| 1 | = FATEK serial = | ||
| 2 | |||
| 3 | Supported Series: FATEK FBS Series, B1 Series, B1Z Series. | ||
| 4 | |||
| 5 | **V-Box Settings** | ||
| 6 | |||
| 7 | |=**Item**|=**Settings**|=**Note** | ||
| 8 | |Protocol|FATEK ASCII| | ||
| 9 | |Connection|RS232| | ||
| 10 | |Baud rate|9600| | ||
| 11 | |Data bit|7| | ||
| 12 | |Parity|Even| | ||
| 13 | |Stop bit|1| | ||
| 14 | |PLC station No.|0| | ||
| 15 | |||
| 16 | **Address List** | ||
| 17 | |||
| 18 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 19 | |(% colspan="1" rowspan="7" %)Bit|X|XDDDDDD|0~~999999|Input Contact | ||
| 20 | |Y|YDDDDDD|0~~999999|Output Relay | ||
| 21 | |M|MDDDDDD|0~~999999|Internal Relay | ||
| 22 | |S|SDDDDDD|0~~999999|Step Relay | ||
| 23 | |T|TDDDDDD|0~~999999|Timer "Time-Up" Status Contact | ||
| 24 | |C|CDDDDDD|0~~999999|Counter "Count-Up" Status Contact | ||
| 25 | |(% colspan="1" %)Z|ZD|0| | ||
| 26 | |(% colspan="1" rowspan="10" %)Word|(% colspan="1" %)D|(% colspan="1" %)DDDDDDD|0~~999999|Data Register | ||
| 27 | |(% colspan="1" %)R|(% colspan="1" %)RDDDDDD|(% colspan="1" %)0~~999999| | ||
| 28 | |(% colspan="1" %)WX|(% colspan="1" %)WXDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %)Input Register(IR) | ||
| 29 | |(% colspan="1" %)WY|(% colspan="1" %)WYDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %)Output Register(OR) | ||
| 30 | |(% colspan="1" %)WM|(% colspan="1" %)WMDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %) | ||
| 31 | |(% colspan="1" %)WS|(% colspan="1" %)WSDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %) | ||
| 32 | |(% colspan="1" %)RT|(% colspan="1" %)RTDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %)Timer Register | ||
| 33 | |(% colspan="1" %)RC|(% colspan="1" %)RCDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %)Counter Register | ||
| 34 | |(% colspan="1" %)DRT|(% colspan="1" %)DRTDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %)Double Word Timer Register | ||
| 35 | |(% colspan="1" %)DRC|(% colspan="1" %)DRCDDDDDD|(% colspan="1" %)0~~999999|(% colspan="1" %)Double Word Counter Register | ||
| 36 | |||
| 37 | **PLC Settings** | ||
| 38 | |||
| 39 | Create new project, and naming the project, select the specific model according to the actual PLC. | ||
| 40 | |||
| 41 | (% style="text-align:center" %) | ||
| 42 | [[image:WPLadd01Createnew.png]] | ||
| 43 | |||
| 44 | Program the PLC | ||
| 45 | |||
| 46 | (% style="text-align:center" %) | ||
| 47 | [[image:WPLadd02Programming.png]] | ||
| 48 | |||
| 49 | Connect the PLC to PC by RS232-USB converter cable, and online PLC by using the Auto Check function. | ||
| 50 | |||
| 51 | (% style="text-align:center" %) | ||
| 52 | [[image:WPLadd03onlinePLC.png]] | ||
| 53 | |||
| 54 | If there is some PLC detected by WinProLadder, it will prompt like the following window, and click [Yes] to go on. | ||
| 55 | |||
| 56 | (% style="text-align:center" %) | ||
| 57 | [[image:WPLadd04connectOK2.png]] | ||
| 58 | |||
| 59 | If the current program is not consistent with the program inside the PLC, it will prompt like the following window, click [Yes] to rewrite the PLC. | ||
| 60 | |||
| 61 | (% style="text-align:center" %) | ||
| 62 | [[image:WPLadd05PLCconsistency.png]] | ||
| 63 | |||
| 64 | After download successfully, it will show the window below, click [OK] to close it. | ||
| 65 | |||
| 66 | (% style="text-align:center" %) | ||
| 67 | [[image:WPLadd06Done.png]] | ||
| 68 | |||
| 69 | **Cable Wiring** | ||
| 70 | |||