Schneider
Last modified by Leo Wei on 2023/08/24 14:11
Schneider
Schneider MODBUS RTU
1)V-BOX Setting
Parameters | Recommended | Notes |
---|---|---|
Protocol | Schneider MODBUS RTU | |
Connection | RS485 | |
Baud rate | 19200 | |
Data bit | 8 | |
Parity | Even | |
Stop bit | 1 | |
PLC station No. | 1 |
2)Address List
Bit/Word | Device type | Format | Range | Memo |
---|---|---|---|---|
B | IX | DDDDDo | 0 ~ 655357 | Input bit (read only) |
B | QX | DDDDDo | 0 ~ 655357 | Write multiple coils |
B | MX | DDDDDDo | 0 ~ 9999997 | Output register bit (octal) |
W | MW | DDDDDD | 0 ~ 999999 | Output register |
DW | MD | DDDDDD | 0 ~ 999999 | Output register |
3)Configure the communication protocol
4)Cable Wiring
RS-485 2W (RJ45 Connector): The following is the view from the soldering point of a connector.