Theodore Xu 39.1 1 == **FX1S,1N,2N Serial ** ==
Leo Wei 2.1 2
3 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
4
Theodore Xu 37.1 5 **V-BOX Settings**
Leo Wei 2.1 6
7 |**Item**|**Settings**|**Note**
8 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
9 |Connection|RS422/RS485/RS232|
10 |Baud rate|9600~~115200|
11 |Data bit|7/8|
12 |Parity|EVEN/Odd/None|
13 |Stop bit|1/2|
14 |PLC station No.|1~~255|
15
Theodore Xu 55.1 16 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dc262f14b14cf564.png||alt="image-20220825102844-3.png" height="1011" width="1920"]]
17
Theodore Xu 37.1 18 **Address List**
Leo Wei 2.1 19
Theodore Xu 37.1 20 |**Type**|**Device registers**|**V-Box registers**|**Format**|**Range**|**Note**
Leo Wei 2.1 21 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
22 |Y|Y|Y o|0~~303237|
23 |M|M|M d|0~~99999|
24 |T|T|T d|0~~99999|
25 |C|C|C d|0~~99999|
26 |S|S|S d|0~~99999|
27 |SM|SM|SM d|8000~~9999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
Theodore Xu 37.1 37 **Cable Wiring**
Leo Wei 2.1 38
Theodore Xu 37.1 39 **RS422**
Leo Wei 2.1 40
Theodore Xu 37.1 41 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9294a40c62eb99be.png||alt="image-20220825103350-4.png" height="284" width="723"]]
Leo Wei 2.1 42
Theodore Xu 35.1 43 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]]
Leo Wei 2.1 44
Theodore Xu 40.1 45 == **FX3U,3G,3GA Serial ** ==
Leo Wei 2.1 46
47 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
48
Theodore Xu 38.1 49 **V-BOX Settings**
Leo Wei 2.1 50
51 |**Item**|**Settings**|**Note**
52 |Protocol|Mitsubishi FX3U/3G/3GA|
53 |Connection|RS422/RS485/RS232|
54 |Baud rate|9600~~115200|
55 |Data bit|7/8|
56 |Parity|EVEN/Odd/None|
57 |Stop bit|1/2|
58 |PLC station No.|1~~255|
59
Theodore Xu 38.1 60 **Address List**
Leo Wei 2.1 61
62 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
63 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
64 |Y|Y|Y o|0~~303237|
65 |M|M|M d|0~~99999|
66 |T|T|T d|0~~99999|
67 |C|C|C d|0~~99999|
68 |S|S|S d|0~~99999|
69 |SM|SM|SM d|8000~~9999|
70 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
71 |Y|Y|Y o|0~~303237|
72 |M|M|M d|0~~99999|
73 |T|T|T d|0~~99999|
74 |C|C|C d|0~~199|
75 |D|D|D d|0~~7999|
76 |S|S|S d|0~~99999|
77 |SD|SD|SD d|8000~~9999|
78
Theodore Xu 38.1 79 **Configure the communication protocol**
Leo Wei 2.1 80
Theodore Xu 38.1 81 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_4d2a4921240d23c6.png||alt="image-20220825102649-2.png" height="1009" width="1920"]]
Leo Wei 2.1 82
Theodore Xu 42.1 83 **PLC Setting**
Leo Wei 2.1 84
Theodore Xu 42.1 85 Open GX Works2, create a new PLC project or open the project that has been created.
86 Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK].
87
88 (% style="text-align:center" %)
89 [[image:1.2.png]]
90
91 PLC Default Parameters:
92 [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0
93 Note:The serial port parameters should be set depending on field requirements
94
95 PC and PLC connection:
96
97 [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK]
98
99 (% style="text-align:center" %)
100 [[image:1.5.1.png]]
101
102 Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.”
103
104 (% style="text-align:center" %)
105 [[image:1.5.2.png]]
106
107 **Cable Wiring**
108
Theodore Xu 38.1 109 **RS422**
Leo Wei 2.1 110
Theodore Xu 38.1 111 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e904556bb758dfe.png||alt="image-20220825103421-5.png" height="296" width="715"]]
Leo Wei 2.1 112
Theodore Xu 38.1 113 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]]
Leo Wei 2.1 114
Theodore Xu 43.1 115 == **FX NOPROTOCOL** ==
116
117 Mitsubishi FX3G-RS232-BD
118
119 **V-Box Settings**
120
121 |=**Item**|=**Settings**|=**Note**
122 |Protocol|Mitsubishi FX NOPROTOCOL|
123 |Connection|RS232|
124 |Baud rate|9600|
125 |Data bit|7|
126 |Parity|EVEN|
127 |Stop bit|1|
128 |PLC station No.|0|
129
130 (% style="text-align:center" %)
131 [[image:三菱 FN盒子通讯配置.png]]
132
133 **Address List**
134
135 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
136 |(% rowspan="8" %)Bit|X|X|X o|0~~303237|
137 |Y|Y|Y o|0~~303237|
138 |M|M|M d|0~~99999|
139 |T|T|T d|0~~99999|
140 |C|C|C d|0~~99999|
141 |S|S|S d|0~~99999|
142 |SM|SM|SM d|8000~~9999|
143 |Lamp|Lamp|Lamp d|0~~0|
144 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
145 |Y|Y|Y o|0~~303237|
146 |M|M|M d|0~~99999|
147 |T|T|T d|0~~99999|
148 |C|C|C d|0~~199|
149 |D|D|D d|0~~7999|
150 |S|S|S d|0~~99999|
151 |SD|SD|SD d|8000~~9999|
152
Theodore Xu 45.1 153 **Cable Wiring**
Theodore Xu 43.1 154
Theodore Xu 44.1 155 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png]]
156
Theodore Xu 41.1 157 == **FX3U Ethernet ** ==
Leo Wei 2.1 158
159 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
160
Theodore Xu 41.1 161 **V-BOX Settings**
Leo Wei 2.1 162
163 |Items|Settings|Note
164 |Protocol|Mitsubishi FX3U|
165 |Connection|Ethernet|
166 |Port No.|5009|Must be the same as the PLC setting
167 |PLC station No.|0|
168
Theodore Xu 41.1 169 **Address List**
Leo Wei 2.1 170
171 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
172 |(% rowspan="7" %)Bit|X|X|X OOO|0~~377|
173 |Y|Y|Y OOO|0~~377|
174 |M|M|M DDDD|0~~7679|
175 |SM|SM|SM DDDD|8000~~8511|
176 |S|S|S DDDD|0~~4095|
177 |TS|TS|TS DDD|0~~511|
178 |CS|CS|CS DDD|0~~255|
179 |(% rowspan="5" %)Word|CN|CN|CN DDD|0~~199|
180 |TN|TN|TN DDD|0~~511|
181 |D|D|D DDDD|0~~7999|
182 |SD|SD|SD DDDD|8000~~8511|
183 |R|R|R DDDDD|0~~32767|
184
Theodore Xu 41.1 185 **Ethernet Module Settings**
Leo Wei 2.1 186
187 FX3U-ENET-L module configuration
188 Set up the FX3U-ENET-L Ethernet module settings as follows.
189 Select the module location, which in this document is Module 0.
190
Theodore Xu 41.1 191 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_949d5d77c1d9cf1e.png||alt="image-20221116105850-1.png" height="573" width="706"]]
Leo Wei 2.1 192
193 Select "Operational setting" to enter the following screen.
194
195 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
196
Theodore Xu 41.1 197 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dfbfdd586c855c47.png||alt="image-20221116105947-1.png" height="573" width="706"]]
Leo Wei 2.1 198
199 Select "Open setting" to enter the setting interface, the settings are as follows.
200
201 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
202
203 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
204
Theodore Xu 41.1 205 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7c01ac15090fcc5b.png||alt="image-20221116110802-1.png" height="549" width="706"]]
Leo Wei 2.1 206
207 Click on "transter setup" - "PC side I/F setting", see the following figure.
208
209 After setting, the first download must use the programming cable, as shown in the figure; after that, can
210
211 use the IP set in the "Ethernet board" to communicate directly with the network cable.
212
Theodore Xu 41.1 213 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221116110832-2.png" height="423" width="708"]]
Leo Wei 2.1 214
215 Read and write data from the Ethernet module
216
Theodore Xu 41.1 217 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_690b3e57b29cfd4b.png||alt="image-20221116110907-3.png" height="549" width="706"]]
Leo Wei 2.1 218
219 Set "Transter setup" to COM communication, and read or write operation as shown below
220
Theodore Xu 41.1 221 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b317253742f7151.png||alt="image-20221116110917-4.png" height="549" width="706"]]
Leo Wei 2.1 222
Theodore Xu 41.1 223 **PLC Settings (GX Works 2)**
Leo Wei 2.1 224
225 Create a blank FX5U project
226
227 Find Current Connection in the navigation
228
Theodore Xu 41.1 229 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d2a46ba9c005cf38.png||alt="image-20221116111427-1.png" height="421" width="705"]]
Leo Wei 2.1 230
231 Select Connection Channel List
232
233 Select Ethernet board communication
234
Theodore Xu 41.1 235 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8f49721a3e5b0ef9.png||alt="image-20221116111451-2.png" height="421" width="705"]]
Leo Wei 2.1 236
237 Select Ethernet Module
238 Set the IP address of the PLC
239
Theodore Xu 41.1 240 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e9a9e29a46a1041.png||alt="image-20221116111509-3.png" height="666" width="699"]]
Leo Wei 2.1 241
242 Read or write PLC data, in this document is read
243
244 {{id name="Iimage-20221116111651-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e3d629103727a423.png||alt="image-20221116111651-4.png" height="416" width="697"]]
245
Theodore Xu 41.1 246 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7f29923ebcb670d1.png||alt="image-20221116111727-5.png" height="416" width="697"]]
Leo Wei 2.1 247
Theodore Xu 41.1 248 **Configure the communication protocol**
Leo Wei 2.1 249
Theodore Xu 41.1 250 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b2cdc33b6eb92b67.png||alt="image-20221119101946-2.png" height="395" width="695"]]
Leo Wei 2.1 251
Theodore Xu 46.1 252 == **FX5U Serial ** ==
Leo Wei 2.1 253
254 Mitsubishi FX5U series PLC
255
Theodore Xu 46.1 256 **V-BOX Settings**
Leo Wei 2.1 257
258 |**Item**|**Settings**|**Note**
259 |Protocol|Mitsubishi FX5U|
260 |Connection|RS422/RS485|
261 |Baud rate|9600|
262 |Data bit|7|
263 |Parity|Odd|
264 |Stop bit|1|
265 |PLC station No.|1~~255|Need to be the same as PLC settings
266
Theodore Xu 54.1 267 (% style="text-align:center" %)
268 [[image:三菱 FX5U 串口协议配置.png]]
269
Theodore Xu 46.1 270 **Address List**
Leo Wei 2.1 271
272 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
273 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
274 |Y|Y|Y o|0~~303237|
275 |M|M|M d|0~~99999|
276 |B|B|B h|0~~7FFF|
277 |F|F|F d|0~~32767|
278 |SB|SB|SB h|0~~7FFF|
279 |TS|TS|TS d|0~~1023|
280 |TC|TC|TC d|0~~1023|
281 |STS|STS|STS d|0~~1023|
282 |STC|STC|STS d|0~~1023|
283 |CS|CS|CS d|0~~1023|
284 |CC|CC|CC d|0~~1023|
285 |SM|SM|SM d|0~~9999|
286 |L|L|L d|0~~32767|
287 |S|S|S d|0~~4095|
288 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
289 |TN|TN|TN d|0~~1023|
290 |STN|STN|STN d|0~~1023|
291 |CN|CN|CN d|0~~1023|
292 |R|R|R d|0~~32767|
293 |SW|SW|SW h|0~~7FFF|
294 |Z|Z|Z d|0~~23|
295 |D|D|D d|0~~7999|
296 |SD|SD|SD d|0~~11999|
297
Theodore Xu 46.1 298 **PLC Settings (GX Works 3)**
Leo Wei 2.1 299
300 Create a blank FX5U project
301
302 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
303
Theodore Xu 46.1 304 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
Leo Wei 2.1 305
306 Select protocol in the setting item, and set parameters.
307
Theodore Xu 46.1 308 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
Leo Wei 2.1 309
310 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
311
Theodore Xu 46.1 312 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
Leo Wei 2.1 313
314 Click the [Apply] button to finish the setting.
315
316 Click download and select the items as below, then click [execute] to download the configuration to PLC.
317
Theodore Xu 46.1 318 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
Leo Wei 2.1 319
320 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
321
322 Done.
323
Theodore Xu 46.1 324 **Cable Wiring**
Leo Wei 2.1 325
Theodore Xu 46.1 326 **RS422**
Leo Wei 2.1 327
328 {{id name="Iimage-20220825105105-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d022c5ff4cf8c68e.png||alt="image-20220825105105-2.png" height="288" width="711"]]
329
330 {{id name="Iimage-20220825105533-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50e173394c73f154.png||alt="image-20220825105533-3.png" height="246" width="420"]]
331
Theodore Xu 33.1 332 == **FX5U Ethernet ** ==
Leo Wei 2.1 333
334 Mitsubishi FX5U series PLC
335
336 **1)V-BOX Settings**
337
338 |**Items**|**Settings**|**Note**
339 |Protocol|Mitsubishi FX5U|
340 |Connection|Ethernet|
341 |Port No.|5002|Must be the same as the PLC setting
342 |PLC station No.|0|
343
344 **2)Address List**
345
346 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
347 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
348 |Y|Y|Y o|0~~303237|
349 |M|M|M d|0~~99999|
350 |B|B|B h|0~~7FFF|
351 |F|F|F d|0~~32767|
352 |SB|SB|SB h|0~~7FFF|
353 |TS|TS|TS d|0~~1023|
354 |TC|TC|TC d|0~~1023|
355 |STS|STS|STS d|0~~1023|
356 |STC|STC|STS d|0~~1023|
357 |CS|CS|CS d|0~~1023|
358 |CC|CC|CC d|0~~1023|
359 |SM|SM|SM d|0~~9999|
360 |L|L|L d|0~~32767|
361 |S|S|S d|0~~4095|
362 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
363 |TN|TN|TN d|0~~1023|
364 |STN|STN|STN d|0~~1023|
365 |CN|CN|CN d|0~~1023|
366 |R|R|R d|0~~32767|
367 |SW|SW|SW h|0~~7FFF|
368 |Z|Z|Z d|0~~23|
369 |D|D|D d|0~~7999|
370 |SD|SD|SD d|0~~11999|
371
372 **3)PLC Settings (GX Works 3)**
373
374 Find the [Ethernet port] in the navigation area.
375
376 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_8e8f85ace087346c.png3Fwidth3D30026height3D59326rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
377
378 Select [Own Node Settings] in the [Setting Item List];
379
380 Set [IP Address], [Subnet Mask], [Default Gateway];
381
382 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
383
384 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_5d98495052c8c10e.png3Fwidth3D60026height3D33926rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
385
386 Select [SLMP Connection Module] and add into host station as below picture shows;
387
388 Set Port number as 5002 (this is necessary settings);
389
390 Click [Close with Reflecting the Setting] to save and close window;
391
392 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_14b489fdc6c6589d.png3Fwidth3D60026height3D35026rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
393
394 Click [Apply] to completed Etherenet settings;
395
396 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
397
398 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FPIStudio2F12.PLC2520protocols2FWebHome2F12.PLC2520Protocol_html_c93025a968a8a9e7.png3Fwidth3D60026height3D43426rev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
399
400 **4)Configure the communication protocol**
401
402 {{id name="Iimage-20220825112403-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_caa9bf4d8cc6de0f.png||alt="图片-20220825112403-1.png" height="1033" width="1920"]]
403
404 **5)Cable Wiring**
405
Theodore Xu 33.1 406 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
Leo Wei 2.1 407
Theodore Xu 47.1 408 == **L02 Serial ** ==
Leo Wei 2.1 409
410 Mitsubishi L02 series CPU built-in serial port.
411
Theodore Xu 47.1 412 **V-BOX Settings**
Leo Wei 2.1 413
414 |**Item**|**Settings**|**Note**
415 |Protocol|Mitsubishi L02|
416 |Connection|RS422|
417 |Baud rate|115200|
418 |Data bit|8|
419 |Parity|Odd|
420 |Stop bit|1|
421 |PLC station No.|1~~255|Need to be the same as PLC settings
422
Theodore Xu 53.1 423 (% style="text-align:center" %)
424 [[image:三菱 L02串口协议配置.png]]
425
Theodore Xu 47.1 426 **Address List**
Leo Wei 2.1 427
428 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
Theodore Xu 47.1 429 |(% colspan="1" rowspan="20" %)Bit
430 |X|X|X h|0~~FFFF|
431 |Y|Y|Y h|0~~FFFF|
432 |M|M|M d|0~~9999|
433 |L|L|L d|0~~9999|
434 |F|F|F d|0~~9999|
435 |B|B|B h|0~~FFFF|
436 |V|V|V d|0~~2047|
437 |TC|TC|TC d|0~~9999|
438 |SS|SS|SS d|0~~9999|
439 |SC|SC|SC d|0~~9999|
440 |CS|CS|CS d|0~~9999|
441 |CC|CC|CC d|0~~9999|
442 |SB|SB|SB h|0~~FFFF|
443 |SM|SM|SM d|0~~2047|
444 |STS|STS|STS d|0~~1023|
445 |S|S|S d|0~~9999|
446 |DX|DX|DX h|0~~FFFF|
447 |DY|DY|DY h|0~~FFFF|
448 |TS|TS|TS d|0~~9999|
449 |Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
450 |(% colspan="1" rowspan="9" %)Word
451 |W|W|W h|0~~FFFF|
452 |TN|TN|TN d|0~~99999|
453 |SN|SN|SN d|0~~99999|
454 |CN|CN|CN d|0~~99999|
455 |R|R|R d|0~~99999|
456 |SW|SW|SW h|0~~FFFF|
457 |Z|Z|Z d|0~~99999|
458 |ZR|ZR|ZR h|0~~FFFF|
459 |D|D|D d|0~~99999|
Leo Wei 2.1 460
Theodore Xu 47.1 461 **Cable Wiring**
Leo Wei 2.1 462
Theodore Xu 47.1 463 **RS422**
Leo Wei 2.1 464
Theodore Xu 47.1 465 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_90e38f152d639809.png||alt="image-20220825161612-8.png" height="278" width="612"]]
Leo Wei 2.1 466
Theodore Xu 47.1 467 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d301e675d8224725.png||alt="image-20220825160820-4.png" height="208" width="359"]]
Leo Wei 2.1 468
Theodore Xu 48.1 469 == **L02 Ethernet ** ==
Leo Wei 2.1 470
471 Mitsubishi L series CPU built-in Ethernet port.
472
Theodore Xu 48.1 473 **V-BOX Settings**
Leo Wei 2.1 474
475 |**Items**|**Settings**|**Note**
476 |Protocol|MIT L02 CPU MELSEC|
477 |Connection|Ethernet|
478 |Port No.|1025|Must be the same as the PLC setting
479 |PLC station No.|0|Must be the same as the PLC setting
480
Theodore Xu 52.1 481 (% style="text-align:center" %)
482 [[image:三菱 L02以太网协议配置1.png]]
Theodore Xu 51.1 483
Theodore Xu 48.1 484 **PLC Settings (GX Works2 )**
Leo Wei 2.1 485
486 Create a project
487
488 Set PLC IP, subnet mask and gateway;
489
490 Select [Binary Code] as communication data code;
491
Theodore Xu 49.1 492 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
Leo Wei 2.1 493
494 Set PLC port number, for example 1025
495
Theodore Xu 49.1 496 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
Leo Wei 2.1 497
498 Save settings;
499
500 Download project into PLC device;
501
502 Restart PLC device;
503
Theodore Xu 49.1 504 **Cable Wiring**
Leo Wei 2.1 505
Theodore Xu 49.1 506 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
Leo Wei 2.1 507
508 == {{id name="HQ12HSerial"/}}**Q12H Serial ** ==
509
510 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
511
512 **[[Download link>>url:https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]**
513
Theodore Xu 32.1 514 == **QJ71E71 Ethernet ** ==
Leo Wei 2.1 515
516 Mitsubishi QJ71E71 Ethernet communication module;
517
Theodore Xu 50.1 518 **V-BOX Settings**
Leo Wei 2.1 519
520 |**Items**|**Settings**|**Note**
521 |Protocol|MIT QJ71E71 MELSEC|
522 |Connection|Ethernet|
523 |Port No.|1025|Must be the same as the PLC setting
524 |PLC station No.|0|Must be the same as the PLC setting
525
Theodore Xu 50.1 526 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50990385ef491b9e.png||alt="image-20221119171832-5.png" height="354" width="625"]]
Leo Wei 2.1 527
Theodore Xu 50.1 528 **Address List**
529
Leo Wei 2.1 530 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
531 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
532 |Y|Y|Y h|0~~1FFF|
533 |M|M|M d|0~~99999|
534 |L|L|L d|0~~8191|
535 |F|F|F d|0~~2047|
536 |B|B|B h|0~~1FFF|
537 |V|V|V d|0~~2047|
538 |TS|TS|TS d|0~~2047|
539 |TC|TC|TC d|0~~2047|
540 |SS|SS|SS d|0~~2047|
541 |SC|SC|SC d|0~~2047|
542 |CS|CS|CS d|0~~1023|
543 |CC|CC|CC d|0~~1023|
544 |SB|SB|SB h|0~~7FF|
545 |S|S|S d|0~~8191|
546 |DX|DX|DX h|0~~1FFF|
547 |DY|DY|DY h|0~~1FFF|
548 |SM|SM|SM d|8000~~9999|
549 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
550 |D|D|D d|0~~12287|
551 |W|W|W h|0~~1FFF|
552 |TN|TN|TN d|0~~2047|
553 |SN|SN|SN d|0~~2047|
554 |CN|CN|CN d|0~~1023|
555 |R|R|R d|0~~32767|
556 |SW|SW|SW h|0~~7FF|
557 |Z|Z|Z d|0~~15|
558 |ZR|ZR|ZR h|0~~FE7FF|
559
Theodore Xu 50.1 560 **PLC Settings(GX Works2)**
Leo Wei 2.1 561
562 * Click [Ethernet/CC IE/MELSECNET];
563 * Please select [Ethernet] as network type;
564 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
565 * Select [Online] as Mode;
Theodore Xu 50.1 566 * [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d54f23688c520f78.png||alt="image-20221119171343-2.png" height="341" width="587"]]
Leo Wei 2.1 567 * Click [Operation setting] to set IP;
568 * Select [Binary Code] as [Communication Data Code];
Theodore Xu 50.1 569 * [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ce8e6a671b9508e0.png||alt="image-20221119171436-3.png" height="354" width="588"]]
Leo Wei 2.1 570 * Click [Open setting]
571 * Set protocol: TCP;
572 * Set [unpassive] in [Open system];
573 * Set [receive] in [Fixed buffer];
574 * Set [procedure Exist] in [Fixed buffer communication];
575 * Disable [Pairing open];
576 * Set [No confirm] in [Existence confirmation];
577 * Host station port number: 5009;
578 * Save settings;
579 * {{id name="Iimage-20221119171611-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1d8e2f4fb7c72471.png||alt="image-20221119171611-4.png" height="354" width="588"]]
580 * Download project into PLC and restart it
581
Theodore Xu 50.1 582 **Cable Wiring**