]192.168.40.122, [Subnet Mask]255.255.255.0,[Gateway]
209 192.168.40.1→[Download]
210
211 (% style="text-align:center" %)
212 [[image:台达2.3-.png]]
213
214 (% style="text-align:center" %)
215 [[image:台达2.4.png]]
216
Theodore Xu 15.1 217 **Cable Wiring**
Leo Wei 2.1 218
219 Figure
220
Theodore Xu 15.1 221 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_f2c92ecd57ebfbd0.png||alt="image-20220831155101-1.png" height="262" width="118"]] [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_32ea98dfbc23a591.png||alt="image-20220831160055-5.png" height="198" width="455"]]