Changes for page HollySys PLC

Last modified by Theodore Xu on 2023/09/16 13:43

From version 1.1
edited by Leo Wei
on 2023/08/24 14:11
Change comment: Changed document syntax from [XWiki 2.1] to [xwiki/2.1].
To version 6.1
edited by Theodore Xu
on 2023/09/16 13:43
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,0 +1,1 @@
1 +HollySys PLC
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.admin
1 +XWiki.AiXia
Content
... ... @@ -1,0 +1,65 @@
1 += **LK Modbus RTU ** =
2 +
3 +Supported Series: HollySys LK series PLC
4 +
5 +**V-BOX setting**
6 +
7 +|**Items**|**Settings**|**Note**
8 +|Protocol|HollySys LK Modbus RTU|
9 +|Connection|RS485|
10 +|Baud rate|38400|
11 +|Data bit|8|
12 +|Parity|None|
13 +|Stop bit|1|
14 +|Device station No.|1|
15 +
16 +**Address List**
17 +
18 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
19 +|Bit|QX|QXDDDDD.dd|0~~65535.15|
20 +|Bit|IX|IXDDDDD.dd|0~~65535.15|
21 +|Bit|MX|MXDDDDD.dd|0~~65535.15|
22 +|Word|QW|QWDDDDD|0~~99999|
23 +|Word|IW|IWDDDDD|0~~99999|
24 +|Word|MW|MWDDDDD|0~~99999|
25 +|Word|MD|MDDDDDD|0~~99999|
26 +
27 +**3)Cable Wiring**
28 +
29 +[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e3620dfba17d0c4d.png||alt="Hollysys485-2.png" height="247" width="400"]]
30 +
31 +== **LM Modbus RTU** ==
32 +
33 +Supported Series: HollySys LM3109/LM3107 PLC
34 +
35 +**V-BOX setting**
36 +
37 +|**Items**|**Settings**|**Optional**|**Note**
38 +|Protocol|HollySys LM Modbus RTU|HollySys LM Modbus RTU|
39 +|Connection|RS232|RS485|
40 +|Baud rate|38400|38400|
41 +|Data bit|8|8|
42 +|Parity|None|None|
43 +|Stop bit|1|1|
44 +|Device station No.|1|1|
45 +
46 +**Address List**
47 +
48 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
49 +|Bit|QX|QXDDDDD.o|0~~99999.7|
50 +|Bit|IX|IXDDDDD.o|0~~99999.7|
51 +|Bit|MX|MXDDDDD.o|0~~99999.7|
52 +|Word|QW|QWDDDDD|0~~99999|
53 +|Word|IW|IWDDDDD|0~~99999|
54 +|Word|MW|MWDDDDD|0~~99999|
55 +|Word|MD|MDDDDDD|0~~99999|
56 +
57 +**Cable Wiring**
58 +
59 +RS232
60 +
61 +[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_f3891a236efc8665.png||alt="HollySysRS232.png" height="247" width="400"]]
62 +
63 +RS485
64 +
65 +{{id name="IHollysysLMModbusRTU.gif"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_eb81e5d8a6025505.gif||alt="Hollysys LM Modbus RTU.gif" height="247" width="400"]]
xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e3620dfba17d0c4d.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.5 KB
Content
xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_eb81e5d8a6025505.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +7.1 KB
Content
xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_f3891a236efc8665.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +10.4 KB
Content