Wiki source code of Inovance
Version 12.1 by Theodore Xu on 2023/11/01 10:07
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
12.1 | 1 | == **H3U serial** == |
![]() |
2.1 | 2 | |
![]() |
7.1 | 3 | **V-BOX Settings** |
![]() |
2.1 | 4 | |
5 | |**Item**|**Settings**|**Note** | ||
6 | |Protocol|INOVANCE H3U PLC| | ||
7 | |Connection|RS422| | ||
8 | |Baud rate|9600| | ||
9 | |Data bit|7| | ||
10 | |Parity|EVEN| | ||
11 | |Stop bit|1| | ||
12 | |PLC station No.|0| | ||
13 | |||
![]() |
7.1 | 14 | **Address List** |
![]() |
2.1 | 15 | |
![]() |
8.1 | 16 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** |
17 | |Bit|X|X OOOOOO|0~~303237| | ||
18 | |Bit|Y|Y OOOOOO|0~~303237| | ||
19 | |Bit|M|M DDDDD|0~~99999| | ||
20 | |Bit|T|T DDDDD|0~~99999| | ||
21 | |Bit|C|C DDDDD|0~~99999| | ||
22 | |Bit|SM|SM DDDD|8000~~9999| | ||
23 | |Bit|S|S DDDDD|0~~99999| | ||
24 | |Bit|Lamp|Lamp0|0~~0|((( | ||
25 | Communication Indicator Lamp | ||
![]() |
2.1 | 26 | |
![]() |
8.1 | 27 | 0: Connected |
![]() |
2.1 | 28 | |
![]() |
8.1 | 29 | 1: Disconnected |
30 | ))) | ||
31 | |Word|X|X OOOOOO|0~~303237| | ||
32 | |Word|Y|Y OOOOOO|0~~303237| | ||
33 | |Word|M|M DDDDD|0~~99999| | ||
34 | |Word|T|T DDDDD|0~~99999| | ||
35 | |Word|C|C DDD|0~~199| | ||
36 | |Word|D|D DDDD|0~~7999| | ||
37 | |Word|S|S DDDDD|0~~99999| | ||
38 | |Word|SD|SD DDDD|8000~~9999| | ||
39 | |Word|R|R DDDDD|0~~32767| | ||
40 | |Double Word|CH|CH DDD|200~~255 | ||
![]() |
2.1 | 41 | |
![]() |
8.1 | 42 | **PLC Settings** |
43 | |||
44 | Create the new project, and select Series and models as H3U. | ||
45 | |||
46 | (% style="text-align:center" %) | ||
47 | [[image:AutoShop01createprj.png]] | ||
48 | |||
49 | Configure the COM0 settings from [Communication Config]-[COM0(Download/HMI Monitor Protocol)], the default communication parameters we could see it is 9600,1,7,EVEN. After setting finished, click OK to save the settings. | ||
50 | |||
51 | (% style="text-align:center" %) | ||
52 | [[image:AutoShop02setupCOM0.png]] | ||
53 | |||
54 | Program the PLC project, and click compile. | ||
55 | |||
56 | (% style="text-align:center" %) | ||
57 | [[image:AutoShopPrg.png]] | ||
58 | |||
59 | |||
60 | Connect PLC with PC via USB cable or RS422-USB converter cable, and test the connection status. If it shows like the below, which means the connection is set up successfully. And click OK. | ||
61 | |||
62 | (% style="text-align:center" %) | ||
63 | [[image:AutoShop03pcconnect.png]] | ||
64 | |||
65 | Download PLC program into PLC. | ||
66 | |||
67 | (% style="text-align:center" %) | ||
68 | [[image:AutoShop04Download.png]] | ||
69 | |||
![]() |
7.1 | 70 | **Cable Wiring** |
![]() |
2.1 | 71 | |
72 | Figure | ||
73 | |||
![]() |
7.1 | 74 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_addddf687771b2a9.png||alt="image-20220831164646-2.png" height="258" width="100"]] [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_63add2bcd04520f6.png||alt="image-20220831164700-3.png" height="191" width="496"]] |
![]() |
2.1 | 75 | |
76 | Pin Definition Diagram | ||
77 | |||
![]() |
7.1 | 78 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d332c6eb75105461.png||alt="image-20220831164731-4.png" height="168" width="330"]] |
![]() |
8.1 | 79 | |
![]() |
10.1 | 80 | == **H3U Ethernet** == |
![]() |
8.1 | 81 | |
82 | Support Series: INOVANCE H3U Series | ||
83 | |||
84 | **HMI Settings** | ||
85 | |||
86 | |=**Item**|=**Settings**|=**Note** | ||
87 | |Protocol|INOVANCE H3U PLC Ethernet| | ||
88 | |Connection|Ethernet| | ||
89 | |Port No.|502| | ||
90 | |Device No.|1| | ||
91 | |HMI No.|0| | ||
92 | |||
93 | **Address List** | ||
94 | |||
95 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
96 | |Bit|M|M DDDD|0~~8511| | ||
97 | |Bit|SM|SM DDDD|0~~1023| | ||
98 | |Bit|S|S DDDD|0~~4095| | ||
99 | |Bit|T|T DDD|0~~511| | ||
100 | |Bit|C|C DDD|0~~255| | ||
101 | |Bit|X|X OOO|0~~571| | ||
102 | |Bit|Y|Y OOO|0~~571| | ||
103 | |Word|D|D DDDD|0~~8511| | ||
104 | |Word|SD |SD DDDD|0~~1023| | ||
105 | |Word|R|R DDDDD|0~~32767| | ||
106 | |Word|T|T DDD|0~~255| | ||
107 | |Word|C|C DDD|0~~199| | ||
108 | |Double Word|C|C DDD|200~~255| | ||
109 | |||
110 | **PLC Settings** | ||
111 | |||
112 | Create the new project, and select Series and models as H3U. | ||
113 | |||
114 | (% style="text-align:center" %) | ||
115 | [[image:AutoShop01createprj.png]] | ||
116 | |||
117 | Configure the Ethernet settings from [Communication Config]-[Ethernet]. | ||
118 | |||
119 | (% style="text-align:center" %) | ||
120 | [[image:AutoShopEthernetSetup.png]] | ||
121 | |||
122 | Program the PLC project, and click compile. | ||
123 | |||
124 | (% style="text-align:center" %) | ||
125 | [[image:AutoShopPrg.png]] | ||
126 | |||
127 | Connect PLC with PC via USB cable or RS422-USB converter cable, and test the connection status. If it shows like the below, which means the connection is set up successfully. And click OK. | ||
128 | |||
129 | (% style="text-align:center" %) | ||
130 | [[image:AutoShop03pcconnect.png]] | ||
131 | |||
132 | If don't want to change the IP, user could also read the IP parameter from the PLC after the PC connection is set up successfully. | ||
133 | |||
134 | (% style="text-align:center" %) | ||
135 | [[image:AutoShopreadip.png]] | ||
136 | |||
137 | Download PLC program into PLC. | ||
138 | |||
139 | (% style="text-align:center" %) | ||
140 | [[image:AutoShop04Download.png]] | ||
141 | |||