1 +== **FX1S,1N,2N Serial ** ==
2 +
3 +Supported Series: Mitsubishi FX1S, FX1N, FX2N series
4 +
5 +**V-BOX Settings**
6 +
7 +|**Item**|**Settings**|**Note**
8 +|Protocol|Mitsubishi FX1S/FX1N/FX2N|
9 +|Connection|RS422/RS485/RS232|
10 +|Baud rate|9600~~115200|
11 +|Data bit|7/8|
12 +|Parity|EVEN/Odd/None|
13 +|Stop bit|1/2|
14 +|PLC station No.|1~~255|
15 +
16 +**Address List**
17 +
18 +|**Type**|**Device registers**|**V-Box registers**|**Format**|**Range**|**Note**
19 +|(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
20 +|Y|Y|Y o|0~~303237|
21 +|M|M|M d|0~~99999|
22 +|T|T|T d|0~~99999|
23 +|C|C|C d|0~~99999|
24 +|S|S|S d|0~~99999|
25 +|SM|SM|SM d|8000~~9999|
26 +|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
27 +|Y|Y|Y o|0~~303237|
28 +|M|M|M d|0~~99999|
29 +|T|T|T d|0~~99999|
30 +|C|C|C d|0~~199|
31 +|D|D|D d|0~~7999|
32 +|S|S|S d|0~~99999|
33 +|SD|SD|SD d|8000~~9999|
34 +
35 +**Configure the communication protocol**
36 +
37 +{{id name="Iimage-20220825102844-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dc262f14b14cf564.png||alt="image-20220825102844-3.png" height="1011" width="1920"]]
38 +
39 +**Cable Wiring**
40 +
41 +**RS422**
42 +
43 +[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9294a40c62eb99be.png||alt="image-20220825103350-4.png" height="284" width="723"]]
44 +
45 +[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]]
46 +
1 1  == **FX3U,3G,3GA Serial ** ==
2 2  
3 3  Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
... ... @@ -220,9 +220,6 @@
220 220  |Stop bit|1|
221 221  |PLC station No.|1~~255|Need to be the same as PLC settings
222 222  
223 -(% style="text-align:center" %)
224 -[[image:三菱 FX5U 串口协议配置.png]]
225 -
226 226  **Address List**
227 227  
228 228  |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
... ... @@ -277,6 +277,10 @@
277 277  
278 278  Done.
279 279  
323 +**Configure the communication protocol**
324 +
325 +{{id name="Iimage-20220825104904-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dbaddd53e9951a17.png||alt="image-20220825104904-1.png" height="1033" width="1920"]]
326 +
280 280  **Cable Wiring**
281 281  
282 282  **RS422**
... ... @@ -376,9 +376,6 @@
376 376  |Stop bit|1|
377 377  |PLC station No.|1~~255|Need to be the same as PLC settings
378 378  
379 -(% style="text-align:center" %)
380 -[[image:三菱 L02串口协议配置.png]]
381 -
382 382  **Address List**
383 383  
384 384  |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
... ... @@ -414,6 +414,10 @@
414 414  |ZR|ZR|ZR h|0~~FFFF|
415 415  |D|D|D d|0~~99999|
416 416  
461 +**Communication Settings**
462 +
463 +[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_cfed67f2ecb4ccec.png||alt="image-20220825160648-3.png" height="1009" width="1920"]]
464 +
417 417  **Cable Wiring**
418 418  
419 419  **RS422**
... ... @@ -434,9 +434,6 @@
434 434  |Port No.|1025|Must be the same as the PLC setting
435 435  |PLC station No.|0|Must be the same as the PLC setting
436 436  
437 -(% style="text-align:center" %)
438 -[[image:三菱 L02以太网协议配置1.png]]
439 -
440 440  **PLC Settings (GX Works2 )**
441 441  
442 442  Create a project
... ... @@ -457,6 +457,10 @@
457 457  
458 458  Restart PLC device;
459 459  
505 +**Configure the communication protocol**
506 +
507 +[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_fafc9b29e20178c0.png||alt="image-20220825142659-1.png" height="1010" width="1920"]]
508 +
460 460  **Cable Wiring**
461 461  
462 462  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
... ... @@ -471,7 +471,7 @@
471 471  
472 472  Mitsubishi QJ71E71 Ethernet communication module;
473 473  
474 -**V-BOX Settings**
523 +**1)V-BOX Settings**
475 475  
476 476  |**Items**|**Settings**|**Note**
477 477  |Protocol|MIT QJ71E71 MELSEC|
... ... @@ -479,10 +479,8 @@
479 479  |Port No.|1025|Must be the same as the PLC setting
480 480  |PLC station No.|0|Must be the same as the PLC setting
481 481  
482 -[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50990385ef491b9e.png||alt="image-20221119171832-5.png" height="354" width="625"]]
531 +**2)Address List**
483 483  
484 -**Address List**
485 -
486 486  |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
487 487  |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
488 488  |Y|Y|Y h|0~~1FFF|
... ... @@ -513,16 +513,16 @@
513 513  |Z|Z|Z d|0~~15|
514 514  |ZR|ZR|ZR h|0~~FE7FF|
515 515  
516 -**PLC Settings(GX Works2)**
563 +**3)PLC Settings(GX Works2)**
517 517  
518 518  * Click [Ethernet/CC IE/MELSECNET];
519 519  * Please select [Ethernet] as network type;
520 520  * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
521 521  * Select [Online] as Mode;
522 -* [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d54f23688c520f78.png||alt="image-20221119171343-2.png" height="341" width="587"]]
569 +* {{id name="Iimage-20221119171343-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d54f23688c520f78.png||alt="image-20221119171343-2.png" height="341" width="587"]]
523 523  * Click [Operation setting] to set IP;
524 524  * Select [Binary Code] as [Communication Data Code];
525 -* [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ce8e6a671b9508e0.png||alt="image-20221119171436-3.png" height="354" width="588"]]
572 +* {{id name="Iimage-20221119171436-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ce8e6a671b9508e0.png||alt="image-20221119171436-3.png" height="354" width="588"]]
526 526  * Click [Open setting]
527 527  * Set protocol: TCP;
528 528  * Set [unpassive] in [Open system];
... ... @@ -535,6 +535,10 @@
535 535  * {{id name="Iimage-20221119171611-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1d8e2f4fb7c72471.png||alt="image-20221119171611-4.png" height="354" width="588"]]
536 536  * Download project into PLC and restart it
537 537  
538 -**Cable Wiring**
585 +**4)Configure the communication protocol**
539 539  
587 +{{id name="Iimage-20221119171832-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50990385ef491b9e.png||alt="image-20221119171832-5.png" height="354" width="625"]]
588 +
589 +**5)Cable Wiring**
590 +
540 540  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
三菱 FX5U 串口协议配置.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -65.0 KB
Content
三菱 L02 以太网盒子通讯配置.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -66.5 KB
Content
三菱 L02串口协议配置.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -64.4 KB
Content
三菱 L02以太网协议配置1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -66.7 KB
Content