Hide last authors
| author | version | line-number | content |
|---|---|---|---|
| |
1.1 | 1 | = MC Series = |
| 2 | |||
| 3 | Supported Series: MEGMEET MC280 Series | ||
| 4 | |||
| 5 | **V-Box Settings** | ||
| 6 | |||
| 7 | |=**Item**|=**Settings**|=**Note** | ||
| 8 | |Protocol|megmeet| | ||
| 9 | |Connection|RS232| | ||
| 10 | |Baud rate|9600| | ||
| 11 | |Data bit|8| | ||
| 12 | |Parity|Even| | ||
| 13 | |Stop bit|1| | ||
| 14 | |PLC station No.|0| | ||
| 15 | |||
| 16 | (% style="text-align:center" %) | ||
| 17 | [[image:麦格米特串口协议配置.png]] | ||
| 18 | |||
| 19 | **Address List** | ||
| 20 | |||
| 21 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
| 22 | |(% colspan="1" rowspan="14" %)Bit|Y|YOOO|0~~377| | ||
| 23 | |X|XOOO|0~~377| | ||
| 24 | |M0|M0DDDD|0~~2047| | ||
| 25 | |M1|M1DDDD|2048~~10239| | ||
| 26 | |SM0|SM0DDD|0~~255| | ||
| 27 | |SM1|SM1DDD|256~~512| | ||
| 28 | |S0|S0DDDD|0~~1023| | ||
| 29 | |S1|S1DDDD|1024~~4095| | ||
| 30 | |T0|T0DDD|0~~255| | ||
| 31 | |T1|T1DDD|256~~511| | ||
| 32 | |C0|C0DDD|0~~255| | ||
| 33 | |C1|C1DDD|256~~306| | ||
| 34 | |D|DDDDD.dd|0~~7999.15| | ||
| 35 | |R|RDDDDD.dd|0~~32767.15| | ||
| 36 | |(% colspan="1" rowspan="8" %)Word|D|DDDDD|0~~7999| | ||
| 37 | |Z|ZDD|0~~15| | ||
| 38 | |TW0|TW0DDD|0~~255| | ||
| 39 | |TW1|TW1DDD|256~~511| | ||
| 40 | |SD0|SD0DDD|0~~255| | ||
| 41 | |SD1|SD1DDD|256~~511| | ||
| 42 | |CW|CWDDD|0~~306| | ||
| 43 | |R|RDDDDD|0~~32767| | ||
| 44 | |(% colspan="1" rowspan="9" %)Double Word|CW0|TDDDD|0~~9999| | ||
| 45 | |CW1|CDDDD|0~~9999| | ||
| 46 | |||
| 47 | **PLC Settings** | ||
| 48 | |||
| 49 | Create a new project and select the corresponding model | ||
| 50 | |||
| 51 | (% style="text-align:center" %) | ||
| 52 | [[image:MEG01createproject.png]] | ||
| 53 | |||
| 54 | Set the Comm Port configuration from the System block tree node, select PORT0 as Program port protocol. | ||
| 55 | |||
| 56 | (% style="text-align:center" %) | ||
| 57 | [[image:MEG02COMMport.png]] | ||
| 58 | |||
| 59 | Program the PLC project | ||
| 60 | |||
| 61 | (% style="text-align:center" %) | ||
| 62 | [[image:MEGprogram.png]] | ||
| 63 | |||
| 64 | Connect PLC by RS232-USB convertor cable, and set the Serial Port settings. If the pop up like the following prompt, which means the connection is setup successfully. | ||
| 65 | |||
| 66 | (% style="text-align:center" %) | ||
| 67 | [[image:MEG03PCserialconnect.png]] | ||
| 68 | |||
| 69 | Find the PLC option on the toolbar, and click [Download...]-[Yes]-[Download] to process the download procedure. | ||
| 70 | |||
| 71 | (% style="text-align:center" %) | ||
| 72 | [[image:MEG04downloadprg.png]] | ||
| 73 | |||
| 74 | **Cable Wiring** | ||
| 75 | |||