Wiki source code of Mitsubishi

Version 74.1 by Theodore Xu on 2023/09/15 11:57

Show last authors
1 == **FX3U,3G,3GA Serial ** ==
2
3 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
4
5 **V-BOX Settings**
6
7 |**Item**|**Settings**|**Note**
8 |Protocol|Mitsubishi FX3U/3G/3GA|
9 |Connection|RS422/RS485/RS232|
10 |Baud rate|9600~~115200|
11 |Data bit|7/8|
12 |Parity|EVEN/Odd/None|
13 |Stop bit|1/2|
14 |PLC station No.|1~~255|
15
16 (% style="text-align:center" %)
17 [[image:三菱 FX3U 串口协议配置.png]]
18
19 **Address List**
20
21 |**Type**|**Device registers**|**Format**|**Range**|**Note**
22 |(% rowspan="7" %)Bit|X|Xo|0~~303237|
23 |Y|Y o|0~~303237|
24 |M|M d|0~~99999|
25 |T|T d|0~~99999|
26 |C|C d|0~~99999|
27 |S|S d|0~~99999|
28 |SM|SM d|8000~~9999|
29 |(% rowspan="8" %)Word|X|Xo|0~~303237|
30 |Y|Y o|0~~303237|
31 |M|M d|0~~99999|
32 |T|T d|0~~99999|
33 |C|C d|0~~199|
34 |D|D d|0~~7999|
35 |S|S d|0~~99999|
36 |SD|SD d|8000~~9999|
37
38 **PLC Setting**
39
40 Open GX Works2, create a new PLC project or open the project that has been created.
41 Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK].
42
43 (% style="text-align:center" %)
44 [[image:1.2.png]]
45
46 PLC Default Parameters:
47 [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0
48 Note:The serial port parameters should be set depending on field requirements
49
50 PC and PLC connection:
51
52 [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK]
53
54 (% style="text-align:center" %)
55 [[image:1.5.1.png]]
56
57 Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.”
58
59 (% style="text-align:center" %)
60 [[image:1.5.2.png]]
61
62 **Cable Wiring**
63
64 **RS422**
65
66 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e904556bb758dfe.png||alt="image-20220825103421-5.png" height="296" width="715"]]
67
68 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]]
69
70 == **FX NOPROTOCOL** ==
71
72 Mitsubishi FX3G-RS232-BD
73
74 **V-Box Settings**
75
76 |=**Item**|=**Settings**|=**Note**
77 |Protocol|Mitsubishi FX NOPROTOCOL|
78 |Connection|RS232|
79 |Baud rate|9600|
80 |Data bit|7|
81 |Parity|EVEN|
82 |Stop bit|1|
83 |PLC station No.|0|
84
85 (% style="text-align:center" %)
86 [[image:三菱 FN盒子通讯配置.png]]
87
88 **Address List**
89
90 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
91 |(% rowspan="8" %)Bit|X|X o|0~~303237|
92 |Y|Y o|0~~303237|
93 |M|M d|0~~99999|
94 |T|T d|0~~99999|
95 |C|C d|0~~99999|
96 |S|S d|0~~99999|
97 |SM|SM d|8000~~9999|
98 |Lamp|Lamp d|0~~0|
99 |(% rowspan="8" %)Word|X|X o|0~~303237|
100 |Y|Y o|0~~303237|
101 |M|M d|0~~99999|
102 |T|T d|0~~99999|
103 |C|C d|0~~199|
104 |D|D d|0~~7999|
105 |S|S d|0~~99999|
106 |SD|SD d|8000~~9999|
107
108 **Cable Wiring**
109
110 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png]]
111
112 == **FX3U Ethernet ** ==
113
114 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
115
116 **V-BOX Settings**
117
118 |Items|Settings|Note
119 |Protocol|Mitsubishi FX3U|
120 |Connection|Ethernet|
121 |Port No.|5009|Must be the same as the PLC setting
122 |PLC station No.|0|
123
124 (% style="text-align:center" %)
125 [[image:三菱 FX3U 以太网协议配置.png]]
126
127 **Address List**
128
129 |**Type**|**Device registers**|**Format**|**Range**|**Note**
130 |(% rowspan="7" %)Bit|X|X OOO|0~~377|
131 |Y|Y OOO|0~~377|
132 |M|M DDDD|0~~7679|
133 |SM|SM DDDD|8000~~8511|
134 |S|S DDDD|0~~4095|
135 |TS|TS DDD|0~~511|
136 |CS|CS DDD|0~~255|
137 |(% rowspan="5" %)Word|CN|CN DDD|0~~199|
138 |TN|TN DDD|0~~511|
139 |D|D DDDD|0~~7999|
140 |SD|SD DDDD|8000~~8511|
141 |R|R DDDDD|0~~32767|
142
143 **Ethernet Module Settings**
144
145 FX3U-ENET-L module configuration
146 Set up the FX3U-ENET-L Ethernet module settings as follows.
147 Select the module location, which in this document is Module 0.
148
149 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_949d5d77c1d9cf1e.png||alt="image-20221116105850-1.png" height="573" width="706"]]
150
151 Select "Operational setting" to enter the following screen.
152
153 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
154
155 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_dfbfdd586c855c47.png||alt="image-20221116105947-1.png" height="573" width="706"]]
156
157 Select "Open setting" to enter the setting interface, the settings are as follows.
158
159 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
160
161 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
162
163 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7c01ac15090fcc5b.png||alt="image-20221116110802-1.png" height="549" width="706"]]
164
165 Click on "transter setup" - "PC side I/F setting", see the following figure.
166
167 After setting, the first download must use the programming cable, as shown in the figure; after that, can
168
169 use the IP set in the "Ethernet board" to communicate directly with the network cable.
170
171 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221116110832-2.png" height="423" width="708"]]
172
173 Read and write data from the Ethernet module
174
175 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_690b3e57b29cfd4b.png||alt="image-20221116110907-3.png" height="549" width="706"]]
176
177 Set "Transter setup" to COM communication, and read or write operation as shown below
178
179 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b317253742f7151.png||alt="image-20221116110917-4.png" height="549" width="706"]]
180
181 **PLC Settings (GX Works 2)**
182
183 Create a blank FX5U project
184
185 Find Current Connection in the navigation
186
187 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d2a46ba9c005cf38.png||alt="image-20221116111427-1.png" height="421" width="705"]]
188
189 Select Connection Channel List
190
191 Select Ethernet board communication
192
193 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8f49721a3e5b0ef9.png||alt="image-20221116111451-2.png" height="421" width="705"]]
194
195 Select Ethernet Module
196 Set the IP address of the PLC
197
198 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e9a9e29a46a1041.png||alt="image-20221116111509-3.png" height="666" width="699"]]
199
200 Read or write PLC data, in this document is read
201
202 {{id name="Iimage-20221116111651-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e3d629103727a423.png||alt="image-20221116111651-4.png" height="416" width="697"]]
203
204 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7f29923ebcb670d1.png||alt="image-20221116111727-5.png" height="416" width="697"]]
205
206 == **FX5U Serial ** ==
207
208 Mitsubishi FX5U series PLC
209
210 **V-BOX Settings**
211
212 |**Item**|**Settings**|**Note**
213 |Protocol|Mitsubishi FX5U|
214 |Connection|RS422/RS485|
215 |Baud rate|9600|
216 |Data bit|7|
217 |Parity|Odd|
218 |Stop bit|1|
219 |PLC station No.|1~~255|Need to be the same as PLC settings
220
221 (% style="text-align:center" %)
222 [[image:三菱 FX5U 串口协议配置.png]]
223
224 **Address List**
225
226 |**Type**|**Device registers**|**Format**|**Range**|**Note**
227 |(% rowspan="15" %)Bit|X|X o|0~~303237|
228 |Y|Y o|0~~303237|
229 |M|M d|0~~99999|
230 |B|B h|0~~7FFF|
231 |F|F d|0~~32767|
232 |SB|SB h|0~~7FFF|
233 |TS|TS d|0~~1023|
234 |TC|TC d|0~~1023|
235 |STS|STS d|0~~1023|
236 |STC|STS d|0~~1023|
237 |CS|CS d|0~~1023|
238 |CC|CC d|0~~1023|
239 |SM|SM d|0~~9999|
240 |L|L d|0~~32767|
241 |S|S d|0~~4095|
242 |(% rowspan="9" %)Word|W|W h|0~~3FF|
243 |TN|TN d|0~~1023|
244 |STN|STN d|0~~1023|
245 |CN|CN d|0~~1023|
246 |R|R d|0~~32767|
247 |SW|SW h|0~~7FFF|
248 |Z|Z d|0~~23|
249 |D|D d|0~~7999|
250 |SD|SD d|0~~11999|
251
252 **PLC Settings (GX Works 3)**
253
254 Create a blank FX5U project
255
256 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
257
258 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
259
260 Select protocol in the setting item, and set parameters.
261
262 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
263
264 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
265
266 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
267
268 Click the [Apply] button to finish the setting.
269
270 Click download and select the items as below, then click [execute] to download the configuration to PLC.
271
272 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
273
274 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
275
276 Done.
277
278 **Cable Wiring**
279
280 **RS422**
281
282 {{id name="Iimage-20220825105105-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d022c5ff4cf8c68e.png||alt="image-20220825105105-2.png" height="288" width="711"]]
283
284 {{id name="Iimage-20220825105533-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50e173394c73f154.png||alt="image-20220825105533-3.png" height="246" width="420"]]
285
286 == **FX5U Ethernet ** ==
287
288 Mitsubishi FX5U series PLC
289
290 **V-BOX Settings**
291
292 |**Items**|**Settings**|**Note**
293 |Protocol|Mitsubishi FX5U|
294 |Connection|Ethernet|
295 |Port No.|5002|Must be the same as the PLC setting
296 |PLC station No.|0|
297
298 (% style="text-align:center" %)
299 [[image:三菱 FX5U 以太网协议配置.png]]
300
301 **Address List**
302
303 |**Type**|**Device registers**|**Format**|**Range**|**Note**
304 |(% rowspan="15" %)Bit|X|X o|0~~303237|
305 |Y|Y o|0~~303237|
306 |M|M d|0~~99999|
307 |B|B h|0~~7FFF|
308 |F|F d|0~~32767|
309 |SB|SB h|0~~7FFF|
310 |TS|TS d|0~~1023|
311 |TC|TC d|0~~1023|
312 |STS|STS d|0~~1023|
313 |STC|STS d|0~~1023|
314 |CS|CS d|0~~1023|
315 |CC|CC d|0~~1023|
316 |SM|SM d|0~~9999|
317 |L|L d|0~~32767|
318 |S|S d|0~~4095|
319 |(% rowspan="9" %)Word|W|W h|0~~3FF|
320 |TN|TN d|0~~1023|
321 |STN|STN d|0~~1023|
322 |CN|CN d|0~~1023|
323 |R|R d|0~~32767|
324 |SW|SW h|0~~7FFF|
325 |Z|Z d|0~~23|
326 |D|D d|0~~7999|
327 |SD|SD d|0~~11999|
328
329 **PLC Settings (GX Works 3)**
330
331 Find the [Ethernet port] in the navigation area.
332
333 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
334
335 Select [Own Node Settings] in the [Setting Item List];
336
337 Set [IP Address], [Subnet Mask], [Default Gateway];
338
339 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
340
341 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
342
343 Select [SLMP Connection Module] and add into host station as below picture shows;
344
345 Set Port number as 5002 (this is necessary settings);
346
347 Click [Close with Reflecting the Setting] to save and close window;
348
349 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
350
351 Click [Apply] to completed Etherenet settings;
352
353 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
354
355 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
356
357
358 **Cable Wiring**
359
360 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
361
362 == **L02 Serial ** ==
363
364 Mitsubishi L02 series CPU built-in serial port.
365
366 **V-BOX Settings**
367
368 |**Item**|**Settings**|**Note**
369 |Protocol|Mitsubishi L02|
370 |Connection|RS422|
371 |Baud rate|115200|
372 |Data bit|8|
373 |Parity|Odd|
374 |Stop bit|1|
375 |PLC station No.|1~~255|Need to be the same as PLC settings
376
377 (% style="text-align:center" %)
378 [[image:三菱 L02串口协议配置.png]]
379
380 **Address List**
381
382 |**Type**|**Device registers**|**Format**|**Range**|**Note**
383 |(% colspan="1" rowspan="20" %)Bit
384 |X|X h|0~~FFFF|
385 |Y|Y h|0~~FFFF|
386 |M|M d|0~~9999|
387 |L|L d|0~~9999|
388 |F|F d|0~~9999|
389 |B|B h|0~~FFFF|
390 |V|V d|0~~2047|
391 |TC|TC d|0~~9999|
392 |SS|SS d|0~~9999|
393 |SC|SC d|0~~9999|
394 |CS|CS d|0~~9999|
395 |CC|CC d|0~~9999|
396 |SB|SB h|0~~FFFF|
397 |SM|SM d|0~~2047|
398 |STS|STS d|0~~1023|
399 |S|S d|0~~9999|
400 |DX|DX h|0~~FFFF|
401 |DY|DY h|0~~FFFF|
402 |TS|TS d|0~~9999|
403 |Dbit|Dbit d.d|0~~99999.0~~15|
404 |(% colspan="1" rowspan="9" %)Word
405 |W|W h|0~~FFFF|
406 |TN|TN d|0~~99999|
407 |SN|SN d|0~~99999|
408 |CN|CN d|0~~99999|
409 |R|R d|0~~99999|
410 |SW|SW h|0~~FFFF|
411 |Z|Z d|0~~99999|
412 |ZR|ZR h|0~~FFFF|
413 |D|D d|0~~99999|
414
415 **Cable Wiring**
416
417 **RS422**
418
419 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_90e38f152d639809.png||alt="image-20220825161612-8.png" height="278" width="612"]]
420
421 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d301e675d8224725.png||alt="image-20220825160820-4.png" height="208" width="359"]]
422
423 == **L02 Ethernet ** ==
424
425 Mitsubishi L series CPU built-in Ethernet port.
426
427 **V-BOX Settings**
428
429 |**Items**|**Settings**|**Note**
430 |Protocol|MIT L02 CPU MELSEC|
431 |Connection|Ethernet|
432 |Port No.|1025|Must be the same as the PLC setting
433 |PLC station No.|0|Must be the same as the PLC setting
434
435 (% style="text-align:center" %)
436 [[image:三菱 L02以太网协议配置1.png]]
437
438 **PLC Settings (GX Works2 )**
439
440 Create a project
441
442 Set PLC IP, subnet mask and gateway;
443
444 Select [Binary Code] as communication data code;
445
446 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
447
448 Set PLC port number, for example 1025
449
450 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
451
452 Save settings;
453
454 Download project into PLC device;
455
456 Restart PLC device;
457
458 **Cable Wiring**
459
460 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
461
462 == {{id name="HQ12HSerial"/}}**Q12H Serial ** ==
463
464 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
465
466 **[[Download link>>url:https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]**
467
468 == **QJ71E71 Ethernet ** ==
469
470 Mitsubishi QJ71E71 Ethernet communication module;
471
472 **V-BOX Settings**
473
474 |**Items**|**Settings**|**Note**
475 |Protocol|MIT QJ71E71 MELSEC|
476 |Connection|Ethernet|
477 |Port No.|1025|Must be the same as the PLC setting
478 |PLC station No.|0|Must be the same as the PLC setting
479
480 (% style="text-align:center" %)
481 [[image:三菱 QJ71 以太网协议配置.png]]
482
483 **Address List**
484
485 |**Type**|**Device registers**|**Format**|**Range**|**Note**
486 |(% rowspan="18" %)Bit|X|X h|0~~1FFF|
487 |Y|Y h|0~~1FFF|
488 |M|M d|0~~99999|
489 |L|L d|0~~8191|
490 |F|F d|0~~2047|
491 |B|B h|0~~1FFF|
492 |V|V d|0~~2047|
493 |TS|TS d|0~~2047|
494 |TC|TC d|0~~2047|
495 |SS|SS d|0~~2047|
496 |SC|SC d|0~~2047|
497 |CS|CS d|0~~1023|
498 |CC|CC d|0~~1023|
499 |SB|SB h|0~~7FF|
500 |S|S d|0~~8191|
501 |DX|DX h|0~~1FFF|
502 |DY|DY h|0~~1FFF|
503 |SM|SM d|8000~~9999|
504 |(% rowspan="10" %)Word|SD|SD d|0~~2047|
505 |D|D d|0~~12287|
506 |W|W h|0~~1FFF|
507 |TN|TN d|0~~2047|
508 |SN|SN d|0~~2047|
509 |CN|CN d|0~~1023|
510 |R|R d|0~~32767|
511 |SW|SW h|0~~7FF|
512 |Z|Z d|0~~15|
513 |ZR|ZR h|0~~FE7FF|
514
515 **PLC Settings(GX Works2)**
516
517 * Click [Ethernet/CC IE/MELSECNET];
518 * Please select [Ethernet] as network type;
519 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
520 * Select [Online] as Mode;
521 * [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d54f23688c520f78.png||alt="image-20221119171343-2.png" height="341" width="587"]]
522 * Click [Operation setting] to set IP;
523 * Select [Binary Code] as [Communication Data Code];
524 * [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ce8e6a671b9508e0.png||alt="image-20221119171436-3.png" height="354" width="588"]]
525 * Click [Open setting]
526 * Set protocol: TCP;
527 * Set [unpassive] in [Open system];
528 * Set [receive] in [Fixed buffer];
529 * Set [procedure Exist] in [Fixed buffer communication];
530 * Disable [Pairing open];
531 * Set [No confirm] in [Existence confirmation];
532 * Host station port number: 5009;
533 * Save settings;
534 * {{id name="Iimage-20221119171611-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1d8e2f4fb7c72471.png||alt="image-20221119171611-4.png" height="354" width="588"]]
535 * Download project into PLC and restart it
536