INVT
Last modified by Theodore Xu on 2023/09/16 11:36
V-BOX setting
Item | Settings | Note |
Protocol | INVT_IVC2L | |
Connection | RS232 | |
Baud rate | 19200 | |
Data bit | 8 | |
Parity | EVEN | |
Stop bit | 1 | |
PLC station No. | 1 |
Address List
Type | Device registers | Format | Range | Note |
Bit | X | XOOO | 0~377 | |
Y | YOOO | 0~377 | ||
M | MDDDD | 0~1999 | ||
SM | SMDDD | 0~255 | ||
S | SDDD | 0~991 | ||
T | TDDD | 0~255 | ||
C | CDDD | 0~255 | ||
Word | D | DDDDD | 0~7999 | |
SD | SDDDD | 0~255 | ||
Z | ZDD | 0~15 | ||
T | TDDD | 0~255 | ||
C | CDDD | 0~199 | ||
Double word | C | CDDD | 200~255 |
PLC settings
Open the INVI plc software, create a new project or open a project that has already been created
Configure serial port parameters.
PC connect PLC
Download
Cable Wiring