... ... @@ -182,7 +182,7 @@
182 182  
183 183  MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
184 184  
185 -**1)PLC Settings**
185 +**1)V-BOX setting**
186 186  
187 187  |**Item**|**Settings**|**Note**
188 188  |Protocol|Allen-Bradlley DF1 Advanced|
... ... @@ -436,7 +436,7 @@
436 436  
437 437  Supported Series: Siemens S7-300 series PLC
438 438  
439 -**1)PLC Setting**
439 +**1)V-BOX setting**
440 440  
441 441  |**Items**|**Settings**|**Note**
442 442  |Protocol|Simens S7-300 Ethernet|
... ... @@ -498,7 +498,7 @@
498 498  
499 499  Supported Series: Siemens S7-400, S7-1200 and S7-1500
500 500  
501 -**1)PLC Setting**
501 +**1)V-BOX setting**
502 502  
503 503  |=**Items**|=**Settings**|=**Note**
504 504  |Protocol|Siemens S7-XXX|
... ... @@ -1312,6 +1312,41 @@
1312 1312  
1313 1313  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220830160232-3.png?rev=1.1||alt="image-20220830160232-3.png"]]
1314 1314  
1315 +
1316 += Create communication with **Schneider PLC** =
1317 +
1318 +== **Schneider MODBUS RTU** ==
1319 +
1320 +**1)V-BOX Setting**
1321 +
1322 +|=**Parameters**|=**Recommended**|=**Notes**
1323 +|**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
1324 +|**Connection**|RS485|
1325 +|**Baud rate**|19200|
1326 +|**Data bit**|8|
1327 +|**Parity**|Even|
1328 +|**Stop bit**|1|
1329 +|**PLC station No.**|1|
1330 +
1331 +**2)Address List**
1332 +
1333 +|=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
1334 +|B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
1335 +|B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
1336 +|B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
1337 +|W|MW|DDDDDD|0 ~~ 999999|Output register
1338 +|DW|MD|DDDDDD|0 ~~ 999999|Output register
1339 +
1340 +**3)Configure the communication protocol**
1341 +
1342 +[[image:image-20220902104329-1.png]]
1343 +
1344 +**4)Cable Wiring**
1345 +
1346 +**RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
1347 +
1348 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/image-20220817154212-1.jpeg?width=554&height=315&rev=1.1||alt="image-20220817154212-1.jpeg" height="315" width="554"]]
1349 +
1315 1315  = Create communication with Inovance** PLC** =
1316 1316  
1317 1317  == **H3U serial protocol** ==
... ... @@ -1511,9 +1511,9 @@
1511 1511  
1512 1512  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1513 1513  
1514 -= Create communication with **Modbus RTU** =
1549 += Create communication with **Modbus ** =
1515 1515  
1516 -== **V-BOX as Slave** ==
1551 +== **MODBUS RTU Slave (All function)** ==
1517 1517  
1518 1518  Select the protocol "Modbus RTU Slave (All Fuction)",
1519 1519  
... ... @@ -1522,7 +1522,7 @@
1522 1522  (% style="text-align:center" %)
1523 1523  [[image:1624342015914-382.png||height="486" width="800" class="img-thumbnail"]]
1524 1524  
1525 -== **V-BOX as Master** ==
1560 +== **MODBUS RTU Master** ==
1526 1526  
1527 1527  Select the protocol "Modbus RTU Master",
1528 1528  
... ... @@ -1558,6 +1558,67 @@
1558 1558  |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1559 1559  |0F (Write multiple bits)
1560 1560  
1596 +== **MODBUS TCP Slave (All function)** ==
1597 +
1598 +Supported series: MODBUS TCP controller
1599 +
1600 +HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1601 +
1602 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_8877cb7f39c2b607.png?width=544&height=571&rev=1.1||alt="12.PLC Protocol_html_8877cb7f39c2b607.png" height="571" width="544"]]
1603 +
1604 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_e7e1f06f127a9175.png?width=553&height=426&rev=1.1||alt="12.PLC Protocol_html_e7e1f06f127a9175.png" height="426" width="553"]]
1605 +
1606 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_60bbfe5de79417a6.png?width=553&height=163&rev=1.1||alt="12.PLC Protocol_html_60bbfe5de79417a6.png" height="163" width="553"]]
1607 +
1608 +**HMI Setting**
1609 +
1610 +|**Items**|**Settings**|**Note**
1611 +|Protocol|MODBUS TCP Slave (All function)|
1612 +|Connection|Ethernet|
1613 +|Port No.|502|
1614 +|PLC station No.|1|
1615 +
1616 +**Address List**
1617 +
1618 +|**Type**|**Register**|**Function code & Description**
1619 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1620 +|06 (write single register: write a binary value to a holding register)
1621 +|10 (write values to multiple addresses )
1622 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1623 +|06 (write single register: write a binary value to a holding register)
1624 +|10 (write values to multiple addresses )
1625 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1626 +|06 (write single register: write a binary value to a holding register)
1627 +|10 (write values to multiple addresses )
1628 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1629 +|10 (write values to multiple addresses )
1630 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1631 +|05 (Force a single coil to force the on/off state of a logic coil)
1632 +|0F (Write multiple bits, ie write continuously)
1633 +|(% rowspan="3" %)1|02 (Read the input state)
1634 +|05 (Force a single coil to force the on/off state of a logic coil)
1635 +|0F (Write multiple bits)
1636 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1637 +|05 (Force a single coil to force the on/off state of a logic coil)
1638 +|0F (Write multiple bits)
1639 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1640 +|0F (Write multiple bits)
1641 +
1642 +**Communication Settings**
1643 +
1644 +Enable HMI Ethernet in [Project Settings];
1645 +
1646 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_43b671f18153910d.png?width=405&height=107&rev=1.1||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
1647 +
1648 +Set PLC IP in [Device IP] settings;
1649 +
1650 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_4bd3cc8348adecf8.png?width=554&height=190&rev=1.1||alt="12.PLC Protocol_html_4bd3cc8348adecf8.png" height="190" width="554"]]
1651 +
1652 +**Cable Wiring**
1653 +
1654 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1655 +
1656 +
1561 1561  == **communicate with VB inverter** ==
1562 1562  
1563 1563  [[download link>>url:https://ftp.we-con.com.cn/Download/WIKI/V-BOX/Demo/%E9%80%9A%E8%AE%AF%E6%A1%88%E4%BE%8B/Communicate%20with%20VB%20inverter.zip]]