Wiki source code of Siemens

Version 19.1 by Theodore Xu on 2023/08/25 16:17

Hide last authors
Leo Wei 2.1 1 = {{id name="HSiemens"/}}**Siemens ** =
2
Theodore Xu 16.1 3 == **S7-200 Smart Serial** ==
4
Theodore Xu 14.1 5 == **S7-200 Smart Ethernet ** ==
Leo Wei 2.1 6
7 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
8
Theodore Xu 17.1 9 (% class="wikigeneratedid" id="H1FF09V-BOX" %)
10 **1)V-BOX **
Theodore Xu 16.1 11
12 (% style="text-align:center" %)
13 [[image:西门子200smart 以太网.png]]
14
Theodore Xu 18.1 15 **2)PLC software**
Theodore Xu 14.1 16
17 (% style="text-align:center" %)
18 [[image:西门子软件版本.png]]
19
Theodore Xu 19.1 20 **3)PLC Software Configuration**
Theodore Xu 14.1 21
22 (% style="text-align:center" %)
23 [[image:以太网通讯配置.png]]
24
Theodore Xu 19.1 25 **4)Connect PC software and Download**
Theodore Xu 14.1 26
27 (% style="text-align:center" %)
Theodore Xu 19.1 28 [[image:以太网 PC和PLC连接.png]]
29
30
31 (% style="text-align:center" %)
Theodore Xu 14.1 32 [[image:以太网下载.png]]
33
Theodore Xu 15.1 34 **5)wiring**
35
36 V-Box : RJ45 Ethernet interface
37
38 PLC : RJ45 Ethernet interface
39
40 (% style="text-align:center" %)
41 [[image:以太网连接.png]]
42
Leo Wei 2.1 43 == {{id name="HS7-300Ethernet"/}}**S7-300 Ethernet ** ==
44
45 Supported Series: Siemens S7-300 series PLC
46
47 **1)V-BOX setting**
48
49 |**Items**|**Settings**|**Note**
50 |Protocol|Simens S7-300 Ethernet|
51 |Connection|Ethernet|
52 |Port No.|102|
53 |PLC station No.|2|Need to be same as the PLC setting
54
55 **2)Address List**
56
57 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
58 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
59 |Q|Q|Q ddddd.o|0.0~~99999.7|
60 |M|M|M ddddd.o|0.0~~99999.7|
61 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
62 nn: block number;
63
64 dddd: address;
65 )))
66 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
67 |Q|QW|QW ddddd|0~~99999|
68 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
69 |MW|MW ddddd|0~~99999|(((
70 MW0=MB(0~~1)
71
72 MW2=MB(2~~3)
73
74 Address value is a multiple of 2
75 )))
76 |MD|MD ddddd|0~~99999|(((
77 MD0=MB(0~~3)
78
79 MD4=MB(4~~7)
80
81 Address value is a multiple of 4
82 )))
83 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
84 nn: block number;
85
86 dddd: address
87 )))
88 |DBxDBW|DBxDBW nndddd|0~~99999999
89 |DBxDBD|DBxDBD nndddd|0~~99999999
90
91 **3)Configure the communication protocol**
92
93 {{id name="Iimage-20220824161345-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
94
95 **4)Cable Wiring**
96
97 {{id name="Iimage-20220824161450-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
98
99 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
100
101 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
102
103 == {{id name="HS7-XXXEthernetl"/}}**S7-XXX Ethernet l** ==
104
105 Supported Series: Siemens S7-400, S7-1200 and S7-1500
106
107 **1)V-BOX setting**
108
109 |=**Items**|=**Settings**|=**Note**
110 |Protocol|Siemens S7-XXX|
111 |Connection|Ethernet|
112 |Port No.|102|
113 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
114 |HMI No.|Rack (Default as 0)|
115
116 Slot from TIA Portal is equal to Device No. of V-net
117
118 Rack from TIA Portal is equal to HMI No. of V-net
119
120 {{id name="Iimage-20220824162459-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
121
122 {{id name="Iimage-20220824163305-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
123
124 **2)Address List**
125
126 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
127 |(% rowspan="4" %)Bit|I|I|M d.o|(((
128 d:0~-~-9999
129
130 o:0-7
131 )))|
132 |Q|Q|Q d.o|(((
133 d:0~-~-9999
134
135 o:0-7
136 )))|
137 |M|M|M d.o|(((
138 d:0~-~-9999
139
140 o:0-7
141 )))|
142 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
143 nn:0-9999,
144
145 dddd:0-9999,
146
147 o:0-7
148 )))|(((
149 nn:DB No.
150
151 dddd:address value
152
153 o: digit address
154 )))
155 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
156 |M|MW|MW d|d:0-99999|(((
157 MW0=MB(0~~1)
158
159 MW2=MB(2~~3)
160
161 Address value is a multiple of 2
162 )))
163 |M|MD|MD d|d:0-99999|(((
164 MD0=MB(0~~3)
165
166 MD4=MB(4~~7)
167
168 Address value is a multiple of 4
169 )))
170 |I|IW|IW d|d:0-99999|
171 |Q|QW|QW d|d:0-99999|
172 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
173 nn:0-9999
174
175 dddd:0-9999
176 )))|(((
177 nn:DB No.
178
179 dddd:address value
180 )))
181 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
182 nn:0-9999
183
184 dddd:0-9999
185 )))|(((
186 nn:DB No.
187
188 dddd:address value
189
190 Address value is a multiple of 2
191 )))
192 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
193 nn:0-9999
194
195 dddd:0-9999
196 )))|(((
197 nn:DB No.
198
199 dddd:address value
200
201 Address value is a multiple of 4
202 )))
203
204 **3)Configure the communication protocol**
205
206 {{id name="Iimage-20220824163448-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
207
208 **✎Note:**
209
210 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
211 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
212
213 **4)Cable Wiring**
214
215 {{id name="Iimage-20220824162342-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
216
217 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
218
219 Supported Series: Siemens Logo 0BA0, 0BA1 series
220
221 **V-BOX Settings**
222
223 |**Items**|**Settings**|**Note**
224 |Protocol|Siemens LOGO|
225 |Connection|Ethernet|
226 |Port No.|102|
227 |PLC station No.|2|
228
229 **Address List**
230
231 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
232 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
233 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
234 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
235 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
236 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
237 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
238 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
239 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
240 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
241 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
242 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
243 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
244 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
245 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
246 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
247
248 **PLC Settings in LOGO Software:**
249
250 Click [Tools]~-~-[Ethernet Connections],shown as below.
251
252 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
253
254 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
255
256 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
257
258 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
259
260 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
261
262 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
263
264 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
265
266 **V-BOX Communication Settings**
267
268 Set PLC IP in [IP Address] settings;
269
270 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
271
272 Enable V-BOX Ethernet in [Network];
273
274 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
275
276 TSAP setting
277
278 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
279
280 **function** **init**.main()
281 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
282 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
Theodore Xu 17.1 283 **end**
Leo Wei 2.1 284
285 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
286
287 **✎Note:**
288
289 * **Communication port configuration: **
290 ** Continuous length needs to be set to 0.
291 ** Integration interval needs to be set to 1. (no change may result in data errors)
292 ** Set Port and Device Station NO.
293 ** Other set as defaulted.
294 * **Notes on the use of registers:**
295 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
296 ** Register VW: Use only registers thay are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )