Wiki source code of Siemens

Version 49.3 by Joe on 2024/04/30 14:53

Hide last authors
Theodore Xu 16.1 1 == **S7-200 Smart Serial** ==
2
Theodore Xu 31.1 3 **V-BOX setting**
Theodore Xu 27.1 4
Theodore Xu 33.1 5 (% style="width:1323.87px" %)
Theodore Xu 37.1 6 |**Items**|**Settings**|**Note**
7 |Protocol|(% style="width:783px" %)Siemens S7-200 CPU22x/Smart PPI|
8 |Connection|(% style="width:783px" %)RS485|
9 |Baud rate|(% style="width:783px" %)9600|
10 |Data bit|(% style="width:783px" %)8|
11 |Parity|(% style="width:783px" %)EVEN|
12 |Stop bit|(% style="width:783px" %)1|
13 |PLC station No.|(% style="width:783px" %)2|
Theodore Xu 27.1 14
15 (% style="text-align:center" %)
16 [[image:西门子200串口.png]]
17
Theodore Xu 31.1 18 **Address List **
Theodore Xu 27.1 19
Theodore Xu 39.1 20 |**Type**|**Device register**|**Format**|**Range**|**Note**
21 |(% rowspan="9" %)Bit|I|I ddddd.o|0.0~~99999.7|
22 |Q|Q ddddd.o|0.0~~99999.7|
23 |V|VWbit ddddd.o|0.0~~99999.7|
24 |V|V ddddd.o|0.0~~99999.7|
25 |M|M ddddd.o|0.0~~99999.7|
26 |SM|ddddd.o|0.0~~99999.7|
27 |S|ddddd.o|0.0~~99999.7|Read only
28 |T|ddddd|0~~99999|Timer state, read only
29 |C|ddddd|0~~99999|Counter state, read only
30 |(% rowspan="12" %)Word|I|IW ddddd|0~~99999|
31 |Q|QW ddddd|0~~99999|
32 |AI|AIW ddddd|0~~99999|
33 |AQ|VB ddddd|0~~99999|
34 |V|VW ddddd|0~~99998|(((
Theodore Xu 26.1 35 VW0=VB (0~~1)
36
37 VW2=VB (2~~3)
38
39 Address value is a multiple of 2
40 )))
Theodore Xu 39.1 41 |V|VD ddddd|0~~99998|(((
Theodore Xu 26.1 42 VD0=VB (0~~3)
43
44 VD2=VB (4~~7)
45
46 Address value is a multiple of 4
47 )))
Theodore Xu 39.1 48 |M|MB ddddd|0~~99999|
49 |M|MW ddddd|0~~99999|(((
Theodore Xu 26.1 50 MW0=MB(0~~1)
51
52 MW2=MB(2~~3)
53
54 Address value is a multiple of 2
55 )))
Theodore Xu 39.1 56 |M|MD ddddd|0~~99999|(((
Theodore Xu 26.1 57 MD0=MB(0~~3)
58
59 MD4=MB(4~~7)
60
61 Address value is a multiple of 4
62 )))
Theodore Xu 39.1 63 |T|TW ddddd|0~~99999|Value of timer
64 |C|CW ddddd|0~~99999|Value of counter
65 |W|SW ddddd|0~~99999|
Theodore Xu 26.1 66
Theodore Xu 31.1 67 **PLC setting**
Theodore Xu 20.1 68
69 (% style="text-align:center" %)
70 [[image:西门子软件版本.png]]
71
72 (% style="text-align:center" %)
73 [[image:485通讯配置.png]]
74
Theodore Xu 31.1 75 **Connect and Download**
Theodore Xu 20.1 76
77 (% style="text-align:center" %)
78 [[image:以太网 PC和PLC连接.png]]
79
80 (% style="text-align:center" %)
81 [[image:以太网下载.png]]
82
Theodore Xu 31.1 83 **Cable Wiring**
Theodore Xu 20.1 84
85 (% style="text-align:center" %)
86 [[image:485接线.png]]
87
Theodore Xu 14.1 88 == **S7-200 Smart Ethernet ** ==
Leo Wei 2.1 89
Theodore Xu 32.1 90 **V-BOX setting**
Theodore Xu 16.1 91
Theodore Xu 34.1 92 |**Items**|**Settings**
93 |Protocol|Siemens S7-200 Smart(Ethernet)
94 |Connection|Ethernet
95 |Port No.|102
96 |PLC station No.|2
Theodore Xu 29.1 97
Theodore Xu 16.1 98 (% style="text-align:center" %)
99 [[image:西门子200smart 以太网.png]]
100
Theodore Xu 32.1 101 **PLC setting**
Theodore Xu 14.1 102
103 (% style="text-align:center" %)
104 [[image:西门子软件版本.png]]
105
106 (% style="text-align:center" %)
107 [[image:以太网通讯配置.png]]
108
Theodore Xu 32.1 109 **Connect and Download**
Theodore Xu 14.1 110
111 (% style="text-align:center" %)
Theodore Xu 19.1 112 [[image:以太网 PC和PLC连接.png]]
113
114 (% style="text-align:center" %)
Theodore Xu 14.1 115 [[image:以太网下载.png]]
116
Theodore Xu 32.1 117 **Cable Wiring**
Theodore Xu 15.1 118
119 V-Box : RJ45 Ethernet interface
120
121 PLC : RJ45 Ethernet interface
122
123 (% style="text-align:center" %)
124 [[image:以太网连接.png]]
125
Theodore Xu 41.1 126 == **S7-300 Ethernet ** ==
Leo Wei 2.1 127
128 Supported Series: Siemens S7-300 series PLC
129
Theodore Xu 41.1 130 **V-BOX setting**
Leo Wei 2.1 131
132 |**Items**|**Settings**|**Note**
133 |Protocol|Simens S7-300 Ethernet|
134 |Connection|Ethernet|
135 |Port No.|102|
136 |PLC station No.|2|Need to be same as the PLC setting
137
Theodore Xu 41.1 138 **Address List**
Leo Wei 2.1 139
Theodore Xu 40.1 140 |**Type**|**Device register**|**Format**|**Range**|**Note**
141 |(% rowspan="4" %)Bit|I|I ddddd.o|0.0~~99999.7|
142 |Q|Q ddddd.o|0.0~~99999.7|
143 |M|M ddddd.o|0.0~~99999.7|
144 |DB0.DB~~DB99.DB|DBxDB nndddd.o|0.0~~99999999.7|(((
Leo Wei 2.1 145 nn: block number;
146
147 dddd: address;
148 )))
Theodore Xu 40.1 149 |(% rowspan="8" %)Word|I|IW ddddd|0~~99999|
150 |Q|QW ddddd|0~~99999|
151 |(% rowspan="3" %)M|MB ddddd|0~~99999|
152 |MW ddddd|0~~99999|(((
Leo Wei 2.1 153 MW0=MB(0~~1)
154
155 MW2=MB(2~~3)
156
157 Address value is a multiple of 2
158 )))
Theodore Xu 40.1 159 |MD ddddd|0~~99999|(((
Leo Wei 2.1 160 MD0=MB(0~~3)
161
162 MD4=MB(4~~7)
163
164 Address value is a multiple of 4
165 )))
Theodore Xu 40.1 166 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
Leo Wei 2.1 167 nn: block number;
168
169 dddd: address
170 )))
Theodore Xu 40.1 171 |DBxDBW nndddd|0~~99999999
172 |DBxDBD nndddd|0~~99999999
Leo Wei 2.1 173
Theodore Xu 41.1 174 **Configure the communication protocol**
Leo Wei 2.1 175
Theodore Xu 41.1 176 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_8e00ed9483ddb629.png||alt="image-20220824161345-1.png" height="1011" width="1920"]]
Leo Wei 2.1 177
Theodore Xu 41.1 178 **Cable Wiring**
Leo Wei 2.1 179
Theodore Xu 41.1 180 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824161450-2.png" height="170" width="401"]]
Leo Wei 2.1 181
Theodore Xu 45.1 182 == **S7-1200 Ethernet ** ==
Leo Wei 2.1 183
184 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
185
Theodore Xu 45.1 186 **V-BOX Setting**
187
188 |**Items**|**Settings**|**Note**
189 |Protocol|Siemens S7-1200|
190 |Connection|Ethernet|
191 |Port No.|102|
192 |PLC station No.|2|
193
Theodore Xu 46.1 194 (% style="text-align:center" %)
195 [[image:西门子1200协议参数.png]]
196
Theodore Xu 45.1 197 **Address List**
198
199 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
200 |(% rowspan="4" %)Bit|I|I|M d.o|(((
201 d:0~-~-9999
202
203 o:0-7
204 )))|
205 |Q|Q|Q d.o|(((
206 d:0~-~-9999
207
208 o:0-7
209 )))|
210 |M|M|M d.o|(((
211 d:0~-~-9999
212
213 o:0-7
214 )))|
215 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
216 nn:0-9999,
217
218 dddd:0-9999,
219
220 o:0-7
221 )))|(((
222 nn:DB No.
223
224 dddd:address value
225
226 o: digit address
227 )))
228 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
229 |M|MW|MW d|d:0-99999|(((
230 MW0=MB(0~~1)
231
232 MW2=MB(2~~3)
233
234 Address value is a multiple of 2
235 )))
236 |M|MD|MD d|d:0-99999|(((
237 MD0=MB(0~~3)
238
239 MD4=MB(4~~7)
240
241 Address value is a multiple of 4
242 )))
243 |I|IW|IW d|d:0-99999|
244 |Q|QW|QW d|d:0-99999|
245 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
246 nn:0-9999
247
248 dddd:0-9999
249 )))|(((
250 nn:DB No.
251
252 dddd:address value
253 )))
254 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
255 nn:0-9999
256
257 dddd:0-9999
258 )))|(((
259 nn:DB No.
260
261 dddd:address value
262
263 Address value is a multiple of 2
264 )))
265 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
266 nn:0-9999
267
268 dddd:0-9999
269 )))|(((
270 nn:DB No.
271
272 dddd:address value
273
274 Address value is a multiple of 4
275 )))
276
Theodore Xu 46.1 277 {{info}}
278 ✎Note:
Theodore Xu 45.1 279
Theodore Xu 46.1 280 * The S7-1200 supports simultaneous connection of three devices.
281 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (S7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
282 * S7-1200 String type, the default first two bytes are used to store the maximum character and valid characters, so the text data will be shifted back one word address. When interacting with the data, what way this address plc is displayed with is unknown. And because of an extra word of data causes us to display the wrong. The solution is if we use String, then the actual data address we want to operate on is actually shifted back two bytes, so as long as the address on the project is shifted back 2 bits to correspond with the actual data address.
283 {{/info}}
Theodore Xu 45.1 284
Theodore Xu 46.1 285 **PLC Settings**
286
287 Add BD
288
289 * Please uncheck [Symbolic access only] option;
290
291 (% style="text-align:center" %)
292 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_872ec32d12b55aa.png]]
293
294 Address settings, using BD2 as example.
295
296 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
297 * 2 represent DB block number
298 * xxxx represent address
299
300 **Such as:**
301
302 * DBxDBB20000 = DB2.DBB0
303 * DBxDBW20004 = DB2.DBW4
304
305 (% style="text-align:center" %)
306 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8ee8d3ac3637bfc4.png]]
307
Joe 49.3 308 **How to setting String in PLC and V-net**
309 PLC configuration
310
311 choosing Data type~-~-String→add"[]" after String and input data length
312
313 (% style="text-align:center" %)
314 [[image:yUYuRVmMcL.png]]
315
316 V-box configuration
317
318 (% style="text-align:center" %)
319 [[image:BSRBeEWL0O.png]]
320
321 choosing Word and DBxDBW →input  register number →Data format is String →input data length you want to use → choosing Byte corder~-~-Little-endian
322
Theodore Xu 46.1 323 **How to connect with S7-1200 Firmware V4.0**
324
325 PLC configuration
326
327 * Double click [device configuration] in Siemens via software
328 * Double click [protection] to enter protection configuration screen
329
330 (% style="text-align:center" %)
331 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_664a826cd356c830.png]]
332
333 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
334
335 (% style="text-align:center" %)
336 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_78026942a88f0fdb.png]]
337
338 DB settings
339
340 * Right click [DB], select [properties]
341 * Uncheck [optimized block access]
342
343 **Cable Wiring**
344
345 (% style="text-align:center" %)
346 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png]]
347
Leo Wei 25.2 348 == **S7-XXX Ethernet** ==
Leo Wei 2.1 349
350 Supported Series: Siemens S7-400, S7-1200 and S7-1500
351
Theodore Xu 44.1 352 **V-BOX setting**
Leo Wei 2.1 353
354 |=**Items**|=**Settings**|=**Note**
355 |Protocol|Siemens S7-XXX|
356 |Connection|Ethernet|
357 |Port No.|102|
358 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
359 |HMI No.|Rack (Default as 0)|
360
361 Slot from TIA Portal is equal to Device No. of V-net
362
363 Rack from TIA Portal is equal to HMI No. of V-net
364
Theodore Xu 44.1 365 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d78bc267e5fc6394.png||alt="image-20220824162459-3.png" height="503" width="798"]]
Leo Wei 2.1 366
Theodore Xu 44.1 367 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c9ae84ef5d418580.png||alt="image-20220824163305-2.png" height="1009" width="1920"]]
Leo Wei 2.1 368
Theodore Xu 44.1 369 **Address List**
Leo Wei 2.1 370
Theodore Xu 42.1 371 |**Type**|**Device register**|**Format**|**Range**|**Note**
372 |(% rowspan="4" %)Bit|I|M d.o|(((
Leo Wei 2.1 373 d:0~-~-9999
374
375 o:0-7
376 )))|
Theodore Xu 42.1 377 |Q|Q d.o|(((
Leo Wei 2.1 378 d:0~-~-9999
379
380 o:0-7
381 )))|
Theodore Xu 42.1 382 |M|M d.o|(((
Leo Wei 2.1 383 d:0~-~-9999
384
385 o:0-7
386 )))|
Theodore Xu 42.1 387 |DB0.DB-DB99.DB|DBxDBnndddd.o|(((
Leo Wei 2.1 388 nn:0-9999,
389
390 dddd:0-9999,
391
392 o:0-7
393 )))|(((
394 nn:DB No.
395
396 dddd:address value
397
398 o: digit address
399 )))
Theodore Xu 42.1 400 |(% rowspan="8" %)Word|M|MB d|d:0-99999|
401 |M|MW d|d:0-99999|(((
Leo Wei 2.1 402 MW0=MB(0~~1)
403
404 MW2=MB(2~~3)
405
406 Address value is a multiple of 2
407 )))
Theodore Xu 42.1 408 |M|MD d|d:0-99999|(((
Leo Wei 2.1 409 MD0=MB(0~~3)
410
411 MD4=MB(4~~7)
412
413 Address value is a multiple of 4
414 )))
Theodore Xu 42.1 415 |I|IW d|d:0-99999|
416 |Q|QW d|d:0-99999|
417 |DB0.DB-DB99.DB|DBxDBBnndddd|(((
Leo Wei 2.1 418 nn:0-9999
419
420 dddd:0-9999
421 )))|(((
422 nn:DB No.
423
424 dddd:address value
425 )))
Theodore Xu 42.1 426 |DB0.DB-DB99.DB|DBxDBWnndddd|(((
Leo Wei 2.1 427 nn:0-9999
428
429 dddd:0-9999
430 )))|(((
431 nn:DB No.
432
433 dddd:address value
434
435 Address value is a multiple of 2
436 )))
Theodore Xu 42.1 437 |DB0.DB-DB99.DB|DBxDBDnndddd|(((
Leo Wei 2.1 438 nn:0-9999
439
440 dddd:0-9999
441 )))|(((
442 nn:DB No.
443
444 dddd:address value
445
446 Address value is a multiple of 4
447 )))
448
Theodore Xu 44.1 449 **Configure the communication protocol**
Leo Wei 2.1 450
Theodore Xu 44.1 451 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_9e740a8bf83ea3bf.png||alt="image-20220824163448-3.png" height="557" width="974"]]
Leo Wei 2.1 452
453 **✎Note:**
454
455 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
456 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
457
Theodore Xu 44.1 458 **Cable Wiring**
Leo Wei 2.1 459
Theodore Xu 44.1 460 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ac8ece9a26719fda.png||alt="image-20220824162342-2.png" height="170" width="401"]]
Leo Wei 2.1 461
462 == {{id name="HLOGOEthernet"/}}**LOGO Ethernet ** ==
463
464 Supported Series: Siemens Logo 0BA0, 0BA1 series
465
466 **V-BOX Settings**
467
468 |**Items**|**Settings**|**Note**
469 |Protocol|Siemens LOGO|
470 |Connection|Ethernet|
471 |Port No.|102|
472 |PLC station No.|2|
473
474 **Address List**
475
476 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
477 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
478 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
479 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
480 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
481 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
482 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
483 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
484 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
485 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
486 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
487 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
488 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
489 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
490 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
491 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
492
493 **PLC Settings in LOGO Software:**
494
495 Click [Tools]~-~-[Ethernet Connections],shown as below.
496
Theodore Xu 46.1 497 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d13df637bfedcc52.png||alt="12.PLC Protocol_html_8b9d2322edf89519.png" height="641" width="423"]]
Leo Wei 2.1 498
499 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
500
Joe 48.2 501 (% style="text-align:center" %)
502 [[image:hXadxkZTuR.png]]
Leo Wei 2.1 503
Joe 48.2 504 **TSAP set**: The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
Leo Wei 2.1 505
Theodore Xu 46.1 506 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_facc6ee1af05162f.png||alt="image-20221228143047-5.png" height="626" width="1088"]]
Leo Wei 2.1 507
508 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
509
Theodore Xu 46.1 510 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_d43d2b7b2599ee64.png||alt="image-20221228143246-6.png" height="698" width="688"]]
Leo Wei 2.1 511
512 **V-BOX Communication Settings**
513
514 Set PLC IP in [IP Address] settings;
515
Theodore Xu 47.1 516 (% style="text-align:center" %)
Theodore Xu 48.1 517 [[image:V-NET_Client logo.png]]
Leo Wei 2.1 518
519 TSAP setting
520
521 * The initialization script needs to set the source TSAP address and the target TSAP address, otherwise the communication will not be successful.
522
Joe 48.2 523 You can copy the following script into V-net directly.
524
525 (% class="box successmessage" %)
526 (((
Leo Wei 2.1 527 **function** **init**.main()
528 addr_setword("@W_0#HSW1200",8192) //~-~- Set the source TSAP address//
529 addr_setword("@W_0#HSW1201",4096) //~-~- Set the destination TSAP address//
Theodore Xu 17.1 530 **end**
Joe 48.2 531 )))
Leo Wei 2.1 532
Joe 48.2 533 (% class="box infomessage" %)
534 (((
535 Note:
536 The name of the test script must be “init”, 8192 and 4096 are the data used for the test, there is no HSW address in the register option, but you can directly set the value of the corresponding address through the code.
537 )))
Leo Wei 2.1 538
539 **✎Note:**
540
541 * **Communication port configuration: **
542 ** Continuous length needs to be set to 0.
543 ** Integration interval needs to be set to 1. (no change may result in data errors)
544 ** Set Port and Device Station NO.
545 ** Other set as defaulted.
546 * **Notes on the use of registers:**
547 ** Register VD: Use only registers that are multiples of 4, such as 0, 4, 8, etc.
Joe 48.2 548 ** Register VW: Use only registers they are multiples of 2, such as 0, 2, 4 etc. (Using an odd-length register may result in data errors, such as 2 3 4 )