Wiki source code of Mitsubishi
Last modified by Joe on 2024/05/21 10:53
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
40.1 | 1 | == **FX3U,3G,3GA Serial ** == |
![]() |
2.1 | 2 | |
3 | Supported Series: Mitsubishi FX3U, FX3G, FX3GA series | ||
4 | |||
![]() |
38.1 | 5 | **V-BOX Settings** |
![]() |
2.1 | 6 | |
7 | |**Item**|**Settings**|**Note** | ||
8 | |Protocol|Mitsubishi FX3U/3G/3GA| | ||
9 | |Connection|RS422/RS485/RS232| | ||
10 | |Baud rate|9600~~115200| | ||
11 | |Data bit|7/8| | ||
12 | |Parity|EVEN/Odd/None| | ||
13 | |Stop bit|1/2| | ||
14 | |PLC station No.|1~~255| | ||
15 | |||
![]() |
58.1 | 16 | (% style="text-align:center" %) |
17 | [[image:三菱 FX3U 串口协议配置.png]] | ||
18 | |||
![]() |
38.1 | 19 | **Address List** |
![]() |
2.1 | 20 | |
![]() |
67.1 | 21 | |**Type**|**Device registers**|**Format**|**Range**|**Note** |
![]() |
83.16 | 22 | |(% rowspan="7" %)Bit|X|X o|0~~303237| |
![]() |
67.1 | 23 | |Y|Y o|0~~303237| |
24 | |M|M d|0~~99999| | ||
25 | |T|T d|0~~99999| | ||
26 | |C|C d|0~~99999| | ||
27 | |S|S d|0~~99999| | ||
28 | |SM|SM d|8000~~9999| | ||
![]() |
83.16 | 29 | |(% rowspan="8" %)Word|X|X o|0~~303237| |
![]() |
67.1 | 30 | |Y|Y o|0~~303237| |
31 | |M|M d|0~~99999| | ||
32 | |T|T d|0~~99999| | ||
33 | |C|C d|0~~199| | ||
34 | |D|D d|0~~7999| | ||
35 | |S|S d|0~~99999| | ||
36 | |SD|SD d|8000~~9999| | ||
![]() |
2.1 | 37 | |
![]() |
42.1 | 38 | **PLC Setting** |
![]() |
2.1 | 39 | |
![]() |
42.1 | 40 | Open GX Works2, create a new PLC project or open the project that has been created. |
41 | Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK]. | ||
42 | |||
43 | (% style="text-align:center" %) | ||
![]() |
77.1 | 44 | [[image:GX2.png]] |
45 | |||
46 | (% style="text-align:center" %) | ||
![]() |
42.1 | 47 | [[image:1.2.png]] |
48 | |||
49 | PLC Default Parameters: | ||
50 | [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0 | ||
51 | Note:The serial port parameters should be set depending on field requirements | ||
52 | |||
53 | PC and PLC connection: | ||
54 | |||
55 | [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK] | ||
56 | |||
57 | (% style="text-align:center" %) | ||
58 | [[image:1.5.1.png]] | ||
59 | |||
60 | Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.” | ||
61 | |||
62 | (% style="text-align:center" %) | ||
63 | [[image:1.5.2.png]] | ||
64 | |||
![]() |
77.1 | 65 | [PLC]→[Write to PLC]→[Online operation]→[Param+program]→[Execute]→[OK] |
66 | |||
67 | (% style="text-align:center" %) | ||
![]() |
78.1 | 68 | [[image:FX3U串口下载.png]] |
![]() |
77.1 | 69 | |
![]() |
42.1 | 70 | **Cable Wiring** |
71 | |||
![]() |
38.1 | 72 | **RS422** |
![]() |
2.1 | 73 | |
![]() |
38.1 | 74 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e904556bb758dfe.png||alt="image-20220825103421-5.png" height="296" width="715"]] |
![]() |
2.1 | 75 | |
![]() |
38.1 | 76 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_860bcf87f6ca7b98.png||alt="image-20220825100845-4.png" height="246" width="419"]] |
![]() |
2.1 | 77 | |
![]() |
43.1 | 78 | == **FX NOPROTOCOL** == |
79 | |||
80 | Mitsubishi FX3G-RS232-BD | ||
81 | |||
82 | **V-Box Settings** | ||
83 | |||
84 | |=**Item**|=**Settings**|=**Note** | ||
85 | |Protocol|Mitsubishi FX NOPROTOCOL| | ||
86 | |Connection|RS232| | ||
87 | |Baud rate|9600| | ||
88 | |Data bit|7| | ||
89 | |Parity|EVEN| | ||
90 | |Stop bit|1| | ||
91 | |PLC station No.|0| | ||
92 | |||
93 | (% style="text-align:center" %) | ||
94 | [[image:三菱 FN盒子通讯配置.png]] | ||
95 | |||
96 | **Address List** | ||
97 | |||
![]() |
68.1 | 98 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** |
99 | |(% rowspan="8" %)Bit|X|X o|0~~303237| | ||
100 | |Y|Y o|0~~303237| | ||
101 | |M|M d|0~~99999| | ||
102 | |T|T d|0~~99999| | ||
103 | |C|C d|0~~99999| | ||
104 | |S|S d|0~~99999| | ||
105 | |SM|SM d|8000~~9999| | ||
106 | |Lamp|Lamp d|0~~0| | ||
107 | |(% rowspan="8" %)Word|X|X o|0~~303237| | ||
108 | |Y|Y o|0~~303237| | ||
109 | |M|M d|0~~99999| | ||
110 | |T|T d|0~~99999| | ||
111 | |C|C d|0~~199| | ||
112 | |D|D d|0~~7999| | ||
113 | |S|S d|0~~99999| | ||
114 | |SD|SD d|8000~~9999| | ||
![]() |
43.1 | 115 | |
![]() |
45.1 | 116 | **Cable Wiring** |
![]() |
43.1 | 117 | |
![]() |
44.1 | 118 | [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png]] |
119 | |||
![]() |
41.1 | 120 | == **FX3U Ethernet ** == |
![]() |
2.1 | 121 | |
122 | Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L | ||
123 | |||
![]() |
41.1 | 124 | **V-BOX Settings** |
![]() |
2.1 | 125 | |
126 | |Items|Settings|Note | ||
127 | |Protocol|Mitsubishi FX3U| | ||
128 | |Connection|Ethernet| | ||
129 | |Port No.|5009|Must be the same as the PLC setting | ||
130 | |PLC station No.|0| | ||
131 | |||
![]() |
60.1 | 132 | (% style="text-align:center" %) |
133 | [[image:三菱 FX3U 以太网协议配置.png]] | ||
![]() |
57.1 | 134 | |
![]() |
41.1 | 135 | **Address List** |
![]() |
2.1 | 136 | |
![]() |
69.1 | 137 | |**Type**|**Device registers**|**Format**|**Range**|**Note** |
138 | |(% rowspan="7" %)Bit|X|X OOO|0~~377| | ||
139 | |Y|Y OOO|0~~377| | ||
140 | |M|M DDDD|0~~7679| | ||
141 | |SM|SM DDDD|8000~~8511| | ||
142 | |S|S DDDD|0~~4095| | ||
143 | |TS|TS DDD|0~~511| | ||
144 | |CS|CS DDD|0~~255| | ||
145 | |(% rowspan="5" %)Word|CN|CN DDD|0~~199| | ||
146 | |TN|TN DDD|0~~511| | ||
147 | |D|D DDDD|0~~7999| | ||
148 | |SD|SD DDDD|8000~~8511| | ||
149 | |R|R DDDDD|0~~32767| | ||
![]() |
2.1 | 150 | |
![]() |
41.1 | 151 | **Ethernet Module Settings** |
![]() |
2.1 | 152 | |
153 | FX3U-ENET-L module configuration | ||
154 | Set up the FX3U-ENET-L Ethernet module settings as follows. | ||
155 | Select the module location, which in this document is Module 0. | ||
156 | |||
![]() |
41.1 | 157 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_949d5d77c1d9cf1e.png||alt="image-20221116105850-1.png" height="573" width="706"]] |
![]() |
2.1 | 158 | |
159 | Select "Operational setting" to enter the following screen. | ||
160 | |||
161 | The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default. | ||
![]() |
86.2 | 162 | |
![]() |
2.1 | 163 | |
![]() |
83.18 | 164 | (% style="text-align:center" %) |
![]() |
86.2 | 165 | [[image:Inku25HyY8.png]] |
![]() |
2.1 | 166 | |
167 | Select "Open setting" to enter the setting interface, the settings are as follows. | ||
168 | |||
169 | The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the | ||
170 | |||
171 | Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module. | ||
172 | |||
![]() |
41.1 | 173 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7c01ac15090fcc5b.png||alt="image-20221116110802-1.png" height="549" width="706"]] |
![]() |
2.1 | 174 | |
![]() |
85.1 | 175 | (% class="box infomessage" %) |
176 | ((( | ||
![]() |
86.1 | 177 | Note: If you can't communicate PLC to box normally, changing ''No confirm" to "confirm" |
![]() |
85.1 | 178 | ))) |
179 | |||
![]() |
2.1 | 180 | Click on "transter setup" - "PC side I/F setting", see the following figure. |
181 | |||
182 | After setting, the first download must use the programming cable, as shown in the figure; after that, can | ||
183 | |||
184 | use the IP set in the "Ethernet board" to communicate directly with the network cable. | ||
![]() |
86.2 | 185 | |
![]() |
2.1 | 186 | |
![]() |
83.18 | 187 | (% style="text-align:center" %) |
![]() |
86.2 | 188 | [[image:WstTyoGrxG.png]] |
![]() |
2.1 | 189 | |
![]() |
83.18 | 190 | (% style="text-align:center" %) |
![]() |
86.2 | 191 | [[image:aak9XC8xDH.png]] |
![]() |
2.1 | 192 | |
![]() |
83.18 | 193 | |
194 | |||
![]() |
41.1 | 195 | **PLC Settings (GX Works 2)** |
![]() |
2.1 | 196 | |
197 | Create a blank FX5U project | ||
198 | |||
199 | Find Current Connection in the navigation | ||
200 | |||
![]() |
41.1 | 201 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d2a46ba9c005cf38.png||alt="image-20221116111427-1.png" height="421" width="705"]] |
![]() |
2.1 | 202 | |
203 | Select Connection Channel List | ||
204 | |||
205 | Select Ethernet board communication | ||
206 | |||
![]() |
41.1 | 207 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8f49721a3e5b0ef9.png||alt="image-20221116111451-2.png" height="421" width="705"]] |
![]() |
2.1 | 208 | |
209 | Select Ethernet Module | ||
210 | Set the IP address of the PLC | ||
211 | |||
![]() |
41.1 | 212 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1e9a9e29a46a1041.png||alt="image-20221116111509-3.png" height="666" width="699"]] |
![]() |
2.1 | 213 | |
214 | Read or write PLC data, in this document is read | ||
215 | |||
216 | {{id name="Iimage-20221116111651-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_e3d629103727a423.png||alt="image-20221116111651-4.png" height="416" width="697"]] | ||
217 | |||
![]() |
41.1 | 218 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7f29923ebcb670d1.png||alt="image-20221116111727-5.png" height="416" width="697"]] |
![]() |
2.1 | 219 | |
![]() |
46.1 | 220 | == **FX5U Serial ** == |
![]() |
2.1 | 221 | |
222 | Mitsubishi FX5U series PLC | ||
223 | |||
![]() |
46.1 | 224 | **V-BOX Settings** |
![]() |
2.1 | 225 | |
226 | |**Item**|**Settings**|**Note** | ||
227 | |Protocol|Mitsubishi FX5U| | ||
228 | |Connection|RS422/RS485| | ||
229 | |Baud rate|9600| | ||
230 | |Data bit|7| | ||
231 | |Parity|Odd| | ||
232 | |Stop bit|1| | ||
233 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
234 | |||
![]() |
54.1 | 235 | (% style="text-align:center" %) |
236 | [[image:三菱 FX5U 串口协议配置.png]] | ||
237 | |||
![]() |
46.1 | 238 | **Address List** |
![]() |
2.1 | 239 | |
![]() |
70.1 | 240 | |**Type**|**Device registers**|**Format**|**Range**|**Note** |
241 | |(% rowspan="15" %)Bit|X|X o|0~~303237| | ||
242 | |Y|Y o|0~~303237| | ||
243 | |M|M d|0~~99999| | ||
244 | |B|B h|0~~7FFF| | ||
245 | |F|F d|0~~32767| | ||
246 | |SB|SB h|0~~7FFF| | ||
247 | |TS|TS d|0~~1023| | ||
248 | |TC|TC d|0~~1023| | ||
249 | |STS|STS d|0~~1023| | ||
250 | |STC|STS d|0~~1023| | ||
251 | |CS|CS d|0~~1023| | ||
252 | |CC|CC d|0~~1023| | ||
253 | |SM|SM d|0~~9999| | ||
254 | |L|L d|0~~32767| | ||
255 | |S|S d|0~~4095| | ||
256 | |(% rowspan="9" %)Word|W|W h|0~~3FF| | ||
257 | |TN|TN d|0~~1023| | ||
258 | |STN|STN d|0~~1023| | ||
259 | |CN|CN d|0~~1023| | ||
260 | |R|R d|0~~32767| | ||
261 | |SW|SW h|0~~7FFF| | ||
262 | |Z|Z d|0~~23| | ||
263 | |D|D d|0~~7999| | ||
264 | |SD|SD d|0~~11999| | ||
![]() |
2.1 | 265 | |
![]() |
79.1 | 266 | **PLC Settings ** |
![]() |
2.1 | 267 | |
268 | Create a blank FX5U project | ||
269 | |||
![]() |
79.1 | 270 | Open GX Works3, create a new PLC project or open the project that has been created. Create new project: [Project]→[New]→[Series] FX5CPU→[Type] FX5U→[OK]. |
![]() |
2.1 | 271 | |
![]() |
79.1 | 272 | (% style="text-align:center" %) |
273 | [[image:GX3.png]] | ||
![]() |
2.1 | 274 | |
275 | |||
![]() |
79.1 | 276 | (% style="text-align:center" %) |
277 | [[image:FX5U 串口选型号.png]] | ||
![]() |
2.1 | 278 | |
![]() |
79.1 | 279 | PLC Default Parameters: |
280 | [Navigation]→[Parameter]→[FX5UCPU]→[Module Parameter]→[485 Serial Port]:[Basic Settings] →[ Communication Protocol Type] MC Protocol→[Advanced Settings]:[Baud rate]9600Kbps, [Data Length]7, [Stop bit]1,[Parity]Odd. | ||
![]() |
2.1 | 281 | |
![]() |
79.1 | 282 | (% style="text-align:center" %) |
283 | [[image:FX5U plc串口参数配置.png]] | ||
![]() |
2.1 | 284 | |
285 | |||
![]() |
79.1 | 286 | [Navigation]→[Parameter]→[FX5UCPU]→[Module Parameter]→[485 Serial Port]: [fixed Setting] →[Station No.]0→[Message Pattern] Pattern 1 (X,Y OCT)→[Apply] |
![]() |
2.1 | 287 | |
![]() |
79.1 | 288 | {{info}} |
289 | **✎Note:** The serial port parameters should be set depending on field requirements. | ||
290 | {{/info}} | ||
![]() |
2.1 | 291 | |
![]() |
79.1 | 292 | (% style="text-align:center" %) |
293 | [[image:FX5U plc串口参数.png]] | ||
![]() |
2.1 | 294 | |
![]() |
46.1 | 295 | **Cable Wiring** |
![]() |
2.1 | 296 | |
![]() |
46.1 | 297 | **RS422** |
![]() |
2.1 | 298 | |
![]() |
80.1 | 299 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d022c5ff4cf8c68e.png||alt="image-20220825105105-2.png" height="288" width="711"]] |
![]() |
2.1 | 300 | |
![]() |
80.1 | 301 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_50e173394c73f154.png||alt="image-20220825105533-3.png" height="246" width="420"]] |
![]() |
2.1 | 302 | |
![]() |
33.1 | 303 | == **FX5U Ethernet ** == |
![]() |
2.1 | 304 | |
305 | Mitsubishi FX5U series PLC | ||
306 | |||
![]() |
59.1 | 307 | **V-BOX Settings** |
![]() |
2.1 | 308 | |
309 | |**Items**|**Settings**|**Note** | ||
310 | |Protocol|Mitsubishi FX5U| | ||
311 | |Connection|Ethernet| | ||
312 | |Port No.|5002|Must be the same as the PLC setting | ||
313 | |PLC station No.|0| | ||
314 | |||
![]() |
59.1 | 315 | (% style="text-align:center" %) |
316 | [[image:三菱 FX5U 以太网协议配置.png]] | ||
![]() |
2.1 | 317 | |
![]() |
59.1 | 318 | **Address List** |
319 | |||
![]() |
71.1 | 320 | |**Type**|**Device registers**|**Format**|**Range**|**Note** |
321 | |(% rowspan="15" %)Bit|X|X o|0~~303237| | ||
322 | |Y|Y o|0~~303237| | ||
323 | |M|M d|0~~99999| | ||
324 | |B|B h|0~~7FFF| | ||
325 | |F|F d|0~~32767| | ||
326 | |SB|SB h|0~~7FFF| | ||
327 | |TS|TS d|0~~1023| | ||
328 | |TC|TC d|0~~1023| | ||
329 | |STS|STS d|0~~1023| | ||
330 | |STC|STS d|0~~1023| | ||
331 | |CS|CS d|0~~1023| | ||
332 | |CC|CC d|0~~1023| | ||
333 | |SM|SM d|0~~9999| | ||
334 | |L|L d|0~~32767| | ||
335 | |S|S d|0~~4095| | ||
336 | |(% rowspan="9" %)Word|W|W h|0~~3FF| | ||
337 | |TN|TN d|0~~1023| | ||
338 | |STN|STN d|0~~1023| | ||
339 | |CN|CN d|0~~1023| | ||
340 | |R|R d|0~~32767| | ||
341 | |SW|SW h|0~~7FFF| | ||
342 | |Z|Z d|0~~23| | ||
343 | |D|D d|0~~7999| | ||
344 | |SD|SD d|0~~11999| | ||
![]() |
2.1 | 345 | |
![]() |
81.1 | 346 | **PLC Settings ** |
![]() |
2.1 | 347 | |
![]() |
81.1 | 348 | Open GX Works3, create a new PLC project or open the project that has been created. |
349 | |||
350 | Create new project: [Project]→[New]→[Series] FX5CPU→[Type] FX5U→[OK]. | ||
351 | |||
![]() |
75.2 | 352 | (% style="text-align:center" %) |
![]() |
81.1 | 353 | [[image:GX3.png]] |
![]() |
2.1 | 354 | |
![]() |
81.1 | 355 | (% style="text-align:center" %) |
356 | [[image:FX5U 串口选型号.png]] | ||
357 | |||
358 | PLC Default Parameters: | ||
359 | [Navigation]→[Parameter]→[FX5UCPU]→[Module Parameter]→[Ethernet Port]:[Basic Settings] →[Own node settings]:[IP Address]192.168.40.11, [Subnet Mask]255.255.255.0, [Default Gateway]192.168.40.1,[ Communication Data Code] Binary. | ||
360 | |||
361 | (% style="text-align:center" %) | ||
362 | [[image:FX5U 以太网配置.png]] | ||
363 | |||
![]() |
75.2 | 364 | [External Device Configuration]→[Detailed Settings]→[Ethernet Configuration(Built-in Ethernet Port)]→[Ethernet Device (General)]→[SLMP Connection Module] Drag under Host for Connection No.1→[Port No.]5002→[Close with Reflecting the Setting] |
![]() |
2.1 | 365 | |
![]() |
75.2 | 366 | (% style="text-align:center" %) |
367 | [[image:1.3.2.png]] | ||
![]() |
2.1 | 368 | |
![]() |
81.1 | 369 | PC and PLC connection |
370 | |||
371 | [Online]→[Current Connection Destination]→[Direct Coupled Setting]→[Ethernet]→[Adapter] Realtek PCIe GBE Family Controller→[Communication Test]: Successfully connected with the FX5UCPU. | ||
372 | |||
373 | (% style="text-align:center" %) | ||
374 | [[image:FX5U 以太网连接PLC.png]] | ||
375 | |||
376 | Downloading PLC project | ||
377 | [Online]→[Write to PLC]→[Online Data operation]→[Param+program]→[Execute]→[Yes] →[Yes to all] | ||
378 | |||
379 | (% style="text-align:center" %) | ||
380 | [[image:FX5U以太网下载.png]] | ||
381 | |||
![]() |
59.1 | 382 | **Cable Wiring** |
![]() |
2.1 | 383 | |
![]() |
33.1 | 384 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]] |
![]() |
2.1 | 385 | |
![]() |
47.1 | 386 | == **L02 Serial ** == |
![]() |
2.1 | 387 | |
388 | Mitsubishi L02 series CPU built-in serial port. | ||
389 | |||
![]() |
47.1 | 390 | **V-BOX Settings** |
![]() |
2.1 | 391 | |
392 | |**Item**|**Settings**|**Note** | ||
393 | |Protocol|Mitsubishi L02| | ||
394 | |Connection|RS422| | ||
395 | |Baud rate|115200| | ||
396 | |Data bit|8| | ||
397 | |Parity|Odd| | ||
398 | |Stop bit|1| | ||
399 | |PLC station No.|1~~255|Need to be the same as PLC settings | ||
400 | |||
![]() |
53.1 | 401 | (% style="text-align:center" %) |
402 | [[image:三菱 L02串口协议配置.png]] | ||
403 | |||
![]() |
47.1 | 404 | **Address List** |
![]() |
2.1 | 405 | |
![]() |
72.1 | 406 | |**Type**|**Device registers**|**Format**|**Range**|**Note** |
![]() |
47.1 | 407 | |(% colspan="1" rowspan="20" %)Bit |
![]() |
72.1 | 408 | |X|X h|0~~FFFF| |
409 | |Y|Y h|0~~FFFF| | ||
410 | |M|M d|0~~9999| | ||
411 | |L|L d|0~~9999| | ||
412 | |F|F d|0~~9999| | ||
413 | |B|B h|0~~FFFF| | ||
414 | |V|V d|0~~2047| | ||
415 | |TC|TC d|0~~9999| | ||
416 | |SS|SS d|0~~9999| | ||
417 | |SC|SC d|0~~9999| | ||
418 | |CS|CS d|0~~9999| | ||
419 | |CC|CC d|0~~9999| | ||
420 | |SB|SB h|0~~FFFF| | ||
421 | |SM|SM d|0~~2047| | ||
422 | |STS|STS d|0~~1023| | ||
423 | |S|S d|0~~9999| | ||
424 | |DX|DX h|0~~FFFF| | ||
425 | |DY|DY h|0~~FFFF| | ||
426 | |TS|TS d|0~~9999| | ||
427 | |Dbit|Dbit d.d|0~~99999.0~~15| | ||
![]() |
47.1 | 428 | |(% colspan="1" rowspan="9" %)Word |
![]() |
72.1 | 429 | |W|W h|0~~FFFF| |
430 | |TN|TN d|0~~99999| | ||
431 | |SN|SN d|0~~99999| | ||
432 | |CN|CN d|0~~99999| | ||
433 | |R|R d|0~~99999| | ||
434 | |SW|SW h|0~~FFFF| | ||
435 | |Z|Z d|0~~99999| | ||
436 | |ZR|ZR h|0~~FFFF| | ||
437 | |D|D d|0~~99999| | ||
![]() |
2.1 | 438 | |
![]() |
47.1 | 439 | **Cable Wiring** |
![]() |
2.1 | 440 | |
![]() |
47.1 | 441 | **RS422** |
![]() |
2.1 | 442 | |
![]() |
47.1 | 443 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_90e38f152d639809.png||alt="image-20220825161612-8.png" height="278" width="612"]] |
![]() |
2.1 | 444 | |
![]() |
47.1 | 445 | [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d301e675d8224725.png||alt="image-20220825160820-4.png" height="208" width="359"]] |
![]() |
2.1 | 446 | |
![]() |
48.1 | 447 | == **L02 Ethernet ** == |
![]() |
2.1 | 448 | |
449 | Mitsubishi L series CPU built-in Ethernet port. | ||
450 | |||
![]() |
48.1 | 451 | **V-BOX Settings** |
![]() |
2.1 | 452 | |
453 | |**Items**|**Settings**|**Note** | ||
454 | |Protocol|MIT L02 CPU MELSEC| | ||
455 | |Connection|Ethernet| | ||
456 | |Port No.|1025|Must be the same as the PLC setting | ||
457 | |PLC station No.|0|Must be the same as the PLC setting | ||
458 | |||
![]() |
52.1 | 459 | (% style="text-align:center" %) |
460 | [[image:三菱 L02以太网协议配置1.png]] | ||
![]() |
51.1 | 461 | |
![]() |
48.1 | 462 | **PLC Settings (GX Works2 )** |
![]() |
2.1 | 463 | |
464 | Create a project | ||
465 | |||
466 | Set PLC IP, subnet mask and gateway; | ||
467 | |||
468 | Select [Binary Code] as communication data code; | ||
469 | |||
![]() |
49.1 | 470 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]] |
![]() |
2.1 | 471 | |
472 | Set PLC port number, for example 1025 | ||
473 | |||
![]() |
49.1 | 474 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]] |
![]() |
2.1 | 475 | |
476 | Save settings; | ||
477 | |||
478 | Download project into PLC device; | ||
479 | |||
480 | Restart PLC device; | ||
481 | |||
![]() |
49.1 | 482 | **Cable Wiring** |
![]() |
2.1 | 483 | |
![]() |
49.1 | 484 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]] |
![]() |
2.1 | 485 | |
486 | == {{id name="HQ12HSerial"/}}**Q12H Serial ** == | ||
487 | |||
488 | This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol | ||
489 | |||
490 | **[[Download link>>url:https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]** | ||
491 | |||
![]() |
32.1 | 492 | == **QJ71E71 Ethernet ** == |
![]() |
2.1 | 493 | |
494 | Mitsubishi QJ71E71 Ethernet communication module; | ||
495 | |||
![]() |
50.1 | 496 | **V-BOX Settings** |
![]() |
2.1 | 497 | |
498 | |**Items**|**Settings**|**Note** | ||
499 | |Protocol|MIT QJ71E71 MELSEC| | ||
500 | |Connection|Ethernet| | ||
501 | |Port No.|1025|Must be the same as the PLC setting | ||
502 | |PLC station No.|0|Must be the same as the PLC setting | ||
503 | |||
![]() |
61.1 | 504 | (% style="text-align:center" %) |
505 | [[image:三菱 QJ71 以太网协议配置.png]] | ||
![]() |
2.1 | 506 | |
![]() |
50.1 | 507 | **Address List** |
508 | |||
![]() |
74.1 | 509 | |**Type**|**Device registers**|**Format**|**Range**|**Note** |
510 | |(% rowspan="18" %)Bit|X|X h|0~~1FFF| | ||
511 | |Y|Y h|0~~1FFF| | ||
512 | |M|M d|0~~99999| | ||
513 | |L|L d|0~~8191| | ||
514 | |F|F d|0~~2047| | ||
515 | |B|B h|0~~1FFF| | ||
516 | |V|V d|0~~2047| | ||
517 | |TS|TS d|0~~2047| | ||
518 | |TC|TC d|0~~2047| | ||
519 | |SS|SS d|0~~2047| | ||
520 | |SC|SC d|0~~2047| | ||
521 | |CS|CS d|0~~1023| | ||
522 | |CC|CC d|0~~1023| | ||
523 | |SB|SB h|0~~7FF| | ||
524 | |S|S d|0~~8191| | ||
525 | |DX|DX h|0~~1FFF| | ||
526 | |DY|DY h|0~~1FFF| | ||
527 | |SM|SM d|8000~~9999| | ||
528 | |(% rowspan="10" %)Word|SD|SD d|0~~2047| | ||
529 | |D|D d|0~~12287| | ||
530 | |W|W h|0~~1FFF| | ||
531 | |TN|TN d|0~~2047| | ||
532 | |SN|SN d|0~~2047| | ||
533 | |CN|CN d|0~~1023| | ||
534 | |R|R d|0~~32767| | ||
535 | |SW|SW h|0~~7FF| | ||
536 | |Z|Z d|0~~15| | ||
537 | |ZR|ZR h|0~~FE7FF| | ||
![]() |
2.1 | 538 | |
![]() |
50.1 | 539 | **PLC Settings(GX Works2)** |
![]() |
2.1 | 540 | |
541 | * Click [Ethernet/CC IE/MELSECNET]; | ||
542 | * Please select [Ethernet] as network type; | ||
543 | * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order); | ||
544 | * Select [Online] as Mode; | ||
![]() |
50.1 | 545 | * [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d54f23688c520f78.png||alt="image-20221119171343-2.png" height="341" width="587"]] |
![]() |
2.1 | 546 | * Click [Operation setting] to set IP; |
547 | * Select [Binary Code] as [Communication Data Code]; | ||
![]() |
50.1 | 548 | * [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ce8e6a671b9508e0.png||alt="image-20221119171436-3.png" height="354" width="588"]] |
![]() |
2.1 | 549 | * Click [Open setting] |
550 | * Set protocol: TCP; | ||
551 | * Set [unpassive] in [Open system]; | ||
552 | * Set [receive] in [Fixed buffer]; | ||
553 | * Set [procedure Exist] in [Fixed buffer communication]; | ||
554 | * Disable [Pairing open]; | ||
555 | * Set [No confirm] in [Existence confirmation]; | ||
556 | * Host station port number: 5009; | ||
557 | * Save settings; | ||
558 | * {{id name="Iimage-20221119171611-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_1d8e2f4fb7c72471.png||alt="image-20221119171611-4.png" height="354" width="588"]] | ||
559 | * Download project into PLC and restart it | ||
560 | |||
![]() |
50.1 | 561 | **Cable Wiring** |
![]() |
2.1 | 562 | |
![]() |
34.1 | 563 | [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]] |
![]() |
83.2 | 564 | |
565 | == Q03UDV == | ||
![]() |
83.3 | 566 | |
567 | Mitsubishi Q03UDV | ||
568 | |||
569 | **V-BOX Settings** | ||
570 | |||
![]() |
83.4 | 571 | |**Items**|**Settings**|**Note** |
![]() |
83.7 | 572 | |Protocol|MIT L02 CPU MELSEC PROTOCOL| |
![]() |
83.4 | 573 | |Connection|Ethernet| |
![]() |
83.5 | 574 | |Port No.|1025|Must be the same as the PLC setting |
![]() |
83.6 | 575 | |PLC station No.|0|Must be the same as the PLC setting |
![]() |
83.7 | 576 | |
![]() |
83.8 | 577 | [[image:1709779590561-640.png]] |
578 | |||
579 | **Address List** | ||
580 | |||
581 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
582 | |(% colspan="1" rowspan="18" %)Bit|X|X h|0~~1fff| | ||
583 | |Y|Y h|0~~1fff| | ||
584 | |SM|SM d|0~~2047| | ||
585 | |M|M d|0~~99999| | ||
586 | |L|L d|0~~8191| | ||
587 | |F|F d|0~~2047| | ||
588 | |V|V d|0~~2047| | ||
589 | |B|B h|0~~1fff| | ||
590 | |TS|TS d|0~~2047| | ||
591 | |TC|TC d|0~~2047| | ||
592 | |SS|SS d|0~~2047| | ||
593 | |SC|SC d|0~~2047| | ||
594 | |CS|CS d|0~~1023| | ||
595 | |CC|CC d|0~~1023| | ||
596 | |SB|SB h|0~~7ff| | ||
597 | |S|S d|0~~8191| | ||
598 | |DX|DX h|0~~1fff| | ||
599 | |DY|DY h|0~~1fff| | ||
![]() |
83.9 | 600 | |(% colspan="1" rowspan="10" %)Word|SD|SD d|0~~2047| |
![]() |
83.8 | 601 | |D|D d|0~~12287| |
602 | |W|W h|0~~1fff| | ||
603 | |TN|TN d|0~~2047| | ||
604 | |SN|SN d|0~~2047| | ||
605 | |CN|CN d|0~~1023| | ||
606 | |SW|SW h|0~~7ff| | ||
607 | |Z|Z d|0~~15| | ||
608 | |R|R d|0~~32767| | ||
609 | |ZR|ZR h|0~~fe7ff| | ||
![]() |
83.10 | 610 | |
![]() |
83.12 | 611 | (% class="wikigeneratedid" id="HPLCSettings" %) |
612 | **PLC Settings(GX Works2)** | ||
613 | |||
614 | (% class="wikigeneratedid" %) | ||
615 | PC and PLC connection: | ||
616 | |||
![]() |
83.15 | 617 | * Online→Read from PLC |
![]() |
83.12 | 618 | |
619 | (% style="text-align:center" %) | ||
620 | [[image:1.png]] | ||
621 | |||
![]() |
83.15 | 622 | * choose PLC Series→OK |
![]() |
83.14 | 623 | |
![]() |
83.12 | 624 | (% style="text-align:center" %) |
625 | [[image:StqCG53paq.png]] | ||
626 | |||
![]() |
83.15 | 627 | * serial USB→OK |
![]() |
83.14 | 628 | |
![]() |
83.12 | 629 | (% style="text-align:center" %) |
630 | [[image:Y7H80eq2Eb.png]] | ||
631 | |||
![]() |
83.15 | 632 | * Choose Parameter、Global Device Comment and Device Memory→Execute |
![]() |
83.14 | 633 | |
![]() |
83.12 | 634 | (% style="text-align:center" %) |
635 | [[image:6PAsdFz58I.png]] | ||
636 | |||
![]() |
83.15 | 637 | * OK→wait loading successfully→Close |
![]() |
83.14 | 638 | |
![]() |
83.13 | 639 | (% style="text-align:center" %) |
640 | [[image:0GBGUNn4hQ.png]] | ||
641 | |||
![]() |
83.15 | 642 | * Navigation→Parameter→PLC Parameter→IP Address Setting→Built-in Ethernet Port Setting→Host Station(Same as the port on V-box)→End |
![]() |
83.14 | 643 | |
![]() |
83.13 | 644 | (% style="text-align:center" %) |
645 | [[image:Ypyl4SUHcf.png]] | ||
646 | |||
![]() |
83.15 | 647 | * Debug→Start/ Stop Simulation→wait loading successfully→Close |
![]() |
83.14 | 648 | |
![]() |
83.13 | 649 | (% style="text-align:center" %) |
650 | [[image:ZmUzFbS39y.png]] | ||
651 | |||
652 | (% style="text-align:center" %) | ||
653 | [[image:ehoO3C6bry.png]] | ||