Leo Wei 2.1 1 = {{id name="HSiemens"/}}**Siemens ** =
2
Theodore Xu 16.1 3 == **S7-200 Smart Serial** ==
4
Theodore Xu 14.1 5 == **S7-200 Smart Ethernet ** ==
Leo Wei 2.1 6
7 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
8
Theodore Xu 16.1 9 = **1)V-BOX ** =
10
11 |**Item**|**Settings**|**Note**
12 |Protocol|Siemens S7-200 Smart(Ethemet)|
13 |Connection|Ethernet|
14 |Port No.|5002|Must be the same as the PLC setting
15 |PLC station No.|0|
16
17 (% style="text-align:center" %)
18 [[image:西门子200smart 以太网.png]]
19
Theodore Xu 14.1 20 **1)PLC software**
21
22 (% style="text-align:center" %)
23 [[image:西门子软件版本.png]]
24
25 **2)Ethernet Configuration**
26
27 (% style="text-align:center" %)
28 [[image:以太网通讯配置.png]]
29
30 **3)Connect PC software**
31
32 (% style="text-align:center" %)
33 [[image:以太网下载.png]]
34
35
Theodore Xu 15.1 36 **5)wiring**
37
38
39 V-Box : RJ45 Ethernet interface
40
41 PLC : RJ45 Ethernet interface
42
43 (% style="text-align:center" %)
44 [[image:以太网连接.png]]
45
46
47
Leo Wei 2.1 48 == {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
49
50 Supported Series: Siemens S7-300 series PLC
51
52 **1)V-BOX setting**
53
54 |**Items**|**Settings**|**Note**
55 |Protocol|Simens S7-300 Ethernet|
56 |Connection|Ethernet|
57 |Port No.|102|
58 |PLC station No.|2|Need to be same as the PLC setting
59
60 **2)Address List**
61
62 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
63 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
64 |Q|Q|Q ddddd.o|0.0~~99999.7|
65 |M|M|M ddddd.o|0.0~~99999.7|
66 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
67 nn: block number;
68
69 dddd: address;
70 )))
71 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
72 |Q|QW|QW ddddd|0~~99999|
73 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
74 |MW|MW ddddd|0~~99999|(((
75 MW0=MB(0~~1)
76
77 MW2=MB(2~~3)
78
79 Address value is a multiple of 2
80 )))
81 |MD|MD ddddd|0~~99999|(((
82 MD0=MB(0~~3)
83
84 MD4=MB(4~~7)
85
86 Address value is a multiple of 4
87 )))
88 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
89 nn: block number;
90
91 dddd: address
92 )))
93 |DBxDBW|DBxDBW nndddd|0~~99999999
94 |DBxDBD|DBxDBD nndddd|0~~99999999
95
96 **3)Configure the communication protocol**
97
98 {{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
99
100 **4)Cable Wiring**
101
102 {{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
103
104 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
105
106 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
107
108 == {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
109
110 Supported Series: Siemens S7-400, S7-1200 and S7-1500
111
112 **1)V-BOX setting**
113
114 |=**Items**|=**Settings**|=**Note**
115 |Protocol|Siemens S7-XXX|
116 |Connection|Ethernet|
117 |Port No.|102|
118 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
119 |HMI No.|Rack (Default as 0)|
120
121 Slot from TIA Portal is equal to Device No. of V-net
122
123 Rack from TIA Portal is equal to HMI No. of V-net
124
125 {{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
126
127 {{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
128
129 **2)Address List**
130
131 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
132 |(% rowspan="4" %)Bit|I|I|M d.o|(((
133 d:0~-~-9999
134
135 o:0-7
136 )))|
137 |Q|Q|Q d.o|(((
138 d:0~-~-9999
139
140 o:0-7
141 )))|
142 |M|M|M d.o|(((
143 d:0~-~-9999
144
145 o:0-7
146 )))|
147 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
148 nn:0-9999,
149
150 dddd:0-9999,
151
152 o:0-7
153 )))|(((
154 nn:DB No.
155
156 dddd:address value
157
158 o: digit address
159 )))
160 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
161 |M|MW|MW d|d:0-99999|(((
162 MW0=MB(0~~1)
163
164 MW2=MB(2~~3)
165
166 Address value is a multiple of 2
167 )))
168 |M|MD|MD d|d:0-99999|(((
169 MD0=MB(0~~3)
170
171 MD4=MB(4~~7)
172
173 Address value is a multiple of 4
174 )))
175 |I|IW|IW d|d:0-99999|
176 |Q|QW|QW d|d:0-99999|
177 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
178 nn:0-9999
179
180 dddd:0-9999
181 )))|(((
182 nn:DB No.
183
184 dddd:address value
185 )))
186 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
187 nn:0-9999
188
189 dddd:0-9999
190 )))|(((
191 nn:DB No.
192
193 dddd:address value
194
195 Address value is a multiple of 2
196 )))
197 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
198 nn:0-9999
199
200 dddd:0-9999
201 )))|(((
202 nn:DB No.
203
204 dddd:address value
205
206 Address value is a multiple of 4
207 )))
208
209 **3)Configure the communication protocol**
210
211 {{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
212
213 **✎Note:**
214
215 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
216 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
217
218 **4)Cable Wiring**
219
220 {{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
221
222 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
223
224 Supported Series: Siemens Logo 0BA0, 0BA1 series
225
226 **V-BOX Settings**
227
228 |**Items**|**Settings**|**Note**
229 |Protocol|Siemens LOGO|
230 |Connection|Ethernet|
231 |Port No.|102|
232 |PLC station No.|2|
233
234 **Address List**
235
236 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
237 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
238 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
239 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
240 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
241 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
242 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
243 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
244 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
245 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
246 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
247 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
248 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
249 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
250 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
251 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
252
253 **PLC Settings in LOGO Software:**
254
255 Click [Tools]~-~-[Ethernet Connections],shown as below.
256
257 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
258
259 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
260
261 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
262
263 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
264
265 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
266
267 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
268
269 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
270
271 **V-BOX Communication Settings**
272
273 Set PLC IP in [IP Address] settings;
274
275 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
276
277 Enable V-BOX Ethernet in [Network];
278
279 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
280
281 TSAP setting
282
283 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
284
285 **function** **init**.main()
286 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
287 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
288 **end**
289
290 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
291
292 **✎Note:**
293
294 * **Communication port configuration: **
295 ** Continuous length needs to be set to 0.
296 ** Integration interval needs to be set to 1. (no change may result in data errors)
297 ** Set Port and Device Station NO.
298 ** Other set as defaulted.