1 = **XC serial** =
2
3 Support Series: Xinjie XC Series
4
5 **V-Box Settings**
6
7 |**Item**|**Settings**|**Note**
8 |Protocol|XINJE XC MODBUS|
9 |Connection|RS232|
10 |Baud rate|19200|
11 |Data bit|8|
12 |Parity|EVEN|
13 |Stop bit|1|
14 |PLC station No.|1|
15
16 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_848ef1522d877523.png||alt="image-20220831163041-1.png" height="705" width="1676"]]
17
18 **Address List**
19
20 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
21 |Bit|M|M|M d|0~~8511|
22 |Bit|X|X|X o|0~~1747|
23 |Bit|Y|Y|Y o|0~~1747|
24 |Bit|S|S|S d|0~~1023|
25 |Bit|T|T|T d|0~~4095|
26 |Bit|C|C|C d|0~~634|
27 |Word|D|D|D d|0~~8511|
28 |Word|TD|TD|TD d|0~~618|
29 |Word|CD|CD|CD d|0~~634|
30 |Word|FD|FD|FD d|0~~8511|
31
32 **PLC Settings**
33
34 Create the new project, and select the specific model according to the actual PLC
35
36 (% style="text-align:center" %)
37 [[image:XinjieXCcreatenew.png]]
38
39 Program the PLC
40
41 (% style="text-align:center" %)
42 [[image:XinjieXCPrg.png]]
43
44 Connect PLC with PC through RS232-USB converter cable. Click [Option]-[Software Serial Port Config] to open the software connection setup window, and select the serial port, if the red text prompt "Connect To PLC Succeeded", which means the connection is setup successfully, then click OK to save the settings.
45
46 (% style="text-align:center" %)
47 [[image:XinjieXCPCconn.png]]
48
49 Change the PLC communication setup if required. Double click the tree node [PLC Serial Port] from Project tree. And change Modbus parameters, then click [Write to PLC] and OK to finish.
50
51 (% style="text-align:center" %)
52 [[image:XinjieXCPLCModbusConfig.png]]
53
54 Click [Online]-[Download Program] to download program into PLC. And the download pop up window would pop up, then click OK.
55
56 (% style="text-align:center" %)
57 [[image:XinjieXCDownloadPLC.png]]
58
59 **Cable Wiring**
60
61 Figure
62
63 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a14861f1794a6a42.png||alt="image-20220831163406-2.png" height="266" width="101"]] [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_3e55283fe70031d.png||alt="image-20220831163422-3.png" height="232" width="533"]]
64
65 Pin Definition Diagram
66
67 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_4e0c72812b72a12a.png||alt="image-20220831163441-4.png" height="167" width="336"]]
68
69 == **XD serial** ==
70
71 **V-Box Settings**
72
73 Supported Series: Xinjie XD/XE Series PLC
74
75 |**Item**|**Settings**|**Note**
76 |Protocol|XINJE XD/XC MODBUS|
77 |Connection|RS232|
78 |Baud rate|19200|
79 |Data bit|8|
80 |Parity|EVEN|
81 |Stop bit|1|
82 |PLC station No.|1|
83
84 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_2094eb9a27becb2c.png||alt="image-20220831163923-7.png" height="709" width="1677"]]
85
86 **Address List**
87
88 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
89 |Bit|M|M|M d|0~~74999|
90 |Bit|X1xx|X1xx|X1xx o|0~~1177|
91 |Bit|X2xx|X2xx|X2xx o|0~~277|
92 |Bit|X|X|X o|0~~77|
93 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
94 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
95 |Bit|Y|Y|Y o|0~~4095|
96 |Bit|SM|SM|SM d|0~~4999|
97 |Bit|T|T|T d|0~~4999|
98 |Bit|C|C|C d|0~~4999|
99 |Bit|ET|ET|ET d|0~~31|
100 |Bit|SE|SE|SE d|0~~31|
101 |Bit|HM|HM|HM d|0~~11999|
102 |Bit|HSC|HSC|HSC d|0~~39|
103 |Bit|HS|HS|HS d|0~~999|
104 |Bit|HT|HT|HT d|0~~1999|
105 |Bit|HC|HC|HC d|0~~1999|
106 |Bit|S|S|S d|0~~7999|
107 |Word|D|D|D d|0~~69999|
108 |Word|ID|ID|ID d|0~~99|
109 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
110 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
111 |Word|QD|QD|QD d|0~~99|
112 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
113 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
114 |Word|SD|SD|SD d|0~~4999|
115 |Word|TD|TD|TD d|0~~575|
116 |Word|CD|CD|CD d|0~~575|
117 |Word|ETD|ETD|ETD d|0~~31|
118 |Word|HD|HD|HD d|0~~24999|
119 |Word|HSD|HSD|HSD d|0~~1023|
120 |Word|HTD|HTD|HTD d|0~~95|
121 |Word|HCD|HCD|HCD d|0~~95|
122 |Word|HSCD|HSCD|HSCD d|0~~31|
123 |Word|FD|FD|FD d|0~~8191|
124 |Word|SFD|SFD|SFD d|0~~5999|
125 |Word|FS|FS|FS d|0~~47|
126
127 **PLC Settings**
128
129 Create the new project, and select the specific model according to the actual PLC
130
131 (% style="text-align:center" %)
132 [[image:XinjieXDcreatenew.png]]
133
134 Program the PLC
135
136 (% style="text-align:center" %)
137 [[image:XinjieXDLDprg.png]]
138
139 Connect PLC with PC through RS232-USB converter cable. Click [Option]-[Software Serial Port Config]-[Communication configuration] to open the PC connection configuration.
140
141 (% style="text-align:center" %)
142 [[image:XinjieXDopenSWcom (1).png]]
143
144 New a Modbus configuration, and Click [Comm-Test] to test connection, if shows "Connect To PLC Succeeded", which means PLC connection set up successfully. And click OK to save the settings.
145
146 (% style="text-align:center" %)
147 [[image:XinjieXDPLCtestconn.png]]
148
149 Remember to click the Status cell of new created Modbus configuration for change the status into "in use", then click OK to exit.
150
151 (% style="text-align:center" %)
152 [[image:XinjieXDclickto.png]]
153
154 After done the previous steps, it would prompt like the below.
155
156 (% style="text-align:center" %)
157 [[image:XinjieXDsuccessprompt.png]]
158
159 Click [Online]-[Download Program & Data], and wait for a while, the pop up window would ask for whether to stop PLC, and click [Stop PLC, contitue download]
160
161 (% style="text-align:center" %)
162 [[image:XinjieXDdownload.png]]
163
164 And then the XDPro ask for which options want to rewrite, and click OK to finish.
165
166 (% style="text-align:center" %)
167 [[image:XinjieXDdownloadopt.png]]
168
169 If download successfully, it would prompt like the below.
170
171 (% style="text-align:center" %)
172 [[image:XinjieXDcomplete.png]]
173
174 **Cable Wiring**
175
176 Figure
177
178 [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a14861f1794a6a42.png||alt="image-20220831163406-2.png" height="266" width="101"]] [[image:xwiki_V-BOX_V-Net_Training_1+Communication_WebHome_a8ea42846b443604.png||alt="image-20220831163553-6.png" height="206" width="465"]]
179
180 Pin Definition Diagram
181
182 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png" height="218" width="709"]]