Wiki source code of Siemens

Version 47.1 by Theodore Xu on 2024/02/27 19:56

Hide last authors
Theodore Xu 16.1 1 == **S7-200 Smart Serial** ==
2
Theodore Xu 31.1 3 **V-BOX setting**
Theodore Xu 27.1 4
Theodore Xu 33.1 5 (% style="width:1323.87px" %)
Theodore Xu 37.1 6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
Theodore Xu 27.1 14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
Theodore Xu 31.1 18 **Address List **
Theodore Xu 27.1 19
Theodore Xu 39.1 20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
Theodore Xu 26.1 35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
Theodore Xu 39.1 41 |V|VD ddddd|0~~99998|(((
Theodore Xu 26.1 42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
Theodore Xu 39.1 48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
Theodore Xu 26.1 50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
Theodore Xu 39.1 56 |M|MD ddddd|0~~99999|(((
Theodore Xu 26.1 57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
Theodore Xu 39.1 63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
Theodore Xu 26.1 66
Theodore Xu 31.1 67 **PLC setting**
Theodore Xu 20.1 68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
Theodore Xu 31.1 75 **Connect and Download**
Theodore Xu 20.1 76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
Theodore Xu 31.1 83 **Cable Wiring**
Theodore Xu 20.1 84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
Theodore Xu 14.1 88 == **S7-200 Smart Ethernet ** ==
Leo Wei 2.1 89
Theodore Xu 32.1 90 **V-BOX setting**
Theodore Xu 16.1 91
Theodore Xu 34.1 92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
Theodore Xu 29.1 97
Theodore Xu 16.1 98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
Theodore Xu 32.1 101 **PLC setting**
Theodore Xu 14.1 102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
Theodore Xu 32.1 109 **Connect and Download**
Theodore Xu 14.1 110
111 (% style="text-align:center" %)
Theodore Xu 19.1 112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
Theodore Xu 14.1 115 [[image:以太网下载.png]]
116
Theodore Xu 32.1 117 **Cable Wiring**
Theodore Xu 15.1 118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
Theodore Xu 41.1 126 == **S7-300 Ethernet ** ==
Leo Wei 2.1 127
128 Supported Series: Siemens S7-300 series PLC
129
Theodore Xu 41.1 130 **V-BOX setting**
Leo Wei 2.1 131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
Theodore Xu 41.1 138 **Address List**
Leo Wei 2.1 139
Theodore Xu 40.1 140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
Leo Wei 2.1 145 nn: block number;
146
147 dddd: address;
148 )))
Theodore Xu 40.1 149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
Leo Wei 2.1 153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
Theodore Xu 40.1 159 |MD ddddd|0~~99999|(((
Leo Wei 2.1 160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
Theodore Xu 40.1 166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
Leo Wei 2.1 167 nn: block number;
168
169 dddd: address
170 )))
Theodore Xu 40.1 171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
Leo Wei 2.1 173
Theodore Xu 41.1 174 **Configure the communication protocol**
Leo Wei 2.1 175
Theodore Xu 41.1 176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
Leo Wei 2.1 177
Theodore Xu 41.1 178 **Cable Wiring**
Leo Wei 2.1 179
Theodore Xu 41.1 180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
Leo Wei 2.1 181
Theodore Xu 45.1 182 == **S7-1200 Ethernet ** ==
Leo Wei 2.1 183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
Theodore Xu 45.1 186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
Theodore Xu 46.1 194 (% style="text-align:center" %)
195 [[image:西门子1200协议参数.png]]
196
Theodore Xu 45.1 197 **Address List**
198
199 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
200 |(% rowspan="4" %)Bit|I|I|M d.o|(((
201 d:0~-~-9999
202
203 o:0-7
204 )))|
205 |Q|Q|Q d.o|(((
206 d:0~-~-9999
207
208 o:0-7
209 )))|
210 |M|M|M d.o|(((
211 d:0~-~-9999
212
213 o:0-7
214 )))|
215 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
216 nn:0-9999,
217
218 dddd:0-9999,
219
220 o:0-7
221 )))|(((
222 nn:DB No.
223
224 dddd:address value
225
226 o: digit address
227 )))
228 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
229 |M|MW|MW d|d:0-99999|(((
230 MW0=MB(0~~1)
231
232 MW2=MB(2~~3)
233
234 Address value is a multiple of 2
235 )))
236 |M|MD|MD d|d:0-99999|(((
237 MD0=MB(0~~3)
238
239 MD4=MB(4~~7)
240
241 Address value is a multiple of 4
242 )))
243 |I|IW|IW d|d:0-99999|
244 |Q|QW|QW d|d:0-99999|
245 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
246 nn:0-9999
247
248 dddd:0-9999
249 )))|(((
250 nn:DB No.
251
252 dddd:address value
253 )))
254 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
255 nn:0-9999
256
257 dddd:0-9999
258 )))|(((
259 nn:DB No.
260
261 dddd:address value
262
263 Address value is a multiple of 2
264 )))
265 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
266 nn:0-9999
267
268 dddd:0-9999
269 )))|(((
270 nn:DB No.
271
272 dddd:address value
273
274 Address value is a multiple of 4
275 )))
276
Theodore Xu 46.1 277 {{info}}
278 ✎Note:
Theodore Xu 45.1 279
Theodore Xu 46.1 280 * The S7-1200 supports simultaneous connection of three devices.
281 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
282 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
283 * V-BOX operation character length needs to be set to 2 times the length of the Siemens character for proper display
284 {{/info}}
Theodore Xu 45.1 285
Theodore Xu 46.1 286 **PLC Settings**
287
288 Add BD
289
290 * Please uncheck [Symbolic access only] option;
291
292 (% style="text-align:center" %)
293 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_872ec32d12b55aa.png]]
294
295 Address settings, using BD2 as example.
296
297 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
298 * 2 represent DB block number
299 * xxxx represent address
300
301 **Such as:**
302
303 * DBxDBB20000 = DB2.DBB0
304 * DBxDBW20004 = DB2.DBW4
305
306 (% style="text-align:center" %)
307 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8ee8d3ac3637bfc4.png]]
308
309 **How to connect with S7-1200 Firmware V4.0**
310
311 PLC configuration
312
313 * Double click [device configuration] in Siemens via software
314 * Double click [protection] to enter protection configuration screen
315
316 (% style="text-align:center" %)
317 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_664a826cd356c830.png]]
318
319 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
320
321 (% style="text-align:center" %)
322 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_78026942a88f0fdb.png]]
323
324 DB settings
325
326 * Right click [DB], select [properties]
327 * Uncheck [optimized block access]
328
329 **Cable Wiring**
330
331 (% style="text-align:center" %)
332 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]]
333
Leo Wei 25.2 334 == **S7-XXX Ethernet** ==
Leo Wei 2.1 335
336 Supported Series: Siemens S7-400, S7-1200 and S7-1500
337
Theodore Xu 44.1 338 **V-BOX setting**
Leo Wei 2.1 339
340 |=**Items**|=**Settings**|=**Note**
341 |Protocol|Siemens S7-XXX|
342 |Connection|Ethernet|
343 |Port No.|102|
344 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
345 |HMI No.|Rack (Default as 0)|
346
347 Slot from TIA Portal is equal to Device No. of V-net
348
349 Rack from TIA Portal is equal to HMI No. of V-net
350
Theodore Xu 44.1 351 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
Leo Wei 2.1 352
Theodore Xu 44.1 353 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
Leo Wei 2.1 354
Theodore Xu 44.1 355 **Address List**
Leo Wei 2.1 356
Theodore Xu 42.1 357 |**Type**|**Device register**|**Format**|**Range**|**Note**
358 |(% rowspan="4" %)Bit|I|M d.o|(((
Leo Wei 2.1 359 d:0~-~-9999
360
361 o:0-7
362 )))|
Theodore Xu 42.1 363 |Q|Q d.o|(((
Leo Wei 2.1 364 d:0~-~-9999
365
366 o:0-7
367 )))|
Theodore Xu 42.1 368 |M|M d.o|(((
Leo Wei 2.1 369 d:0~-~-9999
370
371 o:0-7
372 )))|
Theodore Xu 42.1 373 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
Leo Wei 2.1 374 nn:0-9999,
375
376 dddd:0-9999,
377
378 o:0-7
379 )))|(((
380 nn:DB No.
381
382 dddd:address value
383
384 o: digit address
385 )))
Theodore Xu 42.1 386 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
387 |M|MW d|d:0-99999|(((
Leo Wei 2.1 388 MW0=MB(0~~1)
389
390 MW2=MB(2~~3)
391
392 Address value is a multiple of 2
393 )))
Theodore Xu 42.1 394 |M|MD d|d:0-99999|(((
Leo Wei 2.1 395 MD0=MB(0~~3)
396
397 MD4=MB(4~~7)
398
399 Address value is a multiple of 4
400 )))
Theodore Xu 42.1 401 |I|IW d|d:0-99999|
402 |Q|QW d|d:0-99999|
403 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
Leo Wei 2.1 404 nn:0-9999
405
406 dddd:0-9999
407 )))|(((
408 nn:DB No.
409
410 dddd:address value
411 )))
Theodore Xu 42.1 412 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
Leo Wei 2.1 413 nn:0-9999
414
415 dddd:0-9999
416 )))|(((
417 nn:DB No.
418
419 dddd:address value
420
421 Address value is a multiple of 2
422 )))
Theodore Xu 42.1 423 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
Leo Wei 2.1 424 nn:0-9999
425
426 dddd:0-9999
427 )))|(((
428 nn:DB No.
429
430 dddd:address value
431
432 Address value is a multiple of 4
433 )))
434
Theodore Xu 44.1 435 **Configure the communication protocol**
Leo Wei 2.1 436
Theodore Xu 44.1 437 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
Leo Wei 2.1 438
439 **✎Note:**
440
441 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
442 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
443
Theodore Xu 44.1 444 **Cable Wiring**
Leo Wei 2.1 445
Theodore Xu 44.1 446 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
Leo Wei 2.1 447
448 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
449
450 Supported Series: Siemens Logo 0BA0, 0BA1 series
451
452 **V-BOX Settings**
453
454 |**Items**|**Settings**|**Note**
455 |Protocol|Siemens LOGO|
456 |Connection|Ethernet|
457 |Port No.|102|
458 |PLC station No.|2|
459
460 **Address List**
461
462 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
463 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
464 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
465 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
466 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
467 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
468 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
469 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
470 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
471 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
472 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
473 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
474 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
475 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
476 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
477 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
478
479 **PLC Settings in LOGO Software:**
480
481 Click [Tools]~-~-[Ethernet Connections],shown as below.
482
Theodore Xu 46.1 483 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
Leo Wei 2.1 484
485 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
486
Theodore Xu 46.1 487 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_316247e0130c4c55.png||alt="image-20221228142937-4.png" height="484" width="366"]]
Leo Wei 2.1 488
489 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
490
Theodore Xu 46.1 491 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
Leo Wei 2.1 492
493 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
494
Theodore Xu 46.1 495 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
Leo Wei 2.1 496
497 **V-BOX Communication Settings**
498
499 Set PLC IP in [IP Address] settings;
500
Theodore Xu 47.1 501 (% style="text-align:center" %)
502 [[image:V-NET_Client logo8.png]]
Leo Wei 2.1 503
504
505 TSAP setting
506
507 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
508
509 **function** **init**.main()
510 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
511 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
Theodore Xu 17.1 512 **end**
Leo Wei 2.1 513
514 Note: The name of the test script is init, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
515
516 **✎Note:**
517
518 * **Communication port configuration: **
519 ** Continuous length needs to be set to 0.
520 ** Integration interval needs to be set to 1. (no change may result in data errors)
521 ** Set Port and Device Station NO.
522 ** Other set as defaulted.