Wiki source code of Siemens

Version 44.1 by Theodore Xu on 2023/10/12 16:32

Hide last authors
Theodore Xu 16.1 1 == **S7-200 Smart Serial** ==
2
Theodore Xu 31.1 3 **V-BOX setting**
Theodore Xu 27.1 4
Theodore Xu 33.1 5 (% style="width:1323.87px" %)
Theodore Xu 37.1 6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
Theodore Xu 27.1 14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
Theodore Xu 31.1 18 **Address List **
Theodore Xu 27.1 19
Theodore Xu 39.1 20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
Theodore Xu 26.1 35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
Theodore Xu 39.1 41 |V|VD ddddd|0~~99998|(((
Theodore Xu 26.1 42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
Theodore Xu 39.1 48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
Theodore Xu 26.1 50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
Theodore Xu 39.1 56 |M|MD ddddd|0~~99999|(((
Theodore Xu 26.1 57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
Theodore Xu 39.1 63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
Theodore Xu 26.1 66
Theodore Xu 31.1 67 **PLC setting**
Theodore Xu 20.1 68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
Theodore Xu 31.1 75 **Connect and Download**
Theodore Xu 20.1 76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
Theodore Xu 31.1 83 **Cable Wiring**
Theodore Xu 20.1 84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
Theodore Xu 14.1 88 == **S7-200 Smart Ethernet ** ==
Leo Wei 2.1 89
Theodore Xu 32.1 90 **V-BOX setting**
Theodore Xu 16.1 91
Theodore Xu 34.1 92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
Theodore Xu 29.1 97
Theodore Xu 16.1 98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
Theodore Xu 32.1 101 **PLC setting**
Theodore Xu 14.1 102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
Theodore Xu 32.1 109 **Connect and Download**
Theodore Xu 14.1 110
111 (% style="text-align:center" %)
Theodore Xu 19.1 112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
Theodore Xu 14.1 115 [[image:以太网下载.png]]
116
Theodore Xu 32.1 117 **Cable Wiring**
Theodore Xu 15.1 118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
Theodore Xu 41.1 126 == **S7-300 Ethernet ** ==
Leo Wei 2.1 127
128 Supported Series: Siemens S7-300 series PLC
129
Theodore Xu 41.1 130 **V-BOX setting**
Leo Wei 2.1 131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
Theodore Xu 41.1 138 **Address List**
Leo Wei 2.1 139
Theodore Xu 40.1 140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
Leo Wei 2.1 145 nn: block number;
146
147 dddd: address;
148 )))
Theodore Xu 40.1 149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
Leo Wei 2.1 153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
Theodore Xu 40.1 159 |MD ddddd|0~~99999|(((
Leo Wei 2.1 160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
Theodore Xu 40.1 166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
Leo Wei 2.1 167 nn: block number;
168
169 dddd: address
170 )))
Theodore Xu 40.1 171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
Leo Wei 2.1 173
Theodore Xu 41.1 174 **Configure the communication protocol**
Leo Wei 2.1 175
Theodore Xu 41.1 176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
Leo Wei 2.1 177
Theodore Xu 41.1 178 **Cable Wiring**
Leo Wei 2.1 179
Theodore Xu 41.1 180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
Leo Wei 2.1 181
182 == {{id name="HS7-1200A0Ethernet"/}}**S7-1200 Ethernet ** ==
183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
Leo Wei 25.2 186 == **S7-XXX Ethernet** ==
Leo Wei 2.1 187
188 Supported Series: Siemens S7-400, S7-1200 and S7-1500
189
Theodore Xu 44.1 190 **V-BOX setting**
Leo Wei 2.1 191
192 |=**Items**|=**Settings**|=**Note**
193 |Protocol|Siemens S7-XXX|
194 |Connection|Ethernet|
195 |Port No.|102|
196 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
197 |HMI No.|Rack (Default as 0)|
198
199 Slot from TIA Portal is equal to Device No. of V-net
200
201 Rack from TIA Portal is equal to HMI No. of V-net
202
Theodore Xu 44.1 203 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
Leo Wei 2.1 204
Theodore Xu 44.1 205 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
Leo Wei 2.1 206
Theodore Xu 44.1 207 **Address List**
Leo Wei 2.1 208
Theodore Xu 42.1 209 |**Type**|**Device register**|**Format**|**Range**|**Note**
210 |(% rowspan="4" %)Bit|I|M d.o|(((
Leo Wei 2.1 211 d:0~-~-9999
212
213 o:0-7
214 )))|
Theodore Xu 42.1 215 |Q|Q d.o|(((
Leo Wei 2.1 216 d:0~-~-9999
217
218 o:0-7
219 )))|
Theodore Xu 42.1 220 |M|M d.o|(((
Leo Wei 2.1 221 d:0~-~-9999
222
223 o:0-7
224 )))|
Theodore Xu 42.1 225 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
Leo Wei 2.1 226 nn:0-9999,
227
228 dddd:0-9999,
229
230 o:0-7
231 )))|(((
232 nn:DB No.
233
234 dddd:address value
235
236 o: digit address
237 )))
Theodore Xu 42.1 238 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
239 |M|MW d|d:0-99999|(((
Leo Wei 2.1 240 MW0=MB(0~~1)
241
242 MW2=MB(2~~3)
243
244 Address value is a multiple of 2
245 )))
Theodore Xu 42.1 246 |M|MD d|d:0-99999|(((
Leo Wei 2.1 247 MD0=MB(0~~3)
248
249 MD4=MB(4~~7)
250
251 Address value is a multiple of 4
252 )))
Theodore Xu 42.1 253 |I|IW d|d:0-99999|
254 |Q|QW d|d:0-99999|
255 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
Leo Wei 2.1 256 nn:0-9999
257
258 dddd:0-9999
259 )))|(((
260 nn:DB No.
261
262 dddd:address value
263 )))
Theodore Xu 42.1 264 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
Leo Wei 2.1 265 nn:0-9999
266
267 dddd:0-9999
268 )))|(((
269 nn:DB No.
270
271 dddd:address value
272
273 Address value is a multiple of 2
274 )))
Theodore Xu 42.1 275 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
Leo Wei 2.1 276 nn:0-9999
277
278 dddd:0-9999
279 )))|(((
280 nn:DB No.
281
282 dddd:address value
283
284 Address value is a multiple of 4
285 )))
286
Theodore Xu 44.1 287 **Configure the communication protocol**
Leo Wei 2.1 288
Theodore Xu 44.1 289 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
Leo Wei 2.1 290
291 **✎Note:**
292
293 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
294 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
295
Theodore Xu 44.1 296 **Cable Wiring**
Leo Wei 2.1 297
Theodore Xu 44.1 298 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
Leo Wei 2.1 299
300 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
301
302 Supported Series: Siemens Logo 0BA0, 0BA1 series
303
304 **V-BOX Settings**
305
306 |**Items**|**Settings**|**Note**
307 |Protocol|Siemens LOGO|
308 |Connection|Ethernet|
309 |Port No.|102|
310 |PLC station No.|2|
311
312 **Address List**
313
314 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
315 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
316 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
317 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
318 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
319 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
320 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
321 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
322 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
323 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
324 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
325 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
326 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
327 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
328 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
329 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
330
331 **PLC Settings in LOGO Software:**
332
333 Click [Tools]~-~-[Ethernet Connections],shown as below.
334
335 {{id name="IPIStudio.125C.PLCprotocols.WebHome4012.PLCProtocol_html_8b9d2322edf89519.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
336
337 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
338
339 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228142937-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
340
341 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
342
343 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143047-5.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
344
345 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
346
347 {{id name="IPIStudio.125C.PLCprotocols.WebHome40image-20221228143246-6.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
348
349 **V-BOX Communication Settings**
350
351 Set PLC IP in [IP Address] settings;
352
353 {{id name="ILldwDGntf4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ab570912d299c09.png||alt="LldwDGntf4.png" height="530" width="899"]]
354
355 Enable V-BOX Ethernet in [Network];
356
357 {{id name="IWgvjfWbQif.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_637860db3ca1ca1b.png||alt="WgvjfWbQif.png" height="654" width="1195"]]
358
359 TSAP setting
360
361 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
362
363 **function** **init**.main()
364 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
365 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
Theodore Xu 17.1 366 **end**
Leo Wei 2.1 367
368 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
369
370 **✎Note:**
371
372 * **Communication port configuration: **
373 ** Continuous length needs to be set to 0.
374 ** Integration interval needs to be set to 1. (no change may result in data errors)
375 ** Set Port and Device Station NO.
376 ** Other set as defaulted.