Wiki source code of 1 Communication

Version 202.1 by Hunter on 2023/01/15 16:36

Show last authors
1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with **Rockwell PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
278
279 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
280
281 **1)V-BOX setting**
282
283 |**Item**|**Settings**|**Note**
284 |Protocol|Allen-Bradley DF1 Advanced|
285 |Connection|RS232|
286 |Baud rate|19200|
287 |Data bit|8|
288 |Parity|None|
289 |Stop bit|1|
290 |PLC station No.|1|
291
292 **2)Address List**
293
294 |**Type**|**Device registers**|**Format**|**Range**|**Note**
295 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
296 |O|O d.d|0.0~~255.15|
297 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
298 |S|S d.d|0.0~~255.15|
299 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
300 |(% rowspan="9" %)Word|S|S d|0~~255|
301 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
302 |TP|TP nnhh|0~~ffff
303 |CS|CS nnhh|0~~ffff
304 |CP|CP nnhh|0~~ffff
305 |N|N nnhh|0~~ffff
306 |C|C nnhh|0~~ffff
307 |T|T nnhh|0~~ffff
308 |R|R nnhh|0~~ffff
309
310 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
311
312 **4)Configure the communication protocol**
313
314 [[image:image-20220824110724-1.png]]
315
316 == **Micro850_FreeTag Protocol** ==
317
318 (((
319 (((
320 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
321 )))
322 )))
323
324 (((
325 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
326 (((
327 **Software configuration of PLC**
328 )))
329
330 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
331 (((
332 **1)PLC programming software**
333 )))
334
335 [[image:image-20220714162600-1.png]]
336
337 (% class="wikigeneratedid" id="HNewPLCproject" %)
338 (((
339 **2)New PLC project**
340 )))
341
342 (((
343 (((
344 Click New Project and select the PLC model.
345 )))
346 )))
347
348 (((
349 [[image:image-20220714162617-2.png]]
350 )))
351
352 (((
353
354
355 [[image:image-20220714162652-4.png]]
356 )))
357
358 (((
359 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
360 (((
361 **3)Set Ethernet parameters**
362 )))
363
364 (((
365 (((
366 (((
367 Follow the steps below to configure Ethernet parameters
368 )))
369 )))
370 )))
371
372 (((
373 (((
374 (((
375 PLC IP address:192.168.40.101
376 )))
377 )))
378 )))
379
380 (((
381 (((
382 (((
383 default gateway:192.168.40.1
384 )))
385 )))
386 )))
387
388 (((
389 (((
390 (((
391 subnet mask:255.255.255.0
392 )))
393 )))
394 )))
395
396 (((
397 [[image:image-20220714162713-5.png]]
398 )))
399
400 (((
401
402 )))
403
404 (((
405 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
406 (((
407 **V-box software configuration**
408 )))
409
410 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
411 (((
412 **1)V-box programming software**
413 )))
414
415 (% class="wikigeneratedid" %)
416 (((
417 [[image:image-20220714162725-6.png]]
418 )))
419
420 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
421 (((
422 **2)Configure device network**
423 )))
424
425 (((
426 (((
427 (((
428 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
429 )))
430
431 (((
432 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
433 )))
434 )))
435 )))
436
437 (((
438 (((
439 [[image:image-20220714162737-7.png]]
440
441
442 )))
443 )))
444 )))
445 )))
446
447 (% class="wikigeneratedid" id="HV-netadddevice" %)
448 (((
449 **3)V-net add device**
450 )))
451 )))
452
453 (((
454 (((
455 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
456 )))
457
458
459 )))
460
461 (((
462 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
463 (((
464 **4)Set communication port parameters**
465 )))
466
467 (((
468 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
469 )))
470
471 [[image:image-20220714162805-9.png]]
472 )))
473
474 (((
475 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
476 )))
477
478 [[image:image-20220824164346-1.png]]
479
480
481 (((
482 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
483 )))
484
485 (% class="wikigeneratedid" id="HEngineeringproduction" %)
486 (((
487 **5)Engineering production**
488 )))
489
490 (% class="wikigeneratedid" %)
491 (((
492 (((
493 According to your own needs, use the V-NET client software to edit the required data monitoring points.
494 )))
495
496 [[image:image-20220714162841-12.png]]
497
498
499 (((
500 **hardware connection**
501 )))
502 )))
503
504 (((
505 **1)Hardware wiring diagram**
506 )))
507
508 (((
509 (((
510 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
511 )))
512
513 [[image:image-20220714162856-13.png]]
514
515 (((
516 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
517
518
519 = **Allen-Bradley Ethernet DF1** =
520
521 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
522
523
524 = Create communication with **Siemens PLC** =
525
526 == **S7-200 Smart Ethernet Protocol** ==
527
528 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
529
530
531 == **S7-300 Ethernet Protocol** ==
532
533 Supported Series: Siemens S7-300 series PLC
534
535 **1)V-BOX setting**
536
537 |**Items**|**Settings**|**Note**
538 |Protocol|Simens S7-300 Ethernet|
539 |Connection|Ethernet|
540 |Port No.|102|
541 |PLC station No.|2|Need to be same as the PLC setting
542
543 **2)Address List**
544
545 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
546 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
547 |Q|Q|Q ddddd.o|0.0~~99999.7|
548 |M|M|M ddddd.o|0.0~~99999.7|
549 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
550 nn: block number;
551
552 dddd: address;
553 )))
554 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
555 |Q|QW|QW ddddd|0~~99999|
556 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
557 |MW|MW ddddd|0~~99999|(((
558 MW0=MB(0~~1)
559
560 MW2=MB(2~~3)
561
562 Address value is a multiple of 2
563 )))
564 |MD|MD ddddd|0~~99999|(((
565 MD0=MB(0~~3)
566
567 MD4=MB(4~~7)
568
569 Address value is a multiple of 4
570 )))
571 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
572 nn: block number;
573
574 dddd: address
575 )))
576 |DBxDBW|DBxDBW nndddd|0~~99999999
577 |DBxDBD|DBxDBD nndddd|0~~99999999
578
579 **3)Configure the communication protocol**
580
581 [[image:image-20220824161345-1.png]]
582
583 **4)Cable Wiring**
584
585 [[image:image-20220824161450-2.png]]
586 )))
587 )))
588
589 == **S7-1200 Ethernet Protocol** ==
590
591 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
592
593 == **S7-XXX Ethernet Protocol** ==
594
595 Supported Series: Siemens S7-400, S7-1200 and S7-1500
596
597 **1)V-BOX setting**
598
599 |=**Items**|=**Settings**|=**Note**
600 |Protocol|Siemens S7-XXX|
601 |Connection|Ethernet|
602 |Port No.|102|
603 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
604 |HMI No.|Rack (Default as 0)|
605
606 Slot from TIA Portal is equal to Device No. of V-net
607
608 Rack from TIA Portal is equal to HMI No. of V-net
609
610 [[image:image-20220824162459-3.png]]
611
612 [[image:image-20220824163305-2.png]]
613
614 **2)Address List**
615
616 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
617 |(% rowspan="4" %)Bit|I|I|M d.o|(((
618 d:0~-~-9999
619
620 o:0-7
621 )))|
622 |Q|Q|Q d.o|(((
623 d:0~-~-9999
624
625 o:0-7
626 )))|
627 |M|M|M d.o|(((
628 d:0~-~-9999
629
630 o:0-7
631 )))|
632 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
633 nn:0-9999,
634
635 dddd:0-9999,
636
637 o:0-7
638 )))|(((
639 nn:DB No.
640
641 dddd:address value
642
643 o: digit address
644 )))
645 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
646 |M|MW|MW d|d:0-99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD d|d:0-99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |I|IW|IW d|d:0-99999|
661 |Q|QW|QW d|d:0-99999|
662 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
663 nn:0-9999
664
665 dddd:0-9999
666 )))|(((
667 nn:DB No.
668
669 dddd:address value
670 )))
671 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
672 nn:0-9999
673
674 dddd:0-9999
675 )))|(((
676 nn:DB No.
677
678 dddd:address value
679
680 Address value is a multiple of 2
681 )))
682 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
683 nn:0-9999
684
685 dddd:0-9999
686 )))|(((
687 nn:DB No.
688
689 dddd:address value
690
691 Address value is a multiple of 4
692 )))
693
694 **3)Configure the communication protocol**
695
696 [[image:image-20220824163448-3.png]]
697
698 **✎Note:**
699
700 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
701 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
702
703 **4)Cable Wiring**
704
705 [[image:image-20220824162342-2.png]]
706
707 = Create communication with **Mitsubishi PLC** =
708
709 == **FX1S,1N,2N Serial Protocol** ==
710
711 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
712
713 **1)V-BOX Settings**
714
715 |**Item**|**Settings**|**Note**
716 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
717 |Connection|RS422/RS485/RS232|
718 |Baud rate|9600~~115200|
719 |Data bit|7/8|
720 |Parity|EVEN/Odd/None|
721 |Stop bit|1/2|
722 |PLC station No.|1~~255|
723
724 **2)Address List**
725
726 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
727 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
728 |Y|Y|Y o|0~~303237|
729 |M|M|M d|0~~99999|
730 |T|T|T d|0~~99999|
731 |C|C|C d|0~~99999|
732 |S|S|S d|0~~99999|
733 |SM|SM|SM d|8000~~9999|
734 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
735 |Y|Y|Y o|0~~303237|
736 |M|M|M d|0~~99999|
737 |T|T|T d|0~~99999|
738 |C|C|C d|0~~199|
739 |D|D|D d|0~~7999|
740 |S|S|S d|0~~99999|
741 |SD|SD|SD d|8000~~9999|
742
743 **3)Configure the communication protocol**
744
745 [[image:image-20220825102844-3.png]]
746
747 **4)Cable Wiring**
748
749 * **RS422**
750
751 [[image:image-20220825103350-4.png]]
752
753 [[image:image-20220825100845-4.png]]
754
755
756 == **FX3U,3G,3GA Serial Protocol** ==
757
758 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
759
760 **1)V-BOX Settings**
761
762 |**Item**|**Settings**|**Note**
763 |Protocol|Mitsubishi FX3U/3G/3GA|
764 |Connection|RS422/RS485/RS232|
765 |Baud rate|9600~~115200|
766 |Data bit|7/8|
767 |Parity|EVEN/Odd/None|
768 |Stop bit|1/2|
769 |PLC station No.|1~~255|
770
771 **2)Address List**
772
773 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
774 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
775 |Y|Y|Y o|0~~303237|
776 |M|M|M d|0~~99999|
777 |T|T|T d|0~~99999|
778 |C|C|C d|0~~99999|
779 |S|S|S d|0~~99999|
780 |SM|SM|SM d|8000~~9999|
781 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
782 |Y|Y|Y o|0~~303237|
783 |M|M|M d|0~~99999|
784 |T|T|T d|0~~99999|
785 |C|C|C d|0~~199|
786 |D|D|D d|0~~7999|
787 |S|S|S d|0~~99999|
788 |SD|SD|SD d|8000~~9999|
789
790 **3)Configure the communication protocol**
791
792 [[image:image-20220825102649-2.png]]
793
794 **4)Cable Wiring**
795
796 * **RS422**
797
798 [[image:image-20220825103421-5.png]]
799
800 [[image:image-20220825100845-4.png]]
801
802
803 == **FX3U Ethernet Protocol** ==
804
805 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
806
807 **1)V-BOX Settings**
808
809 |Items|Settings|Note
810 |Protocol|Mitsubishi FX3U|
811 |Connection|Ethernet|
812 |Port No.|5009|Must be the same as the PLC setting
813 |PLC station No.|0|
814
815 **2)Address List**
816
817 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
818 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
819 |Y|Y|Y OOO|0~~377|
820 |M|M|M DDDD|0~~7679|
821 |SM|SM|SM DDDD|8000~~8511|
822 |S|S|S DDDD|0~~4095|
823 |TS|TS|TS DDD|0~~511|
824 |CS|CS|CS DDD|0~~255|
825 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
826 |TN|TN|TN DDD|0~~511|
827 |D|D|D DDDD|0~~7999|
828 |SD|SD|SD DDDD|8000~~8511|
829 |R|R|R DDDDD|0~~32767|
830
831 **3)Ethernet Module Settings**
832
833 FX3U-ENET-L module configuration
834 Set up the FX3U-ENET-L Ethernet module settings as follows.
835 Select the module location, which in this document is Module 0.
836
837 [[image:image-20221116105850-1.png]]
838
839 Select "Operational setting" to enter the following screen.
840
841 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
842
843 [[image:image-20221116105947-1.png]]
844
845 Select "Open setting" to enter the setting interface, the settings are as follows.
846
847 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
848
849 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
850
851 [[image:image-20221116110802-1.png]]
852
853 Click on "transter setup" - "PC side I/F setting", see the following figure.
854
855 After setting, the first download must use the programming cable, as shown in the figure; after that, can
856
857 use the IP set in the "Ethernet board" to communicate directly with the network cable.
858
859 [[image:image-20221116110832-2.png||height="423" width="708"]]
860
861 Read and write data from the Ethernet module
862
863 [[image:image-20221116110907-3.png]]
864
865 Set "Transter setup" to COM communication, and read or write operation as shown below
866
867 [[image:image-20221116110917-4.png]]
868
869 **4)PLC Settings (GX Works 2)**
870
871 Create a blank FX5U project
872
873 Find Current Connection in the navigation
874
875 [[image:image-20221116111427-1.png||height="421" width="705"]]
876
877 Select Connection Channel List
878
879 Select Ethernet board communication
880
881 [[image:image-20221116111451-2.png||height="421" width="705"]]
882
883 Select Ethernet Module
884 Set the IP address of the PLC
885
886 [[image:image-20221116111509-3.png||height="666" width="699"]]
887
888 Read or write PLC data, in this document is read
889
890 [[image:image-20221116111651-4.png||height="416" width="697"]]
891
892 [[image:image-20221116111727-5.png||height="416" width="697"]]
893
894 **4)Configure the communication protocol**
895
896 [[image:image-20221119101946-2.png||height="395" width="695"]]
897
898 == **FX5U Serial Protocol** ==
899
900 Mitsubishi FX5U series PLC
901
902 **1)V-BOX Settings**
903
904 |**Item**|**Settings**|**Note**
905 |Protocol|Mitsubishi FX5U|
906 |Connection|RS422/RS485|
907 |Baud rate|9600|
908 |Data bit|7|
909 |Parity|Odd|
910 |Stop bit|1|
911 |PLC station No.|1~~255|Need to be the same as PLC settings
912
913 **2)Address List**
914
915 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
916 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
917 |Y|Y|Y o|0~~303237|
918 |M|M|M d|0~~99999|
919 |B|B|B h|0~~7FFF|
920 |F|F|F d|0~~32767|
921 |SB|SB|SB h|0~~7FFF|
922 |TS|TS|TS d|0~~1023|
923 |TC|TC|TC d|0~~1023|
924 |STS|STS|STS d|0~~1023|
925 |STC|STC|STS d|0~~1023|
926 |CS|CS|CS d|0~~1023|
927 |CC|CC|CC d|0~~1023|
928 |SM|SM|SM d|0~~9999|
929 |L|L|L d|0~~32767|
930 |S|S|S d|0~~4095|
931 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
932 |TN|TN|TN d|0~~1023|
933 |STN|STN|STN d|0~~1023|
934 |CN|CN|CN d|0~~1023|
935 |R|R|R d|0~~32767|
936 |SW|SW|SW h|0~~7FFF|
937 |Z|Z|Z d|0~~23|
938 |D|D|D d|0~~7999|
939 |SD|SD|SD d|0~~11999|
940
941 **3)PLC Settings (GX Works 3)**
942
943 Create a blank FX5U project
944
945 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
946
947 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
948
949 Select protocol in the setting item, and set parameters.
950
951 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
952
953 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
954
955 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
956
957 Click the [Apply] button to finish the setting.
958
959 Click download and select the items as below, then click [execute] to download the configuration to PLC.
960
961 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
962
963 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
964
965 Done.
966
967 **4)Configure the communication protocol**
968
969 [[image:image-20220825104904-1.png]]
970
971 **5)Cable Wiring**
972
973
974 * **RS422**
975
976 [[image:image-20220825105105-2.png]]
977
978 [[image:image-20220825105533-3.png]]
979
980 == **FX5U Ethernet Protocol** ==
981
982 Mitsubishi FX5U series PLC
983
984 **1)V-BOX Settings**
985
986 |**Items**|**Settings**|**Note**
987 |Protocol|Mitsubishi FX5U|
988 |Connection|Ethernet|
989 |Port No.|5002|Must be the same as the PLC setting
990 |PLC station No.|0|
991
992 **2)Address List**
993
994 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
995 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
996 |Y|Y|Y o|0~~303237|
997 |M|M|M d|0~~99999|
998 |B|B|B h|0~~7FFF|
999 |F|F|F d|0~~32767|
1000 |SB|SB|SB h|0~~7FFF|
1001 |TS|TS|TS d|0~~1023|
1002 |TC|TC|TC d|0~~1023|
1003 |STS|STS|STS d|0~~1023|
1004 |STC|STC|STS d|0~~1023|
1005 |CS|CS|CS d|0~~1023|
1006 |CC|CC|CC d|0~~1023|
1007 |SM|SM|SM d|0~~9999|
1008 |L|L|L d|0~~32767|
1009 |S|S|S d|0~~4095|
1010 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1011 |TN|TN|TN d|0~~1023|
1012 |STN|STN|STN d|0~~1023|
1013 |CN|CN|CN d|0~~1023|
1014 |R|R|R d|0~~32767|
1015 |SW|SW|SW h|0~~7FFF|
1016 |Z|Z|Z d|0~~23|
1017 |D|D|D d|0~~7999|
1018 |SD|SD|SD d|0~~11999|
1019
1020 **3)PLC Settings (GX Works 3)**
1021
1022 Find the [Ethernet port] in the navigation area.
1023
1024 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1025
1026 Select [Own Node Settings] in the [Setting Item List];
1027
1028 Set [IP Address], [Subnet Mask], [Default Gateway];
1029
1030 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1031
1032 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1033
1034 Select [SLMP Connection Module] and add into host station as below picture shows;
1035
1036 Set Port number as 5002 (this is necessary settings);
1037
1038 Click [Close with Reflecting the Setting] to save and close window;
1039
1040 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1041
1042 Click [Apply] to completed Etherenet settings;
1043
1044 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1045
1046 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1047
1048 **4)Configure the communication protocol**
1049
1050 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1051
1052 **5)Cable Wiring**
1053
1054 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1055
1056 == **L02 Serial Protocol** ==
1057
1058 Mitsubishi L02 series CPU built-in serial port.
1059
1060 **1)V-BOX Settings**
1061
1062 |**Item**|**Settings**|**Note**
1063 |Protocol|Mitsubishi L02|
1064 |Connection|RS422|
1065 |Baud rate|115200|
1066 |Data bit|8|
1067 |Parity|Odd|
1068 |Stop bit|1|
1069 |PLC station No.|1~~255|Need to be the same as PLC settings
1070
1071 **2)Address List**
1072
1073 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1074 |Bit|X|X|X h|0~~FFFF|
1075 |Bit|Y|Y|Y h|0~~FFFF|
1076 |Bit|M|M|M d|0~~9999|
1077 |Bit|L|L|L d|0~~9999|
1078 |Bit|F|F|F d|0~~9999|
1079 |Bit|B|B|B h|0~~FFFF|
1080 |Bit|V|V|V d|0~~2047|
1081 |Bit|TC|TC|TC d|0~~9999|
1082 |Bit|SS|SS|SS d|0~~9999|
1083 |Bit|SC|SC|SC d|0~~9999|
1084 |Bit|CS|CS|CS d|0~~9999|
1085 |Bit|CC|CC|CC d|0~~9999|
1086 |Bit|SB|SB|SB h|0~~FFFF|
1087 |Bit|SM|SM|SM d|0~~2047|
1088 |Bit|STS|STS|STS d|0~~1023|
1089 |Bit|S|S|S d|0~~9999|
1090 |Bit|DX|DX|DX h|0~~FFFF|
1091 |Bit|DY|DY|DY h|0~~FFFF|
1092 |Bit|TS|TS|TS d|0~~9999|
1093 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1094 |Word|W|W|W h|0~~FFFF|
1095 |Word|TN|TN|TN d|0~~99999|
1096 |Word|SN|SN|SN d|0~~99999|
1097 |Word|CN|CN|CN d|0~~99999|
1098 |Word|R|R|R d|0~~99999|
1099 |Word|SW|SW|SW h|0~~FFFF|
1100 |Word|Z|Z|Z d|0~~99999|
1101 |Word|ZR|ZR|ZR h|0~~FFFF|
1102 |Word|D|D|D d|0~~99999|
1103
1104 **3)Communication Settings**
1105
1106 [[image:image-20220825160648-3.png]]
1107
1108 **4)Cable Wiring**
1109
1110 * **RS422**
1111
1112 [[image:image-20220825161612-8.png]]
1113
1114 [[image:image-20220825160820-4.png]]
1115
1116 == **L02 Ethernet Protocol** ==
1117
1118 Mitsubishi L series CPU built-in Ethernet port.
1119
1120 **1)V-BOX Settings**
1121
1122 |**Items**|**Settings**|**Note**
1123 |Protocol|MIT L02 CPU MELSEC|
1124 |Connection|Ethernet|
1125 |Port No.|1025|Must be the same as the PLC setting
1126 |PLC station No.|0|Must be the same as the PLC setting
1127
1128 **2)Address List**
1129
1130 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1131 |Bit|X|X|X h|0~~FFFF|
1132 |Bit|Y|Y|Y h|0~~FFFF|
1133 |Bit|M|M|M d|0~~9999|
1134 |Bit|L|L|L d|0~~9999|
1135 |Bit|F|F|F d|0~~9999|
1136 |Bit|B|B|B h|0~~FFFF|
1137 |Bit|V|V|V d|0~~2047|
1138 |Bit|TC|TC|TC d|0~~9999|
1139 |Bit|SS|SS|SS d|0~~9999|
1140 |Bit|SC|SC|SC d|0~~9999|
1141 |Bit|CS|CS|CS d|0~~9999|
1142 |Bit|CC|CC|CC d|0~~9999|
1143 |Bit|SB|SB|SB h|0~~FFFF|
1144 |Bit|SM|SM|SM d|0~~2047|
1145 |Bit|STS|STS|STS d|0~~1023|
1146 |Bit|S|S|S d|0~~9999|
1147 |Bit|DX|DX|DX h|0~~FFFF|
1148 |Bit|DY|DY|DY h|0~~FFFF|
1149 |Bit|TS|TS|TS d|0~~9999|
1150 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1151 |Word|W|W|W h|0~~FFFF|
1152 |Word|TN|TN|TN d|0~~99999|
1153 |Word|SN|SN|SN d|0~~99999|
1154 |Word|CN|CN|CN d|0~~99999|
1155 |Word|R|R|R d|0~~99999|
1156 |Word|SW|SW|SW h|0~~FFFF|
1157 |Word|Z|Z|Z d|0~~99999|
1158 |Word|ZR|ZR|ZR h|0~~FFFF|
1159 |Word|D|D|D d|0~~99999|
1160
1161 **3)PLC Settings (GX Works2 )**
1162
1163 Create a project
1164
1165 Set PLC IP, subnet mask and gateway;
1166
1167 Select [Binary Code] as communication data code;
1168
1169 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1170
1171 Set PLC port number, for example 1025
1172
1173 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1174
1175 Save settings;
1176
1177 Download project into PLC device;
1178
1179 Restart PLC device;
1180
1181 **4)Configure the communication protocol**
1182
1183 [[image:image-20220825142659-1.png]]
1184
1185 **5)Cable Wiring**
1186
1187 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1188
1189 == **Q12H Serial Protocol** ==
1190
1191 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1192
1193 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1194
1195 == **QJ71E71 Ethernet Protocol** ==
1196
1197 Mitsubishi QJ71E71 Ethernet communication module;
1198
1199 **1)V-BOX Settings**
1200
1201 |**Items**|**Settings**|**Note**
1202 |Protocol|MIT QJ71E71 MELSEC|
1203 |Connection|Ethernet|
1204 |Port No.|1025|Must be the same as the PLC setting
1205 |PLC station No.|0|Must be the same as the PLC setting
1206
1207 **2)Address List**
1208
1209 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1210 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1211 |Y|Y|Y h|0~~1FFF|
1212 |M|M|M d|0~~99999|
1213 |L|L|L d|0~~8191|
1214 |F|F|F d|0~~2047|
1215 |B|B|B h|0~~1FFF|
1216 |V|V|V d|0~~2047|
1217 |TS|TS|TS d|0~~2047|
1218 |TC|TC|TC d|0~~2047|
1219 |SS|SS|SS d|0~~2047|
1220 |SC|SC|SC d|0~~2047|
1221 |CS|CS|CS d|0~~1023|
1222 |CC|CC|CC d|0~~1023|
1223 |SB|SB|SB h|0~~7FF|
1224 |S|S|S d|0~~8191|
1225 |DX|DX|DX h|0~~1FFF|
1226 |DY|DY|DY h|0~~1FFF|
1227 |SM|SM|SM d|8000~~9999|
1228 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1229 |D|D|D d|0~~12287|
1230 |W|W|W h|0~~1FFF|
1231 |TN|TN|TN d|0~~2047|
1232 |SN|SN|SN d|0~~2047|
1233 |CN|CN|CN d|0~~1023|
1234 |R|R|R d|0~~32767|
1235 |SW|SW|SW h|0~~7FF|
1236 |Z|Z|Z d|0~~15|
1237 |ZR|ZR|ZR h|0~~FE7FF|
1238
1239 **3)PLC Settings(GX Works2)**
1240
1241 * Click [Ethernet/CC IE/MELSECNET];
1242 * Please select [Ethernet] as network type;
1243 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1244 * Select [Online] as Mode;
1245 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1246 * Click [Operation setting] to set IP;
1247 * Select [Binary Code] as [Communication Data Code];
1248 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1249 * Click [Open setting]
1250 * Set protocol: TCP;
1251 * Set [unpassive] in [Open system];
1252 * Set [receive] in [Fixed buffer];
1253 * Set [procedure Exist] in [Fixed buffer communication];
1254 * Disable [Pairing open];
1255 * Set [No confirm] in [Existence confirmation];
1256 * Host station port number: 5009;
1257 * Save settings;
1258 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1259 * Download project into PLC and restart it
1260
1261 **4)Configure the communication protocol**
1262
1263 [[image:image-20221119171832-5.png||height="354" width="625"]]
1264
1265
1266 **5)Cable Wiring**
1267
1268 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1269
1270 = Create communication with **Delta PLC** =
1271
1272 == **DVP Ethernet Protocol** ==
1273
1274 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1275
1276 **1)V-BOX Settings**
1277
1278 |=**Items**|=**Settings**|=**Note**
1279 |Protocol|DELTA DVP MODBUS TCP|
1280 |Connection|Ethernet|
1281 |Port No.|502|
1282 |Device No.|1|
1283 |VBox Device No.|0|
1284
1285 **2)Address List **
1286
1287 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1288 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1289 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1290 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1291 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1292 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1293 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1294 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1295 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1296 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1297 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1298 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1299 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1300
1301 **3) PLC Setting:**
1302
1303 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1304
1305 (% style="text-align:center" %)
1306 [[image:DVPEthernetWPLSoft2.png]]
1307
1308 2. Set up the communication type and PLC IP:
1309
1310 (% style="text-align:center" %)
1311 [[image:DVPEthernetSetup.png]]
1312
1313 (% class="wikigeneratedid" %)
1314 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1315
1316 (% style="text-align:center" %)
1317 [[image:DVPEthernetTransfer.png]]
1318
1319 (% class="wikigeneratedid" %)
1320 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1321
1322 (% style="text-align:center" %)
1323 [[image:DVPEthernetPLCtoPC.png]]
1324
1325 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1326
1327 (% style="text-align:center" %)
1328 [[image:DVPEthernetAutoSearch.png]]
1329
1330 **4) V-BOX Setting:**
1331
1332 Set the same IP address according to the setting from WPL Soft:
1333
1334 (% style="text-align:center" %)
1335 [[image:DVPEthernetVNETPortocol.png]]
1336
1337 == **DVP serial protocol** ==
1338
1339 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1340
1341 **1)V-BOX Settings**
1342
1343 |=**Items**|=**Settings**|=**Note**
1344 |Protocol|DELTA DVP PROTOCOL|
1345 |Connection|RS232|
1346 |Baud Rate|9600|
1347 |Stop Bit|1|
1348 |Data Bit|7|
1349 |Parity|EVEN|
1350 |Device No.|1|
1351
1352 (% class="wikigeneratedid" %)
1353 **2)Address List**
1354
1355 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1356 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1357 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1358 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1359 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1360 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1361 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1362 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1363 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1364 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1365 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1366
1367 (% class="wikigeneratedid" %)
1368 **3)Wiring Diagram**
1369
1370 (% style="text-align:center" %)
1371 [[image:Delta DVP PROTOCOLSerial232.png]]
1372
1373 == **AS Ethernet Protocol** ==
1374
1375 **1)V-BOX Settings**
1376
1377 |=**Items**|=**Settings**|=**Note**
1378 |Protocol|DELTA AS300 MODBUS TCP|
1379 |Connection|Ethernet|
1380 |Port No.|502|
1381 |Device No.|1|
1382 |HMI No.|0|
1383
1384 **2)Address List**
1385
1386 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1387 |Bit|X|X|X d|0~~63|
1388 |Bit|Y|Y|Y d|0~~63|
1389 |Bit|D|D|D d|0~~29999|
1390 |Bit|M|M|M d|0~~8191|
1391 |Bit|SM|SM|SM d|0~~4095|
1392 |Bit|S|S|S h|0~~2047|
1393 |Bit|T|T|T d|0~~511|
1394 |Bit|C|C|C d|0~~511|
1395 |Bit|HC|HC|HC d|0~~255|
1396 |Word|X|X|X h|0~~63|
1397 |Word|Y|Y|Y d|0~~63|
1398 |Word|SR|SR|SR d|0~~2047|
1399 |Word|D|D|D d|0~~29999|
1400 |Word|T|T|T d|0~~511|
1401 |Word|C|C|C h|0~~511|
1402 |Word|E|E|E d|0~~9|
1403
1404 **3)Configure the communication protocol**
1405
1406 [[image:image-20220831160010-4.png]]
1407
1408 **4)Cable Wiring**
1409
1410 Figure
1411
1412 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1413
1414 Pin Definition Diagram
1415
1416 [[image:image-20220831155157-3.png]]
1417
1418 = Create communication with **Omron PLC** =
1419
1420 == **CP1 Series Protocol ** ==
1421
1422 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1423
1424 == **CP2M Series Protocol** ==
1425
1426 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1427
1428
1429 == **EC55 Series Protocol** ==
1430
1431 Supported device: EC55 temperature instrument
1432
1433 **1)V-BOX Settings**
1434
1435 |**Items**|**Settings**|**Note**
1436 |Protocol|Omron EC55|
1437 |Connection|RS485 (9600, 2, 7, EVEN)|
1438 |Port No.|None|
1439 |PLC station No.|0|
1440
1441 **2)Address List**
1442
1443 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1444 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1445 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1446 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1447 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1448 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1449 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1450 |CP|-|0-6|Read controller intrinsic property
1451 |CS|-|0-2|Read controller states
1452 |CA|-|0-17|Action command
1453
1454 **3)Device Settings**
1455
1456 Omron E5CC PLC configuration
1457
1458 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1459
1460 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1461
1462 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1463
1464 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1465
1466 **✎Note:** The communication settings for HMI should be consistent with this setting.
1467
1468 **4)Configure the communication protocol**
1469
1470 [[image:image-20220831161041-1.png]]
1471
1472 **5)Cable Wiring**
1473
1474 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1475
1476 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1477
1478 **✎Note:**
1479
1480 * COM3 only available in PI8000/PI9000 series.
1481 * CA address could not support continuous writing function;
1482 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1483 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1484 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1485 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1486 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1487 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1488 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1489
1490 = Create communication with Xinje** PLC** =
1491
1492 == **XC serial protocol** ==
1493
1494 **1)V-BOX Settings**
1495
1496 |**Item**|**Settings**|**Note**
1497 |Protocol|XINJE XC MODBUS|
1498 |Connection|RS232|
1499 |Baud rate|19200|
1500 |Data bit|8|
1501 |Parity|EVEN|
1502 |Stop bit|1|
1503 |PLC station No.|1|
1504
1505 **2)Address List**
1506
1507 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1508 |Bit|M|M|M d|0~~8511|
1509 |Bit|X|X|X o|0~~1747|
1510 |Bit|Y|Y|Y o|0~~1747|
1511 |Bit|S|S|S d|0~~1023|
1512 |Bit|T|T|T d|0~~4095|
1513 |Bit|C|C|C d|0~~634|
1514 |Word|D|D|D d|0~~8511|
1515 |Word|TD|TD|TD d|0~~618|
1516 |Word|CD|CD|CD d|0~~634|
1517 |Word|FD|FD|FD d|0~~8511|
1518
1519 **3)Configure the communication protocol**
1520
1521
1522 [[image:image-20220831163041-1.png]]
1523
1524 **4)Cable Wiring**
1525
1526 Figure
1527
1528 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1529
1530 Pin Definition Diagram
1531
1532 [[image:image-20220831163441-4.png]]
1533
1534 == **XD serial protocol** ==
1535
1536 **1)V-BOX Settings**
1537
1538 Supported Series: Xinjie XD/XE Series PLC
1539
1540 |**Item**|**Settings**|**Note**
1541 |Protocol|XINJE XD/XC MODBUS|
1542 |Connection|RS232|
1543 |Baud rate|19200|
1544 |Data bit|8|
1545 |Parity|EVEN|
1546 |Stop bit|1|
1547 |PLC station No.|1|
1548
1549 **2)Address List**
1550
1551 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1552 |Bit|M|M|M d|0~~74999|
1553 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1554 |Bit|X2xx|X2xx|X2xx o|0~~277|
1555 |Bit|X|X|X o|0~~77|
1556 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1557 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1558 |Bit|Y|Y|Y o|0~~4095|
1559 |Bit|SM|SM|SM d|0~~4999|(((
1560
1561 )))
1562 |Bit|T|T|T d|0~~4999|
1563 |Bit|C|C|C d|0~~4999|
1564 |Bit|ET|ET|ET d|0~~31|
1565 |Bit|SE|SE|SE d|0~~31|
1566 |Bit|HM|HM|HM d|0~~11999|
1567 |Bit|HSC|HSC|HSC d|0~~39|
1568 |Bit|HS|HS|HS d|0~~999|
1569 |Bit|HT|HT|HT d|0~~1999|
1570 |Bit|HC|HC|HC d|0~~1999|
1571 |Bit|S|S|S d|0~~7999|
1572 |Word|D|D|D d|0~~69999|
1573 |Word|ID|ID|ID d|0~~99|
1574 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1575 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1576 |Word|QD|QD|QD d|0~~99|
1577 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1578 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1579 |Word|SD|SD|SD d|0~~4999|
1580 |Word|TD|TD|TD d|0~~575|
1581 |Word|CD|CD|CD d|0~~575|
1582 |Word|ETD|ETD|ETD d|0~~31|
1583 |Word|HD|HD|HD d|0~~24999|
1584 |Word|HSD|HSD|HSD d|0~~1023|
1585 |Word|HTD|HTD|HTD d|0~~95|
1586 |Word|HCD|HCD|HCD d|0~~95|
1587 |Word|HSCD|HSCD|HSCD d|0~~31|
1588 |Word|FD|FD|FD d|0~~8191|
1589 |Word|SFD|SFD|SFD d|0~~5999|
1590 |Word|FS|FS|FS d|0~~47|
1591
1592 **3)Configure the communication protocol**
1593
1594 [[image:image-20220831163923-7.png]]
1595
1596
1597
1598 **4)Cable Wiring**
1599
1600 Figure
1601
1602 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1603
1604 Pin Definition Diagram
1605
1606 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1607
1608 = Create communication with **Schneider PLC** =
1609
1610 == **Schneider MODBUS RTU** ==
1611
1612 **1)V-BOX Setting**
1613
1614 |=**Parameters**|=**Recommended**|=**Notes**
1615 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1616 |**Connection**|RS485|
1617 |**Baud rate**|19200|
1618 |**Data bit**|8|
1619 |**Parity**|Even|
1620 |**Stop bit**|1|
1621 |**PLC station No.**|1|
1622
1623 **2)Address List**
1624
1625 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1626 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1627 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1628 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1629 |W|MW|DDDDDD|0 ~~ 999999|Output register
1630 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1631
1632 **3)Configure the communication protocol**
1633
1634 [[image:image-20220902104329-1.png]]
1635
1636 **4)Cable Wiring**
1637
1638 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1639
1640 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1641
1642 = Create communication with Inovance** PLC** =
1643
1644 == **H3U serial protocol** ==
1645
1646 **1)V-BOX Settings**
1647
1648 |**Item**|**Settings**|**Note**
1649 |Protocol|INOVANCE H3U PLC|
1650 |Connection|RS422|
1651 |Baud rate|9600|
1652 |Data bit|7|
1653 |Parity|EVEN|
1654 |Stop bit|1|
1655 |PLC station No.|0|
1656
1657 **2)Address List**
1658
1659 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1660 |Bit|X|X|X o|0~~303237|
1661 |Bit|Y|Y|Y o|0~~303237|
1662 |Bit|M|M|M d|0~~99999|
1663 |Bit|T|T|T d|0~~99999|
1664 |Bit|C|C|C d|0~~99999|
1665 |Bit|SM|SM|SM d|8000~~999|
1666 |Bit|S|T|S d|0~~99999|
1667 |Bit|Lamp|Lamp|Lamp d|0~~0|
1668 |Word|X|X|X o|0~~303237|
1669 |Word|Y|Y|Y o|0~~303237|
1670 |Word|M|M|M d|0~~99999|
1671 |Word|T|T|T d|0~~99999|
1672 |Word|C|C|C d|0~~199|
1673 |Word|D|D|D d|0~~7999|
1674 |Word|S|S|S d|0~~99999|
1675 |Word|SD|SD|SD d|8000~~9999|
1676 |Word|R|R|R d|0~~32767|
1677
1678 **3)Configure the communication protocol**
1679
1680 [[image:image-20220831164626-1.png]]
1681
1682
1683
1684 **4)Cable Wiring**
1685
1686 Figure
1687
1688 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1689
1690 Pin Definition Diagram
1691
1692 [[image:image-20220831164731-4.png]]
1693
1694 = Create communication with Panasonic** PLC** =
1695
1696 == **FP serial protocol** ==
1697
1698 **1)V-BOX Settings**
1699
1700 |**Item**|**Settings**|**Note**
1701 |Protocol|Panasonic FP MFWTOCOL|
1702 |Connection|RS232|
1703 |Baud rate|9600|
1704 |Data bit|8|
1705 |Parity|ODD|
1706 |Stop bit|1|
1707 |PLC station No.|1|
1708
1709 **2)Address List**
1710
1711 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1712 |Bit|X|X|X d|0~~9999|
1713 |Bit|Y|Y|Y d|0~~9999|
1714 |Bit|R|R|R d|0~~9999|
1715 |Bit|T|T|T d|0~~9999|
1716 |Bit|C|C|C d|0~~9999|
1717 |Bit|L|L|L d|0~~9999|
1718 |Word|WX|WX|WX d|0~~9999|
1719 |Word|WY|WY|WY d|0~~9999|
1720 |Word|WR|WR|WR d|0~~9999|
1721 |Word|WL|WL|WL d|0~~9999|
1722 |Word|LD|LD|LD d|0~~9999|
1723 |Word|DT|DT|DT d|0~~65535|
1724 |Word|FL|FL|FL d|0~~9999|
1725 |Word|EV|EV|EV d|0~~9999|
1726 |Word|SV|SV|SV d|0~~9999|
1727
1728 **3)Configure the communication protocol**
1729
1730 [[image:image-20220831165238-4.png]]
1731
1732
1733
1734 **4)Cable Wiring**
1735
1736 Figure
1737
1738 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1739
1740 Pin Definition Diagram
1741
1742 [[image:image-20220831165008-1.png]]
1743
1744 = Create communication with LS** PLC** =
1745
1746 == **XBC serial protocol** ==
1747
1748 **1)V-BOX Settings**
1749
1750 |**Item**|**Settings**|**Note**
1751 |Protocol|LS XBC CNet|
1752 |Connection|RS232|
1753 |Baud rate|115200|
1754 |Data bit|8|
1755 |Parity|NONE|
1756 |Stop bit|1|
1757 |PLC station No.|1|
1758
1759 **2)Address List**
1760
1761 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1762 |Bit|P|P|P d|0~~2047|
1763 |Bit|M|M|M d|0~~2047|
1764 |Bit|L|L|L d|0~~11263|
1765 |Bit|K|K|K d|0~~16183|
1766 |Bit|F|F|F d|0~~2047|
1767 |Bit|D|D|D d|0~~32767|
1768 |Bit|R|R|R d|0~~32767|
1769 |Bit|U|U|U d|0~~4095|
1770 |Word|P|P|P d|0~~2047|
1771 |Word|M|M|M d|0~~2047|
1772 |Word|L|L|L d|0~~11263|
1773 |Word|K|K|K d|0~~16183|
1774 |Word|F|F|F d|0~~2047|
1775 |Word|C|C|C d|0~~2047|
1776 |Word|T|T|T d|0~~2047|
1777 |Word|D|D|D d|0~~32767|
1778 |Word|N|N|N d|0~~21503|
1779 |Word|R|R|R d|0~~32767|
1780 |Word|U|U|U d|0~~4095|
1781 |Word|Z|Z|Z d|0~~127|
1782 |Word|S|S|S d|0~~127|
1783
1784 **3)Configure the communication protocol**
1785
1786 [[image:image-20220831170147-1.png]]
1787
1788 **4)Cable Wiring**
1789
1790 Figure
1791
1792 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1793
1794 Pin Definition Diagram
1795
1796 [[image:image-20220831170215-2.png]]
1797
1798 == **XGK FEnet Ethernet protocol** ==
1799
1800 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1801
1802 **1)V-BOX Settings**
1803
1804 |**Items**|**Settings**|**Note**
1805 |Protocol|LG XGK FEnet(Ethernet)|
1806 |Connection|Ethernet|
1807 |Port No.|2004|
1808
1809 **2)Address List**
1810
1811 |**Type**|**Register**|**Range**|**Format**|**Note**
1812 |(% rowspan="14" %)Word|P|0~~2047|P d|
1813 |M|0~~2047|M d|
1814 |K|0~~2047|K d|
1815 |F|0~~2047|F d|
1816 |T|0~~2047|T d|
1817 |C|0~~2047|C d|
1818 |Z|0~~127|Z d|
1819 |S|0~~127|S d|
1820 |L|0~~11263|L d|
1821 |N|0~~21503|N d|
1822 |D|0~~32767|D d|
1823 |R|0~~32767|R d|
1824 |ZR|0~~65535|ZR d|
1825 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1826
1827 **✎Note:**
1828
1829 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1830 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1831 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1832
1833 **3)Communication Settings**
1834
1835 [[image:image-20220831171127-1.png]]
1836
1837 **4)Cable Wiring**
1838
1839 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1840
1841 = Create communication with **Modbus ** =
1842
1843 == **MODBUS RTU Slave (All function)** ==
1844
1845 Select the protocol "Modbus RTU Slave (All Fuction)",
1846
1847 Then set baud rate, port, stop bits, data bits, parity.
1848
1849 (% style="text-align:center" %)
1850 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1851
1852 == **MODBUS RTU Master** ==
1853
1854 Select the protocol "Modbus RTU Master",
1855
1856 Then set baud rate, port, stop bits, data bits, parity
1857
1858 (% style="text-align:center" %)
1859 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
1860
1861 **address list**
1862
1863 (% class="table-bordered" %)
1864 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
1865 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1866 |06 (write single register: write a binary value to a holding register)
1867 |10 (write values to multiple addresses )
1868 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1869 |06 (write single register: write a binary value to a holding register)
1870 |10 (write values to multiple addresses )
1871 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1872 |06 (write single register: write a binary value to a holding register)
1873 |10 (write values to multiple addresses )
1874 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1875 |10 (write values to multiple addresses )
1876 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1877 |05 (Force a single coil to force the on/off state of a logic coil)
1878 |0F (Write multiple bits, ie write continuously)
1879 |(% rowspan="3" %)1|02 (Read the input state)
1880 |05 (Force a single coil to force the on/off state of a logic coil)
1881 |0F (Write multiple bits)
1882 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1883 |05 (Force a single coil to force the on/off state of a logic coil)
1884 |0F (Write multiple bits)
1885 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1886 |0F (Write multiple bits)
1887
1888 == **MODBUS TCP Slave (All function)** ==
1889
1890 Supported series: MODBUS TCP controller
1891
1892 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
1893
1894 **1)V-BOX Setting**
1895
1896 |**Items**|**Settings**|**Note**
1897 |Protocol|MODBUS TCP Slave (All function)|
1898 |Connection|Ethernet|
1899 |Port No.|502|
1900 |PLC station No.|1
1901
1902 **2)Address List**
1903
1904 |=**Type**|=**Data Type**|=**Function code & Description**
1905 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1906 |06 (write single register: write a binary value to a holding register)
1907 |10 (write values to multiple addresses )
1908 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1909 |06 (write single register: write a binary value to a holding register)
1910 |10 (write values to multiple addresses )
1911 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1912 |06 (write single register: write a binary value to a holding register)
1913 |10 (write values to multiple addresses )
1914 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1915 |10 (write values to multiple addresses )
1916 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1917 |05 (Force a single coil to force the on/off state of a logic coil)
1918 |0F (Write multiple bits, ie write continuously)
1919 |(% rowspan="3" %)1|02 (Read the input state)
1920 |05 (Force a single coil to force the on/off state of a logic coil)
1921 |0F (Write multiple bits)
1922 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1923 |05 (Force a single coil to force the on/off state of a logic coil)
1924 |0F (Write multiple bits)
1925 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1926 |0F (Write multiple bits)
1927
1928 **3)Communication Settings**
1929
1930 Configure V-BOX Ethernet IP in Networking Settings
1931
1932 [[image:image-20220902111833-3.png]]
1933
1934
1935 Configure PLC Ethernet IP in Communication;
1936
1937 [[image:image-20220902111121-1.png]]
1938
1939 **4)Cable Wiring**
1940
1941 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1942
1943 == **communicate with VB inverter** ==
1944
1945 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
1946
1947 = **User define protocol** =
1948
1949 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
1950
1951 == **Read the temperature sensor.** ==
1952
1953 the commond format is as beliow:
1954
1955 Send commond:01 03 02 00 00 03 04 73
1956
1957 Feedback commond:01 03 06 07 F7 0E 7E B7 35
1958
1959 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
1960
1961 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
1962
1963 Script Demo:
1964
1965 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
1966
1967 function com.main()
1968 ~-~-dosomething
1969 openPlc()
1970 end
1971 function openPlc()
1972 if obj then
1973 ~-~- If the serial port opened,then read/write data by timing
1974
1975 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
1976 local arr = reading(wri)
1977 ~-~- if arr ~~=nil then
1978 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
1979 ~-~- local A = arr[4]*256
1980 ~-~- local B = A+arr[5]
1981 ~-~- addr_setword(v[1],B)
1982 ~-~- end
1983 ~-~- end
1984
1985 else
1986 ~-~-judge if there is a serial object, then initialize and open the serial port
1987 local configs = {
1988 name = 'COM1', ~-~-Select serial port COM1
1989 mode = 485, ~-~-Communication mode RS485
1990 baud_rate = 9600, ~-~-Baud rate 9600
1991 stop_bit = 1, ~-~-stop bit 1
1992 data_len = 8, ~-~-data length 8
1993 check_bit = 'NONE', ~-~-no parity
1994
1995 }
1996 obj,err = serial.open(configs) ~-~-Open serial port
1997 if not obj then
1998 print("serial open :failed", err) ~-~- Open serial port failed
1999 end
2000 end
2001 end
2002
2003 function reading(wri)
2004 obj:flush() ~-~- Clear serial port
2005 obj:write(wri) ~-~- Write serial port
2006 print(string.byte(wri,1,#wri))
2007 obj:flush() ~-~- Clear serial port 
2008 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2009 if readed and readed ~~= "" then 
2010 ~-~- judge that a non-empty string is read
2011 print(string.byte(readed,1,#readed))
2012 a={string.byte(readed, 1, #readed)}
2013 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2014 a1=a[4]*256+a[5]
2015 a2=a[6]*256+a[7]
2016 addr_setword("@HDW0",a1)
2017 addr_setword("@HDW1",a2)
2018 end
2019 return {string.byte(readed, 1, #readed)}
2020 elseif readed == nil then
2021 print("serial read err:", err or "")
2022 return nil
2023 end
2024 return nil
2025 end
2026
2027 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-