Changes for page 1 Communication
Last modified by Hunter on 2024/07/01 10:54
From version 164.1
edited by Ben
on 2022/09/02 11:24
on 2022/09/02 11:24
Change comment:
There is no comment for this version
Summary
-
Page properties (2 modified, 0 added, 0 removed)
Details
- Page properties
-
- Author
-
... ... @@ -1,1 +1,1 @@ 1 -XWiki.B en1 +XWiki.Bob - Content
-
... ... @@ -704,6 +704,109 @@ 704 704 [[image:image-20220825100845-4.png]] 705 705 706 706 707 +== **FX3U Ethernet Protocol** == 708 + 709 + Mitsubishi FX3U series PLC 710 + 711 +**HMI Settings** 712 + 713 +|Items|Settings|Note 714 +|Protocol|Mitsubishi FX3U| 715 +|Connection|Ethernet| 716 +|Port No.|5009|Must be the same as the PLC setting 717 +|PLC station No.|0| 718 + 719 +**Address List** 720 + 721 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note** 722 +|(% colspan="1" rowspan="7" %)Bit|X|X|X OOO|0~~377| 723 +|Y|Y|Y OOO|0~~377| 724 +|M|M|M DDDD|0~~7679| 725 +|SM|SM|SM DDDD|8000~~8511| 726 +|S|S|S DDDD|0~~4095| 727 +|TS|TS|TS DDD|0~~511| 728 +|CS|CS|CS DDD|0~~255| 729 +|(% colspan="1" rowspan="9" %)Word|CN|CN|CN DDD|0~~199| 730 +|TN|TN|TN DDD|0~~511| 731 +|D|D|D DDDD|0~~7999| 732 +|SD|SD|SD DDDD|8000~~8511| 733 +|R|R|R DDDDD|0~~32767| 734 + 735 +**Ethernet Module Settings** 736 + 737 +FX3U-ENET-L module configuration 738 +Set up the FX3U-ENET-L Ethernet module settings as follows. 739 +Select the module location, which in this document is Module 0. 740 + 741 +[[image:image-20221116094003-1.png]] 742 + 743 + 744 +Select "Operational setting" to enter the following screen. 745 + 746 +The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default. 747 + 748 +[[image:image-20221116094019-2.png]] 749 + 750 + 751 +Select "Open setting" to enter the setting interface, the settings are as follows. 752 + 753 +The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the 754 + 755 +Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module. 756 + 757 +[[image:image-20221116094038-3.png]] 758 + 759 + 760 +Click on "transter setup" - "PC side I/F setting", see the following figure. 761 + 762 +After setting, the first download must use the programming cable, as shown in the figure; after that, can 763 + 764 +use the IP set in the "Ethernet board" to communicate directly with the network cable. 765 + 766 +[[image:image-20221116094122-4.png||height="422" width="707"]] 767 + 768 + 769 +Read and write data from the Ethernet module 770 + 771 +[[image:image-20221116094131-5.png||height="551" width="708"]] 772 + 773 + 774 +Set "Transter setup" to COM communication, and read or write operation as shown below 775 + 776 +[[image:image-20221116094150-6.png]] 777 + 778 + 779 +**PLC Settings (GX Works 2)** 780 + 781 +Create a blank FX5U project 782 + 783 +Find Current Connection in the navigation 784 + 785 +[[image:image-20221116094206-7.png||height="425" width="711"]] 786 + 787 + 788 +Select Connection Channel List 789 + 790 +Select Ethernet board communication 791 + 792 +[[image:image-20221116094709-9.png||height="427" width="715"]] 793 + 794 + 795 +Select Ethernet Module 796 +Set the IP address of the PLC 797 + 798 +[[image:image-20221116094736-11.png||height="682" width="716"]] 799 + 800 + 801 +Read or write PLC data, in this document is read 802 + 803 +[[image:image-20221116094755-12.png||height="426" width="715"]] 804 + 805 +[[image:image-20221116094803-13.png||height="427" width="715"]] 806 + 807 + 808 + 809 + 707 707 == **FX5U Serial Protocol** == 708 708 709 709 Mitsubishi FX5U series PLC