Changes for page 1 Communication
Last modified by Hunter on 2024/07/01 10:54
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -1194,494 +1194,6 @@ 1194 1194 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests. 1195 1195 * [[image:image-20220831161356-1.png]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written. 1196 1196 1197 -= Create communication with Xinje** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=34]] = 1198 - 1199 -== **XC serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=35]] == 1200 - 1201 -**1)HMI Settings** 1202 - 1203 -|**Item**|**Settings**|**Note** 1204 -|Protocol|XINJE XC MODBUS| 1205 -|Connection|RS232| 1206 -|Baud rate|19200| 1207 -|Data bit|8| 1208 -|Parity|EVEN| 1209 -|Stop bit|1| 1210 -|PLC station No.|1| 1211 - 1212 -**2)Address List** 1213 - 1214 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 1215 -|Bit|M|M|M d|0~~8511| 1216 -|Bit|X|X|X o|0~~1747| 1217 -|Bit|Y|Y|Y o|0~~1747| 1218 -|Bit|S|S|S d|0~~1023| 1219 -|Bit|T|T|T d|0~~4095| 1220 -|Bit|C|C|C d|0~~634| 1221 -|Word|D|D|D d|0~~8511| 1222 -|Word|TD|TD|TD d|0~~618| 1223 -|Word|CD|CD|CD d|0~~634| 1224 -|Word|FD|FD|FD d|0~~8511| 1225 - 1226 -**3)Configure the communication protocol** 1227 - 1228 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830154105-1.png?rev=1.1||alt="image-20220830154105-1.png"]] 1229 - 1230 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830154159-3.png?rev=1.1||alt="image-20220830154159-3.png"]] 1231 - 1232 -**4)Cable Wiring** 1233 - 1234 -Figure 1235 - 1236 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830155728-4.png?rev=1.1||alt="image-20220830155728-4.png"]] 1237 - 1238 -Pin Definition Diagram 1239 - 1240 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830154131-2.png?rev=1.1||alt="image-20220830154131-2.png"]] 1241 - 1242 -== **XD serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=36]] == 1243 - 1244 -**1)HMI Settings** 1245 - 1246 -Supported Series: Delta Xinjie XD/XE Series PLC 1247 - 1248 -|**Item**|**Settings**|**Note** 1249 -|Protocol|XINJE XD/XC MODBUS| 1250 -|Connection|RS232| 1251 -|Baud rate|19200| 1252 -|Data bit|8| 1253 -|Parity|EVEN| 1254 -|Stop bit|1| 1255 -|PLC station No.|1| 1256 - 1257 -**2)Address List** 1258 - 1259 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 1260 -|Bit|M|M|M d|0~~74999| 1261 -|Bit|X1xx|X1xx|X1xx o|0~~1177| 1262 -|Bit|X2xx|X2xx|X2xx o|0~~277| 1263 -|Bit|X|X|X o|0~~77| 1264 -|Bit|Y1xx|Y1xx|Y1xx o|0~~1177| 1265 -|Bit|Y2xx|Y2xx|Y2xx o|0~~277| 1266 -|Bit|Y|Y|Y o|0~~4095| 1267 -|Bit|SM|SM|SM d|0~~4999|((( 1268 - 1269 -))) 1270 -|Bit|T|T|T d|0~~4999| 1271 -|Bit|C|C|C d|0~~4999| 1272 -|Bit|ET|ET|ET d|0~~31| 1273 -|Bit|SE|SE|SE d|0~~31| 1274 -|Bit|HM|HM|HM d|0~~11999| 1275 -|Bit|HSC|HSC|HSC d|0~~39| 1276 -|Bit|HS|HS|HS d|0~~999| 1277 -|Bit|HT|HT|HT d|0~~1999| 1278 -|Bit|HC|HC|HC d|0~~1999| 1279 -|Bit|S|S|S d|0~~7999| 1280 -|Word|D|D|D d|0~~69999| 1281 -|Word|ID|ID|ID d|0~~99| 1282 -|Word|ID1xx|ID1xx|ID1xx d|0~~999| 1283 -|Word|ID2xx|ID2xx|ID2xx d|0~~299| 1284 -|Word|QD|QD|QD d|0~~99| 1285 -|Word|QD1xx|QD1xx|QD1xx d|0~~999| 1286 -|Word|QD2xx|QD2xx|QD2xx d|0~~299| 1287 -|Word|SD|SD|SD d|0~~4999| 1288 -|Word|TD|TD|TD d|0~~575| 1289 -|Word|CD|CD|CD d|0~~575| 1290 -|Word|ETD|ETD|ETD d|0~~31| 1291 -|Word|HD|HD|HD d|0~~24999| 1292 -|Word|HSD|HSD|HSD d|0~~1023| 1293 -|Word|HTD|HTD|HTD d|0~~95| 1294 -|Word|HCD|HCD|HCD d|0~~95| 1295 -|Word|HSCD|HSCD|HSCD d|0~~31| 1296 -|Word|FD|FD|FD d|0~~8191| 1297 -|Word|SFD|SFD|SFD d|0~~5999| 1298 -|Word|FS|FS|FS d|0~~47| 1299 - 1300 -**3)Configure the communication protocol** 1301 - 1302 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160042-1.png?rev=1.1||alt="image-20220830160042-1.png"]] 1303 - 1304 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160129-2.png?rev=1.1||alt="image-20220830160129-2.png"]] 1305 - 1306 -**4)Cable Wiring** 1307 - 1308 -Figure 1309 - 1310 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160257-4.png?rev=1.1||alt="image-20220830160257-4.png"]] 1311 - 1312 -Pin Definition Diagram 1313 - 1314 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]] 1315 - 1316 -= Create communication with Inovance** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=37]] = 1317 - 1318 -== **H3U serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=38]] == 1319 - 1320 -**1)HMI Settings** 1321 - 1322 -|**Item**|**Settings**|**Note** 1323 -|Protocol|INOVANCE H3U PLC| 1324 -|Connection|RS22| 1325 -|Baud rate|9600| 1326 -|Data bit|7| 1327 -|Parity|EVEN| 1328 -|Stop bit|1| 1329 -|PLC station No.|0| 1330 - 1331 -**2)Address List** 1332 - 1333 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 1334 -|Bit|X|X|X o|0~~303237| 1335 -|Bit|Y|Y|Y o|0~~303237| 1336 -|Bit|M|M|M d|0~~99999| 1337 -|Bit|T|T|T d|0~~99999| 1338 -|Bit|C|C|C d|0~~99999| 1339 -|Bit|SM|SM|SM d|8000~~999| 1340 -|Bit|S|T|S d|0~~99999| 1341 -|Bit|Lamp|Lamp|Lamp d|0~~0| 1342 -|Word|X|X|X o|0~~303237| 1343 -|Word|Y|Y|Y o|0~~303237| 1344 -|Word|M|M|M d|0~~99999| 1345 -|Word|T|T|T d|0~~99999| 1346 -|Word|C|C|C d|0~~199| 1347 -|Word|D|D|D d|0~~7999| 1348 -|Word|S|S|S d|0~~99999| 1349 -|Word|SD|SD|SD d|8000~~9999| 1350 -|Word|R|R|R d|0~~32767| 1351 - 1352 -**3)Configure the communication protocol** 1353 - 1354 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830170114-4.png?rev=1.1||alt="image-20220830170114-4.png"]] 1355 - 1356 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830170017-3.png?rev=1.1||alt="image-20220830170017-3.png"]] 1357 - 1358 -**4)Cable Wiring** 1359 - 1360 -Figure 1361 - 1362 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830165930-1.png?rev=1.1||alt="image-20220830165930-1.png"]] 1363 - 1364 -Pin Definition Diagram 1365 - 1366 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830165947-2.png?rev=1.1||alt="image-20220830165947-2.png"]] 1367 - 1368 -= Create communication with Panasonic** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=39]] = 1369 - 1370 -== **FP serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=40]] == 1371 - 1372 -**1)HMI Settings** 1373 - 1374 -|**Item**|**Settings**|**Note** 1375 -|Protocol|Panasonic FP MFWTOCOL| 1376 -|Connection|RS232| 1377 -|Baud rate|9600| 1378 -|Data bit|8| 1379 -|Parity|ODD| 1380 -|Stop bit|1| 1381 -|PLC station No.|1| 1382 - 1383 -**2)Address List** 1384 - 1385 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 1386 -|Bit|X|X|X d|0~~9999| 1387 -|Bit|Y|Y|Y d|0~~9999| 1388 -|Bit|R|R|R d|0~~9999| 1389 -|Bit|T|T|T d|0~~9999| 1390 -|Bit|C|C|C d|0~~9999| 1391 -|Bit|L|L|L d|0~~9999| 1392 -|Word|WX|WX|WX d|0~~9999| 1393 -|Word|WY|WY|WY d|0~~9999| 1394 -|Word|WR|WR|WR d|0~~9999| 1395 -|Word|WL|WL|WL d|0~~9999| 1396 -|Word|LD|LD|LD d|0~~9999| 1397 -|Word|DT|DT|DT d|0~~65535| 1398 -|Word|FL|FL|FL d|0~~9999| 1399 -|Word|EV|EV|EV d|0~~9999| 1400 -|Word|SV|SV|SV d|0~~9999| 1401 - 1402 -**3)Configure the communication protocol** 1403 - 1404 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171050-1.png?rev=1.1||alt="image-20220830171050-1.png"]] 1405 - 1406 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171126-2.png?rev=1.1||alt="image-20220830171126-2.png"]] 1407 - 1408 -**4)Cable Wiring** 1409 - 1410 -Figure 1411 - 1412 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171328-4.png?rev=1.1||alt="image-20220830171328-4.png"]] 1413 - 1414 -Pin Definition Diagram 1415 - 1416 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830171146-3.png?rev=1.1||alt="image-20220830171146-3.png"]] 1417 - 1418 -= Create communication with LS** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=41]] = 1419 - 1420 -== **XBC serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=42]] == 1421 - 1422 -**1)HMI Settings** 1423 - 1424 -|**Item**|**Settings**|**Note** 1425 -|Protocol|LS XBC CNet| 1426 -|Connection|RS232| 1427 -|Baud rate|115200| 1428 -|Data bit|8| 1429 -|Parity|NONE| 1430 -|Stop bit|1| 1431 -|PLC station No.|1| 1432 - 1433 -**2)Address List** 1434 - 1435 -|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 1436 -|Bit|P|P|P d|0~~2047| 1437 -|Bit|M|M|M d|0~~2047| 1438 -|Bit|L|L|L d|0~~11263| 1439 -|Bit|K|K|K d|0~~16183| 1440 -|Bit|F|F|F d|0~~2047| 1441 -|Bit|D|D|D d|0~~32767| 1442 -|Bit|R|R|R d|0~~32767| 1443 -|Bit|U|U|U d|0~~4095| 1444 -|Word|P|P|P d|0~~2047| 1445 -|Word|M|M|M d|0~~2047| 1446 -|Word|L|L|L d|0~~11263| 1447 -|Word|K|K|K d|0~~16183| 1448 -|Word|F|F|F d|0~~2047| 1449 -|Word|C|C|C d|0~~2047| 1450 -|Word|T|T|T d|0~~2047| 1451 -|Word|D|D|D d|0~~32767| 1452 -|Word|N|N|N d|0~~21503| 1453 -|Word|R|R|R d|0~~32767| 1454 -|Word|U|U|U d|0~~4095| 1455 -|Word|Z|Z|Z d|0~~127| 1456 -|Word|S|S|S d|0~~127| 1457 - 1458 -**3)Configure the communication protocol** 1459 - 1460 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174853-3.png?rev=1.1||alt="image-20220830174853-3.png"]] 1461 - 1462 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174733-2.png?rev=1.1||alt="image-20220830174733-2.png"]] 1463 - 1464 -**4)Cable Wiring** 1465 - 1466 -Figure 1467 - 1468 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174659-1.png?rev=1.1||alt="image-20220830174659-1.png"]] 1469 - 1470 -Pin Definition Diagram 1471 - 1472 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830173402-8.png?rev=1.1||alt="image-20220830173402-8.png"]] 1473 - 1474 -== **XGK FEnet Ethernet protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=43]] == 1475 - 1476 -Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module 1477 - 1478 -**HMI Settings** 1479 - 1480 -|**Items**|**Settings**|**Note** 1481 -|Protocol|LG XGK FEnet(Ethernet)| 1482 -|Connection|Ethernet| 1483 -|Port No.|2004| 1484 - 1485 -**Address List** 1486 - 1487 -|**Type**|**Register**|**Range**|**Format**|**Note** 1488 -|(% rowspan="14" %)Word|P|0~~2047|P d| 1489 -|M|0~~2047|M d| 1490 -|K|0~~2047|K d| 1491 -|F|0~~2047|F d| 1492 -|T|0~~2047|T d| 1493 -|C|0~~2047|C d| 1494 -|Z|0~~127|Z d| 1495 -|S|0~~127|S d| 1496 -|L|0~~11263|L d| 1497 -|N|0~~21503|N d| 1498 -|D|0~~32767|D d| 1499 -|R|0~~32767|R d| 1500 -|ZR|0~~65535|ZR d| 1501 -|UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31 1502 - 1503 -**✎Note:** 1504 - 1505 -* In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC; 1506 -* The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC; 1507 -* All bit registers are in the form of bits in word, and the range is the same as the word register; 1508 - 1509 -**Communication settings in HMI** 1510 - 1511 -Enable HMI Ethernet in [Project Settings]; 1512 - 1513 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_43b671f18153910d.png?width=405&height=107&rev=1.1||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]] 1514 - 1515 -Set PLC IP in [Device IP] settings; 1516 - 1517 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_a2a19b5003ad4090.png?width=554&height=189&rev=1.1||alt="12.PLC Protocol_html_a2a19b5003ad4090.png" height="189" width="554"]] 1518 - 1519 -**Cable Wiring** 1520 - 1521 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]] 1522 - 1523 -= Create communication with **SHIMADEN PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=44]] = 1524 - 1525 -== **FP23 series protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=45]] == 1526 - 1527 -Supported series: SHIMADEN FP23 series 1528 - 1529 -**HMI Setting** 1530 - 1531 -|**Items**|**Settings**|**Note** 1532 -|Protocol|SHIMADEN FP23 series| 1533 -|Connection|RS485 (9600, 1, 7, EVEN)| 1534 -|Port No.|None| 1535 -|PLC station No.|0| 1536 - 1537 -**Address List** 1538 - 1539 -|**Device address**|**HMI register**|**Address range**|**Type** 1540 -|0040-0043(HEX)|FP040|100064-200067|Read only 1541 -|0100-010B(HEX)|FP100|100256-200267|Read only 1542 -|0110-0142(HEX)|FP110|100272-200322|Read only 1543 -|0182-0252(HEX)|FP182|100386-200594|Write only 1544 -|0280-0281(HEX)|FP280|100640-200641|Read only 1545 -|0300-030B(HEX)|FP300|100768-200779|Read and write 1546 -|0380-039F(HEX)|FP380|100896-200927|Read and write 1547 -|0400-04D7(HEX)|FP400|101024-201239|Read and write 1548 -|0500-05B0(HEX)|FP500|101280-201456|Read and write 1549 -|0600-0670(HEX)|FP600|101536-201814|Read and write 1550 -|0720-0738(HEX)|FP720|101824-201848|Read and write 1551 -|0800-083F(HEX)|FP800|102048-202111|Read and write 1552 -|0900-0952(HEX)|FP900|102304-202386|Read and write 1553 -| |Ctrl|0-2| 1554 - 1555 -**✎Note:** 1556 - 1557 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 1558 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23; 1559 -* The Ctrl register is used to store the control group number and BCC check mode. 1560 - 1561 -**Ctrl Register Description** 1562 - 1563 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 1564 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . 1565 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 1566 -* Ctrl3 reserved 1567 - 1568 -**✎Note:** 1569 - 1570 -After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. 1571 - 1572 -**Cable Wiring** 1573 - 1574 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]] 1575 - 1576 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]] 1577 - 1578 -**✎Note:** COM3 only available in PI8000/PI9000 series. 1579 - 1580 -== **SR90 protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=46]] == 1581 - 1582 -Supported series: SHIMADEN SR90 series 1583 - 1584 -**HMI Setting** 1585 - 1586 -|**Items**|**Settings**|**Note** 1587 -|Protocol|SHIMADEN SR90 protocol| 1588 -|Connection|RS485 (1200, 1, 7, EVEN)| 1589 -|Port No.|None| 1590 -|PLC station No.|0| 1591 - 1592 -**Address List** 1593 - 1594 -|**Device address**|**HMI register**|**Address range**|**Type** 1595 -|0040-0043 (HEX)|SR040|100064-100067|Read only 1596 -|0100-010A(HEX)|SR0100|100256-100266|Read only 1597 -|0182-018C(HEX)|SR0182|100386-100396|Write only 1598 -|0300-04FE(HEX)|SR0300|100768-101278|Write/read 1599 -|0500-050B(HEX)|SR0500|101280-101291|Write/read 1600 -|0590-0611(HEX)|SR0590|101424-101553|Write/read 1601 -|0701-0709(HEX)|SR0701|101793-101801|Write/read 1602 -| |Ctrl|0-2|~-~- 1603 - 1604 -**✎Note:** 1605 - 1606 -* The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 1607 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90; 1608 -* The Ctrl register is used to store the control group number and BCC check mode. See how to use it below; 1609 - 1610 -**Ctrl Register Description** 1611 - 1612 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 1613 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR . 1614 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 1615 -* Ctrl3 reserved 1616 - 1617 -**✎Note:** 1618 - 1619 -After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. 1620 - 1621 -**Cable Wiring** 1622 - 1623 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]] 1624 - 1625 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]] 1626 - 1627 -**✎Note:** COM3 only available in PI8000/PI9000 series. 1628 - 1629 -== **MR13 series(standard protocol)**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=47]] == 1630 - 1631 -Supported series: SHIMADEN MR13 series 1632 - 1633 -**HMI Setting** 1634 - 1635 -|**Items**|**Settings**|**Note** 1636 -|Protocol|SHIMADEN standard protocol| 1637 -|Connection|RS485 (1200, 1, 7, EVEN)| 1638 -|Port No.|None| 1639 -|PLC station No.|0| 1640 - 1641 -**Address List** 1642 - 1643 -|**Device address**|**HMI register**|**Address range**|**Type** 1644 -|0100-010B(HEX)|MR100|100256-300267|Read only 1645 -|0111-0126(HEX)|MR111|100273-300294|Read only 1646 -|0184-0192(HEX)|MR184|100388-300402|Write only 1647 -|0280-0282(HEX)|MR280|100640-300642|Read only 1648 -|0300-030B(HEX)|MR300|100768-300779|Read/write 1649 -|0314-0317(HEX)|MR314|100788-300791|Read/write 1650 -|031A(HEX)|MR31A|100794-300794|Read/write 1651 -|0320-0321(HEX)|MR320|100800-300801|Read/write 1652 -|0400-0504(HEX)|MR400|101024-301284|Read/write 1653 -|0506(HEX)|MR506|101286-301286|Read/write 1654 -|0510-0514(HEX)|MR510|101296-301300|Read/write 1655 -|0516-0524(HEX)|MR516|101302-301316|Read/write 1656 -|0526(HEX)|MR526|101318-301318|Read/write 1657 -|0580-08C3(HEX)|MR580|101408-302243|Read/write 1658 -|~-~-|Ctrl|0-2|~-~- 1659 - 1660 -**✎Note:** 1661 - 1662 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address); 1663 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13; 1664 -* The Ctrl register is used to store the control group number and BCC check mode. 1665 - 1666 -**Ctrl Register Description** 1667 - 1668 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller. 1669 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR . 1670 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None; 1671 -* Ctrl3 reserved 1672 - 1673 -**✎Note:** 1674 - 1675 -After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal. 1676 - 1677 -**Cable Wiring** 1678 - 1679 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]] 1680 - 1681 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]] 1682 - 1683 -**✎Note:** COM3 only available in PI8000/PI9000 series. 1684 - 1685 1685 = Create communication with **Modbus RTU** = 1686 1686 1687 1687 == **V-BOX as Slave** ==