1 = Create communication with WECON PLC =
2
3 == **LX3V Serial Protocol** ==
4
5 Supported series: Wecon LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6
7 **1)V-BOX setting**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 |Connection|RS422/RS485|
12 |Baud rate|9600|
13 |Data bit|7|
14 |Parity|EVEN|
15 |Stop bit|1|
16 |PLC station No.|1|
17
18 **2)Address List**
19
20
21 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
22 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
23 |Y|Y|Y o|0~~303237|
24 |M|M|M d|0~~99999|
25 |T|T|T d|0~~99999|
26 |C|C|C d|0~~99999|
27 |S|S|S d|0~~99999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **3)Configure the communication protocol**
38
39 [[image:image-20220824152217-1.png||alt="图片-20220824152217-1.png"]]
40
41 **4)Cable Wiring**
42
43 * **RS422**
44
45 [[image:image-20220824120614-5.png]]
46
47 * **RS485**
48
49 [[image:image-20220824120524-3.png]]
50
51 == **LX5V Serial Protocol** ==
52
53 This example introduces the establishment of serial port communication between V-BOX and LX5V. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
54
55 **Software configuration of PLC**
56
57 **1)PLC programming software**
58
59 [[image:image-20220824142722-1.png]]
60
61 **2)New PLC project**
62
63 Click New Project and select the PLC model.
64
65 [[image:image-20220822172623-2.png]]
66
67 **3)Set Serial port parameters**
68
69 Follow the steps below to configure Serial port parameters
70
71 Baud rate:115200
72
73 Data bit:8
74
75 Stop bit:1
76
77 Parity:No verification
78
79 [[image:image-20220822172657-3.png]]
80
81 **4)Registers list**
82
83 [[image:image-20220822172730-4.png]]
84
85 **V-BOX software configuration**
86
87 **1)V-BOX programming software**
88
89 [[image:image-20220824104124-1.png]]
90
91 **2)V-NET add device**
92
93 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
94
95 [[image:image-20220824104909-2.png]]
96
97 **3)Set communication port parameters**
98
99 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
100
101 Baud rate:115200
102
103 Data bit:8
104
105 Stop bit:1
106
107 Parity:No verification
108
109 [[image:image-20220824142130-1.png]]
110
111 **hardware connection**
112
113 **1)Hardware wiring diagram**
114
115 [[image:image-20220824142546-2.png]]
116
117 [[image:image-20220824142643-3.png]]
118
119 The above are all the steps for establishing serial port communication between V-BOX with LX5V PLC.
120
121 == **LX5V-N Ethernet protocol** ==
122
123 This example introduces the establishment of Ethernet communication between V-BOX and LX5V-N. It is introduced through three parts: PLC software configuration, V-BOX software configuration, and hardware wiring.
124
125 **Software configuration of PLC**
126
127 **1)PLC programming software**
128
129 [[image:image-20220824142722-1.png]]
130
131 **2)New PLC project**
132
133 Click New Project and select the PLC model.
134
135 [[image:image-20220824143613-1.png]]
136
137 **3)Set Ethernet port parameters**
138
139 Follow the steps below to configure Ethernet parameters
140
141 PLC IP address:192.168.39.200
142
143 default gateway:192.168.39.1
144
145 subnet mask:255.255.255.0
146
147 [[image:image-20220824143744-2.png]]
148
149 **4)Registers list**
150
151 [[image:image-20220822172730-4.png]]
152
153 (% id="cke_bm_22473S" style="display:none" %)** **(%%)**V-BOX software configuration**
154
155 **1)V-BOX programming software**
156
157 [[image:image-20220824104124-1.png]]
158
159 **2)V-NET add device**
160
161 Open V-NET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the access key, password and remark, to add the device.
162
163 [[image:image-20220824104909-2.png]]
164
165 **3)Set communication Protocol**
166
167 Click Communication to configure the LX5V plc protocol and IP address.
168
169 [[image:image-20220824144619-1.png]]
170
171 **hardware connection**
172
173 **1)Hardware wiring diagram**
174
175 [[image:image-20220824151127-2.png]]
176
177 The above are all the steps for establishing ethernet communication between V-BOX with LX5V PLC.
178
179 = Create communication with **Rockwell PLC** =
180
181 == **DF1 Advanced Protocol** ==
182
183 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
184
185 **1) V-Box Settings**
186
187 |=Item|=Recommended |=Note
188 |=Protocol|Allen Bradley DF1 Advanced|
189 |=Connection|RS232|
190 |=Baud rate|19200|
191 |=Stop bits|1|
192 |=Data bits|8|
193 |=Parity|None|
194 |=PLC Station No.|1|
195 |=HMI Station No.|0|
196
197 **2) Address List**
198
199 |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
200 |(% colspan="1" rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
201 |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
202 |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
203 |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
204 |BN|BNddddd.dd|0.0~~99255.15|(((
205 Bit data file B0~~B99
206
207 First two digits is for file number
208
209 For example, BN13001.00 represents file number B13, address 001, the 0th bit.
210 )))
211 |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
212 |NN|NNddddd.dd|0.0~~99255.15|(((
213 Integer data file bit format N0~~N99
214
215 First two digits is for file number
216
217 For example, NN13001.00 represents file number N13, address 001, the 0th bit.
218 )))
219 |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
220 |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
221 |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
222 |TNS|TNSddddd|0~~99255|(((
223 Timer Preset Value
224
225 First two digits is for file number
226
227 For example, TNS99255 represents file number T99, address 255.
228 )))
229 |TNP|TNPddddd|0~~99255|(((
230 Timer Accumulator Value
231
232 First two digits is for file number
233
234 For example, TNP99255 represents file number T99, address 255.
235 )))
236 |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
237 |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
238 |CNS|CNSddddd|0~~99255|(((
239 Counter Preset Value
240
241 First two digits is for file number
242
243 For example, CNS99255 represents file number C99, address 255.
244 )))
245 |CNP|CNPddddd|0~~99255|(((
246 Counter Accumulator Value
247
248 First two digits is for file number
249
250 For example, CNP99255 represents file number C99, address 255.
251 )))
252 |N7|N7ddd|0~~255|Only able to communicate with file number N7
253 |NN|NNddd|0~~99255|(((
254 Integer data file
255
256 First two digits is for file number
257
258 For example, NN99255 represents file number N99, address 255.
259 )))
260 |(% colspan="1" rowspan="3" %)Double Word|F8|F8ddd|0~~255|(((
261 Only able to communicate with file number N7
262 )))
263 |FN|FNddddd|0~~99255|(((
264 Floating point data file
265
266 First two digits is for file number
267
268 For example, FN99255 represents file number F99, address 255.
269 )))
270 |LN|LNddddd|0~~99255|Long
271
272 **3) Cable Wiring**
273
274 (% style="text-align:center" %)
275 [[image:ABRS232.gif]]
276
277 == (% id="cke_bm_5621S" style="display:none" %)** **(%%)**MicroLogix Protocol** ==
278
279 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
280
281 **1)V-BOX setting**
282
283 |**Item**|**Settings**|**Note**
284 |Protocol|Allen-Bradley DF1 Advanced|
285 |Connection|RS232|
286 |Baud rate|19200|
287 |Data bit|8|
288 |Parity|None|
289 |Stop bit|1|
290 |PLC station No.|1|
291
292 **2)Address List**
293
294 |**Type**|**Device registers**|**Format**|**Range**|**Note**
295 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
296 |O|O d.d|0.0~~255.15|
297 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
298 |S|S d.d|0.0~~255.15|
299 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
300 |(% rowspan="9" %)Word|S|S d|0~~255|
301 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
302 |TP|TP nnhh|0~~ffff
303 |CS|CS nnhh|0~~ffff
304 |CP|CP nnhh|0~~ffff
305 |N|N nnhh|0~~ffff
306 |C|C nnhh|0~~ffff
307 |T|T nnhh|0~~ffff
308 |R|R nnhh|0~~ffff
309
310 **3)Configure the communication protocol**[[image:image-20220824152928-1.png]]
311
312 **4)Configure the communication protocol**
313
314 [[image:image-20220824110724-1.png]]
315
316 == **Micro850_FreeTag Protocol** ==
317
318 (((
319 (((
320 This example introduces the establishment of Ethernet communication between Wecon V-box and CompactLogix L1769. It is introduced through three parts: PLC software configuration, V-box software configuration, and hardware wiring.
321 )))
322 )))
323
324 (((
325 (% class="wikigeneratedid" id="HSoftwareconfigurationofPLC" %)
326 (((
327 **Software configuration of PLC**
328 )))
329
330 (% class="wikigeneratedid" id="HPLCprogrammingsoftware" %)
331 (((
332 **1)PLC programming software**
333 )))
334
335 [[image:image-20220714162600-1.png]]
336
337 (% class="wikigeneratedid" id="HNewPLCproject" %)
338 (((
339 **2)New PLC project**
340 )))
341
342 (((
343 (((
344 Click New Project and select the PLC model.
345 )))
346 )))
347
348 (((
349 [[image:image-20220714162617-2.png]]
350 )))
351
352 (((
353
354
355 [[image:image-20220714162652-4.png]]
356 )))
357
358 (((
359 (% class="wikigeneratedid" id="HSetEthernetparameters" %)
360 (((
361 **3)Set Ethernet parameters**
362 )))
363
364 (((
365 (((
366 (((
367 Follow the steps below to configure Ethernet parameters
368 )))
369 )))
370 )))
371
372 (((
373 (((
374 (((
375 PLC IP address:192.168.40.101
376 )))
377 )))
378 )))
379
380 (((
381 (((
382 (((
383 default gateway:192.168.40.1
384 )))
385 )))
386 )))
387
388 (((
389 (((
390 (((
391 subnet mask:255.255.255.0
392 )))
393 )))
394 )))
395
396 (((
397 [[image:image-20220714162713-5.png]]
398 )))
399
400 (((
401
402 )))
403
404 (((
405 (% class="wikigeneratedid" id="HV-boxsoftwareconfiguration" %)
406 (((
407 **V-box software configuration**
408 )))
409
410 (% class="wikigeneratedid" id="HV-boxprogrammingsoftware" %)
411 (((
412 **1)V-box programming software**
413 )))
414
415 (% class="wikigeneratedid" %)
416 (((
417 [[image:image-20220714162725-6.png]]
418 )))
419
420 (% class="wikigeneratedid" id="HConfiguredevicenetwork" %)
421 (((
422 **2)Configure device network**
423 )))
424
425 (((
426 (((
427 (((
428 Click the Configuration Download button[[image:image-20220714115308-8.png||height="22" width="15"]], It is used to configure the device network, update the device time, obtain the device machine code, check the device network, etc.
429 )))
430
431 (((
432 In the example below, the IP address of V-Box is configured as 192.168.40.66, and the networking method is 4G connection
433 )))
434 )))
435 )))
436
437 (((
438 (((
439 [[image:image-20220714162737-7.png]]
440
441
442 )))
443 )))
444 )))
445 )))
446
447 (% class="wikigeneratedid" id="HV-netadddevice" %)
448 (((
449 **3)V-net add device**
450 )))
451 )))
452
453 (((
454 (((
455 Open VNET client software → add device. As shown in the figure below, click "+" in the order of steps, and the Add Device window will pop up, enter the device machine code/product code, device password, and device alias to add the device.   [[image:image-20220714162752-8.png]]
456 )))
457
458
459 )))
460
461 (((
462 (% class="wikigeneratedid" id="HSetcommunicationportparameters" %)
463 (((
464 **4)Set communication port parameters**
465 )))
466
467 (((
468 In the device list on the left, find the Vbox that communicates with the L1769, click it and select configuration,communication port configuration in the main interface to add a communication protocol.
469 )))
470
471 [[image:image-20220714162805-9.png]]
472 )))
473
474 (((
475 The communication port is selected as Ethernet, the device type is selected as Allen-Bradley, the protocol is Allen-BradleyMicro850_FreeTag EthemetIP, and the IP is the internal IP address of the L1769 PLC. The port number is 44818.
476 )))
477
478 [[image:image-20220824164346-1.png]]
479
480
481 (((
482 After adding the protocol Allen-BradleyMicro850_FreeTag, click[[image:image-20220714143838-2.png]]icon add label.[[image:image-20220714162827-11.png]]
483 )))
484
485 (% class="wikigeneratedid" id="HEngineeringproduction" %)
486 (((
487 **5)Engineering production**
488 )))
489
490 (% class="wikigeneratedid" %)
491 (((
492 (((
493 According to your own needs, use the V-NET client software to edit the required data monitoring points.
494 )))
495
496 [[image:image-20220714162841-12.png]]
497
498
499 (((
500 **hardware connection**
501 )))
502 )))
503
504 (((
505 **1)Hardware wiring diagram**
506 )))
507
508 (((
509 (((
510 This example introduces Wecon V-box with Allen-Bradley L1769 PLC to establish communication through Ethernet. The connection diagram is as follows:
511 )))
512
513 [[image:image-20220714162856-13.png]]
514
515 (((
516 The above are all the steps for establishing Ethernet communication between Wecon V-box with CompactLogix L1769 PLC.
517
518
519 = **Allen-Bradley Ethernet DF1** =
520
521 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Allen-Bradley%20Ethernet%20DF1.zip]]
522
523
524 = Create communication with **Siemens PLC** =
525
526 == **S7-200 Smart Ethernet Protocol** ==
527
528 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20S7-200%20Smart.zip]]
529
530
531 == **S7-300 Ethernet Protocol** ==
532
533 Supported Series: Siemens S7-300 series PLC
534
535 **1)V-BOX setting**
536
537 |**Items**|**Settings**|**Note**
538 |Protocol|Simens S7-300 Ethernet|
539 |Connection|Ethernet|
540 |Port No.|102|
541 |PLC station No.|2|Need to be same as the PLC setting
542
543 **2)Address List**
544
545 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
546 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
547 |Q|Q|Q ddddd.o|0.0~~99999.7|
548 |M|M|M ddddd.o|0.0~~99999.7|
549 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
550 nn: block number;
551
552 dddd: address;
553 )))
554 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
555 |Q|QW|QW ddddd|0~~99999|
556 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
557 |MW|MW ddddd|0~~99999|(((
558 MW0=MB(0~~1)
559
560 MW2=MB(2~~3)
561
562 Address value is a multiple of 2
563 )))
564 |MD|MD ddddd|0~~99999|(((
565 MD0=MB(0~~3)
566
567 MD4=MB(4~~7)
568
569 Address value is a multiple of 4
570 )))
571 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
572 nn: block number;
573
574 dddd: address
575 )))
576 |DBxDBW|DBxDBW nndddd|0~~99999999
577 |DBxDBD|DBxDBD nndddd|0~~99999999
578
579 **3)Configure the communication protocol**
580
581 [[image:image-20220824161345-1.png]]
582
583 **4)Cable Wiring**
584
585 [[image:image-20220824161450-2.png]]
586 )))
587 )))
588
589 == **S7-1200 Ethernet Protocol** ==
590
591 [[download link>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20S7-1200%20via%20Ehernet.zip]]
592
593 == **S7-XXX Ethernet Protocol** ==
594
595 Supported Series: Siemens S7-400, S7-1200 and S7-1500
596
597 **1)V-BOX setting**
598
599 |=**Items**|=**Settings**|=**Note**
600 |Protocol|Siemens S7-XXX|
601 |Connection|Ethernet|
602 |Port No.|102|
603 |Device No.|Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|
604 |HMI No.|Rack (Default as 0)|
605
606 Slot from TIA Portal is equal to Device No. of V-net
607
608 Rack from TIA Portal is equal to HMI No. of V-net
609
610 [[image:image-20220824162459-3.png]]
611
612 [[image:image-20220824163305-2.png]]
613
614 **2)Address List**
615
616 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
617 |(% rowspan="4" %)Bit|I|I|M d.o|(((
618 d:0~-~-9999
619
620 o:0-7
621 )))|
622 |Q|Q|Q d.o|(((
623 d:0~-~-9999
624
625 o:0-7
626 )))|
627 |M|M|M d.o|(((
628 d:0~-~-9999
629
630 o:0-7
631 )))|
632 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
633 nn:0-9999,
634
635 dddd:0-9999,
636
637 o:0-7
638 )))|(((
639 nn:DB No.
640
641 dddd:address value
642
643 o: digit address
644 )))
645 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
646 |M|MW|MW d|d:0-99999|(((
647 MW0=MB(0~~1)
648
649 MW2=MB(2~~3)
650
651 Address value is a multiple of 2
652 )))
653 |M|MD|MD d|d:0-99999|(((
654 MD0=MB(0~~3)
655
656 MD4=MB(4~~7)
657
658 Address value is a multiple of 4
659 )))
660 |I|IW|IW d|d:0-99999|
661 |Q|QW|QW d|d:0-99999|
662 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
663 nn:0-9999
664
665 dddd:0-9999
666 )))|(((
667 nn:DB No.
668
669 dddd:address value
670 )))
671 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
672 nn:0-9999
673
674 dddd:0-9999
675 )))|(((
676 nn:DB No.
677
678 dddd:address value
679
680 Address value is a multiple of 2
681 )))
682 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
683 nn:0-9999
684
685 dddd:0-9999
686 )))|(((
687 nn:DB No.
688
689 dddd:address value
690
691 Address value is a multiple of 4
692 )))
693
694 **3)Configure the communication protocol**
695
696 [[image:image-20220824163448-3.png]]
697
698 **✎Note:**
699
700 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three V-BOX.
701 * V-BOX access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
702
703 **4)Cable Wiring**
704
705 [[image:image-20220824162342-2.png]]
706
707 == **LOGO Ethernet Protocol** ==
708
709 Supported Series: Siemens Logo 0BA0, 0BA1 series
710
711 **V-BOX Settings**
712
713
714 |**Items**|**Settings**|**Note**
715 |Protocol|Siemens LOGO|
716 |Connection|Ethernet|
717 |Port No.|102|
718 |PLC station No.|2|
719
720 **Address List**
721
722
723 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
724 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
725 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
726 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
727 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
728 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
729 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
730 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
731 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
732 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
733 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
734 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
735 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
736 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
737 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
738 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
739
740 **PLC Settings in LOGO Software:**
741
742 Click [Tools]~-~-[Ethernet Connections],shown as below.
743
744 (% style="text-align:center" %)
745 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
746
747 = Create communication with **Mitsubishi PLC** =
748
749 == **FX1S,1N,2N Serial Protocol** ==
750
751 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
752
753 **1)V-BOX Settings**
754
755 |**Item**|**Settings**|**Note**
756 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
757 |Connection|RS422/RS485/RS232|
758 |Baud rate|9600~~115200|
759 |Data bit|7/8|
760 |Parity|EVEN/Odd/None|
761 |Stop bit|1/2|
762 |PLC station No.|1~~255|
763
764 **2)Address List**
765
766 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
767 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
768 |Y|Y|Y o|0~~303237|
769 |M|M|M d|0~~99999|
770 |T|T|T d|0~~99999|
771 |C|C|C d|0~~99999|
772 |S|S|S d|0~~99999|
773 |SM|SM|SM d|8000~~9999|
774 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
775 |Y|Y|Y o|0~~303237|
776 |M|M|M d|0~~99999|
777 |T|T|T d|0~~99999|
778 |C|C|C d|0~~199|
779 |D|D|D d|0~~7999|
780 |S|S|S d|0~~99999|
781 |SD|SD|SD d|8000~~9999|
782
783 **3)Configure the communication protocol**
784
785 [[image:image-20220825102844-3.png]]
786
787 **4)Cable Wiring**
788
789 * **RS422**
790
791 [[image:image-20220825103350-4.png]]
792
793 [[image:image-20220825100845-4.png]]
794
795
796 == **FX3U,3G,3GA Serial Protocol** ==
797
798 Supported Series: Mitsubishi FX3U, FX3G, FX3GA series
799
800 **1)V-BOX Settings**
801
802 |**Item**|**Settings**|**Note**
803 |Protocol|Mitsubishi FX3U/3G/3GA|
804 |Connection|RS422/RS485/RS232|
805 |Baud rate|9600~~115200|
806 |Data bit|7/8|
807 |Parity|EVEN/Odd/None|
808 |Stop bit|1/2|
809 |PLC station No.|1~~255|
810
811 **2)Address List**
812
813 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
814 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
815 |Y|Y|Y o|0~~303237|
816 |M|M|M d|0~~99999|
817 |T|T|T d|0~~99999|
818 |C|C|C d|0~~99999|
819 |S|S|S d|0~~99999|
820 |SM|SM|SM d|8000~~9999|
821 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
822 |Y|Y|Y o|0~~303237|
823 |M|M|M d|0~~99999|
824 |T|T|T d|0~~99999|
825 |C|C|C d|0~~199|
826 |D|D|D d|0~~7999|
827 |S|S|S d|0~~99999|
828 |SD|SD|SD d|8000~~9999|
829
830 **3)Configure the communication protocol**
831
832 [[image:image-20220825102649-2.png]]
833
834 **4)Cable Wiring**
835
836 * **RS422**
837
838 [[image:image-20220825103421-5.png]]
839
840 [[image:image-20220825100845-4.png]]
841
842
843 == **FX3U Ethernet Protocol** ==
844
845 Supported Modules: FX3U-ENET-ADP, FX3U-ENET-L
846
847 **1)V-BOX Settings**
848
849 |Items|Settings|Note
850 |Protocol|Mitsubishi FX3U|
851 |Connection|Ethernet|
852 |Port No.|5009|Must be the same as the PLC setting
853 |PLC station No.|0|
854
855 **2)Address List**
856
857 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
858 |(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377|
859 |Y|Y|Y OOO|0~~377|
860 |M|M|M DDDD|0~~7679|
861 |SM|SM|SM DDDD|8000~~8511|
862 |S|S|S DDDD|0~~4095|
863 |TS|TS|TS DDD|0~~511|
864 |CS|CS|CS DDD|0~~255|
865 |(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199|
866 |TN|TN|TN DDD|0~~511|
867 |D|D|D DDDD|0~~7999|
868 |SD|SD|SD DDDD|8000~~8511|
869 |R|R|R DDDDD|0~~32767|
870
871 **3)Ethernet Module Settings**
872
873 FX3U-ENET-L module configuration
874 Set up the FX3U-ENET-L Ethernet module settings as follows.
875 Select the module location, which in this document is Module 0.
876
877 [[image:image-20221116105850-1.png]]
878
879 Select "Operational setting" to enter the following screen.
880
881 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
882
883 [[image:image-20221116105947-1.png]]
884
885 Select "Open setting" to enter the setting interface, the settings are as follows.
886
887 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
888
889 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
890
891 [[image:image-20221116110802-1.png]]
892
893 Click on "transter setup" - "PC side I/F setting", see the following figure.
894
895 After setting, the first download must use the programming cable, as shown in the figure; after that, can
896
897 use the IP set in the "Ethernet board" to communicate directly with the network cable.
898
899 [[image:image-20221116110832-2.png||height="423" width="708"]]
900
901 Read and write data from the Ethernet module
902
903 [[image:image-20221116110907-3.png]]
904
905 Set "Transter setup" to COM communication, and read or write operation as shown below
906
907 [[image:image-20221116110917-4.png]]
908
909 **4)PLC Settings (GX Works 2)**
910
911 Create a blank FX5U project
912
913 Find Current Connection in the navigation
914
915 [[image:image-20221116111427-1.png||height="421" width="705"]]
916
917 Select Connection Channel List
918
919 Select Ethernet board communication
920
921 [[image:image-20221116111451-2.png||height="421" width="705"]]
922
923 Select Ethernet Module
924 Set the IP address of the PLC
925
926 [[image:image-20221116111509-3.png||height="666" width="699"]]
927
928 Read or write PLC data, in this document is read
929
930 [[image:image-20221116111651-4.png||height="416" width="697"]]
931
932 [[image:image-20221116111727-5.png||height="416" width="697"]]
933
934 **4)Configure the communication protocol**
935
936 [[image:image-20221119101946-2.png||height="395" width="695"]]
937
938 == **FX5U Serial Protocol** ==
939
940 Mitsubishi FX5U series PLC
941
942 **1)V-BOX Settings**
943
944 |**Item**|**Settings**|**Note**
945 |Protocol|Mitsubishi FX5U|
946 |Connection|RS422/RS485|
947 |Baud rate|9600|
948 |Data bit|7|
949 |Parity|Odd|
950 |Stop bit|1|
951 |PLC station No.|1~~255|Need to be the same as PLC settings
952
953 **2)Address List**
954
955 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
956 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
957 |Y|Y|Y o|0~~303237|
958 |M|M|M d|0~~99999|
959 |B|B|B h|0~~7FFF|
960 |F|F|F d|0~~32767|
961 |SB|SB|SB h|0~~7FFF|
962 |TS|TS|TS d|0~~1023|
963 |TC|TC|TC d|0~~1023|
964 |STS|STS|STS d|0~~1023|
965 |STC|STC|STS d|0~~1023|
966 |CS|CS|CS d|0~~1023|
967 |CC|CC|CC d|0~~1023|
968 |SM|SM|SM d|0~~9999|
969 |L|L|L d|0~~32767|
970 |S|S|S d|0~~4095|
971 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
972 |TN|TN|TN d|0~~1023|
973 |STN|STN|STN d|0~~1023|
974 |CN|CN|CN d|0~~1023|
975 |R|R|R d|0~~32767|
976 |SW|SW|SW h|0~~7FFF|
977 |Z|Z|Z d|0~~23|
978 |D|D|D d|0~~7999|
979 |SD|SD|SD d|0~~11999|
980
981 **3)PLC Settings (GX Works 3)**
982
983 Create a blank FX5U project
984
985 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
986
987 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5c9cb13fac1e6c93.png?width=200&height=462&rev=1.1||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
988
989 Select protocol in the setting item, and set parameters.
990
991 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_de942589ca070228.png?width=600&height=324&rev=1.1||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
992
993 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
994
995 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_387ec7d00b5feb59.png?width=600&height=323&rev=1.1||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
996
997 Click the [Apply] button to finish the setting.
998
999 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1000
1001 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_cdef1c5ec8cc2105.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
1002
1003 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1004
1005 Done.
1006
1007 **4)Configure the communication protocol**
1008
1009 [[image:image-20220825104904-1.png]]
1010
1011 **5)Cable Wiring**
1012
1013
1014 * **RS422**
1015
1016 [[image:image-20220825105105-2.png]]
1017
1018 [[image:image-20220825105533-3.png]]
1019
1020 == **FX5U Ethernet Protocol** ==
1021
1022 Mitsubishi FX5U series PLC
1023
1024 **1)V-BOX Settings**
1025
1026 |**Items**|**Settings**|**Note**
1027 |Protocol|Mitsubishi FX5U|
1028 |Connection|Ethernet|
1029 |Port No.|5002|Must be the same as the PLC setting
1030 |PLC station No.|0|
1031
1032 **2)Address List**
1033
1034 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1035 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1036 |Y|Y|Y o|0~~303237|
1037 |M|M|M d|0~~99999|
1038 |B|B|B h|0~~7FFF|
1039 |F|F|F d|0~~32767|
1040 |SB|SB|SB h|0~~7FFF|
1041 |TS|TS|TS d|0~~1023|
1042 |TC|TC|TC d|0~~1023|
1043 |STS|STS|STS d|0~~1023|
1044 |STC|STC|STS d|0~~1023|
1045 |CS|CS|CS d|0~~1023|
1046 |CC|CC|CC d|0~~1023|
1047 |SM|SM|SM d|0~~9999|
1048 |L|L|L d|0~~32767|
1049 |S|S|S d|0~~4095|
1050 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1051 |TN|TN|TN d|0~~1023|
1052 |STN|STN|STN d|0~~1023|
1053 |CN|CN|CN d|0~~1023|
1054 |R|R|R d|0~~32767|
1055 |SW|SW|SW h|0~~7FFF|
1056 |Z|Z|Z d|0~~23|
1057 |D|D|D d|0~~7999|
1058 |SD|SD|SD d|0~~11999|
1059
1060 **3)PLC Settings (GX Works 3)**
1061
1062 Find the [Ethernet port] in the navigation area.
1063
1064 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8e8f85ace087346c.png?width=300&height=593&rev=1.1||alt="12.PLC Protocol_html_8e8f85ace087346c.png" height="593" width="300"]]
1065
1066 Select [Own Node Settings] in the [Setting Item List];
1067
1068 Set [IP Address], [Subnet Mask], [Default Gateway];
1069
1070 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
1071
1072 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5d98495052c8c10e.png?width=600&height=339&rev=1.1||alt="12.PLC Protocol_html_5d98495052c8c10e.png" height="339" width="600"]]
1073
1074 Select [SLMP Connection Module] and add into host station as below picture shows;
1075
1076 Set Port number as 5002 (this is necessary settings);
1077
1078 Click [Close with Reflecting the Setting] to save and close window;
1079
1080 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_14b489fdc6c6589d.png?width=600&height=350&rev=1.1||alt="12.PLC Protocol_html_14b489fdc6c6589d.png" height="350" width="600"]]
1081
1082 Click [Apply] to completed Etherenet settings;
1083
1084 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1085
1086 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_c93025a968a8a9e7.png?width=600&height=434&rev=1.1||alt="12.PLC Protocol_html_c93025a968a8a9e7.png" height="434" width="600"]]
1087
1088 **4)Configure the communication protocol**
1089
1090 [[image:image-20220825112403-1.png||alt="图片-20220825112403-1.png"]]
1091
1092 **5)Cable Wiring**
1093
1094 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1095
1096 == **L02 Serial Protocol** ==
1097
1098 Mitsubishi L02 series CPU built-in serial port.
1099
1100 **1)V-BOX Settings**
1101
1102 |**Item**|**Settings**|**Note**
1103 |Protocol|Mitsubishi L02|
1104 |Connection|RS422|
1105 |Baud rate|115200|
1106 |Data bit|8|
1107 |Parity|Odd|
1108 |Stop bit|1|
1109 |PLC station No.|1~~255|Need to be the same as PLC settings
1110
1111 **2)Address List**
1112
1113 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1114 |Bit|X|X|X h|0~~FFFF|
1115 |Bit|Y|Y|Y h|0~~FFFF|
1116 |Bit|M|M|M d|0~~9999|
1117 |Bit|L|L|L d|0~~9999|
1118 |Bit|F|F|F d|0~~9999|
1119 |Bit|B|B|B h|0~~FFFF|
1120 |Bit|V|V|V d|0~~2047|
1121 |Bit|TC|TC|TC d|0~~9999|
1122 |Bit|SS|SS|SS d|0~~9999|
1123 |Bit|SC|SC|SC d|0~~9999|
1124 |Bit|CS|CS|CS d|0~~9999|
1125 |Bit|CC|CC|CC d|0~~9999|
1126 |Bit|SB|SB|SB h|0~~FFFF|
1127 |Bit|SM|SM|SM d|0~~2047|
1128 |Bit|STS|STS|STS d|0~~1023|
1129 |Bit|S|S|S d|0~~9999|
1130 |Bit|DX|DX|DX h|0~~FFFF|
1131 |Bit|DY|DY|DY h|0~~FFFF|
1132 |Bit|TS|TS|TS d|0~~9999|
1133 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1134 |Word|W|W|W h|0~~FFFF|
1135 |Word|TN|TN|TN d|0~~99999|
1136 |Word|SN|SN|SN d|0~~99999|
1137 |Word|CN|CN|CN d|0~~99999|
1138 |Word|R|R|R d|0~~99999|
1139 |Word|SW|SW|SW h|0~~FFFF|
1140 |Word|Z|Z|Z d|0~~99999|
1141 |Word|ZR|ZR|ZR h|0~~FFFF|
1142 |Word|D|D|D d|0~~99999|
1143
1144 **3)Communication Settings**
1145
1146 [[image:image-20220825160648-3.png]]
1147
1148 **4)Cable Wiring**
1149
1150 * **RS422**
1151
1152 [[image:image-20220825161612-8.png]]
1153
1154 [[image:image-20220825160820-4.png]]
1155
1156 == **L02 Ethernet Protocol** ==
1157
1158 Mitsubishi L series CPU built-in Ethernet port.
1159
1160 **1)V-BOX Settings**
1161
1162 |**Items**|**Settings**|**Note**
1163 |Protocol|MIT L02 CPU MELSEC|
1164 |Connection|Ethernet|
1165 |Port No.|1025|Must be the same as the PLC setting
1166 |PLC station No.|0|Must be the same as the PLC setting
1167
1168 **2)Address List**
1169
1170 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1171 |Bit|X|X|X h|0~~FFFF|
1172 |Bit|Y|Y|Y h|0~~FFFF|
1173 |Bit|M|M|M d|0~~9999|
1174 |Bit|L|L|L d|0~~9999|
1175 |Bit|F|F|F d|0~~9999|
1176 |Bit|B|B|B h|0~~FFFF|
1177 |Bit|V|V|V d|0~~2047|
1178 |Bit|TC|TC|TC d|0~~9999|
1179 |Bit|SS|SS|SS d|0~~9999|
1180 |Bit|SC|SC|SC d|0~~9999|
1181 |Bit|CS|CS|CS d|0~~9999|
1182 |Bit|CC|CC|CC d|0~~9999|
1183 |Bit|SB|SB|SB h|0~~FFFF|
1184 |Bit|SM|SM|SM d|0~~2047|
1185 |Bit|STS|STS|STS d|0~~1023|
1186 |Bit|S|S|S d|0~~9999|
1187 |Bit|DX|DX|DX h|0~~FFFF|
1188 |Bit|DY|DY|DY h|0~~FFFF|
1189 |Bit|TS|TS|TS d|0~~9999|
1190 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1191 |Word|W|W|W h|0~~FFFF|
1192 |Word|TN|TN|TN d|0~~99999|
1193 |Word|SN|SN|SN d|0~~99999|
1194 |Word|CN|CN|CN d|0~~99999|
1195 |Word|R|R|R d|0~~99999|
1196 |Word|SW|SW|SW h|0~~FFFF|
1197 |Word|Z|Z|Z d|0~~99999|
1198 |Word|ZR|ZR|ZR h|0~~FFFF|
1199 |Word|D|D|D d|0~~99999|
1200
1201 **3)PLC Settings (GX Works2 )**
1202
1203 Create a project
1204
1205 Set PLC IP, subnet mask and gateway;
1206
1207 Select [Binary Code] as communication data code;
1208
1209 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_776e17505f3fc6c0.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_776e17505f3fc6c0.png" height="524" width="600"]]
1210
1211 Set PLC port number, for example 1025
1212
1213 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8d0d1a22d388f70b.png?width=600&height=524&rev=1.1||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
1214
1215 Save settings;
1216
1217 Download project into PLC device;
1218
1219 Restart PLC device;
1220
1221 **4)Configure the communication protocol**
1222
1223 [[image:image-20220825142659-1.png]]
1224
1225 **5)Cable Wiring**
1226
1227 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1228
1229 == **Q12H Serial Protocol** ==
1230
1231 This Demo shows V-BOX communicate with Q12H PLC by Q02H serial Protocol
1232
1233 [[**Download link**>>https://ftp.we-con.com.cn/Download/WIKI/PI%20HMI/Demo/Communication/V-Box%20connect%20PLC%20Q12H.rar]]
1234
1235 == **QJ71E71 Ethernet Protocol** ==
1236
1237 Mitsubishi QJ71E71 Ethernet communication module;
1238
1239 **1)V-BOX Settings**
1240
1241 |**Items**|**Settings**|**Note**
1242 |Protocol|MIT QJ71E71 MELSEC|
1243 |Connection|Ethernet|
1244 |Port No.|1025|Must be the same as the PLC setting
1245 |PLC station No.|0|Must be the same as the PLC setting
1246
1247 **2)Address List**
1248
1249 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1250 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1251 |Y|Y|Y h|0~~1FFF|
1252 |M|M|M d|0~~99999|
1253 |L|L|L d|0~~8191|
1254 |F|F|F d|0~~2047|
1255 |B|B|B h|0~~1FFF|
1256 |V|V|V d|0~~2047|
1257 |TS|TS|TS d|0~~2047|
1258 |TC|TC|TC d|0~~2047|
1259 |SS|SS|SS d|0~~2047|
1260 |SC|SC|SC d|0~~2047|
1261 |CS|CS|CS d|0~~1023|
1262 |CC|CC|CC d|0~~1023|
1263 |SB|SB|SB h|0~~7FF|
1264 |S|S|S d|0~~8191|
1265 |DX|DX|DX h|0~~1FFF|
1266 |DY|DY|DY h|0~~1FFF|
1267 |SM|SM|SM d|8000~~9999|
1268 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1269 |D|D|D d|0~~12287|
1270 |W|W|W h|0~~1FFF|
1271 |TN|TN|TN d|0~~2047|
1272 |SN|SN|SN d|0~~2047|
1273 |CN|CN|CN d|0~~1023|
1274 |R|R|R d|0~~32767|
1275 |SW|SW|SW h|0~~7FF|
1276 |Z|Z|Z d|0~~15|
1277 |ZR|ZR|ZR h|0~~FE7FF|
1278
1279 **3)PLC Settings(GX Works2)**
1280
1281 * Click [Ethernet/CC IE/MELSECNET];
1282 * Please select [Ethernet] as network type;
1283 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
1284 * Select [Online] as Mode;
1285 * [[image:image-20221119171343-2.png||height="341" width="587"]]
1286 * Click [Operation setting] to set IP;
1287 * Select [Binary Code] as [Communication Data Code];
1288 * [[image:image-20221119171436-3.png||height="354" width="588"]]
1289 * Click [Open setting]
1290 * Set protocol: TCP;
1291 * Set [unpassive] in [Open system];
1292 * Set [receive] in [Fixed buffer];
1293 * Set [procedure Exist] in [Fixed buffer communication];
1294 * Disable [Pairing open];
1295 * Set [No confirm] in [Existence confirmation];
1296 * Host station port number: 5009;
1297 * Save settings;
1298 * [[image:image-20221119171611-4.png||height="354" width="588"]]
1299 * Download project into PLC and restart it
1300
1301 **4)Configure the communication protocol**
1302
1303 [[image:image-20221119171832-5.png||height="354" width="625"]]
1304
1305
1306 **5)Cable Wiring**
1307
1308 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png"]]
1309
1310 = Create communication with **Delta PLC** =
1311
1312 == **DVP Ethernet Protocol** ==
1313
1314 Supoort Series: DELTA DVP20/32/40/60ES200RE/200TE or any DVP models with built-in Ethernet port, DELTA DVPEN01-SL module
1315
1316 **1)V-BOX Settings**
1317
1318 |=**Items**|=**Settings**|=**Note**
1319 |Protocol|DELTA DVP MODBUS TCP|
1320 |Connection|Ethernet|
1321 |Port No.|502|
1322 |Device No.|1|
1323 |VBox Device No.|0|
1324
1325 **2)Address List **
1326
1327 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1328 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOO|(% style="width:225px" %)0~~377|
1329 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOO|(% style="width:225px" %)0~~377|
1330 |Bit|(% style="width:191px" %)M0|(% style="width:217px" %)M0|(% style="width:168px" %)M0DDDD|(% style="width:225px" %)0~~1535|
1331 |Bit|(% style="width:191px" %)M1|(% style="width:217px" %)M1|(% style="width:168px" %)M1DDDD|(% style="width:225px" %)1536~~4096|
1332 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1333 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~255|
1334 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDD|(% style="width:225px" %)0~~1023|
1335 |Word|(% style="width:191px" %)D0|(% style="width:217px" %)D0|(% style="width:168px" %)D0DDDD|(% style="width:225px" %)0~~4095|
1336 |Word|(% style="width:191px" %)D1|(% style="width:217px" %)D1|(% style="width:168px" %)D1DDDD|(% style="width:225px" %)4096~~11999|
1337 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDD|(% style="width:225px" %)0~~255|
1338 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1339 |Double Word|(% style="width:191px" %)HC|(% style="width:217px" %)HC|(% style="width:168px" %)HCDDD|(% style="width:225px" %)200~~255|
1340
1341 **3) PLC Setting:**
1342
1343 ~1. Create new project in Delta WPL Soft, and click Setting to open the communication settings:
1344
1345 (% style="text-align:center" %)
1346 [[image:DVPEthernetWPLSoft2.png]]
1347
1348 2. Set up the communication type and PLC IP:
1349
1350 (% style="text-align:center" %)
1351 [[image:DVPEthernetSetup.png]]
1352
1353 (% class="wikigeneratedid" %)
1354 3. Click OK and save the settings. Then click Communication on toolbar, then click Transfer Setup to open new window:
1355
1356 (% style="text-align:center" %)
1357 [[image:DVPEthernetTransfer.png]]
1358
1359 (% class="wikigeneratedid" %)
1360 4. Select Communication Mode as PC => PLC to download or select PC <=PLC to upload:
1361
1362 (% style="text-align:center" %)
1363 [[image:DVPEthernetPLCtoPC.png]]
1364
1365 5. Click Auto-Search Ethernet Module to find the PLC on the same LAN network:
1366
1367 (% style="text-align:center" %)
1368 [[image:DVPEthernetAutoSearch.png]]
1369
1370 **4) V-BOX Setting:**
1371
1372 Set the same IP address according to the setting from WPL Soft:
1373
1374 (% style="text-align:center" %)
1375 [[image:DVPEthernetVNETPortocol.png]]
1376
1377 == **DVP serial protocol** ==
1378
1379 Supoort Series: DELTA DVP EH/ES/SS/EX/EH2/SV/SA/SC/SX
1380
1381 **1)V-BOX Settings**
1382
1383 |=**Items**|=**Settings**|=**Note**
1384 |Protocol|DELTA DVP PROTOCOL|
1385 |Connection|RS232|
1386 |Baud Rate|9600|
1387 |Stop Bit|1|
1388 |Data Bit|7|
1389 |Parity|EVEN|
1390 |Device No.|1|
1391
1392 (% class="wikigeneratedid" %)
1393 **2)Address List**
1394
1395 |=**Type**|=(% style="width: 191px;" %)**Device registers**|=(% style="width: 217px;" %)**VBox registers**|=(% style="width: 168px;" %)**Format**|=(% style="width: 225px;" %)**Range**|=**Note**
1396 |Bit|(% style="width:191px" %)X|(% style="width:217px" %)X|(% style="width:168px" %)X OOOOOO|(% style="width:225px" %)0~~303237|
1397 |Bit|(% style="width:191px" %)Y|(% style="width:217px" %)Y|(% style="width:168px" %)Y OOOOOO|(% style="width:225px" %)0~~303237|
1398 |Bit|(% style="width:191px" %)M|(% style="width:217px" %)M|(% style="width:168px" %)MDDDDD|(% style="width:225px" %)0~~99999|
1399 |Bit|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1400 |Bit|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)0~~99999|
1401 |Bit|(% style="width:191px" %)S|(% style="width:217px" %)S|(% style="width:168px" %)SDDDDD|(% style="width:225px" %)0~~99999|
1402 |Word|(% style="width:191px" %)D|(% style="width:217px" %)D|(% style="width:168px" %)D DDDDD|(% style="width:225px" %)0~~99999|
1403 |Word|(% style="width:191px" %)T|(% style="width:217px" %)T|(% style="width:168px" %)TDDDDD|(% style="width:225px" %)0~~99999|
1404 |Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDD|(% style="width:225px" %)0~~199|
1405 |Double Word|(% style="width:191px" %)C|(% style="width:217px" %)C|(% style="width:168px" %)CDDDDD|(% style="width:225px" %)200~~99999|
1406
1407 (% class="wikigeneratedid" %)
1408 **3)Wiring Diagram**
1409
1410 (% style="text-align:center" %)
1411 [[image:Delta DVP PROTOCOLSerial232.png]]
1412
1413 == **AS Ethernet Protocol** ==
1414
1415 **1)V-BOX Settings**
1416
1417 |=**Items**|=**Settings**|=**Note**
1418 |Protocol|DELTA AS300 MODBUS TCP|
1419 |Connection|Ethernet|
1420 |Port No.|502|
1421 |Device No.|1|
1422 |HMI No.|0|
1423
1424 **2)Address List**
1425
1426 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1427 |Bit|X|X|X d|0~~63|
1428 |Bit|Y|Y|Y d|0~~63|
1429 |Bit|D|D|D d|0~~29999|
1430 |Bit|M|M|M d|0~~8191|
1431 |Bit|SM|SM|SM d|0~~4095|
1432 |Bit|S|S|S h|0~~2047|
1433 |Bit|T|T|T d|0~~511|
1434 |Bit|C|C|C d|0~~511|
1435 |Bit|HC|HC|HC d|0~~255|
1436 |Word|X|X|X h|0~~63|
1437 |Word|Y|Y|Y d|0~~63|
1438 |Word|SR|SR|SR d|0~~2047|
1439 |Word|D|D|D d|0~~29999|
1440 |Word|T|T|T d|0~~511|
1441 |Word|C|C|C h|0~~511|
1442 |Word|E|E|E d|0~~9|
1443
1444 **3)Configure the communication protocol**
1445
1446 [[image:image-20220831160010-4.png]]
1447
1448 **4)Cable Wiring**
1449
1450 Figure
1451
1452 [[image:image-20220831155101-1.png]][[image:image-20220831160055-5.png]]
1453
1454 Pin Definition Diagram
1455
1456 [[image:image-20220831155157-3.png]]
1457
1458 = Create communication with **Omron PLC** =
1459
1460 == **CP1 Series Protocol ** ==
1461
1462 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CP1%20Series.zip]]
1463
1464 == **CP2M Series Protocol** ==
1465
1466 [[下载链接>>https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communication%20with%20ORMON%20CJ2M.zip]]
1467
1468
1469 == **EC55 Series Protocol** ==
1470
1471 Supported device: EC55 temperature instrument
1472
1473 **1)V-BOX Settings**
1474
1475 |**Items**|**Settings**|**Note**
1476 |Protocol|Omron EC55|
1477 |Connection|RS485 (9600, 2, 7, EVEN)|
1478 |Port No.|None|
1479 |PLC station No.|0|
1480
1481 **2)Address List**
1482
1483 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1484 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1485 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1486 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1487 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1488 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1489 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1490 |CP|-|0-6|Read controller intrinsic property
1491 |CS|-|0-2|Read controller states
1492 |CA|-|0-17|Action command
1493
1494 **3)Device Settings**
1495
1496 Omron E5CC PLC configuration
1497
1498 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1499
1500 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_3d95e093792ba98a.png?width=550&height=229&rev=1.1||alt="12.PLC Protocol_html_3d95e093792ba98a.png" height="229" width="550"]]
1501
1502 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1503
1504 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_be583aa69dd6cf4c.png?width=550&height=242&rev=1.1||alt="12.PLC Protocol_html_be583aa69dd6cf4c.png" height="242" width="550"]]
1505
1506 **✎Note:** The communication settings for HMI should be consistent with this setting.
1507
1508 **4)Configure the communication protocol**
1509
1510 [[image:image-20220831161041-1.png]]
1511
1512 **5)Cable Wiring**
1513
1514 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1515
1516 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1517
1518 **✎Note:**
1519
1520 * COM3 only available in PI8000/PI9000 series.
1521 * CA address could not support continuous writing function;
1522 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1523 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1524 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1525 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1526 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1527 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1528 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1529
1530 = Create communication with Xinje** PLC** =
1531
1532 == **XC serial protocol** ==
1533
1534 **1)V-BOX Settings**
1535
1536 |**Item**|**Settings**|**Note**
1537 |Protocol|XINJE XC MODBUS|
1538 |Connection|RS232|
1539 |Baud rate|19200|
1540 |Data bit|8|
1541 |Parity|EVEN|
1542 |Stop bit|1|
1543 |PLC station No.|1|
1544
1545 **2)Address List**
1546
1547 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1548 |Bit|M|M|M d|0~~8511|
1549 |Bit|X|X|X o|0~~1747|
1550 |Bit|Y|Y|Y o|0~~1747|
1551 |Bit|S|S|S d|0~~1023|
1552 |Bit|T|T|T d|0~~4095|
1553 |Bit|C|C|C d|0~~634|
1554 |Word|D|D|D d|0~~8511|
1555 |Word|TD|TD|TD d|0~~618|
1556 |Word|CD|CD|CD d|0~~634|
1557 |Word|FD|FD|FD d|0~~8511|
1558
1559 **3)Configure the communication protocol**
1560
1561
1562 [[image:image-20220831163041-1.png]]
1563
1564 **4)Cable Wiring**
1565
1566 Figure
1567
1568 [[image:image-20220831163406-2.png]][[image:image-20220831163422-3.png]]
1569
1570 Pin Definition Diagram
1571
1572 [[image:image-20220831163441-4.png]]
1573
1574 == **XD serial protocol** ==
1575
1576 **1)V-BOX Settings**
1577
1578 Supported Series: Xinjie XD/XE Series PLC
1579
1580 |**Item**|**Settings**|**Note**
1581 |Protocol|XINJE XD/XC MODBUS|
1582 |Connection|RS232|
1583 |Baud rate|19200|
1584 |Data bit|8|
1585 |Parity|EVEN|
1586 |Stop bit|1|
1587 |PLC station No.|1|
1588
1589 **2)Address List**
1590
1591 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1592 |Bit|M|M|M d|0~~74999|
1593 |Bit|X1xx|X1xx|X1xx o|0~~1177|
1594 |Bit|X2xx|X2xx|X2xx o|0~~277|
1595 |Bit|X|X|X o|0~~77|
1596 |Bit|Y1xx|Y1xx|Y1xx o|0~~1177|
1597 |Bit|Y2xx|Y2xx|Y2xx o|0~~277|
1598 |Bit|Y|Y|Y o|0~~4095|
1599 |Bit|SM|SM|SM d|0~~4999|(((
1600
1601 )))
1602 |Bit|T|T|T d|0~~4999|
1603 |Bit|C|C|C d|0~~4999|
1604 |Bit|ET|ET|ET d|0~~31|
1605 |Bit|SE|SE|SE d|0~~31|
1606 |Bit|HM|HM|HM d|0~~11999|
1607 |Bit|HSC|HSC|HSC d|0~~39|
1608 |Bit|HS|HS|HS d|0~~999|
1609 |Bit|HT|HT|HT d|0~~1999|
1610 |Bit|HC|HC|HC d|0~~1999|
1611 |Bit|S|S|S d|0~~7999|
1612 |Word|D|D|D d|0~~69999|
1613 |Word|ID|ID|ID d|0~~99|
1614 |Word|ID1xx|ID1xx|ID1xx d|0~~999|
1615 |Word|ID2xx|ID2xx|ID2xx d|0~~299|
1616 |Word|QD|QD|QD d|0~~99|
1617 |Word|QD1xx|QD1xx|QD1xx d|0~~999|
1618 |Word|QD2xx|QD2xx|QD2xx d|0~~299|
1619 |Word|SD|SD|SD d|0~~4999|
1620 |Word|TD|TD|TD d|0~~575|
1621 |Word|CD|CD|CD d|0~~575|
1622 |Word|ETD|ETD|ETD d|0~~31|
1623 |Word|HD|HD|HD d|0~~24999|
1624 |Word|HSD|HSD|HSD d|0~~1023|
1625 |Word|HTD|HTD|HTD d|0~~95|
1626 |Word|HCD|HCD|HCD d|0~~95|
1627 |Word|HSCD|HSCD|HSCD d|0~~31|
1628 |Word|FD|FD|FD d|0~~8191|
1629 |Word|SFD|SFD|SFD d|0~~5999|
1630 |Word|FS|FS|FS d|0~~47|
1631
1632 **3)Configure the communication protocol**
1633
1634 [[image:image-20220831163923-7.png]]
1635
1636
1637
1638 **4)Cable Wiring**
1639
1640 Figure
1641
1642 [[image:image-20220831163406-2.png]][[image:image-20220831163553-6.png]]
1643
1644 Pin Definition Diagram
1645
1646 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1647
1648 = Create communication with **Schneider PLC** =
1649
1650 == **Schneider MODBUS RTU** ==
1651
1652 **1)V-BOX Setting**
1653
1654 |=**Parameters**|=**Recommended**|=**Notes**
1655 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1656 |**Connection**|RS485|
1657 |**Baud rate**|19200|
1658 |**Data bit**|8|
1659 |**Parity**|Even|
1660 |**Stop bit**|1|
1661 |**PLC station No.**|1|
1662
1663 **2)Address List**
1664
1665 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1666 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1667 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1668 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1669 |W|MW|DDDDDD|0 ~~ 999999|Output register
1670 |DW|MD|DDDDDD|0 ~~ 999999|Output register
1671
1672 **3)Configure the communication protocol**
1673
1674 [[image:image-20220902104329-1.png]]
1675
1676 **4)Cable Wiring**
1677
1678 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1679
1680 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1681
1682 = Create communication with Inovance** PLC** =
1683
1684 == **H3U serial protocol** ==
1685
1686 **1)V-BOX Settings**
1687
1688 |**Item**|**Settings**|**Note**
1689 |Protocol|INOVANCE H3U PLC|
1690 |Connection|RS422|
1691 |Baud rate|9600|
1692 |Data bit|7|
1693 |Parity|EVEN|
1694 |Stop bit|1|
1695 |PLC station No.|0|
1696
1697 **2)Address List**
1698
1699 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1700 |Bit|X|X|X o|0~~303237|
1701 |Bit|Y|Y|Y o|0~~303237|
1702 |Bit|M|M|M d|0~~99999|
1703 |Bit|T|T|T d|0~~99999|
1704 |Bit|C|C|C d|0~~99999|
1705 |Bit|SM|SM|SM d|8000~~999|
1706 |Bit|S|T|S d|0~~99999|
1707 |Bit|Lamp|Lamp|Lamp d|0~~0|
1708 |Word|X|X|X o|0~~303237|
1709 |Word|Y|Y|Y o|0~~303237|
1710 |Word|M|M|M d|0~~99999|
1711 |Word|T|T|T d|0~~99999|
1712 |Word|C|C|C d|0~~199|
1713 |Word|D|D|D d|0~~7999|
1714 |Word|S|S|S d|0~~99999|
1715 |Word|SD|SD|SD d|8000~~9999|
1716 |Word|R|R|R d|0~~32767|
1717
1718 **3)Configure the communication protocol**
1719
1720 [[image:image-20220831164626-1.png]]
1721
1722
1723
1724 **4)Cable Wiring**
1725
1726 Figure
1727
1728 [[image:image-20220831164646-2.png]][[image:image-20220831164700-3.png]]
1729
1730 Pin Definition Diagram
1731
1732 [[image:image-20220831164731-4.png]]
1733
1734 = Create communication with Panasonic** PLC** =
1735
1736 == **FP serial protocol** ==
1737
1738 **1)V-BOX Settings**
1739
1740 |**Item**|**Settings**|**Note**
1741 |Protocol|Panasonic FP MFWTOCOL|
1742 |Connection|RS232|
1743 |Baud rate|9600|
1744 |Data bit|8|
1745 |Parity|ODD|
1746 |Stop bit|1|
1747 |PLC station No.|1|
1748
1749 **2)Address List**
1750
1751 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1752 |Bit|X|X|X d|0~~9999|
1753 |Bit|Y|Y|Y d|0~~9999|
1754 |Bit|R|R|R d|0~~9999|
1755 |Bit|T|T|T d|0~~9999|
1756 |Bit|C|C|C d|0~~9999|
1757 |Bit|L|L|L d|0~~9999|
1758 |Word|WX|WX|WX d|0~~9999|
1759 |Word|WY|WY|WY d|0~~9999|
1760 |Word|WR|WR|WR d|0~~9999|
1761 |Word|WL|WL|WL d|0~~9999|
1762 |Word|LD|LD|LD d|0~~9999|
1763 |Word|DT|DT|DT d|0~~65535|
1764 |Word|FL|FL|FL d|0~~9999|
1765 |Word|EV|EV|EV d|0~~9999|
1766 |Word|SV|SV|SV d|0~~9999|
1767
1768 **3)Configure the communication protocol**
1769
1770 [[image:image-20220831165238-4.png]]
1771
1772
1773
1774 **4)Cable Wiring**
1775
1776 Figure
1777
1778 [[image:image-20220831165031-3.png]][[image:image-20220831165017-2.png]]
1779
1780 Pin Definition Diagram
1781
1782 [[image:image-20220831165008-1.png]]
1783
1784 = Create communication with LS** PLC** =
1785
1786 == **XBC serial protocol** ==
1787
1788 **1)V-BOX Settings**
1789
1790 |**Item**|**Settings**|**Note**
1791 |Protocol|LS XBC CNet|
1792 |Connection|RS232|
1793 |Baud rate|115200|
1794 |Data bit|8|
1795 |Parity|NONE|
1796 |Stop bit|1|
1797 |PLC station No.|1|
1798
1799 **2)Address List**
1800
1801 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1802 |Bit|P|P|P d|0~~2047|
1803 |Bit|M|M|M d|0~~2047|
1804 |Bit|L|L|L d|0~~11263|
1805 |Bit|K|K|K d|0~~16183|
1806 |Bit|F|F|F d|0~~2047|
1807 |Bit|D|D|D d|0~~32767|
1808 |Bit|R|R|R d|0~~32767|
1809 |Bit|U|U|U d|0~~4095|
1810 |Word|P|P|P d|0~~2047|
1811 |Word|M|M|M d|0~~2047|
1812 |Word|L|L|L d|0~~11263|
1813 |Word|K|K|K d|0~~16183|
1814 |Word|F|F|F d|0~~2047|
1815 |Word|C|C|C d|0~~2047|
1816 |Word|T|T|T d|0~~2047|
1817 |Word|D|D|D d|0~~32767|
1818 |Word|N|N|N d|0~~21503|
1819 |Word|R|R|R d|0~~32767|
1820 |Word|U|U|U d|0~~4095|
1821 |Word|Z|Z|Z d|0~~127|
1822 |Word|S|S|S d|0~~127|
1823
1824 **3)Configure the communication protocol**
1825
1826 [[image:image-20220831170147-1.png]]
1827
1828 **4)Cable Wiring**
1829
1830 Figure
1831
1832 [[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1833
1834 Pin Definition Diagram
1835
1836 [[image:image-20220831170215-2.png]]
1837
1838 == **XGK FEnet Ethernet protocol** ==
1839
1840 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1841
1842 **1)V-BOX Settings**
1843
1844 |**Items**|**Settings**|**Note**
1845 |Protocol|LG XGK FEnet(Ethernet)|
1846 |Connection|Ethernet|
1847 |Port No.|2004|
1848
1849 **2)Address List**
1850
1851 |**Type**|**Register**|**Range**|**Format**|**Note**
1852 |(% rowspan="14" %)Word|P|0~~2047|P d|
1853 |M|0~~2047|M d|
1854 |K|0~~2047|K d|
1855 |F|0~~2047|F d|
1856 |T|0~~2047|T d|
1857 |C|0~~2047|C d|
1858 |Z|0~~127|Z d|
1859 |S|0~~127|S d|
1860 |L|0~~11263|L d|
1861 |N|0~~21503|N d|
1862 |D|0~~32767|D d|
1863 |R|0~~32767|R d|
1864 |ZR|0~~65535|ZR d|
1865 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
1866
1867 **✎Note:**
1868
1869 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
1870 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1871 * All bit registers are in the form of bits in word, and the range is the same as the word register;
1872
1873 **3)Communication Settings**
1874
1875 [[image:image-20220831171127-1.png]]
1876
1877 **4)Cable Wiring**
1878
1879 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1880
1881 = Create communication with **Modbus ** =
1882
1883 == **MODBUS RTU Slave (All function)** ==
1884
1885 Select the protocol "Modbus RTU Slave (All Fuction)",
1886
1887 Then set baud rate, port, stop bits, data bits, parity.
1888
1889 (% style="text-align:center" %)
1890 [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1891
1892 == **MODBUS RTU Master** ==
1893
1894 Select the protocol "Modbus RTU Master",
1895
1896 Then set baud rate, port, stop bits, data bits, parity
1897
1898 (% style="text-align:center" %)
1899 [[image:1624348709622-711.png||queryString="width=809&height=493" height="488" width="800" class="img-thumbnail"]]
1900
1901 **address list**
1902
1903 (% class="table-bordered" %)
1904 |=(% scope="row" %)**Type**|=**Data Type**|=**Function code and description**
1905 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (Read Input Registers: Read the current binary value in one or more input registers)
1906 |06 (write single register: write a binary value to a holding register)
1907 |10 (write values to multiple addresses )
1908 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1909 |06 (write single register: write a binary value to a holding register)
1910 |10 (write values to multiple addresses )
1911 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1912 |06 (write single register: write a binary value to a holding register)
1913 |10 (write values to multiple addresses )
1914 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1915 |10 (write values to multiple addresses )
1916 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1917 |05 (Force a single coil to force the on/off state of a logic coil)
1918 |0F (Write multiple bits, ie write continuously)
1919 |(% rowspan="3" %)1|02 (Read the input state)
1920 |05 (Force a single coil to force the on/off state of a logic coil)
1921 |0F (Write multiple bits)
1922 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1923 |05 (Force a single coil to force the on/off state of a logic coil)
1924 |0F (Write multiple bits)
1925 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1926 |0F (Write multiple bits)
1927
1928 == **MODBUS TCP Slave (All function)** ==
1929
1930 Supported series: MODBUS TCP controller
1931
1932 V-B0X works as MODBUS TCP MASTER connecting with TCP SLAVE
1933
1934 **1)V-BOX Setting**
1935
1936 |**Items**|**Settings**|**Note**
1937 |Protocol|MODBUS TCP Slave (All function)|
1938 |Connection|Ethernet|
1939 |Port No.|502|
1940 |PLC station No.|1
1941
1942 **2)Address List**
1943
1944 |=**Type**|=**Data Type**|=**Function code & Description**
1945 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1946 |06 (write single register: write a binary value to a holding register)
1947 |10 (write values to multiple addresses )
1948 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1949 |06 (write single register: write a binary value to a holding register)
1950 |10 (write values to multiple addresses )
1951 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1952 |06 (write single register: write a binary value to a holding register)
1953 |10 (write values to multiple addresses )
1954 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1955 |10 (write values to multiple addresses )
1956 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1957 |05 (Force a single coil to force the on/off state of a logic coil)
1958 |0F (Write multiple bits, ie write continuously)
1959 |(% rowspan="3" %)1|02 (Read the input state)
1960 |05 (Force a single coil to force the on/off state of a logic coil)
1961 |0F (Write multiple bits)
1962 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1963 |05 (Force a single coil to force the on/off state of a logic coil)
1964 |0F (Write multiple bits)
1965 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1966 |0F (Write multiple bits)
1967
1968 **3)Communication Settings**
1969
1970 Configure V-BOX Ethernet IP in Networking Settings
1971
1972 [[image:image-20220902111833-3.png]]
1973
1974
1975 Configure PLC Ethernet IP in Communication;
1976
1977 [[image:image-20220902111121-1.png]]
1978
1979 **4)Cable Wiring**
1980
1981 [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1982
1983 == **communicate with VB inverter** ==
1984
1985 [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]
1986
1987 = **User define protocol** =
1988
1989 More serial port script instruction,please refer manual:[[Lua script function>>doc:V-BOX.V-Net.Manual.04 Lua Script.01 Lua Functions.WebHome]]~-~-->[[3.Serial port operation>>url:http://docs.we-con.com.cn/wiki/vbox/view/HMI/04.Lua%20script%20%20function%20and%20operation/01.Lua%20script%20function/#H3.Serialportoperation]]
1990
1991 == **Read the temperature sensor.** ==
1992
1993 the commond format is as beliow:
1994
1995 Send commond:01 03 02 00 00 03 04 73
1996
1997 Feedback commond:01 03 06 07 F7 0E 7E B7 35
1998
1999 Temperature data:07 F7,desimal = 2039,it means temperature is 20.39℃.
2000
2001 Humidity data:0E 7E,desimal = 3710, it mean humidity is 37.10%RH.
2002
2003 Script Demo:
2004
2005 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~--
2006
2007 function com.main()
2008 ~-~-dosomething
2009 openPlc()
2010 end
2011 function openPlc()
2012 if obj then
2013 ~-~- If the serial port opened,then read/write data by timing
2014
2015 local wri = string.pack(">HHHH",0X0103,0X0200,0X0003,0X0473)
2016 local arr = reading(wri)
2017 ~-~- if arr ~~=nil then
2018 ~-~- if arr[1] ==33 and arr[2] ==v[2][2] and arr[3] ==v[2][3] then
2019 ~-~- local A = arr[4]*256
2020 ~-~- local B = A+arr[5]
2021 ~-~- addr_setword(v[1],B)
2022 ~-~- end
2023 ~-~- end
2024
2025 else
2026 ~-~-judge if there is a serial object, then initialize and open the serial port
2027 local configs = {
2028 name = 'COM1', ~-~-Select serial port COM1
2029 mode = 485, ~-~-Communication mode RS485
2030 baud_rate = 9600, ~-~-Baud rate 9600
2031 stop_bit = 1, ~-~-stop bit 1
2032 data_len = 8, ~-~-data length 8
2033 check_bit = 'NONE', ~-~-no parity
2034
2035 }
2036 obj,err = serial.open(configs) ~-~-Open serial port
2037 if not obj then
2038 print("serial open :failed", err) ~-~- Open serial port failed
2039 end
2040 end
2041 end
2042
2043 function reading(wri)
2044 obj:flush() ~-~- Clear serial port
2045 obj:write(wri) ~-~- Write serial port
2046 print(string.byte(wri,1,#wri))
2047 obj:flush() ~-~- Clear serial port 
2048 local readed =obj:read(9,1000) ~-~- Read 9 bytes, timeout 1 second
2049 if readed and readed ~~= "" then 
2050 ~-~- judge that a non-empty string is read
2051 print(string.byte(readed,1,#readed))
2052 a={string.byte(readed, 1, #readed)}
2053 if nil ~~= a[4] and nil ~~= a[5] and nil ~~= a[6] and nil ~~= a[7] then
2054 a1=a[4]*256+a[5]
2055 a2=a[6]*256+a[7]
2056 addr_setword("@HDW0",a1)
2057 addr_setword("@HDW1",a2)
2058 end
2059 return {string.byte(readed, 1, #readed)}
2060 elseif readed == nil then
2061 print("serial read err:", err or "")
2062 return nil
2063 end
2064 return nil
2065 end
2066
2067 ~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-