Changes for page Omron

Last modified by Theodore Xu on 2023/09/16 10:47

From version 4.1
edited by Leo Wei
on 2023/08/24 14:11
Change comment: There is no comment for this version
To version 5.1
edited by Theodore Xu
on 2023/09/07 19:18
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.admin
1 +XWiki.AiXia
Content
... ... @@ -1,15 +1,88 @@
1 -= {{id name="HOmron"/}}**Omron** =
1 += **Omron** =
2 2  
3 -== {{id name="HCP1Series"/}}**CP1 Series** ==
3 +== **CP1 Series** ==
4 4  
5 5  [[Download>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
6 6  
7 -== {{id name="HCP2MSeries"/}}**CP2M Series** ==
7 +== **CP2M Series** ==
8 8  
9 9  [[Download>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
10 10  
11 -== {{id name="HEC55Series"/}}**EC55 Series ** ==
11 +== **CJ TCP FINS Ethemet** ==
12 12  
13 +Supported device:CJ series, CJ1W-EIP21,CJ2M-EIP21
14 +
15 +**V-Box Settings**
16 +
17 +|=**Items**|=**Settings**
18 +|Protocol|OMRON CJ TCP FINS Ethemet
19 +|Connection|Ethernet
20 +|Port No.|9600
21 +|Device No.|0
22 +|V-Box No.|0
23 +
24 +(% style="text-align:center" %)
25 +[[image:欧姆龙创建.png]]
26 +
27 +**2)Address List **
28 +
29 +
30 +|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
31 +|(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
32 +|Q|Q|Q ddddd.o|0.0~~99999.7|
33 +|V|VWbit|VWbit ddddd.o|0.0~~99999.7|
34 +|V|V|V ddddd.o|0.0~~99999.7|
35 +|M|M|M ddddd.o|0.0~~99999.7|
36 +|SM|SM|ddddd.o|0.0~~99999.7|
37 +|S|S|ddddd.o|0.0~~99999.7|Read only
38 +|T|T|ddddd|0~~99999|Timer state, read only
39 +|C|C|ddddd|0~~99999|Counter state, read only
40 +|(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
41 +|Q|QW|QW ddddd|0~~99999|
42 +|AI|AIW|AIW ddddd|0~~99999|
43 +|AQ|VB|VB ddddd|0~~99999|
44 +|V|VW|VW ddddd|0~~99998|(((
45 +VW0=VB (0~~1)
46 +
47 +VW2=VB (2~~3)
48 +
49 +Address value is a multiple of 2
50 +)))
51 +|V|VD|VD ddddd|0~~99998|(((
52 +VD0=VB (0~~3)
53 +
54 +VD2=VB (4~~7)
55 +
56 +Address value is a multiple of 4
57 +)))
58 +|M|MB|MB ddddd|0~~99999|
59 +|M|MW|MW ddddd|0~~99999|(((
60 +MW0=MB(0~~1)
61 +
62 +MW2=MB(2~~3)
63 +
64 +Address value is a multiple of 2
65 +)))
66 +|M|MD|MD ddddd|0~~99999|(((
67 +MD0=MB(0~~3)
68 +
69 +MD4=MB(4~~7)
70 +
71 +Address value is a multiple of 4
72 +)))
73 +|T|TW|TW ddddd|0~~99999|Value of timer
74 +|C|CW|CW ddddd|0~~99999|Value of counter
75 +|W|SW|SW ddddd|0~~99999|
76 +
77 +(% class="wikigeneratedid" %)
78 +**3)PLC software**
79 +
80 +(% class="wikigeneratedid" %)
81 +①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
82 +Note:The IP address of the PLC is displayed on the LED when the PLC is powered up
83 +
84 +== **EC55 Series ** ==
85 +
13 13  Supported device: EC55 temperature instrument
14 14  