Wiki source code of Siemens

Version 15.1 by Theodore Xu on 2023/08/25 15:37

Hide last authors
Leo Wei 2.1 1 = {{id name="HSiemens"/}}**Siemens ** =
2
Theodore Xu 14.1 3 == **S7-200 Smart Ethernet ** ==
Leo Wei 2.1 4
5 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
6
Theodore Xu 14.1 7 **1)PLC software**
8
9 (% style="text-align:center" %)
10 [[image:西门子软件版本.png]]
11
12 **2)Ethernet Configuration**
13
14 (% style="text-align:center" %)
15 [[image:以太网通讯配置.png]]
16
17 **3)Connect PC software**
18
19 (% style="text-align:center" %)
20 [[image:以太网下载.png]]
21
Theodore Xu 15.1 22 **4)Configure of V-net**
Theodore Xu 14.1 23
24 (% style="text-align:center" %)
25 [[image:西门子200smart 以太网.png]]
26
Theodore Xu 15.1 27 **5)wiring**
28
29
30 V-Box : RJ45 Ethernet interface
31
32 PLC : RJ45 Ethernet interface
33
34 (% style="text-align:center" %)
35 [[image:以太网连接.png]]
36
37
38
Leo Wei 2.1 39 == {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
40
41 Supported Series: Siemens S7-300 series PLC
42
43 **1)V-BOX setting**
44
45 |**Items**|**Settings**|**Note**
46 |Protocol|Simens S7-300 Ethernet|
47 |Connection|Ethernet|
48 |Port No.|102|
49 |PLC station No.|2|Need to be same as the PLC setting
50
51 **2)Address List**
52
53 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
54 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
55 |Q|Q|Q ddddd.o|0.0~~99999.7|
56 |M|M|M ddddd.o|0.0~~99999.7|
57 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
58 nn: block number;
59
60 dddd: address;
61 )))
62 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
63 |Q|QW|QW ddddd|0~~99999|
64 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
65 |MW|MW ddddd|0~~99999|(((
66 MW0=MB(0~~1)
67
68 MW2=MB(2~~3)
69
70 Address value is a multiple of 2
71 )))
72 |MD|MD ddddd|0~~99999|(((
73 MD0=MB(0~~3)
74
75 MD4=MB(4~~7)
76
77 Address value is a multiple of 4
78 )))
79 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
80 nn: block number;
81
82 dddd: address
83 )))
84 |DBxDBW|DBxDBW nndddd|0~~99999999
85 |DBxDBD|DBxDBD nndddd|0~~99999999
86
87 **3)Configure the communication protocol**
88
89 {{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
90
91 **4)Cable Wiring**
92
93 {{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
94
95 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
96
97 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
98
99 == {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
100
101 Supported Series: Siemens S7-400, S7-1200 and S7-1500
102
103 **1)V-BOX setting**
104
105 |=**Items**|=**Settings**|=**Note**
106 |Protocol|Siemens S7-XXX|
107 |Connection|Ethernet|
108 |Port No.|102|
109 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
110 |HMI No.|Rack (Default as 0)|
111
112 Slot from TIA Portal is equal to Device No. of V-net
113
114 Rack from TIA Portal is equal to HMI No. of V-net
115
116 {{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
117
118 {{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
119
120 **2)Address List**
121
122 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
123 |(% rowspan="4" %)Bit|I|I|M d.o|(((
124 d:0~-~-9999
125
126 o:0-7
127 )))|
128 |Q|Q|Q d.o|(((
129 d:0~-~-9999
130
131 o:0-7
132 )))|
133 |M|M|M d.o|(((
134 d:0~-~-9999
135
136 o:0-7
137 )))|
138 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
139 nn:0-9999,
140
141 dddd:0-9999,
142
143 o:0-7
144 )))|(((
145 nn:DB No.
146
147 dddd:address value
148
149 o: digit address
150 )))
151 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
152 |M|MW|MW d|d:0-99999|(((
153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
159 |M|MD|MD d|d:0-99999|(((
160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
166 |I|IW|IW d|d:0-99999|
167 |Q|QW|QW d|d:0-99999|
168 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
169 nn:0-9999
170
171 dddd:0-9999
172 )))|(((
173 nn:DB No.
174
175 dddd:address value
176 )))
177 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
178 nn:0-9999
179
180 dddd:0-9999
181 )))|(((
182 nn:DB No.
183
184 dddd:address value
185
186 Address value is a multiple of 2
187 )))
188 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
189 nn:0-9999
190
191 dddd:0-9999
192 )))|(((
193 nn:DB No.
194
195 dddd:address value
196
197 Address value is a multiple of 4
198 )))
199
200 **3)Configure the communication protocol**
201
202 {{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
203
204 **✎Note:**
205
206 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
207 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
208
209 **4)Cable Wiring**
210
211 {{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
212
213 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
214
215 Supported Series: Siemens Logo 0BA0, 0BA1 series
216
217 **V-BOX Settings**
218
219 |**Items**|**Settings**|**Note**
220 |Protocol|Siemens LOGO|
221 |Connection|Ethernet|
222 |Port No.|102|
223 |PLC station No.|2|
224
225 **Address List**
226
227 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
228 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
229 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
230 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
231 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
232 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
233 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
234 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
235 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
236 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
237 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
238 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
239 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
240 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
241 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
242 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
243
244 **PLC Settings in LOGO Software:**
245
246 Click [Tools]~-~-[Ethernet Connections],shown as below.
247
248 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
249
250 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
251
252 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
253
254 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
255
256 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
257
258 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
259
260 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
261
262 **V-BOX Communication Settings**
263
264 Set PLC IP in [IP Address] settings;
265
266 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
267
268 Enable V-BOX Ethernet in [Network];
269
270 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
271
272 TSAP setting
273
274 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
275
276 **function** **init**.main()
277 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
278 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
279 **end**
280
281 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
282
283 **✎Note:**
284
285 * **Communication port configuration: **
286 ** Continuous length needs to be set to 0.
287 ** Integration interval needs to be set to 1. (no change may result in data errors)
288 ** Set Port and Device Station NO.
289 ** Other set as defaulted.
290 * **Notes on the use of registers:**
291 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
292 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )