Xinje

Last modified by Theodore Xu on 2023/11/06 10:28

XC serial

Support Series: Xinjie XC Series

V-Box Settings

ItemSettingsNote
ProtocolXINJE XC MODBUS 
ConnectionRS232 
Baud rate19200 
Data bit8 
ParityEVEN 
Stop bit1 
PLC station No.1 

image-20220831163041-1.png

Address List

TypeDevice registersHMI registersFormatRangeNote
BitMMM d0~8511 
BitXXX o0~1747 
BitYYY o0~1747 
BitSSS d0~1023 
BitTTT d0~4095 
BitCCC d0~634 
WordDDD d0~8511 
WordTDTDTD d0~618 
WordCDCDCD d0~634 
WordFDFDFD d0~8511 

PLC Settings

Create the new project, and select the specific model according to the actual PLC

XinjieXCcreatenew.png

Program the PLC

XinjieXCPrg.png

Connect PLC with PC through RS232-USB converter cable. Click [Option]-[Software Serial Port Config] to open the software connection setup window, and select the serial port, if the red text prompt "Connect To PLC Succeeded", which means the connection is setup successfully, then click OK to save the settings.

XinjieXCPCconn.png

Change the PLC communication setup if required. Double click the tree node [PLC Serial Port] from Project tree. And change Modbus parameters, then click [Write to PLC] and OK to finish.

XinjieXCPLCModbusConfig.png

Click [Online]-[Download Program] to download program into PLC. And the download pop up window would pop up, then click OK.

XinjieXCDownloadPLC.png

Cable Wiring

Figure

image-20220831163406-2.png image-20220831163422-3.png

Pin Definition Diagram

image-20220831163441-4.png

XD serial

V-Box Settings

Supported Series: Xinjie XD/XE Series PLC

ItemSettingsNote
ProtocolXINJE XD/XC MODBUS 
ConnectionRS232 
Baud rate19200 
Data bit8 
ParityEVEN 
Stop bit1 
PLC station No.1 

image-20220831163923-7.png

Address List

TypeDevice registersHMI registersFormatRangeNote
BitMMM d0~74999 
BitX1xxX1xxX1xx o0~1177 
BitX2xxX2xxX2xx o0~277 
BitXXX o0~77 
BitY1xxY1xxY1xx o0~1177 
BitY2xxY2xxY2xx o0~277 
BitYYY o0~4095 
BitSMSMSM d0~4999 
BitTTT d0~4999 
BitCCC d0~4999 
BitETETET d0~31 
BitSESESE d0~31 
BitHMHMHM d0~11999 
BitHSCHSCHSC d0~39 
BitHSHSHS d0~999 
BitHTHTHT d0~1999 
BitHCHCHC d0~1999 
BitSSS d0~7999 
WordDDD d0~69999 
WordIDIDID d0~99 
WordID1xxID1xxID1xx d0~999 
WordID2xxID2xxID2xx d0~299 
WordQDQDQD d0~99 
WordQD1xxQD1xxQD1xx d0~999 
WordQD2xxQD2xxQD2xx d0~299 
WordSDSDSD d0~4999 
WordTDTDTD d0~575 
WordCDCDCD d0~575 
WordETDETDETD d0~31 
WordHDHDHD d0~24999 
WordHSDHSDHSD d0~1023 
WordHTDHTDHTD d0~95 
WordHCDHCDHCD d0~95 
WordHSCDHSCDHSCD d0~31 
WordFDFDFD d0~8191 
WordSFDSFDSFD d0~5999 
WordFSFSFS d0~47 

PLC Settings

Create the new project, and select the specific model according to the actual PLC

XinjieXDcreatenew.png

Program the PLC

XinjieXDLDprg.png

Connect PLC with PC through RS232-USB converter cable. Click [Option]-[Software Serial Port Config]-[Communication configuration] to open the PC connection configuration.

XinjieXDopenSWcom (1).png

New a Modbus configuration, and Click [Comm-Test] to test connection, if shows "Connect To PLC Succeeded", which means PLC connection set up successfully. And click OK to save the settings.

XinjieXDPLCtestconn.png

Remember to click the Status cell of new created Modbus configuration for change the status into "in use", then click OK to exit.

XinjieXDclickto.png

After done the previous steps, it would prompt like the below.

XinjieXDsuccessprompt.png

Click [Online]-[Download Program & Data], and wait for a while, the pop up window would ask for whether to stop PLC, and click [Stop PLC, contitue download]

XinjieXDdownload.png

And then the XDPro ask for which options want to rewrite, and click OK to finish.

XinjieXDdownloadopt.png

If download successfully, it would prompt like the below.

XinjieXDcomplete.png

Cable Wiring

Figure

image-20220831163406-2.png image-20220831163553-6.png

Pin Definition Diagram

image-20220830160232-3.png