FATEK
Last modified by Wecon on 2025/09/03 21:04
FATEK serial
Supported Series: FATEK FBS Series, B1 Series, B1Z Series.
V-Box Settings
| Item | Settings | Note |
|---|---|---|
| Protocol | FATEK ASCII | |
| Connection | RS232 | |
| Baud rate | 9600 | |
| Data bit | 7 | |
| Parity | Even | |
| Stop bit | 1 | |
| PLC station No. | 0 |
Address List
| Type | Device registers | Format | Range | Note |
|---|---|---|---|---|
| Bit | X | XDDDDDD | 0~999999 | Input Contact |
| Y | YDDDDDD | 0~999999 | Output Relay | |
| M | MDDDDDD | 0~999999 | Internal Relay | |
| S | SDDDDDD | 0~999999 | Step Relay | |
| T | TDDDDDD | 0~999999 | Timer "Time-Up" Status Contact | |
| C | CDDDDDD | 0~999999 | Counter "Count-Up" Status Contact | |
| Z | ZD | 0 | ||
| Word | D | DDDDDDD | 0~999999 | Data Register |
| R | RDDDDDD | 0~999999 | ||
| WX | WXDDDDDD | 0~999999 | Input Register(IR) | |
| WY | WYDDDDDD | 0~999999 | Output Register(OR) | |
| WM | WMDDDDDD | 0~999999 | ||
| WS | WSDDDDDD | 0~999999 | ||
| RT | RTDDDDDD | 0~999999 | Timer Register | |
| RC | RCDDDDDD | 0~999999 | Counter Register | |
| DRT | DRTDDDDDD | 0~999999 | Double Word Timer Register | |
| DRC | DRCDDDDDD | 0~999999 | Double Word Counter Register |
PLC Settings
Create new project, and naming the project, select the specific model according to the actual PLC.

Program the PLC

Connect the PLC to PC by RS232-USB converter cable, and online PLC by using the Auto Check function.

If there is some PLC detected by WinProLadder, it will prompt like the following window, and click [Yes] to go on.

If the current program is not consistent with the program inside the PLC, it will prompt like the following window, click [Yes] to rewrite the PLC.

After download successfully, it will show the window below, click [OK] to close it.

Cable Wiring