Delta

Last modified by Wecon on 2025/09/03 21:04

DVP Serial

Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX 

V-BOX Settings

ItemsSettingsNote
ProtocolDELTA DVP PROTOCOL 
ConnectionRS232 
Baud Rate9600 
Stop Bit1 
Data Bit7 
ParityEVEN 
Device No.1 

Address List

TypeDevice registersHMI registersFormatRangeNote
BitXXX d0~303237 
BitYYY d0~303237 
BitMMM d0~99999 
BitTTT d0~99999 
BitCCT d0~99999 
BitSST d0~99999 
WordDDD d0~99999 
WordTTT d0~99999 
WordCCC d0~99999 

Wiring Diagram

DVP Ethernet

Supported Series: Delta DVP ES2/EX2/SS2/SA2/SX2 Controller

Information

✎Note: It is not suggest DVP SE series controller to use this protocol, please use the MODBUS TCP protocol for SE series.

V-BOX Settings

ItemsSettingsNote
ProtocolDELTA DVP Modbus TCP 
ConnectionEthernet 
Port No.502Must be the same as the PLC setting
PLC station No.0Must be the same as the PLC setting

Address List 

TypeDevice registersVBox registersFormatRangeNote
BitXXX OOO0~377 
BitYYY OOO0~377 
BitM0M0M0DDDD0~1535 
BitM1M1M1DDDD1536~4096 
BitTTTDDD0~255 
BitCCCDDD0~255 
BitSSSDDDD0~1023 
WordD0D0D0DDDD0~4095 
WordD1D1D1DDDD4096~11999 
WordTTTDDD0~255 
WordCCCDDD0~199 
Double WordHCHCHCDDD200~255 

PLC Setting:

1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:

2. Set up the communication type and PLC IP:

3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:

4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:

5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:

AS Series Serial

Supported Series: Delta AS200/AS300

V-BOX Settings

ItemSettingsNote
ProtocolDELTA AS300 MODBUS RTU 
ConnectionRS485 
Baud rate9600 
Data bit8 
ParityNONE 
Stop bit1 
PLC station No.1 

Address List

TypeDevice registersFormatRangeNote
BitXXdd.dd0~63.15Read only
YYdd.dd0~63.15 
DDddddd0~29999 
MMdddd0~8191 
SMSMdddd0~4095 
SSdddd0~2047 
TTddd0~511 
CCddd0~511 
HCHCddd0~255Double Word
WordXXdd0~63 
YYdd0~63 
SRSRdddd0~2047Special register
DDddddd0~29999 
TTddd0~511 
CCddd0~511 
EEd0~9 

PLC Settings

Create project

Open the tool COMMGR, to communicate with PLC, if know the IP, we can directly click Add to input PLC IP. Or search the PLC IP from LAN.

Double click the HWCONFIG to open the communication settings window. 

Expand the Project Tree, open the hardware configuration, double click the PLC icon.

Click COM1 Port Setting, the default Modbus mode is ASCII, need to change to RTU.

Click Ethernet Port Basic Setting, set the PLC IP and Gateway. Make sure the IP and Gateway is same segment. Then download into PLC.

Cable Wiring

Pin Definition Diagram

AS Series Ethernet

ItemsSettingsNote
ProtocolDELTA AS300 MODBUS TCP 
ConnectionEthernet 
Port No.502 
Device No.1 
HMI No.0 

Address List

TypeDevice registersHMI registersFormatRangeNote
BitXXX d0~63 
BitYYY d0~63 
BitDDD d0~29999 
BitMMM d0~8191 
BitSMSMSM d0~4095 
BitSSS h0~2047 
BitTTT d0~511 
BitCCC d0~511 
BitHCHCHC d0~255 
WordXXX h0~63 
WordYYY d0~63 
WordSRSRSR d0~2047 
WordDDD d0~29999 
WordTTT d0~511 
WordCCC h0~511 
WordEEE d0~9 

PLC Setting

1.Open COMMGR ,[Add]→[Driver Name] Driver1→[Connection Setup]→[Type] Ethernet→[Ethernet Card] →[Description] Realtek PCIe GBE Family Controller→[Search] PC and PLC are in
the same LAN, click the corresponding PLC IP searched.→[OK]

2. Open ISPSoft,[Project]→Double click[HWCONFIG]

PLC Default Parameters:
[Device]→[Hardware Configuration]→[CPU(AS332T-A)]→[Hardware Configuration]→[General] →[Ethernet Port Basic Setting]: [IP Address]192.168.40.122, [Subnet Mask]255.255.255.0,[Gateway]
192.168.40.1→[Download]

Cable Wiring

Figure