| author | version | line-number | content |
|---|---|---|---|
| |
1.1 | 1 | == **H3U serial** == |
| 2 | |||
| 3 | **V-Box Settings** | ||
| 4 | |||
| 5 | |**Item**|**Settings**|**Note** | ||
| 6 | |Protocol|INOVANCE H3U PLC| | ||
| 7 | |Connection|RS422| | ||
| 8 | |Baud rate|9600| | ||
| 9 | |Data bit|7| | ||
| 10 | |Parity|EVEN| | ||
| 11 | |Stop bit|1| | ||
| 12 | |PLC station No.|0| | ||
| 13 | |||
| 14 | **Address List** | ||
| 15 | |||
| 16 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 17 | |Bit|X|X OOOOOO|0~~303237| | ||
| 18 | |Bit|Y|Y OOOOOO|0~~303237| | ||
| 19 | |Bit|M|M DDDDD|0~~99999| | ||
| 20 | |Bit|T|T DDDDD|0~~99999| | ||
| 21 | |Bit|C|C DDDDD|0~~99999| | ||
| 22 | |Bit|SM|SM DDDD|8000~~9999| | ||
| 23 | |Bit|S|S DDDDD|0~~99999| | ||
| 24 | |Bit|Lamp|Lamp0|0~~0|((( | ||
| 25 | Communication Indicator Lamp | ||
| 26 | |||
| 27 | 0: Connected | ||
| 28 | |||
| 29 | 1: Disconnected | ||
| 30 | ))) | ||
| 31 | |Word|X|X OOOOOO|0~~303237| | ||
| 32 | |Word|Y|Y OOOOOO|0~~303237| | ||
| 33 | |Word|M|M DDDDD|0~~99999| | ||
| 34 | |Word|T|T DDDDD|0~~99999| | ||
| 35 | |Word|C|C DDD|0~~199| | ||
| 36 | |Word|D|D DDDD|0~~7999| | ||
| 37 | |Word|S|S DDDDD|0~~99999| | ||
| 38 | |Word|SD|SD DDDD|8000~~9999| | ||
| 39 | |Word|R|R DDDDD|0~~32767| | ||
| 40 | |Double Word|CH|CH DDD|200~~255 | ||
| 41 | |||
| 42 | **PLC Settings** | ||
| 43 | |||
| 44 | Create the new project, and select Series and models as H3U. | ||
| 45 | |||
| 46 | (% style="text-align:center" %) | ||
| 47 | [[image:AutoShop01createprj.png]] | ||
| 48 | |||
| 49 | Configure the COM0 settings from [Communication Config]-[COM0(Download/HMI Monitor Protocol)], the default communication parameters we could see it is 9600,1,7,EVEN. After setting finished, click OK to save the settings. | ||
| 50 | |||
| 51 | (% style="text-align:center" %) | ||
| 52 | [[image:AutoShop02setupCOM0.png]] | ||
| 53 | |||
| 54 | Program the PLC project, and click compile. | ||
| 55 | |||
| 56 | (% style="text-align:center" %) | ||
| 57 | [[image:AutoShopPrg.png]] | ||
| 58 | |||
| 59 | |||
| 60 | Connect PLC with PC via USB cable or RS422-USB converter cable, and test the connection status. If it shows like the below, which means the connection is set up successfully. And click OK. | ||
| 61 | |||
| 62 | (% style="text-align:center" %) | ||
| 63 | [[image:AutoShop03pcconnect.png]] | ||
| 64 | |||
| 65 | Download PLC program into PLC. | ||
| 66 | |||
| 67 | (% style="text-align:center" %) | ||
| 68 | [[image:AutoShop04Download.png]] | ||
| 69 | |||
| 70 | **Cable Wiring** | ||
| 71 | |||
| 72 | Figure | ||
| 73 | |||
| 74 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_addddf687771b2a9.png||alt="image-20220831164646-2.png" height="258" width="100"]] [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_63add2bcd04520f6.png||alt="image-20220831164700-3.png" height="191" width="496"]] | ||
| 75 | |||
| 76 | Pin Definition Diagram | ||
| 77 | |||
| 78 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d332c6eb75105461.png||alt="image-20220831164731-4.png" height="168" width="330"]] | ||
| 79 | |||
| 80 | == **H3U Ethernet** == | ||
| 81 | |||
| 82 | Support Series: INOVANCE H3U Series | ||
| 83 | |||
| 84 | **V-Box Settings** | ||
| 85 | |||
| 86 | |=**Item**|=**Settings**|=**Note** | ||
| 87 | |Protocol|INOVANCE H3U PLC Ethernet| | ||
| 88 | |Connection|Ethernet| | ||
| 89 | |Port No.|502| | ||
| 90 | |Device No.|1| | ||
| 91 | |HMI No.|0| | ||
| 92 | |||
| 93 | **Address List** | ||
| 94 | |||
| 95 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 96 | |Bit|M|M DDDD|0~~8511| | ||
| 97 | |Bit|SM|SM DDDD|0~~1023| | ||
| 98 | |Bit|S|S DDDD|0~~4095| | ||
| 99 | |Bit|T|T DDD|0~~511| | ||
| 100 | |Bit|C|C DDD|0~~255| | ||
| 101 | |Bit|X|X OOO|0~~571| | ||
| 102 | |Bit|Y|Y OOO|0~~571| | ||
| 103 | |Word|D|D DDDD|0~~8511| | ||
| 104 | |Word|SD |SD DDDD|0~~1023| | ||
| 105 | |Word|R|R DDDDD|0~~32767| | ||
| 106 | |Word|T|T DDD|0~~255| | ||
| 107 | |Word|C|C DDD|0~~199| | ||
| 108 | |Double Word|C|C DDD|200~~255| | ||
| 109 | |||
| 110 | **PLC Settings** | ||
| 111 | |||
| 112 | Create the new project, and select Series and models as H3U. | ||
| 113 | |||
| 114 | (% style="text-align:center" %) | ||
| 115 | [[image:AutoShop01createprj.png]] | ||
| 116 | |||
| 117 | Configure the Ethernet settings from [Communication Config]-[Ethernet]. | ||
| 118 | |||
| 119 | (% style="text-align:center" %) | ||
| 120 | [[image:AutoShopEthernetSetup.png]] | ||
| 121 | |||
| 122 | Program the PLC project, and click compile. | ||
| 123 | |||
| 124 | (% style="text-align:center" %) | ||
| 125 | [[image:AutoShopPrg.png]] | ||
| 126 | |||
| 127 | Connect PLC with PC via USB cable or RS422-USB converter cable, and test the connection status. If it shows like the below, which means the connection is set up successfully. And click OK. | ||
| 128 | |||
| 129 | (% style="text-align:center" %) | ||
| 130 | [[image:AutoShop03pcconnect.png]] | ||
| 131 | |||
| 132 | If don't want to change the IP, user could also read the IP parameter from the PLC after the PC connection is set up successfully. | ||
| 133 | |||
| 134 | (% style="text-align:center" %) | ||
| 135 | [[image:AutoShopreadip.png]] | ||
| 136 | |||
| 137 | Download PLC program into PLC. | ||
| 138 | |||
| 139 | (% style="text-align:center" %) | ||
| 140 | [[image:AutoShop04Download.png]] | ||
| 141 | |||
| 142 | **Cable Wiring** | ||
| 143 | |||