Changes for page Mitsubishi

Last modified by Joe on 2024/05/21 10:53

From version 55.1
edited by Theodore Xu
on 2023/09/15 11:10
Change comment: There is no comment for this version
To version 57.1
edited by Theodore Xu
on 2023/09/15 11:13
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,47 +45,3 @@
1 -== **FX1S,1N,2N Serial ** ==
2 -
3 -Supported Series: Mitsubishi FX1S, FX1N, FX2N series
4 -
5 -**V-BOX Settings**
6 -
7 -|**Item**|**Settings**|**Note**
8 -|Protocol|Mitsubishi FX1S/FX1N/FX2N|
9 -|Connection|RS422/RS485/RS232|
10 -|Baud rate|9600~~115200|
11 -|Data bit|7/8|
12 -|Parity|EVEN/Odd/None|
13 -|Stop bit|1/2|
14 -|PLC station No.|1~~255|
15 -
16 -[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dc262f14b14cf564.png||alt="image-20220825102844-3.png" height="1011" width="1920"]]
17 -
18 -**Address List**
19 -
20 -|**Type**|**Device registers**|**V-Box registers**|**Format**|**Range**|**Note**
21 -|(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
22 -|Y|Y|Y o|0~~303237|
23 -|M|M|M d|0~~99999|
24 -|T|T|T d|0~~99999|
25 -|C|C|C d|0~~99999|
26 -|S|S|S d|0~~99999|
27 -|SM|SM|SM d|8000~~9999|
28 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 -|Y|Y|Y o|0~~303237|
30 -|M|M|M d|0~~99999|
31 -|T|T|T d|0~~99999|
32 -|C|C|C d|0~~199|
33 -|D|D|D d|0~~7999|
34 -|S|S|S d|0~~99999|
35 -|SD|SD|SD d|8000~~9999|
36 -
37 -**Cable Wiring**
38 -
39 -**RS422**
40 -
41 -[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9294a40c62eb99be.png||alt="image-20220825103350-4.png" height="284" width="723"]]
42 -
43 -[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]]
44 -
45 45  == **FX3U,3G,3GA Serial ** ==
46 46  
47 47  Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
... ... @@ -166,6 +166,8 @@
166 166  |Port No.|5009|Must be the same as the PLC setting
167 167  |PLC station No.|0|
168 168  
125 +[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b2cdc33b6eb92b67.png||alt="image-20221119101946-2.png" height="395" width="695"]]
126 +
169 169  **Address List**
170 170  
171 171  |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
... ... @@ -245,10 +245,6 @@
245 245  
246 246  [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7f29923ebcb670d1.png||alt="image-20221116111727-5.png" height="416" width="697"]]
247 247  
248 -**Configure the communication protocol**
249 -
250 -[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b2cdc33b6eb92b67.png||alt="image-20221119101946-2.png" height="395" width="695"]]
251 -
252 252  == **FX5U Serial ** ==
253 253  
254 254  Mitsubishi FX5U series PLC