... ... @@ -1414,11 +1414,11 @@
1414 1414  
1415 1415  [[image:image-20220831165008-1.png]]
1416 1416  
1417 -= Create communication with LS** PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=41]] =
1417 += Create communication with LS** PLC** =
1418 1418  
1419 -== **XBC serial protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=42]] ==
1419 +== **XBC serial protocol** ==
1420 1420  
1421 -**1)HMI Settings**
1421 +**1)V-BOX Settings**
1422 1422  
1423 1423  |**Item**|**Settings**|**Note**
1424 1424  |Protocol|LS XBC CNet|
... ... @@ -1456,25 +1456,23 @@
1456 1456  
1457 1457  **3)Configure the communication protocol**
1458 1458  
1459 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174853-3.png?rev=1.1||alt="image-20220830174853-3.png"]]
1459 +[[image:image-20220831170147-1.png]]
1460 1460  
1461 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174733-2.png?rev=1.1||alt="image-20220830174733-2.png"]]
1462 -
1463 1463  **4)Cable Wiring**
1464 1464  
1465 1465  Figure
1466 1466  
1467 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830174659-1.png?rev=1.1||alt="image-20220830174659-1.png"]]
1465 +[[image:image-20220831170306-4.png]][[image:image-20220831170254-3.png]]
1468 1468  
1469 1469  Pin Definition Diagram
1470 1470  
1471 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830173402-8.png?rev=1.1||alt="image-20220830173402-8.png"]]
1469 +[[image:image-20220831170215-2.png]]
1472 1472  
1473 -== **XGK FEnet Ethernet protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=43]] ==
1471 +== **XGK FEnet Ethernet protocol** ==
1474 1474  
1475 1475  Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
1476 1476  
1477 -**HMI Settings**
1475 +**1)V-BOX Settings**
1478 1478  
1479 1479  |**Items**|**Settings**|**Note**
1480 1480  |Protocol|LG XGK FEnet(Ethernet)|
... ... @@ -1481,7 +1481,7 @@
1481 1481  |Connection|Ethernet|
1482 1482  |Port No.|2004|
1483 1483  
1484 -**Address List**
1482 +**2)Address List**
1485 1485  
1486 1486  |**Type**|**Register**|**Range**|**Format**|**Note**
1487 1487  |(% rowspan="14" %)Word|P|0~~2047|P d|
... ... @@ -1505,182 +1505,14 @@
1505 1505  * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
1506 1506  * All bit registers are in the form of bits in word, and the range is the same as the word register;
1507 1507  
1508 -**Communication settings in HMI**
1506 +**3)Communication Settings**
1509 1509  
1510 -Enable HMI Ethernet in [Project Settings];
1508 +[[image:image-20220831171127-1.png]]
1511 1511  
1512 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_43b671f18153910d.png?width=405&height=107&rev=1.1||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
1510 +**4)Cable Wiring**
1513 1513  
1514 -Set PLC IP in [Device IP] settings;
1515 -
1516 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_a2a19b5003ad4090.png?width=554&height=189&rev=1.1||alt="12.PLC Protocol_html_a2a19b5003ad4090.png" height="189" width="554"]]
1517 -
1518 -**Cable Wiring**
1519 -
1520 1520  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1521 1521  
1522 -= Create communication with **SHIMADEN PLC**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=44]] =
1523 -
1524 -== **FP23 series protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=45]] ==
1525 -
1526 -Supported series: SHIMADEN FP23 series
1527 -
1528 -**HMI Setting**
1529 -
1530 -|**Items**|**Settings**|**Note**
1531 -|Protocol|SHIMADEN FP23 series|
1532 -|Connection|RS485 (9600, 1, 7, EVEN)|
1533 -|Port No.|None|
1534 -|PLC station No.|0|
1535 -
1536 -**Address List**
1537 -
1538 -|**Device address**|**HMI register**|**Address range**|**Type**
1539 -|0040-0043(HEX)|FP040|100064-200067|Read only
1540 -|0100-010B(HEX)|FP100|100256-200267|Read only
1541 -|0110-0142(HEX)|FP110|100272-200322|Read only
1542 -|0182-0252(HEX)|FP182|100386-200594|Write only
1543 -|0280-0281(HEX)|FP280|100640-200641|Read only
1544 -|0300-030B(HEX)|FP300|100768-200779|Read and write
1545 -|0380-039F(HEX)|FP380|100896-200927|Read and write
1546 -|0400-04D7(HEX)|FP400|101024-201239|Read and write
1547 -|0500-05B0(HEX)|FP500|101280-201456|Read and write
1548 -|0600-0670(HEX)|FP600|101536-201814|Read and write
1549 -|0720-0738(HEX)|FP720|101824-201848|Read and write
1550 -|0800-083F(HEX)|FP800|102048-202111|Read and write
1551 -|0900-0952(HEX)|FP900|102304-202386|Read and write
1552 -| |Ctrl|0-2|
1553 -
1554 -**✎Note:**
1555 -
1556 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1557 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1558 -* The Ctrl register is used to store the control group number and BCC check mode.
1559 -
1560 -**Ctrl Register Description**
1561 -
1562 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1563 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1564 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1565 -* Ctrl3 reserved
1566 -
1567 -**✎Note:**
1568 -
1569 -After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1570 -
1571 -**Cable Wiring**
1572 -
1573 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1574 -
1575 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1576 -
1577 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1578 -
1579 -== **SR90 protocol**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=46]] ==
1580 -
1581 -Supported series: SHIMADEN SR90 series
1582 -
1583 -**HMI Setting**
1584 -
1585 -|**Items**|**Settings**|**Note**
1586 -|Protocol|SHIMADEN SR90 protocol|
1587 -|Connection|RS485 (1200, 1, 7, EVEN)|
1588 -|Port No.|None|
1589 -|PLC station No.|0|
1590 -
1591 -**Address List**
1592 -
1593 -|**Device address**|**HMI register**|**Address range**|**Type**
1594 -|0040-0043 (HEX)|SR040|100064-100067|Read only
1595 -|0100-010A(HEX)|SR0100|100256-100266|Read only
1596 -|0182-018C(HEX)|SR0182|100386-100396|Write only
1597 -|0300-04FE(HEX)|SR0300|100768-101278|Write/read
1598 -|0500-050B(HEX)|SR0500|101280-101291|Write/read
1599 -|0590-0611(HEX)|SR0590|101424-101553|Write/read
1600 -|0701-0709(HEX)|SR0701|101793-101801|Write/read
1601 -| |Ctrl|0-2|~-~-
1602 -
1603 -**✎Note:**
1604 -
1605 -* The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1606 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1607 -* The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1608 -
1609 -**Ctrl Register Description**
1610 -
1611 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1612 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1613 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1614 -* Ctrl3 reserved
1615 -
1616 -**✎Note:**
1617 -
1618 -After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1619 -
1620 -**Cable Wiring**
1621 -
1622 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1623 -
1624 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1625 -
1626 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1627 -
1628 -== **MR13 series(standard protocol)**[[Edit>>url:https://docs.we-con.com.cn/bin/edit/PIStudio/12.PLC%20protocols/WebHome?section=47]] ==
1629 -
1630 -Supported series: SHIMADEN MR13 series
1631 -
1632 -**HMI Setting**
1633 -
1634 -|**Items**|**Settings**|**Note**
1635 -|Protocol|SHIMADEN standard protocol|
1636 -|Connection|RS485 (1200, 1, 7, EVEN)|
1637 -|Port No.|None|
1638 -|PLC station No.|0|
1639 -
1640 -**Address List**
1641 -
1642 -|**Device address**|**HMI register**|**Address range**|**Type**
1643 -|0100-010B(HEX)|MR100|100256-300267|Read only
1644 -|0111-0126(HEX)|MR111|100273-300294|Read only
1645 -|0184-0192(HEX)|MR184|100388-300402|Write only
1646 -|0280-0282(HEX)|MR280|100640-300642|Read only
1647 -|0300-030B(HEX)|MR300|100768-300779|Read/write
1648 -|0314-0317(HEX)|MR314|100788-300791|Read/write
1649 -|031A(HEX)|MR31A|100794-300794|Read/write
1650 -|0320-0321(HEX)|MR320|100800-300801|Read/write
1651 -|0400-0504(HEX)|MR400|101024-301284|Read/write
1652 -|0506(HEX)|MR506|101286-301286|Read/write
1653 -|0510-0514(HEX)|MR510|101296-301300|Read/write
1654 -|0516-0524(HEX)|MR516|101302-301316|Read/write
1655 -|0526(HEX)|MR526|101318-301318|Read/write
1656 -|0580-08C3(HEX)|MR580|101408-302243|Read/write
1657 -|~-~-|Ctrl|0-2|~-~-
1658 -
1659 -**✎Note:**
1660 -
1661 -* The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1662 -* The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1663 -* The Ctrl register is used to store the control group number and BCC check mode.
1664 -
1665 -**Ctrl Register Description**
1666 -
1667 -* The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1668 -* Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1669 -* Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1670 -* Ctrl3 reserved
1671 -
1672 -**✎Note:**
1673 -
1674 -After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1675 -
1676 -**Cable Wiring**
1677 -
1678 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_5e9a81a14106da9e.png?width=392&height=223&rev=1.1||alt="12.PLC Protocol_html_5e9a81a14106da9e.png" height="223" width="392"]]
1679 -
1680 -[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_1897d92be6948d58.png?width=393&height=223&rev=1.1||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
1681 -
1682 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1683 -
1684 1684  = Create communication with **Modbus RTU** =
1685 1685  
1686 1686  == **V-BOX as Slave** ==
image-20220831170147-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +57.1 KB
Content
image-20220831170215-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +14.3 KB
Content
image-20220831170254-3.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +43.5 KB
Content
image-20220831170306-4.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +28.5 KB
Content
image-20220831171127-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +60.1 KB
Content