Changes for page Omron

Last modified by Theodore Xu on 2023/09/16 10:47

From version 5.1
edited by Theodore Xu
on 2023/09/07 19:18
Change comment: There is no comment for this version
To version 10.1
edited by Theodore Xu
on 2023/09/12 10:44
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -8,7 +8,7 @@
8 8  
9 9  [[Download>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
10 10  
11 -== **CJ TCP FINS Ethemet** ==
11 +== **CJ2M Ethemet** ==
12 12  
13 13  Supported device:CJ series, CJ1W-EIP21,CJ2M-EIP21
14 14  
... ... @@ -24,63 +24,100 @@
24 24  (% style="text-align:center" %)
25 25  [[image:欧姆龙创建.png]]
26 26  
27 -**2)Address List **
27 +**Address List **
28 28  
29 +|=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
30 +|(% colspan="1" rowspan="23" %)Bit
31 + |CIO|CIO|CIO d|0~~99999|
32 +|W|W|W d|0~~99999|
33 +|D|D|D d|0~~99999|
34 +|H|H|H d|0~~99999|
35 +|A|A|A d|0~~99999|
36 +|T|T|T h|0~~99999|
37 +|CF|CF|CF d|0~~99999|
38 +|FF|FF|FF d|0~~99999|
39 +|C|C|C d|0~~99999|
40 +|EM0|EM0|EM0 d|0~~99999|
41 +|EM1|EM1|EM1 d|0~~99999|
42 +|EM2|EM2|EM2 d|0~~99999|
43 +|EM3|EM3|EM3 d|0~~99999|
44 +|EM4|EM4|EM4 d|0~~99999|
45 +|EM5|EM5|EM5 h|0~~99999|
46 +|EM6|EM6|EM6 d|0~~99999|
47 +|EM7|EM7|EM7 d|0~~99999|
48 +|EM8|EM8|EM8 d|0~~99999|
49 +|EM9|EM9|EM9 d|0~~99999|
50 +|EMA|EMA|EMA d|0~~99999|
51 +|EMB|EMB|EMB d|0~~99999|
52 +|EMC|EMC|EMC d|0~~99999|
53 +|Lamp|Lamp|Lamp d|0~~0|
54 +|(% colspan="1" rowspan="24" %)Word
55 + |CIO|CIO|CIO d|0~~99999|
56 +|W|W|W d|0~~99999|
57 +|D|D|D d|0~~99999|
58 +|H|H|H d|0~~99999|
59 +|A|A|A d|0~~99999|
60 +|T|T|T h|0~~99999|
61 +|CF|CF|CF d|0~~99999|
62 +|FF|FF|FF d|0~~99999|
63 +|C|C|C d|0~~99999|
64 +|EM0|EM0|EM0 d|0~~99999|
65 +|EM1|EM1|EM1 d|0~~99999|
66 +|EM2|EM2|EM2 d|0~~99999|
67 +|EM3|EM3|EM3 d|0~~99999|
68 +|EM4|EM4|EM4 d|0~~99999|
69 +|EM5|EM5|EM5 h|0~~99999|
70 +|EM6|EM6|EM6 d|0~~99999|
71 +|EM7|EM7|EM7 d|0~~99999|
72 +|EM8|EM8|EM8 d|0~~99999|
73 +|EM9|EM9|EM9 d|0~~99999|
74 +|EMA|EMA|EMA d|0~~99999|
75 +|EMB|EMB|EMB d|0~~99999|
76 +|EMC|EMC|EMC d|0~~99999|
77 +|IR|IR|IR d|0~~99999|
78 +|DR|DR|DR d|0~~99999|
29 29  
30 -|**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
31 -|(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
32 -|Q|Q|Q ddddd.o|0.0~~99999.7|
33 -|V|VWbit|VWbit ddddd.o|0.0~~99999.7|
34 -|V|V|V ddddd.o|0.0~~99999.7|
35 -|M|M|M ddddd.o|0.0~~99999.7|
36 -|SM|SM|ddddd.o|0.0~~99999.7|
37 -|S|S|ddddd.o|0.0~~99999.7|Read only
38 -|T|T|ddddd|0~~99999|Timer state, read only
39 -|C|C|ddddd|0~~99999|Counter state, read only
40 -|(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
41 -|Q|QW|QW ddddd|0~~99999|
42 -|AI|AIW|AIW ddddd|0~~99999|
43 -|AQ|VB|VB ddddd|0~~99999|
44 -|V|VW|VW ddddd|0~~99998|(((
45 -VW0=VB (0~~1)
80 +(% class="wikigeneratedid" %)
81 +**PLC setting**
46 46  
47 -VW2=VB (2~~3)
83 +(% class="wikigeneratedid" %)
84 +①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
85 +Note:The IP address of the PLC is displayed on the LED when the PLC is powered up
48 48  
49 -Address value is a multiple of 2
50 -)))
51 -|V|VD|VD ddddd|0~~99998|(((
52 -VD0=VB (0~~3)
87 +(% style="text-align:center" %)
88 +[[image:1.3.1.png]]
53 53  
54 -VD2=VB (4~~7)
90 +②[PLC]→[Work Online]→USB connection between PC and PLC→The connection prompt appears→[Yes]
55 55  
56 -Address value is a multiple of 4
57 -)))
58 -|M|MB|MB ddddd|0~~99999|
59 -|M|MW|MW ddddd|0~~99999|(((
60 -MW0=MB(0~~1)
92 +(% style="text-align:center" %)
93 +[[image:1.3.2.png]]
61 61  
62 -MW2=MB(2~~3)
95 +③PLC default parameters: [IO Table and Unit Settings] → [Built-in Port/Inner Board] [1500] CJ2M-EIP21→[TCP/IP] → [Transfer [Unit to PC]] → Transfer successfully, click [Close]
63 63  
64 -Address value is a multiple of 2
65 -)))
66 -|M|MD|MD ddddd|0~~99999|(((
67 -MD0=MB(0~~3)
97 +[IP Address] Use the following address → [IP Address] 192.168.40.99, [Subnet Mask] 255.255.255.0.
98 +Note: Please configure the IP parameters of PLC according to the field needs
68 68  
69 -MD4=MB(4~~7)
100 +(% style="text-align:center" %)
101 +[[image:1694161978199-503.4.png]]
70 70  
71 -Address value is a multiple of 4
72 -)))
73 -|T|TW|TW ddddd|0~~99999|Value of timer
74 -|C|CW|CW ddddd|0~~99999|Value of counter
75 -|W|SW|SW ddddd|0~~99999|
103 +④Two rotary coding switches should be set depanding on the program paremeter:
104 +a) rotary coding switch for unit No. :For example, [Built-in Port/Inner Board] [1500] CJ2M-EIP21(Built In EtherNet/IP Port for CJ2M)(Unit: 0),the rotary coding switch should be dialed to 0
76 76  
77 -(% class="wikigeneratedid" %)
78 -**3)PLC software**
106 +(% style="text-align:center" %)
107 +[[image:WeCom Screenshot_20230828090604.png]]
79 79  
80 -(% class="wikigeneratedid" %)
81 -①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
82 -Note:The IP address of the PLC is displayed on the LED when the PLC is powered up
109 +**b) rotary coding switch for node No. :The high byte 4 of the IP address should be the same as theone configured by the software. such as [IP address] 192.168.40.99. The IP address high byte 4 is 99,rotary coding switch is to use hexadecimal 63 corresponds to decimal 99, node number dialling code 161 corresponds to: 6, 160 corresponds to: 3.Address List**
83 83  
111 +(% style="text-align:center" %)
112 +[[image:WeCom.png]]
113 +
114 +**Cable Wiring**
115 +
116 +Pin Definition Diagram
117 +
118 +(% style="text-align:center" %)
119 +[[image:12.PLC Protocol_html_2297240b57346b2a.png]]
120 +
84 84  == **EC55 Series ** ==
85 85  
86 86  Supported device: EC55 temperature instrument
1.3.1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +74.9 KB
Content
1.3.2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +67.7 KB
Content
12.PLC Protocol_html_2297240b57346b2a.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +107.1 KB
Content
1694161978199-503.4.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +94.6 KB
Content
WeCom Screenshot_20230828090604.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +40.2 KB
Content
WeCom.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +40.2 KB
Content
欧姆龙创建.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.AiXia
Size
... ... @@ -1,0 +1,1 @@
1 +65.8 KB
Content