Wiki source code of Mitsubishi

Version 43.1 by Theodore Xu on 2023/09/15 10:10

Hide last authors
Theodore Xu 39.1 1 == **FX1S,1N,2N Serial ** ==
Leo Wei 2.1 2
3 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
4
Theodore Xu 37.1 5 **V-BOX Settings**
Leo Wei 2.1 6
7 |**Item**|**Settings**|**Note**
8 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
9 |Connection|RS422/RS485/RS232|
10 |Baud rate|9600~~115200|
11 |Data bit|7/8|
12 |Parity|EVEN/Odd/None|
13 |Stop bit|1/2|
14 |PLC station No.|1~~255|
15
Theodore Xu 37.1 16 **Address List**
Leo Wei 2.1 17
Theodore Xu 37.1 18 |**Type**|**Device registers**|**V-Box registers**|**Format**|**Range**|**Note**
Leo Wei 2.1 19 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
20 |Y|Y|Y o|0~~303237|
21 |M|M|M d|0~~99999|
22 |T|T|T d|0~~99999|
23 |C|C|C d|0~~99999|
24 |S|S|S d|0~~99999|
25 |SM|SM|SM d|8000~~9999|
26 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
27 |Y|Y|Y o|0~~303237|
28 |M|M|M d|0~~99999|
29 |T|T|T d|0~~99999|
30 |C|C|C d|0~~199|
31 |D|D|D d|0~~7999|
32 |S|S|S d|0~~99999|
33 |SD|SD|SD d|8000~~9999|
34
Theodore Xu 37.1 35 **Configure the communication protocol**
Leo Wei 2.1 36
37 {{id name="Iimage-20220825102844-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dc262f14b14cf564.png||alt="image-20220825102844-3.png" height="1011" width="1920"]]
38
Theodore Xu 37.1 39 **Cable Wiring**
Leo Wei 2.1 40
Theodore Xu 37.1 41 **RS422**
Leo Wei 2.1 42
Theodore Xu 37.1 43 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9294a40c62eb99be.png||alt="image-20220825103350-4.png" height="284" width="723"]]
Leo Wei 2.1 44
Theodore Xu 35.1 45 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]]
Leo Wei 2.1 46
Theodore Xu 40.1 47 == **FX3U,3G,3GA Serial ** ==
Leo Wei 2.1 48
49 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
50
Theodore Xu 38.1 51 **V-BOX Settings**
Leo Wei 2.1 52
53 |**Item**|**Settings**|**Note**
54 |Protocol|Mitsubishi FX3U/3G/3GA|
55 |Connection|RS422/RS485/RS232|
56 |Baud rate|9600~~115200|
57 |Data bit|7/8|
58 |Parity|EVEN/Odd/None|
59 |Stop bit|1/2|
60 |PLC station No.|1~~255|
61
Theodore Xu 38.1 62 **Address List**
Leo Wei 2.1 63
64 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
65 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
66 |Y|Y|Y o|0~~303237|
67 |M|M|M d|0~~99999|
68 |T|T|T d|0~~99999|
69 |C|C|C d|0~~99999|
70 |S|S|S d|0~~99999|
71 |SM|SM|SM d|8000~~9999|
72 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
73 |Y|Y|Y o|0~~303237|
74 |M|M|M d|0~~99999|
75 |T|T|T d|0~~99999|
76 |C|C|C d|0~~199|
77 |D|D|D d|0~~7999|
78 |S|S|S d|0~~99999|
79 |SD|SD|SD d|8000~~9999|
80
Theodore Xu 38.1 81 **Configure the communication protocol**
Leo Wei 2.1 82
Theodore Xu 38.1 83 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_4d2a4921240d23c6.png||alt="image-20220825102649-2.png" height="1009" width="1920"]]
Leo Wei 2.1 84
Theodore Xu 42.1 85 **PLC Setting**
Leo Wei 2.1 86
Theodore Xu 42.1 87 Open GX Works2, create a new PLC project or open the project that has been created.
88 Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK].
89
90 (% style="text-align:center" %)
91 [[image:1.2.png]]
92
93 PLC Default Parameters:
94 [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0
95 Note:The serial port parameters should be set depending on field requirements
96
97 PC and PLC connection:
98
99 [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK]
100
101 (% style="text-align:center" %)
102 [[image:1.5.1.png]]
103
104 Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.”
105
106 (% style="text-align:center" %)
107 [[image:1.5.2.png]]
108
109 **Cable Wiring**
110
Theodore Xu 38.1 111 **RS422**
Leo Wei 2.1 112
Theodore Xu 38.1 113 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e904556bb758dfe.png||alt="image-20220825103421-5.png" height="296" width="715"]]
Leo Wei 2.1 114
Theodore Xu 38.1 115 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]]
Leo Wei 2.1 116
Theodore Xu 43.1 117 == **FX NOPROTOCOL** ==
118
119 Mitsubishi FX3G-RS232-BD
120
121 **V-Box Settings**
122
123 |=**Item**|=**Settings**|=**Note**
124 |Protocol|Mitsubishi FX NOPROTOCOL|
125 |Connection|RS232|
126 |Baud rate|9600|
127 |Data bit|7|
128 |Parity|EVEN|
129 |Stop bit|1|
130 |PLC station No.|0|
131
132 (% style="text-align:center" %)
133 [[image:三菱 FN盒子通讯配置.png]]
134
135 **Address List**
136
137 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
138 |(% rowspan="8" %)Bit|X|X|X o|0~~303237|
139 |Y|Y|Y o|0~~303237|
140 |M|M|M d|0~~99999|
141 |T|T|T d|0~~99999|
142 |C|C|C d|0~~99999|
143 |S|S|S d|0~~99999|
144 |SM|SM|SM d|8000~~9999|
145 |Lamp|Lamp|Lamp d|0~~0|
146 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
147 |Y|Y|Y o|0~~303237|
148 |M|M|M d|0~~99999|
149 |T|T|T d|0~~99999|
150 |C|C|C d|0~~199|
151 |D|D|D d|0~~7999|
152 |S|S|S d|0~~99999|
153 |SD|SD|SD d|8000~~9999|
154
155 **Configure the communication protocol**
156
Theodore Xu 41.1 157 == **FX3U Ethernet ** ==
Leo Wei 2.1 158
159 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
160
Theodore Xu 41.1 161 **V-BOX Settings**
Leo Wei 2.1 162
163 |Items|Settings|Note
164 |Protocol|Mitsubishi FX3U|
165 |Connection|Ethernet|
166 |Port No.|5009|Must be the same as the PLC setting
167 |PLC station No.|0|
168
Theodore Xu 41.1 169 **Address List**
Leo Wei 2.1 170
171 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
172 |(% rowspan="7" %)Bit|X|X|X OOO|0~~377|
173 |Y|Y|Y OOO|0~~377|
174 |M|M|M DDDD|0~~7679|
175 |SM|SM|SM DDDD|8000~~8511|
176 |S|S|S DDDD|0~~4095|
177 |TS|TS|TS DDD|0~~511|
178 |CS|CS|CS DDD|0~~255|
179 |(% rowspan="5" %)Word|CN|CN|CN DDD|0~~199|
180 |TN|TN|TN DDD|0~~511|
181 |D|D|D DDDD|0~~7999|
182 |SD|SD|SD DDDD|8000~~8511|
183 |R|R|R DDDDD|0~~32767|
184
Theodore Xu 41.1 185 **Ethernet Module Settings**
Leo Wei 2.1 186
187 FX3U-ENET-L module configuration
188 Set up the FX3U-ENET-L Ethernet module settings as follows.
189 Select the module location, which in this document is Module 0.
190
Theodore Xu 41.1 191 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_949d5d77c1d9cf1e.png||alt="image-20221116105850-1.png" height="573" width="706"]]
Leo Wei 2.1 192
193 Select "Operational setting" to enter the following screen.
194
195 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
196
Theodore Xu 41.1 197 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dfbfdd586c855c47.png||alt="image-20221116105947-1.png" height="573" width="706"]]
Leo Wei 2.1 198
199 Select "Open setting" to enter the setting interface, the settings are as follows.
200
201 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
202
203 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
204
Theodore Xu 41.1 205 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7c01ac15090fcc5b.png||alt="image-20221116110802-1.png" height="549" width="706"]]
Leo Wei 2.1 206
207 Click on "transter setup" - "PC side I/F setting", see the following figure.
208
209 After setting, the first download must use the programming cable, as shown in the figure; after that, can
210
211 use the IP set in the "Ethernet board" to communicate directly with the network cable.
212
Theodore Xu 41.1 213 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221116110832-2.png" height="423" width="708"]]
Leo Wei 2.1 214
215 Read and write data from the Ethernet module
216
Theodore Xu 41.1 217 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_690b3e57b29cfd4b.png||alt="image-20221116110907-3.png" height="549" width="706"]]
Leo Wei 2.1 218
219 Set "Transter setup" to COM communication, and read or write operation as shown below
220
Theodore Xu 41.1 221 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b317253742f7151.png||alt="image-20221116110917-4.png" height="549" width="706"]]
Leo Wei 2.1 222
Theodore Xu 41.1 223 **PLC Settings (GX Works 2)**
Leo Wei 2.1 224
225 Create a blank FX5U project
226
227 Find Current Connection in the navigation
228
Theodore Xu 41.1 229 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d2a46ba9c005cf38.png||alt="image-20221116111427-1.png" height="421" width="705"]]
Leo Wei 2.1 230
231 Select Connection Channel List
232
233 Select Ethernet board communication
234
Theodore Xu 41.1 235 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8f49721a3e5b0ef9.png||alt="image-20221116111451-2.png" height="421" width="705"]]
Leo Wei 2.1 236
237 Select Ethernet Module
238 Set the IP address of the PLC
239
Theodore Xu 41.1 240 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e9a9e29a46a1041.png||alt="image-20221116111509-3.png" height="666" width="699"]]
Leo Wei 2.1 241
242 Read or write PLC data, in this document is read
243
244 {{id name="Iimage-20221116111651-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e3d629103727a423.png||alt="image-20221116111651-4.png" height="416" width="697"]]
245
Theodore Xu 41.1 246 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7f29923ebcb670d1.png||alt="image-20221116111727-5.png" height="416" width="697"]]
Leo Wei 2.1 247
Theodore Xu 41.1 248 **Configure the communication protocol**
Leo Wei 2.1 249
Theodore Xu 41.1 250 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b2cdc33b6eb92b67.png||alt="image-20221119101946-2.png" height="395" width="695"]]
Leo Wei 2.1 251
252 == {{id name="HFX5USerial"/}}**FX5U Serial ** ==
253
254 Mitsubishi FX5U series PLC
255
256 **1)V-BOX Settings**
257
258 |**Item**|**Settings**|**Note**
259 |Protocol|Mitsubishi FX5U|
260 |Connection|RS422/RS485|
261 |Baud rate|9600|
262 |Data bit|7|
263 |Parity|Odd|
264 |Stop bit|1|
265 |PLC station No.|1~~255|Need to be the same as PLC settings
266
267 **2)Address List**
268
269 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
270 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
271 |Y|Y|Y o|0~~303237|
272 |M|M|M d|0~~99999|
273 |B|B|B h|0~~7FFF|
274 |F|F|F d|0~~32767|
275 |SB|SB|SB h|0~~7FFF|
276 |TS|TS|TS d|0~~1023|
277 |TC|TC|TC d|0~~1023|
278 |STS|STS|STS d|0~~1023|
279 |STC|STC|STS d|0~~1023|
280 |CS|CS|CS d|0~~1023|
281 |CC|CC|CC d|0~~1023|
282 |SM|SM|SM d|0~~9999|
283 |L|L|L d|0~~32767|
284 |S|S|S d|0~~4095|
285 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
286 |TN|TN|TN d|0~~1023|
287 |STN|STN|STN d|0~~1023|
288 |CN|CN|CN d|0~~1023|
289 |R|R|R d|0~~32767|
290 |SW|SW|SW h|0~~7FFF|
291 |Z|Z|Z d|0~~23|
292 |D|D|D d|0~~7999|
293 |SD|SD|SD d|0~~11999|
294
295 **3)PLC Settings (GX Works 3)**
296
297 Create a blank FX5U project
298
299 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
300
301 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_5c9cb13fac1e6c93.png3Fwidth3D20026height3D46226rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
302
303 Select protocol in the setting item, and set parameters.
304
305 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_de942589ca070228.png3Fwidth3D60026height3D32426rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
306
307 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
308
309 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_387ec7d00b5feb59.png3Fwidth3D60026height3D32326rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
310
311 Click the [Apply] button to finish the setting.
312
313 Click download and select the items as below, then click [execute] to download the configuration to PLC.
314
315 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_cdef1c5ec8cc2105.png3Fwidth3D60026height3D43426rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
316
317 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
318
319 Done.
320
321 **4)Configure the communication protocol**
322
323 {{id name="Iimage-20220825104904-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dbaddd53e9951a17.png||alt="image-20220825104904-1.png" height="1033" width="1920"]]
324
325 **5)Cable Wiring**
326
327 * **RS422**
328
329 {{id name="Iimage-20220825105105-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d022c5ff4cf8c68e.png||alt="image-20220825105105-2.png" height="288" width="711"]]
330
331 {{id name="Iimage-20220825105533-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50e173394c73f154.png||alt="image-20220825105533-3.png" height="246" width="420"]]
332
Theodore Xu 33.1 333 == **FX5U Ethernet ** ==
Leo Wei 2.1 334
335 Mitsubishi FX5U series PLC
336
337 **1)V-BOX Settings**
338
339 |**Items**|**Settings**|**Note**
340 |Protocol|Mitsubishi FX5U|
341 |Connection|Ethernet|
342 |Port No.|5002|Must be the same as the PLC setting
343 |PLC station No.|0|
344
345 **2)Address List**
346
347 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
348 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
349 |Y|Y|Y o|0~~303237|
350 |M|M|M d|0~~99999|
351 |B|B|B h|0~~7FFF|
352 |F|F|F d|0~~32767|
353 |SB|SB|SB h|0~~7FFF|
354 |TS|TS|TS d|0~~1023|
355 |TC|TC|TC d|0~~1023|
356 |STS|STS|STS d|0~~1023|
357 |STC|STC|STS d|0~~1023|
358 |CS|CS|CS d|0~~1023|
359 |CC|CC|CC d|0~~1023|
360 |SM|SM|SM d|0~~9999|
361 |L|L|L d|0~~32767|
362 |S|S|S d|0~~4095|
363 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
364 |TN|TN|TN d|0~~1023|
365 |STN|STN|STN d|0~~1023|
366 |CN|CN|CN d|0~~1023|
367 |R|R|R d|0~~32767|
368 |SW|SW|SW h|0~~7FFF|
369 |Z|Z|Z d|0~~23|
370 |D|D|D d|0~~7999|
371 |SD|SD|SD d|0~~11999|
372
373 **3)PLC Settings (GX Works 3)**
374
375 Find the [Ethernet port] in the navigation area.
376
377 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_8e8f85ace087346c.png3Fwidth3D30026height3D59326rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
378
379 Select [Own Node Settings] in the [Setting Item List];
380
381 Set [IP Address], [Subnet Mask], [Default Gateway];
382
383 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
384
385 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_5d98495052c8c10e.png3Fwidth3D60026height3D33926rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
386
387 Select [SLMP Connection Module] and add into host station as below picture shows;
388
389 Set Port number as 5002 (this is necessary settings);
390
391 Click [Close with Reflecting the Setting] to save and close window;
392
393 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_14b489fdc6c6589d.png3Fwidth3D60026height3D35026rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
394
395 Click [Apply] to completed Etherenet settings;
396
397 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
398
399 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_c93025a968a8a9e7.png3Fwidth3D60026height3D43426rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
400
401 **4)Configure the communication protocol**
402
403 {{id name="Iimage-20220825112403-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_caa9bf4d8cc6de0f.png||alt="图片-20220825112403-1.png" height="1033" width="1920"]]
404
405 **5)Cable Wiring**
406
Theodore Xu 33.1 407 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
Leo Wei 2.1 408
409 == {{id name="HL02Serial"/}}**L02 Serial ** ==
410
411 Mitsubishi L02 series CPU built-in serial port.
412
413 **1)V-BOX Settings**
414
415 |**Item**|**Settings**|**Note**
416 |Protocol|Mitsubishi L02|
417 |Connection|RS422|
418 |Baud rate|115200|
419 |Data bit|8|
420 |Parity|Odd|
421 |Stop bit|1|
422 |PLC station No.|1~~255|Need to be the same as PLC settings
423
424 **2)Address List**
425
426 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
427 |Bit|X|X|X h|0~~FFFF|
428 |Bit|Y|Y|Y h|0~~FFFF|
429 |Bit|M|M|M d|0~~9999|
430 |Bit|L|L|L d|0~~9999|
431 |Bit|F|F|F d|0~~9999|
432 |Bit|B|B|B h|0~~FFFF|
433 |Bit|V|V|V d|0~~2047|
434 |Bit|TC|TC|TC d|0~~9999|
435 |Bit|SS|SS|SS d|0~~9999|
436 |Bit|SC|SC|SC d|0~~9999|
437 |Bit|CS|CS|CS d|0~~9999|
438 |Bit|CC|CC|CC d|0~~9999|
439 |Bit|SB|SB|SB h|0~~FFFF|
440 |Bit|SM|SM|SM d|0~~2047|
441 |Bit|STS|STS|STS d|0~~1023|
442 |Bit|S|S|S d|0~~9999|
443 |Bit|DX|DX|DX h|0~~FFFF|
444 |Bit|DY|DY|DY h|0~~FFFF|
445 |Bit|TS|TS|TS d|0~~9999|
446 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
447 |Word|W|W|W h|0~~FFFF|
448 |Word|TN|TN|TN d|0~~99999|
449 |Word|SN|SN|SN d|0~~99999|
450 |Word|CN|CN|CN d|0~~99999|
451 |Word|R|R|R d|0~~99999|
452 |Word|SW|SW|SW h|0~~FFFF|
453 |Word|Z|Z|Z d|0~~99999|
454 |Word|ZR|ZR|ZR h|0~~FFFF|
455 |Word|D|D|D d|0~~99999|
456
457 **3)Communication Settings**
458
459 {{id name="Iimage-20220825160648-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_cfed67f2ecb4ccec.png||alt="image-20220825160648-3.png" height="1009" width="1920"]]
460
461 **4)Cable Wiring**
462
463 * **RS422**
464
465 {{id name="Iimage-20220825161612-8.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_90e38f152d639809.png||alt="image-20220825161612-8.png" height="278" width="612"]]
466
467 {{id name="Iimage-20220825160820-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d301e675d8224725.png||alt="image-20220825160820-4.png" height="208" width="359"]]
468
469 == {{id name="HL02Ethernet"/}}**L02 Ethernet ** ==
470
471 Mitsubishi L series CPU built-in Ethernet port.
472
473 **1)V-BOX Settings**
474
475 |**Items**|**Settings**|**Note**
476 |Protocol|MIT L02 CPU MELSEC|
477 |Connection|Ethernet|
478 |Port No.|1025|Must be the same as the PLC setting
479 |PLC station No.|0|Must be the same as the PLC setting
480
481 **2)Address List**
482
483 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
484 |Bit|X|X|X h|0~~FFFF|
485 |Bit|Y|Y|Y h|0~~FFFF|
486 |Bit|M|M|M d|0~~9999|
487 |Bit|L|L|L d|0~~9999|
488 |Bit|F|F|F d|0~~9999|
489 |Bit|B|B|B h|0~~FFFF|
490 |Bit|V|V|V d|0~~2047|
491 |Bit|TC|TC|TC d|0~~9999|
492 |Bit|SS|SS|SS d|0~~9999|
493 |Bit|SC|SC|SC d|0~~9999|
494 |Bit|CS|CS|CS d|0~~9999|
495 |Bit|CC|CC|CC d|0~~9999|
496 |Bit|SB|SB|SB h|0~~FFFF|
497 |Bit|SM|SM|SM d|0~~2047|
498 |Bit|STS|STS|STS d|0~~1023|
499 |Bit|S|S|S d|0~~9999|
500 |Bit|DX|DX|DX h|0~~FFFF|
501 |Bit|DY|DY|DY h|0~~FFFF|
502 |Bit|TS|TS|TS d|0~~9999|
503 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
504 |Word|W|W|W h|0~~FFFF|
505 |Word|TN|TN|TN d|0~~99999|
506 |Word|SN|SN|SN d|0~~99999|
507 |Word|CN|CN|CN d|0~~99999|
508 |Word|R|R|R d|0~~99999|
509 |Word|SW|SW|SW h|0~~FFFF|
510 |Word|Z|Z|Z d|0~~99999|
511 |Word|ZR|ZR|ZR h|0~~FFFF|
512 |Word|D|D|D d|0~~99999|
513
514 **3)PLC Settings (GX Works2 )**
515
516 Create a project
517
518 Set PLC IP, subnet mask and gateway;
519
520 Select [Binary Code] as communication data code;
521
522 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_776e17505f3fc6c0.png3Fwidth3D60026height3D52426rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
523
524 Set PLC port number, for example 1025
525
526 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_8d0d1a22d388f70b.png3Fwidth3D60026height3D52426rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
527
528 Save settings;
529
530 Download project into PLC device;
531
532 Restart PLC device;
533
534 **4)Configure the communication protocol**
535
536 {{id name="Iimage-20220825142659-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_fafc9b29e20178c0.png||alt="image-20220825142659-1.png" height="1010" width="1920"]]
537
538 **5)Cable Wiring**
539
540 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_2297240b57346b2a.png3Fwidth3D40126height3D17026rev3D1.1-1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
541
542 == {{id name="HQ12HSerial"/}}**Q12H Serial ** ==
543
544 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
545
546 **[[Download link>>url:https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]**
547
Theodore Xu 32.1 548 == **QJ71E71 Ethernet ** ==
Leo Wei 2.1 549
550 Mitsubishi QJ71E71 Ethernet communication module;
551
552 **1)V-BOX Settings**
553
554 |**Items**|**Settings**|**Note**
555 |Protocol|MIT QJ71E71 MELSEC|
556 |Connection|Ethernet|
557 |Port No.|1025|Must be the same as the PLC setting
558 |PLC station No.|0|Must be the same as the PLC setting
559
560 **2)Address List**
561
562 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
563 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
564 |Y|Y|Y h|0~~1FFF|
565 |M|M|M d|0~~99999|
566 |L|L|L d|0~~8191|
567 |F|F|F d|0~~2047|
568 |B|B|B h|0~~1FFF|
569 |V|V|V d|0~~2047|
570 |TS|TS|TS d|0~~2047|
571 |TC|TC|TC d|0~~2047|
572 |SS|SS|SS d|0~~2047|
573 |SC|SC|SC d|0~~2047|
574 |CS|CS|CS d|0~~1023|
575 |CC|CC|CC d|0~~1023|
576 |SB|SB|SB h|0~~7FF|
577 |S|S|S d|0~~8191|
578 |DX|DX|DX h|0~~1FFF|
579 |DY|DY|DY h|0~~1FFF|
580 |SM|SM|SM d|8000~~9999|
581 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
582 |D|D|D d|0~~12287|
583 |W|W|W h|0~~1FFF|
584 |TN|TN|TN d|0~~2047|
585 |SN|SN|SN d|0~~2047|
586 |CN|CN|CN d|0~~1023|
587 |R|R|R d|0~~32767|
588 |SW|SW|SW h|0~~7FF|
589 |Z|Z|Z d|0~~15|
590 |ZR|ZR|ZR h|0~~FE7FF|
591
592 **3)PLC Settings(GX Works2)**
593
594 * Click [Ethernet/CC IE/MELSECNET];
595 * Please select [Ethernet] as network type;
596 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
597 * Select [Online] as Mode;
598 * {{id name="Iimage-20221119171343-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d54f23688c520f78.png||alt="image-20221119171343-2.png" height="341" width="587"]]
599 * Click [Operation setting] to set IP;
600 * Select [Binary Code] as [Communication Data Code];
601 * {{id name="Iimage-20221119171436-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ce8e6a671b9508e0.png||alt="image-20221119171436-3.png" height="354" width="588"]]
602 * Click [Open setting]
603 * Set protocol: TCP;
604 * Set [unpassive] in [Open system];
605 * Set [receive] in [Fixed buffer];
606 * Set [procedure Exist] in [Fixed buffer communication];
607 * Disable [Pairing open];
608 * Set [No confirm] in [Existence confirmation];
609 * Host station port number: 5009;
610 * Save settings;
611 * {{id name="Iimage-20221119171611-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1d8e2f4fb7c72471.png||alt="image-20221119171611-4.png" height="354" width="588"]]
612 * Download project into PLC and restart it
613
614 **4)Configure the communication protocol**
615
616 {{id name="Iimage-20221119171832-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50990385ef491b9e.png||alt="image-20221119171832-5.png" height="354" width="625"]]
617