2.1 | 1 | = WECON = |
2 | |||
3 | == {{id name="HLX3VSerial"/}}**LX3V Serial ** == | ||
4 | |||
5 | Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM | ||
6 | |||
7 | **1)V-BOX setting** | ||
8 | |||
9 | |**Item**|**Settings**|**Note** | ||
10 | |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| | ||
11 | |Connection|RS422/RS485| | ||
12 | |Baud rate|9600| | ||
13 | |Data bit|7| | ||
14 | |Parity|EVEN| | ||
15 | |Stop bit|1| | ||
16 | |PLC station No.|1| | ||
17 | |||
18 | **2)Address List** | ||
19 | |||
20 | |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** | ||
21 | |(% rowspan="6" %)Bit|X|X|Xo|0~~303237| | ||
22 | |Y|Y|Y o|0~~303237| | ||
23 | |M|M|M d|0~~99999| | ||
24 | |T|T|T d|0~~99999| | ||
25 | |C|C|C d|0~~99999| | ||
26 | |S|S|S d|0~~99999| | ||
27 | |(% rowspan="8" %)Word|X|X|Xo|0~~303237| | ||
28 | |Y|Y|Y o|0~~303237| | ||
29 | |M|M|M d|0~~99999| | ||
30 | |T|T|T d|0~~99999| | ||
31 | |C|C|C d|0~~199| | ||
32 | |D|D|D d|0~~7999| | ||
33 | |S|S|S d|0~~99999| | ||
34 | |SD|SD|SD d|8000~~9999| | ||
35 | |||
36 | **3)Configure the communication protocol** | ||
37 | |||
38 | {{id name="Iimage-20220824152217-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_96093afacee1e597.png||alt="图片-20220824152217-1.png" height="1009" width="1920"]] | ||
39 | |||
40 | **4)Cable Wiring** | ||
41 | |||
42 | * **RS422** | ||
43 | |||
44 | {{id name="Iimage-20220824120614-5.png"/}} [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c30060d3e993c4c2.png||alt="image-20220824120614-5.png" height="197" width="360"]] | ||
45 | |||
46 | * **RS485** | ||
47 | |||
48 | {{id name="Iimage-20220824120524-3.png"/}} [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_97a300cba250cee3.png||alt="image-20220824120524-3.png" height="207" width="400"]] | ||
49 | |||
50 | == {{id name="HLX5VA0Serial"/}}**LX5V Serial ** == | ||
51 | |||
52 | This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring. | ||
53 | |||
54 | **Software configuration of PLC** | ||
55 | |||
56 | **1)PLC programming software** | ||
57 | |||
58 | {{id name="Iimage-20220824142722-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7599c2849074f02b.png||alt="image-20220824142722-1.png" height="326" width="424"]] | ||
59 | |||
60 | **2)New PLC project** | ||
61 | |||
62 | Click New Project and select the PLC model. | ||
63 | |||
64 | {{id name="Iimage-20220822172623-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_41288d6ab0e1b8b2.png||alt="image-20220822172623-2.png" height="646" width="1203"]] | ||
65 | |||
66 | **3)Set Serial port parameters** | ||
67 | |||
68 | Follow the steps below to configure Serial port parameters | ||
69 | |||
70 | Baud rate:115200 | ||
71 | |||
72 | Data bit:8 | ||
73 | |||
74 | Stop bit:1 | ||
75 | |||
76 | Parity:No verification | ||
77 | |||
78 | {{id name="Iimage-20220822172657-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_6c30b7a00702b588.png||alt="image-20220822172657-3.png" height="648" width="1206"]] | ||
79 | |||
80 | **4)Registers list** | ||
81 | |||
82 | {{id name="Iimage-20220822172730-4.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ea5d81cedd19868c.png||alt="image-20220822172730-4.png" height="644" width="1197"]] | ||
83 | |||
84 | **V-BOX software configuration** | ||
85 | |||
86 | **1)V-BOX programming software** | ||
87 | |||
88 | {{id name="Iimage-20220824104124-1.png"/}} [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_5f3372d6421c7729.png||alt="image-20220824104124-1.png" height="446" width="732"]] | ||
89 | |||
90 | **2)V-NET add device** | ||
91 | |||
92 | Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device. | ||
93 | |||
94 | {{id name="Iimage-20220824104909-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_5ccc2489b6abfb.png||alt="image-20220824104909-2.png" height="1021" width="1895"]] | ||
95 | |||
96 | **3)Set communication port parameters** | ||
97 | |||
98 | Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. | ||
99 | |||
100 | Baud rate:115200 | ||
101 | |||
102 | Data bit:8 | ||
103 | |||
104 | Stop bit:1 | ||
105 | |||
106 | Parity:No verification | ||
107 | |||
108 | {{id name="Iimage-20220824142130-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_81423b8c5e2372d0.png||alt="image-20220824142130-1.png" height="1011" width="1920"]] | ||
109 | |||
110 | **hardware connection** | ||
111 | |||
112 | **1)Hardware wiring diagram** | ||
113 | |||
114 | {{id name="Iimage-20220824142546-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c263ecbe93db8ca4.png||alt="image-20220824142546-2.png" height="221" width="818"]] | ||
115 | |||
116 | {{id name="Iimage-20220824142643-3.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_b00640983fe9076f.png||alt="image-20220824142643-3.png" height="235" width="403"]] | ||
117 | |||
118 | The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC. | ||
119 | |||
120 | == {{id name="HLX5V-NEthernet"/}}**LX5V-N Ethernet ** == | ||
121 | |||
122 | This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring. | ||
123 | |||
124 | **Software configuration of PLC** | ||
125 | |||
126 | **1)PLC programming software** | ||
127 | |||
128 | {{id name="Iimage-20220824142722-1.png-1"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_7599c2849074f02b.png||alt="image-20220824142722-1.png" height="326" width="424"]] | ||
129 | |||
130 | **2)New PLC project** | ||
131 | |||
132 | Click New Project and select the PLC model. | ||
133 | |||
134 | {{id name="Iimage-20220824143613-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_c2ed710651b46a92.png||alt="image-20220824143613-1.png" height="1028" width="1920"]] | ||
135 | |||
136 | **3)Set Ethernet port parameters** | ||
137 | |||
138 | Follow the steps below to configure Ethernet parameters | ||
139 | |||
140 | PLC IP address:192.168.39.200 | ||
141 | |||
142 | default gateway:192.168.39.1 | ||
143 | |||
144 | subnet mask:255.255.255.0 | ||
145 | |||
146 | {{id name="Iimage-20220824143744-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_60404ed3c7204071.png||alt="image-20220824143744-2.png" height="1031" width="1920"]] | ||
147 | |||
148 | **4)Registers list** | ||
149 | |||
150 | {{id name="Iimage-20220822172730-4.png-1"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_ea5d81cedd19868c.png||alt="image-20220822172730-4.png" height="644" width="1197"]] | ||
151 | |||
152 | {{id name="cke_bm_22473S"/}}** V-BOX software configuration** | ||
153 | |||
154 | **1)V-BOX programming software** | ||
155 | |||
156 | {{id name="Iimage-20220824104124-1.png-1"/}} [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_5f3372d6421c7729.png||alt="image-20220824104124-1.png" height="446" width="732"]] | ||
157 | |||
158 | **2)V-NET add device** | ||
159 | |||
160 | Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device. | ||
161 | |||
162 | {{id name="Iimage-20220824104909-2.png-1"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_5ccc2489b6abfb.png||alt="image-20220824104909-2.png" height="1021" width="1895"]] | ||
163 | |||
164 | **3)Set communication Protocol** | ||
165 | |||
166 | Click Communication to configure the LX5V plc protocol and IP address. | ||
167 | |||
168 | {{id name="Iimage-20220824144619-1.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_839390ad71e3603a.png||alt="image-20220824144619-1.png" height="1009" width="1920"]] | ||
169 | |||
170 | **hardware connection** | ||
171 | |||
172 | **1)Hardware wiring diagram** | ||
173 | |||
174 | {{id name="Iimage-20220824151127-2.png"/}}[[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_6322371917d6fb55.png||alt="image-20220824151127-2.png" height="269" width="662"]] | ||