Omron

Version 9.1 by Theodore Xu on 2023/09/11 17:55

Omron

CP1 Series

Download

CP2M Series

Download

CJ TCP FINS Ethemet

Supported device:CJ series, CJ1W-EIP21,CJ2M-EIP21

V-Box Settings

ItemsSettings
ProtocolOMRON CJ TCP FINS Ethemet
ConnectionEthernet
Port No.9600
Device No.0
V-Box No.0

欧姆龙创建.png

Address List 

TypeDevice registersHMI registersFormatRangeNote
Bit
 
CIOCIOCIO d0~99999 
WWW d0~99999 
DDD d0~99999 
HHH d0~99999 
AAA d0~99999 
TTT h0~99999 
CFCFCF d0~99999 
FFFFFF d0~99999 
CCC d0~99999 
EM0EM0EM0 d0~99999 
EM1EM1EM1 d0~99999 
EM2EM2EM2 d0~99999 
EM3EM3EM3 d0~99999 
EM4EM4EM4 d0~99999 
EM5EM5EM5 h0~99999 
EM6EM6EM6 d0~99999 
EM7EM7EM7 d0~99999 
EM8EM8EM8 d0~99999 
EM9EM9EM9 d0~99999 
EMAEMAEMA d0~99999 
EMBEMBEMB d0~99999 
EMCEMCEMC d0~99999 
LampLampLamp d0~0 
Word
 
CIOCIOCIO d0~99999 
WWW d0~99999 
DDD d0~99999 
HHH d0~99999 
AAA d0~99999 
TTT h0~99999 
CFCFCF d0~99999 
FFFFFF d0~99999 
CCC d0~99999 
EM0EM0EM0 d0~99999 
EM1EM1EM1 d0~99999 
EM2EM2EM2 d0~99999 
EM3EM3EM3 d0~99999 
EM4EM4EM4 d0~99999 
EM5EM5EM5 h0~99999 
EM6EM6EM6 d0~99999 
EM7EM7EM7 d0~99999 
EM8EM8EM8 d0~99999 
EM9EM9EM9 d0~99999 
EMAEMAEMA d0~99999 
EMBEMBEMB d0~99999 
EMCEMCEMC d0~99999 
IRIRIR d0~99999 
DRDRDR d0~99999 

PLC setting

①[PLC]→[Change Communication Settings]→[Network Type] Ethernet→[setting…]→[Derive]→[IPaddress]set the IP address as PLC’s ,192.168.40.99→[Port Number]9600→[OK]→[OK]
Note:The IP address of the PLC is displayed on the LED when the PLC is powered up

1.3.1.png

②[PLC]→[Work Online]→USB connection between PC and PLC→The connection prompt appears→[Yes]

1.3.2.png

③PLC default parameters: [IO Table and Unit Settings] → [Built-in Port/Inner Board] [1500] CJ2M-EIP21→[TCP/IP] → [Transfer [Unit to PC]] → Transfer successfully, click [Close]

[IP Address] Use the following address → [IP Address] 192.168.40.99, [Subnet Mask] 255.255.255.0.
Note: Please configure the IP parameters of PLC according to the field needs

1694161978199-503.4.png

④Two rotary coding switches should be set depanding on the program paremeter:
a) rotary coding switch for unit No. :For example, [Built-in Port/Inner Board] [1500] CJ2M-EIP21(Built In EtherNet/IP Port for CJ2M)(Unit: 0),the rotary coding switch should be dialed to 0

WeCom Screenshot_20230828090604.png

b) rotary coding switch for node No. :The high byte 4 of the IP address should be the same as theone configured by the software. such as [IP address] 192.168.40.99. The IP address high byte 4 is 99,rotary coding switch is to use hexadecimal 63 corresponds to decimal 99, node number dialling code 161 corresponds to: 6, 160 corresponds to: 3.Address List

WeCom.png

Cable Wiring

Pin Definition Diagram

12.PLC Protocol_html_2297240b57346b2a.png

EC55 Series 

Supported device: EC55 temperature instrument

1)V-BOX Settings

ItemsSettingsNote
ProtocolOmron EC55 
ConnectionRS485 (9600, 2, 7, EVEN) 
Port No.None 
PLC station No.0 

2)Address List

TypeRegisterDevice rangeHMI rangeFunction
Double wordC00-13 (Hex)0-19Set read only parameter for area 0
C10-4D(Hex)0-77Set Read/Write parameter for area 0
C30-CD(Hex)0-205Set Read/Write parameter for area 1
Word800-13(Hex)0-19Set read only parameter in area 0
810-4D(Hex)0-77Set Read/Write parameter in area 0
830-CD(Hex)0-205Set Read/Write parameter in area 1
CP-0-6Read controller intrinsic property
CS-0-2Read controller states
CA-0-17Action command

3)Device Settings

Omron E5CC PLC configuration

After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.

12.PLC Protocol_html_3d95e093792ba98a.png

According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows

12.PLC Protocol_html_be583aa69dd6cf4c.png

✎Note: The communication settings for HMI should be consistent with this setting.

4)Configure the communication protocol

image-20220831161041-1.png

5)Cable Wiring

12.PLC Protocol_html_5e9a81a14106da9e.png

12.PLC Protocol_html_1897d92be6948d58.png

✎Note:

  • COM3 only available in PI8000/PI9000 series.
  • CA address could not support continuous writing function;
  • Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
  • When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
  • When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
  • Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
  • When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
  • Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
  • image-20220831161356-1.png Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.