Changes for page Mitsubishi

Last modified by Joe on 2024/05/21 10:53

From version 75.2
edited by Theodore Xu
on 2023/09/15 18:15
Change comment: There is no comment for this version
To version 75.1
edited by Theodore Xu
on 2023/09/15 11:57
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -327,16 +327,34 @@
327 327  |SD|SD d|0~~11999|
328 328  
329 329  **PLC Settings (GX Works 3)**
330 -[Navigation]→[Parameter]→[FX5UCPU]→[Module Parameter]→[Ethernet Port]:[Basic Settings]→ [Own node settings]:[IP Address]192.168.40.11, [Subnet Mask]255.255.255.0, [Default Gateway]192.168.40.1,[ Communication Data Code] Binary.
331 331  
332 -(% style="text-align:center" %)
333 -[[image:1.3.1.png]]
331 +Find the [Ethernet port] in the navigation area.
334 334  
335 -[External Device Configuration]→[Detailed Settings]→[Ethernet Configuration(Built-in Ethernet Port)]→[Ethernet Device (General)]→[SLMP Connection Module] Drag under Host for Connection No.1→[Port No.]5002→[Close with Reflecting the Setting]
333 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
336 336  
337 -(% style="text-align:center" %)
338 -[[image:1.3.2.png]]
335 +Select [Own Node Settings] in the [Setting Item List];
339 339  
337 +Set [IP Address], [Subnet Mask], [Default Gateway];
338 +
339 +Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
340 +
341 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
342 +
343 +Select [SLMP Connection Module] and add into host station as below picture shows;
344 +
345 +Set Port number as 5002 (this is necessary settings);
346 +
347 +Click [Close with Reflecting the Setting] to save and close window;
348 +
349 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
350 +
351 +Click [Apply] to completed Etherenet settings;
352 +
353 +Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
354 +
355 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
356 +
357 +
340 340  **Cable Wiring**
341 341  
342 342  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1.3.1.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -107.7 KB
Content
1.3.2.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.AiXia
Size
... ... @@ -1,1 +1,0 @@
1 -131.6 KB
Content